Textiles Cooperative Closing in 0 days TDR #27896630

Ht-Lt Electrification Works And Augmentation Of Power System /Modernisation Of Mill Ht/Lt Electrification Works And Augmentation Of Power System /Modernisation Of Mill

Issued by Cooperative · TCSM LTD, Kerala
Tender Value
Ref. Documents
Estimated cost
Bid Submission
07 Jun 2021
0 days left
EMD
1 Lakhs
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
TCSM LTD → Kerala
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Ht-Lt Electrification Works And Augmentation Of Power System / Modernisation Of Mill Ht / Lt Electrification Works And Augmentation Of Power System / Modernisation Of Mill

BOQ

Name of Work: HT/LT ELECTRIFICATION WORKS AND AUGMENTATION OF POWER SYSTEM /MODERNISATION OF MILL
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11H T INSTALLATION [11kV INCOMING AND OUT GOING PANELS- 3PANEL VCB & BUS PT]: Design, fabrication, supply, installation, testing and Commissioning of 11kV VCB panel as per the scope of work, technical specification and drawing. The panel comprises of following major components. 11 kV, 800 A, 350MVA (3 sec) VCB - 3Nos. [1-I/C from Grid Supply and 2 O/Gs to 2Nos 800kVA OCTC ONAN Existing Transformers] Numerial protection relays having Modbus connectivity Digital power analyser/meter having RS 485 communication facilities Analog meters, control MCB, indication lamps, annuunciator, Hooters etc. Panel lighting (LED lamp) and panel heater with temperature control thermostat. Current density of aluminium busbar: 0.8 Amps/Sq.mm. The control supply voltage is 30V DC. [REFER Technical specification and SLDs]El-11SET
2230V DC BATTERY, BATTERY CHARGER AND DC DB.: Supply,Installation, Testing & Commissioning of indoor,floor mounted 30V DC power supply system with 50Amps rated float and boost type battery charger, 15 nos. of 2Volt, 160AH (minimum) stationary type SMF VRLA batteries on a suitable stand. Battery charger shall be suitable for 3 Phase, 415V , 50Hz ,ac input and shall be capable of delivering continuous load of 50A, complete with DC DB Panel having 50A DP MCB as incomer and 6 nos: 25A DP MCB's as outlets. [REFER Technical specification and SLDs] VCB & VCB Panel shall be Manufacturede by Approved VCB Manufacturer; Siemens, ABB, L&T, Schneider]El-21SET
3311kV CABLES AND CABLING:- Supply, Laying/ clamping testing and commissioning of the following HT Cable with Stranded compact circular ALUMINIUM conductor, conductor screened with Extruded semiconducting compound, XLPE Insulated, Insulation Screened with Extruded semiconducting compound in combination with Copper Tape, Aluminium Flat Strip / Round Wire armoured, and overall PVC ST2 Sheathed cable Conforming to IS:7098 Part-II 2011 with latest amendments. 3C X 300 SQ.MM. HT cableEl-3165MTR
44H T CABLE TERMINATIONS: Supply and providing end termination for the following sizes of HT XLPE cables including all materials required for frim joints. (Heat shrinkable type, Raychom/ M Seal Make)----- 3Cx300SQMM OUTDOOREl-41Each
553Cx300SQMM INTDOOREl-55Each
66EMERGENCY OFF PUSH BUTTON:- Supply, Installation ,testing and commissioning of Lockable Push Button for Emergency OFF facility of the HT VCB Panel for the Incomer VCB. [Cable shall also be included, Out side Trfo Room-1, Out side Trfo Room-2 & I/C VCB]El-63Each
77OUT DOOR CT/PT UNITS FOR SUPPLIERS METERING: Supply, installation, testing and commissioning of 11kV outdoor type CT/PT unit with, class 0.2S, 15VA CT with suitable ration as required as per KSEBL and 11kV/110V class 0.2S, 150VA PT on the existing DP structure with all necessary accessories for connecting 11kV lines, control cable, etc. as required. The existing CT PT Unit, Metering KIOSK and control cable shall be dismantled from the structure and stacked in stores as directed by the engineer incharge/ consultant. The Unit shall be duly tested at the TMR section of KSEB and the certificates should be submitted to the concerneed authorities for obtaining HT supply/ Regularised, as required.El-71Each
