Renovation Work Of Electrical Installation In Existing Ward In Bidhan Block To 20 Bed Sari Hdu And 40 Bed Sari Step Down Ward For Covid -19 Patient At Midnapore Medical College Hospital , Paschim Medinipur . --- Supply Installation Testing And Commissio, MIDNAPUR-West Bengal

Public Works Department-PWD has published Renovation Work Of Electrical Installation In Existing Ward In Bidhan Block To 20 Bed Sari Hdu And 40 Bed Sari Step Down Ward For Covid -19 Patient At Midnapore Medical College Hospital , Paschim Medinipur . --- Supply Installation Testing And Commissio. Submission Date for this Tender is 19-05-2021. Electrical Maintenance Tenders in MIDNAPUR West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

27885603
Renovation Work Of Electrical Installation In Existing Ward In Bidhan Block To 20 Bed Sari Hdu And 40 Bed Sari Step Down Ward For Covid -19 Patient At Midnapore Medical College Hospital , Paschim Medinipur . --- Supply Installation Testing And Commissio
Open Tender
Indian
West Bengal
MIDNAPUR
19-05-2021

Tender Details

Renovation Work Of Electrical Installation In Existing Ward In Bidhan Block To 20 Bed Sari Hdu And 40 Bed Sari Step Down Ward For Covid -19 Patient At Midnapore Medical College Hospital , Paschim Medinipur . --- supply installation testing and commissioning Of Diesel Generator Set