88TOD METER - SUPPLIERS METERING]:- Supply, Installation ,testing and commissioning of a TOD meter for KSEB within HT Metering panel including connections from CT and PT etc. as per KSEB/ Suppliers recommendation. The Meter shall be duly tested at the TMR section of KSEB and the certificates should be submitted to the concerneed authorities for obtaining HT supply, as required. [Make L&T; Trivector Meter Class 0.2s, Model ER300P Class 0.2s (Base Mounting) OR Equivalent. All statutory chargers shall be reimbursed from clients on production of proper receipts.El-81Each
99TOD METER KIOSK [OUTDOOR]:- Supply, Installation, testing and commissioning of HT Out door Metering KIOSK/Panel with glass window and sufficient number of terminal connectors with 25% spares, for connections from CT and PT etc. as per KSEB/ Suppliers recommendation, Control fuses, etc. The KIOSK shall be made out of 2mm thick CRCA sheet steel, totally enclosed, IP 54, weather proof, with rain guard, undergone seven tank process, powder coated finish, earthing, entire civil work including suitable foundation and all mounting accessories as required complete as per the rquirement of KSEBL.El-91Each
1010M. V PANELS/ DISTRIBUTION BOARDS- SSB#01 & SSB#01 Refer SLDs and Technical SpecificationsEl-102SET
1111SSB-03 (DRAWING) Refer SLDs and Technical SpecificationsEl-111SET
1212SSB-04 AND SSB-05 (SIMPLEX) Refer SLDs and Technical SpecificationsEl-122SET
1313SSB-06 (COMBER) Refer SLDs and Technical SpecificationsEl-131SET
1414MCC-A AND MCC-B (HUMIDIFICATION PLANT FOR SPG-I&II) Refer SLDs and Technical SpecificationsEl-142SET
1515MCC-C (EXHAUST PLANT FOR SPG-I,II&III) Refer SLDs and Technical SpecificationsEl-151SET
1616MCC-D (EXHAUST PLANT FOR SPG-IV&V) Refer SLDs and Technical SpecificationsEl-161SET
1717MCC-E (SUPPLY&EXHAUST PLANT FOR PREPARATORY) Refer SLDs and Technical SpecificationsEl-171SET
1818MCC-F (SUPPLY&EXHAUST PLANT FOR POST SPG) Refer SLDs and Technical SpecificationsEl-181SET
1919REPAIRING OF LT PANELS Supply of all necessary materials and carrying out repaire and maintenance works of the following LT panels [Existing] as shown in the One Line Diagrams including cleaning, priming, spray painting with required colour [Grey], replacing of Bus Bar insulators/ SMC Supports [Pillar Type/ Finger Type], PVC Sleeves etc. as required and testing and commissioning. All panels boards shall be tested at site [SAT] and ensure all the values are sufficient and satifactory as per standards and requirements at the point of electrical safety rules as per CEA regulations/ KSEI Guidelines/ Orders and shall be recorded in presents of the Engineer in Charge/ Consultant. ------- MSB [MAIN MV PANEL-DOUBLE BUS PANEL]El-191SET
2020PCC-1El-201SET
2121PCC-2El-211SET
2222PCC-3El-221SET
2323PCC-4El-231SET
2424PCC-5El-241SET
2525PCC-6El-251SET
2626PCC-7El-261SET
2727PCC-8El-271SET
2828PCC-9El-281SET
2929PCC-9-AEl-291SET
3030PCC-10El-301SET
3131BUS DUCT 2000A, 4POLE, 415V.El-3120Mtr
3232RETROFITTING DAMAGED SWITCHGEARS/ COMPONENTS.: Supply, installation, testing and commissioning of the following switch gears with in the existing LT Panel Boards including cecessary cutting, drilling, extension of Bus Bars, Interconnections etc. as required as per standards complete. The scope also includes dismantling and stacking of existing damages switches/ bus bars etc. as directed by the Engineer in Charge/ Consultant. ---- 400A TPN IsolatorsEl-322Each
3333315A TPN Switch Fuse UnitsEl-331Each
3434250A TPN Switch Fuse UnitsEl-344Each
3535100A TPN Switch Fuse UnitsEl-356Each
363663A TPN Switch Fuse UnitsEl-364Each
3737Heavy Duty APP Capacitors of Different ratings with in the APFC PanelEl-37250kVAR
3838HRC FUSE LINKS: Supply, installation, testing and commissioning of the following rating HRC Fuse Links DIN Type [Bolted Type for lower rating] suitable for 315A/ 250A/100A/63A SFUs with in the existing Panel Boards/ Switchgears. The Fuse links shall be provided as per the Standards and requirements of the Scheme Approval from the Department of Electrical Inspectorate in order to achieve Grading in between sections. The scope also includes dismantling and stacking of existing damages FUSE LINKS as directed by the Engineer in Charge/ Consultant. 400AEl-383Each
3939300A/315AEl-3930Each
4040250AEl-403Each
4141200AEl-416Each
4242160AEl-4236Each
4343150AEl-4336Each
4444125AEl-4433Each
4545120AEl-4521Each
4646100AEl-469Each
474780AEl-4772Each
484863AEl-483Each
494950AEl-493Each
505040A/35AEl-506Each
515125AEl-513Each
52522A [Control Fuses]El-5260Each
5353METERS AND INSTRUMENTS: Supply, installation, testing and commissioning of the following instruments/ Cast Resin CTs/ panel accessories with in the existing Panel Boards. The CTs shall be provided as per the Standards and requirements of the Scheme Approval from the Department of Electrical Inspectorate. The scope also includes dismantling and stacking of existing damages CTs/ Components Etc. as directed by the Engineer in Charge/ Consultant. --- RYB/ Trip Indication Lamps LEDEl-5348Each
5454Cast Resin CTs 1250/5A, Class 05, 10VAEl-546Each
5555Cast Resin CTs 400/5A, Class 05, 10VAEl-5539Each
5656Cast Resin CTs 300/5A, Class 05, 10VAEl-563Each
575725A HRC Fuse Units [Control Fuses]El-5760Each
5858Digital Combination Meters V,A,F,PF, kVA, PF & kWhrEl-582Each
5959Digital Combination Meters V,A & FEl-5914Each
6060Analogue Ammeters [0-1250A]El-606Each
6161Analogue Volt meters [0-500V]El-612Each
6262Volt Meter Selector SwitchesEl-622Each
6363Mechanical Interlocks between SwitchgearsEl-6310Set
6464LOCAL ISOLATION FOR MOTORS/ EQUIPMENTS:- Supply, Installation, Testing and commissioning of Lockable OFF PBs with in suitable Sheet Steel Powder coated enclosures complete.El-6420Each
6565Supply, Installation, Testing and commissioning of 32A TP Isolators, MCB Type with in suitable Sheet Steel Powder coated enclosures complete.El-6512Each
6666Supply, Installation, Testing and commissioning of 63A TP Isolators, MCB Type with in suitable Sheet Steel Powder coated enclosures complete.El-664Each
6767POWER FACTOR IMPROVEMENT CAPACITORS: Supply, Installation, Testing and commissioning of the following ratings Heavy Duty, APP Capacitors with in suitable Sheet Steel Powder coated enclosures, and giving connections as direct connection near by Motors/ Equipments, complete. --- 15kVAREl-6720Each
686810kVAREl-686Each
6969LT CABLES AND CABLING:- Supply, laying, Testing and Commissioning of the following sizes of 650/1100 Volts Power/ Control Cables with Aluminium/ Copper Conductor (Solid up to 10 sqmm and Stranded for balance), XLPE Insulated, Cores Laid Up, Inner Sheathed, Armoured and Extruded PVC Type ST2 Outer Sheathed As Per IS-7098 (Part 1) 2011 with Up To Date Amendments. The cables shall be laid in cable trenches or on wall or through pipes as per specifications, including providing of cable route makers in every 50M and at all strategic turning/ diversion points [if burried Directly in ground], etc. Necessary clamping should be providing while burying cables in prepared trenches etc.as per standards. ALUMINIUM CONDUCTOR POWER CABLE --- 3.5x240 Sq.mmEl-69460MTR
70713.5x185 Sq.mm AL ArmouredEl-71448MTR