Key Value

Document Fees
Refer document
EMD
INR 35067.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Renovation work of electrical installation in existing Ward in Bidhan Block to 20 Bed SARI HDU & 40 Bed SARI Step Down ward for Covid -19 Patient at Midnapore Medical College & Hospital, Paschim Medinipur.--- SITC of Diesel Generator Set
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, installation, testing and commissioning of new CPCB-II Compliant 3 phase, 415V, 50 HZ, 180 KVA Silent Diesel Generator Set comprising of Engine, Alternator, STD AMF panel, Base frame, Fuel tank, Battery, CPCB approved acoustic enclosure including all interconnection between Generator and panel etc having following specification: Engine should not derate at 50 deg c ambient temperature. BI01010001010000000000000515BI0100001112
2 1.01 Engine:\n(a) Make- CUMMINS / CATTER PILLER / VOLVO/ KOEL / Ashok Leyland / Mahindra\n(b) BHP-Minimum 248 BHP\n(c) Aspiration- Turbocharged, Charge Air Cooled\n(d) No of Stroke / Cylinder- 4 Stroke / 6 Cylinder in-line\n(e) RPM- 1500\n(f) Battery-as per manufacturer standard\n(g) Type of Cooling- Water Cooled. \n(h) Air Intake System- Air intake manifold with air filter system. \n(i) Exhaust System- Provided with turbo charger & residential exhaust silencer with flexible bellow and companion flanges inside the acoustic enclosure. (j) Coupling & Fly Wheels- Befitting coupling, Fly wheel & Fly wheel housing. \n(k) Lubricating System- Provided with Oil pan, engine mounted lube oil pump and lube oil filter along with first fill of lube oil. \n(l) Fuel System- Comprising of MICO fuel pump with electronic governor, 12V solenoid coil and replaceable fuel filter. \n(m) Starting System- 12V DC electric starter \n BI01010001010000000000000515BI0100001113
3 1.02 (n) Control Panel:-\n Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.The control panel consists of the following parts:\ni) Manufacturer standard Controller\nii) Aluminum bus bars with suitable capacity with incoming/outgoing terminals\niii) Indicating lamps for ‘Load ON’ and ‘Set Running’\niv) Instrument fuses duly wired and ferruled\niv) MCCB of suitable rating with overload and short circuit protections\n BI01010001010000000000000515BI0100001114
4 1.03 Power Start Control: Control panel is manufactured with 14/16 gauge CRCA sheet\nand is powder coated for weather-proof and long lasting finish.\nThe control panel consists of the following parts:\ni)controller as per manufacturer standard\nii)Aluminum bus bars with suitable capacity with incoming/\noutgoing terminals\niii)Indicating lamps for ‘Load ON’ and ‘Set Running’\niv)Instrument fuses duly wired and ferruled\nv)Circuit breakers of suitable rating with overload and short circuit protection\n BI01010001010000000000000515BI0100001115
5 1.04 vi) microprocessor based generator set monitoring and control system. This control includes an intuitive operator interface that allows for\ncomplete generator set control as well as system metering, fault annunciation,configuration and diagnostics. vii)Intuitive operator interface which includes LED backlit LCD display with tactile feel soft-switches and generator set status LED lamps\nviii) Remote start-stop\nix) Engine Metering: Oil pressure, Engine temperature, Startingbattery voltage, Engine running hours\nx) AC Alternator Metering: L-L Voltage and L-N Voltage,Current (phase and total), kVA (phase and total) andFrequency.\n BI01010001010000000000000515BI0100001116
6 1.05 xi) Engine Protection: Low lube oil pressure, High/Low coolant temperature, Battery Over/Under/Weak Volts, Fail to Crank/Start, Sensor failure, Cranking lockout, Low fuel level.\nxii)AC Alternator Protection: Over/Under Voltage, Over/Under Frequency, Loss of AC sensing.\nxiii) Data Logging: Engine hours, Control hours and upto 5 recent fault codes\nxiv) Configurable glow plug control\nxv) 12 Volt DC operation\nxvi) Sleep mode\nxvi) Modbus interface (RS485 RTU)\nxvii) InPower compatible (PC based service tool)\nxviii) Certifications - meets the requirement of relevant ISO, EN,Mil Std. and CE standards\n\n BI01010001010000000000000515BI0100001117
7 1.06 Alternator :\n (a) Make: STAMFORD / Leroy sommer / CUMMINS / CATTER PILLER / VOLVO/KOEL/ Ashok Leyland / Mahindra (b) Rating: 180KVA. \n(c) Type of Alternator: Brushless, self excited & self-regulated through (d) Voltage Regulation: ± 1% (max.) in static condition. (e) Overload: Permissible overload of 10% for 1 hour in 12 hours of operation, (f) Protection: IP - 23 protections with Class - H Insulation. BASE FRAME: Common MS Channel fabricated base frame, primer coated & painted, containing the engine and the alternator mounted through AVM Pads. Fuel Tank: Min. 460 LTRS, detachable tank built inside base frame complete with drain valve, air vent inlet & outlet connections, fuel gauge.\n BI01010001010000000000000515BI0100001118
8 1.07 Acoustic Enclosure:\n *Specially designed to meet stringent MoEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions *The acoustic enclosure is made of CRCA sheets in munsel green shade and a structural/ sheet metal base frame painted in black.\ni) High quality noise absorbant and fire-retardant grade\nacoustic Insulation material (P.U. Foam) complying to IS\n8183\nii) Two point lifting for easy handling at customer site\n ii) Designed to have optimum serviceability\niv) Air inlet louvers specially designed to operate at rated load\nv) 11 tank pretreatment process and UV resistant Powder\nCoating of all parts to withstand extreme environment\nvi) Use of special hardware for longer life\nvii) Flush styling - no projections\nviii) Fluid drains for lube oil and fuel\nix) Fuel filling arrangement inside the enclosure\n BI01010001010000000000000515BI0100001119
9 1.08 AMF Panel: Wall/Floor mounted AMF control panel fabricated from 14 SWG CRCA Sheet and powder coated after 7 tank treatment process. The panel comprises of following items\n4P Power contactor - 400 A, 230 V AC, AC1 Duty 400 A, 50 Ka, 4 pole MCCB and microprocessor-based protection release etc.\nIn Built By-Pass switch for rated capacity\nAdd on block for power contactor, 3NO + 1NC\nAuxiliary contactor, 2NO+2NC, 415 V AC\n6A SP MCB, 10KA\n16A DP MCB, 10KA\nIndicating light, RED, 230 V AC\nPush Button (RED), 1NC\nPush Button (Green), 1NO\nAuto Manual Selector switch 3P, 2W,6A\nDG Selector Sw, 2P-ON/OFF\nAux. Relay, 2C/O, 230 V AC\nAux. Relay, 2C/O, 24 V DC\n3P Voltage Monitoring Relay, 415 V\nOn Delay Timer, Coil Voltage 230V AC\nAutomatic Battery Charger I/P-230 V AC, O/P-24 V DC & Terminal.\nMake: CUMMINS / CATTER PILLER / VOLVO/KOEL/ Ashok Leyland / Mahindra 1 Set
10 2 Note : (I) Efficiency not less than 90% \n(II) Warranty minimum 2 years or 5000 running hours whichever is earlier.\n(III) Scope of Work : Placement of DG set on existing foundation at site, Commissioning and Testing. Iv.Necessary connecting Cable required in between AMF panel & DG set --5 Mtrs. to be supplied free of cost v.Necessary clearance certificate of statutory body (environment department and others) must be obtained by executing bidder. BI01010001010000000000000515BI0100001128