71723.5x150 Sq.mm AL ArmouredEl-7215MTR
72733.5x50Sq.mm AL ArmouredEl-7310MTR
73743.5x35Sq.mm AL ArmouredEl-7410MTR
74753.5x25Sq.mm AL ArmouredEl-7510MTR
75763.0x25Sq.mm AL ArmouredEl-76110MTR
76774.0x16Sq.mm AL ArmouredEl-7710MTR
77783.0x16Sq.mm AL ArmouredEl-78270MTR
78794.0x10Sq.mm AL ArmouredEl-7920MTR
79803.0x10Sq.mm AL ArmouredEl-80310MTR
80814.0x6Sq.mm AL ArmouredEl-8110MTR
81823.0x6Sq.mm AL ArmouredEl-82186MTR
8283COPPER CONDUCTOR POWER CABLE --- 3.5x120 Sq.mmEl-83465MTR
83843.5x95 Sq.mm - Cu ArmouredEl-841MTR
84853.5x70Sq.mm - Cu ArmouredEl-85565MTR
85863.5x25Sq.mm - Cu ArmouredEl-86264MTR
86874.0x16Sq.mm - Cu ArmouredEl-8748MTR
87884.0x4Sq.mm - Cu ArmouredEl-885MTR
88893.0x4Sq.mm - Cu ArmouredEl-8935MTR
89904.0x2.5Sq.mm - Cu ArmouredEl-90165MTR
90913.0x2.5Sq.mm - Cu ArmouredEl-91600MTR
9192COPPER CONDUCTOR CONTROL CABLE 16.0x1.5Sq.mmEl-9274MTR
929312.0x1.5Sq.mm - Cu ArmouredEl-93246MTR
939410.0x1.5Sq.mm - Cu ArmouredEl-9445MTR
94958.0x1.5Sq.mm - Cu ArmouredEl-9596MTR
95967.0x1.5Sq.mm - Cu ArmouredEl-9632MTR
96976.0x1.5Sq.mm - Cu ArmouredEl-9738MTR
97984.0x1.5Sq.mm - Cu ArmouredEl-98128MTR
98993.0x1.5Sq.mm - Cu ArmouredEl-991MTR
991002.0x1.5Sq.mm - Cu ArmouredEl-1001MTR
1001013Cx0.75sQ.mm Copper Shielded CableEl-10190MTR
101102CABLE TERMINATIONS- ALUMINIUM CONDUCTOR POWER CABLE:- Supply and providing end terminations using siemens type compression gland for PVC insulated and PVC sheathed armoured conductor cable 1.1KV grade for the followings sizes including earthing the glands as required as per standards.--- 3.5x240 Sq.mmEl-10214Each
1021033.5x185 Sq.mmEl-10324Each
1031043.5x150 Sq.mmEl-1042Each
1041053.5x50Sq.mmEl-1052Each
1051063.5/3.0x35Sq.mmEl-1062Each
1061073.5x25Sq.mmEl-1072Each
1071083.0x25Sq.mmEl-1088Each
1081094.0x16Sq.mmEl-1092Each
1091103.0x16Sq.mmEl-11016Each
1101114.0x10Sq.mmEl-1111Each
1111123.0x10Sq.mmEl-1128Each
1121134.0x6Sq.mmEl-1131Each
1131143.0x6Sq.mmEl-11412Each
114115CABLE TERMINATIONS- COPPER CONDUCTOR POWER CABLE --3.5x120 Sq.mmEl-11518Each
1151163.5x95 Sq.mmEl-1162Each
1161173.5x70Sq.mmEl-1172Each
1171184.0x25Sq.mmEl-11814Each
1181194.0x16Sq.mmEl-1192Each
1191204.0x4Sq.mmEl-1202Each
1201213.0x4Sq.mmEl-1212Each
1211224.0x2.5Sq.mmEl-12216Each
1221233.0x2.5Sq.mmEl-12348Each
123124CABLE TERMINATIONS- COPPER CONDUCTOR CONTROL CABLE --16.0x1.5Sq.mmEl-1244Each
12412512.0x1.5Sq.mmEl-1258Each
12512610.0x1.5Sq.mmEl-1262Each
1261278.0x1.5Sq.mmEl-1274Each
1271287.0x1.5Sq.mmEl-1282Each
1281296.0x1.5Sq.mmEl-1292Each
1291304.0x1.5Sq.mmEl-1308Each
1301313.0x1.5Sq.mmEl-1312Each
1311322.0x1.5Sq.mmEl-1322Each
1321333Cx0.75sQ.mm Copper Shielded CableEl-1332Each
133134GENERAL EARTHING BARE COPPER EARTHING CONDUCTORS:- Supply, Laying/ fixing of earthing conductor with Purity not less than 99% of the following sizes/ type, jointing as per IS:3043/87 in trench walls pulling through pipes etc.as required. All joints in the system shall be braced properly with lead. 50x6 mm Copper StripEl-134560MTR
13413540x6 mm Copper StripEl-135360MTR
13513631x6 mm Copper StripEl-136470MTR
13613725x3 mm Copper StripEl-137530MTR
137138Copper wire No.4 SWGEl-138310MTR
138139Copper wire No.10 SWGEl-1391700MTR
139140MAINTENANCE OF EARTHING STATIONS: Supply of all necessary materials and carrying out repaire works of the existing stations including replacing of damaged bolts/ nuts/ washers/ bracing the ends, etc. and taking earth reading in presence of the EIC/ Consultant to obtain a satifactory value for each station, etc. complete.El-14010Each
140141MISCELLANEOUS ITEMS:- Supply and Fixing of FRAMED KEY ONE LINE DIAGRAM in A-1 Size with frame work and glass at desired locations including supply of all fixing materials as required and as directed by EIC/ Consultant.El-1412Each
141142Supply and fixing of standard Shock Treatment Chart with frame work and glass including supply of all fixing materials as required and as directed by EIC/ Consultant.El-1424Each
142143CABLE TRAYS/ SUPPORTS: Supply and Erection of Vertical/Horizontal type M.S. Cable Trays and cable supports fabricated out of M.S.Angles (ISA) and M.S. flats with sufficient width and Spacing between successive cross members and supported at adequate spacing. The cable trays and supports 'shall be painted with 2coats of Zinc chromate 'primer and 2coats of enamel paint. 25x25x6mm MS angles and 20x6mm MS flats shall be used for trays up to 450mm wide and 40x40x6mm MS angles and 20x6mm MS flats shall be used for trays up to 900mm wide.El-1431200KG
143144CIVIL WORKS: Excavtion of soil in all classes up to a depth of 750mm suitable for Cable Trench directly burrying and backfilling with excavated soil after laying of cable including supply and laying of bricks, sand cushioning, etc. as required as per the standards for cable laying.El-14412MTR
144145CT&PT METER TESTING: Transporting CT/PT units and TOD meter (11KV) to the testing laboratories of KSEB and obtaining the necessary certificates for approval and load sanction from power supply company.El-1451LS
145146TRANSFORMER PROTECTION CUM MAINTENANCE:- 'Supply and Providing protection Class, Cast Resin, CTs suitable for REF Protection Relay [4 CT Method], Class PS, 10VA with suitable ID and outer dimensions.El-1468Each
146147Supply and Providing protection Class, Cast Resin, CTs suitable for Low set E/F Protection Relay. The NCT provided in the Earthing conductor shall be provided with necessary control box and supports.El-1472Each
147148Supply and providing Buchholz Relay, Oil Temperature and Winding Temperature [high] Indicators [OTI&WTI], with marshaling box and provision for alarm trip at Primary Breaker.El-1482Set
148149Supply of all necessary materials, labour etc. and carrying out Over all maintenance for the Existing 800 kVA ONAN OCTC Transformer, replacement of full set Gasket, Breather, Cleaning, Primimg and Painting with approved cloour Epoxy Paint, etc. complete. Test certificates/reports shall also be issued after conducting all necessary routeen tests, through competent and approved agency.El-1492Set
149150Supply and Filling of Brand New Transformer Oil as per IS 335 of sufficient quantity for 800kVA ONAN Transformer, [740 Ltr] tested for BDV including draining out the old oil, cleaning and washing the tank etc. complete.El-1502Set
150151Supply and providing new Radiators (4nos) with dimensions of (1100mm x 520mm x 10 fins.). Butterfly valve (8nos) along with fasteners and all necessary accessories, pipes etc. This scope includes all necessary fabrication, assembling and including replacing the existing tank, comlete.El-1512Set
151152DOCUMENTS & APPROVAL- ELECTRICAL INSPECTORATE APPROVALS & SANCTION ORDERS: Preparation of all documents, applications, forms and conducting Soil resistivity tests, submission of Scheme, obtaining Scheme Approval, Conducting Electrical Inspection, as installaed drawings, obtaining Energisation Sanction Orders for the Entire Installation including installations/ equipments/ panels/ loads, etc. existing at the premises but to be regularised as per statutes, etc. complete. (Excluding statutory charges).El-1521LS
152153SUPPLY AUTHORITY CONNECTED LOAD/ CD REGULARISATION: 'Preparation of necessary documents, forms, drawings, schemes, certificates, submitting completion reports, Executing HT Supply Agreement, etc. and obtaining Power sanction/ additional Power Sanction service connection @ 11kV from KSEB for the installation. All statutory charges shall be remitted by the clients.El-1531LS

AI Tender Summary

OUR REF NO 27896630
AUTHORITY Cooperative
TENDER VALUE Ref. Documents
LAST DATE 07-06-2021
Authority
Authority Name Cooprative Spinning Mills Limited
Work Description Ht-Lt Electrification Works And Augmentation Of Power System / Modernisation Of Mill Ht / Lt Electrification Works And Augmentation Of Power System / Modernisation Of Mill
Basic Detail
Tender No TCSM/NCDC/E-Proc/2021-22/Elec3
Bidding Type Tender
Location
City TCSM LTD
State Kerala
Key Dates
Publish Date 14 May 2021
Submission Date 07 Jun 2021
Open Date 08 Jun 2021
Finance
Tender Value Ref. Documents
Tender Fee 5900
EMD 1 Lakhs
Exemption Not Available
Document List
BOQ_600416.xls
Tendernotice_1.pdf
9D671ADD-5B26-4460-9C4B-56BDE6140941.html
ElecNIT.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

May 14, 2021
11:30 IST

Tender Published

Tender notice published.

Completed
Jun 07, 2021
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Jun 08, 2021

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
xls

BOQ_600416.xls

pdf

Tendernotice_1.pdf

html

9D671ADD-5B26-4460-9C4B-56BDE6140941.html

pdf

ElecNIT.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders