Maintenance Of Electrical Installation , Fans , Street Light/ Compound Light/ Security Light , Rmo Air-Conditioning , Pump Set , Dg Set In Various Fire Stations At Connaught Place , Rakaab Ganj , Chanakya Puri , New Delhi Routine Maintenance O, New Delhi.-Delhi

Public Works Department-PWD has published Maintenance Of Electrical Installation , Fans , Street Light/ Compound Light/ Security Light , Rmo Air-Conditioning , Pump Set , Dg Set In Various Fire Stations At Connaught Place , Rakaab Ganj , Chanakya Puri , New Delhi Routine Maintenance O. Submission Date for this Tender is 24-05-2021. Electrical Maintenance Tenders in New Delhi. Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

27884711
Maintenance Of Electrical Installation , Fans , Street Light/ Compound Light/ Security Light , Rmo Air-Conditioning , Pump Set , Dg Set In Various Fire Stations At Connaught Place , Rakaab Ganj , Chanakya Puri , New Delhi Routine Maintenance O
Open Tender
Indian
Delhi
New Delhi.
24-05-2021

Tender Details

Maintenance Of Electrical Installation , Fans , Street Light/ Compound Light/ Security Light , Rmo Air-Conditioning , Pump Set , Dg Set In Various Fire Stations At Connaught Place , Rakaab Ganj , Chanakya Puri , New Delhi Routine Maintenance Of Ei , Fans , Compound Light , Rmo Dg Set And Drinking Water Supply Pump Set , Miscellaneous Electrical Work

Key Value

Document Fees
Refer document
EMD
INR 58950.0 /-
Tender Value
INR 29.47 Lakhs /-

BOQ Items

Name of Work: MOEI & Fans, Street Light/ Compound Light/ Security Light & RMO Air-Conditioning, Pump Set, DG Set in various Fire Stations at Connaught Place, Rakaab Ganj & Chanakya Puri, New Delhi (SH:- Routine Maintenance of EI & Fans, Compound Light & RMO DG Set and Drinking Water Supply Pump Set & Miscellaneous Electrical Work).
Sl. No. Item Description Item Code / Make Quantity Units
1 1 SH-I - Routine Maintenance & Operation\nRoutine maintenance and attending day to day complaints of electrical installations and compound/ street lights including repairing the wiring and lighting fixture complete with carrying out the daily drill comprising of cleaning of the electrical installation, lodging of electrical complaint in the complaint register, testing the insulation resistance, earth resistance, rectification of faults, up keeping and preventive maintenance of E.I. etc and providing assistance to the Engineer-in-Charge during breakdown maintenance complete with replacement of worn-out parts issued by the department to the contractor including running maintenance & operation and general upkeep of various capacity drinking water supply pump sets alongwith starter, sluice/ gate valves etc. to fill up over head water tank for timely delivery of water supply and carrying out the daily drill comprising of cleaning of pump house and maintaining log book for above installation and running maintenance & operation, general upkeep for maintaining essential power supply, as and when required for D.G. set comprising of A.M.F. Panel & allied accessories, for maintaining essential power supply, as and when required, on account of failure of main electrical power supply/ load shedding, minor repair works, as and when required and recording reading in log book by deploying staffs as per terms & conditions attached etc. as reqd. 12 Months
2 2 SH-II - Repair/Replacement of minor Electrical Installations\nWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.\n(a) Group C 80 Points
3 3 Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.\n(a) Group B 45 Points
4 4 Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.\n(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire 150 Meters
5 4.01 (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 80 Meters
6 4.02 (c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 130 Meters
7 4.03 (d) 4 X 4 sq. mm + 2 X 4 sq. mm earth wire 250 Meters
8 5 Supplying and drawing of following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.\n(a) 3 x 1.5 sq. Mm 120 Meters
9 5.01 (b) 3 x 4 sq. Mm 70 Meters
10 5.02 (c) 3 x 6 sq. Mm 50 Meters
11 5.03 (d) 6 x 4 sq. Mm 35 Meters
12 6 Supplying and fixing of suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 & 5/6 ampers modular socket outlet and 15/16 ampers modular switch, connection, painting etc. as required. 30 Nos.
13 7 Supplying and fixing of following way, single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)\n(a) 8 way, Double door 1 Nos.
14 7.01 (b) 12 way , Double door 1 Nos.
15 8 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 Volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)\n(a) 8 way (4 + 24), Double door 1 Nos.
16 8.01 (b) 12 way (4 + 36), Double door 1 Nos.
17 9 Supplying and fixing 5 Ampers to 32 Ampers rating, 240/415 Volts, 10 kA, breaking capacity “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc as required.\n(a) Single pole 60 Nos.
18 9.01 (b) Single pole and neutral 2 Nos.
19 10 Supplying and fixing of 20 Ampers, 240 Volts, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 Ampers "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. 10 Nos.
20 11 Supplying, installation, testing & commissioning of energy efficient following size ceiling fan, including wiring the down rod of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable including providing and fixing phenolic laminated sheet cover on fan box etc. as required.\n(a) 1400 mm sweep size 15 Nos.
21 11.01 (b) 1200 mm sweep size 20 Nos.
22 12 Supply and fixing of 400 mm sweep size wall mounted fan complete with inbuilt Electronic Regulator, Blade, wire lead with moulded plug top etc as required. 10 Nos.
23 13 Supplying and fixing of fresh air fan of 250 mm sweep size suitable for 220 volts, 50 hz, A.C. supply , in the existing opening including , making the hole to suit the size of the above fan, making good the damages, connection, testing, commissioning etc as required. 10 Nos.
24 14 Supplying and installation of Heavy duty exhaust fan of following size, 900 rpm speed with shutter & louvers in the existing opening alongwith connection, testing & commissioning etc. as required.\n(a) 300 mm sweep size 10 Nos.
25 14.01 (b) 380 mm sweep size 10 Nos.
26 15 Supplying, installation, testing & commissioning of 20W to 22W, 6000K (1200 mm) energy efficient LED wall mounted light luminaries, extruded aluminum heat sink provided for efficient heat dissipation & integrated electronic driver, suitable to work on 230 volts, AC supply complete with connection etc. with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required at site. 50 Nos.
27 16 Supplying, installation, testing & commissioning of 15 watt recess/surface mounted glarefree round/square LED downlight, system lumen efficancy 90Lm/W, cool day light (5700K to 6500K), power factor>0.90, CRI>80, LED lamp complete with all accessories, testing & commissioning etc as required. 10 Nos.
28 17 Supplying, installation, testing & commissioning of energy efficient recessed mounted type 34W to 36W full window glare free opal diffuser LED panel luminaries of size 595mm x 595mm (nominal size) suitable for both Armstrong/POP/Geypsum Board or grid false ceiling fabricated with MS powder coated white CRCA housing including mounting with the help of chain/other suitable method, hanging from the ceiling including connections with 3 x 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. The total system wattage not more than of 34W to 36W, LED lumen should be = 3600 system efficacy of = 130 lumen /watt colour temperature 5500K to 6500K, power factor>0.95, CRI (Ra)>80, THD <10%, with APFC driver having driver efficiency >85%, operating voltage 150-270 volts with minimum 2.5KV surge protection. The luminaries shall be submitted with LM-80 report with a life of 50000 Hours @ L-70 and LED photo biological safety report conforming to IEC 62471 & LED source manufacturer and LM-79 report from NABL accredited Lab. The LED chip should be of Cree, Nichia, Philips Lumiled, Osram, Edison. 15 Nos.
29 18 Supplying, installation, testing & commissioning of LED surface mounted 10 watts IP66 (waterproof) glarefree, pressure die cast aluminum housing with unbreakable polycarbonate diffuser bulk head fitting. Total system Lumen of 10W LED should be 550 or above in cool day light (5700K to 6500K), power factor>0.95, CRI>75 complete with all accessories as required including connections with 1.5 sq. mm PVC copper wire etc. as required. 20 Nos.
30 19 Supplying, installation, testing & commissioning of energy efficient LED flood light luminaries of system wattages 120 watts complete with mounting brackets and accessories on the street light pole with help of tower wagon including connections complete as required. The LED luminaries should confirm the following technical specifications:-\na) Type of LED: High power LEDs Nichia / Osram / Cree / Philips\nb) driver efficiency >85%\nc) System Efficacy >120lm/w\nd) color Index(CRI) Ra>70\ne) Color Temperature (CCT) Cool white: 4000°K\nf) Input Voltage. 140-270V AC\ng) Frequency Range 50-60Hz\nh) Power Factor(PF) > 0.95\ni) Surge protection = 10KV\nj) Total Harmonic Distortion(THD)< 10%\nk) Working Environment 0°C to 50°C;10%-90%RH \nl) Working lifetime: >50000 hrs.\nm) IP Rating :- IP66\nn) Housing and finish:-epoxy powder coated die cast aluminum housing with elegantly designed heat sink for efficient thermal management and to excellent corrosion resistant, cable gland P49 is provided at cable entry cover & high quality toughened glass.\n 5 Nos.
31 20 Supplying, laying and fixing of following size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade etc as reqd. in the following manner:\n(a) 3 x 6 sq.mm on wall surface 200 Meters
32 20.01 (b) 3 x 6 sq.mm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. 100 Meters
33 20.02 (c) 4 x 25 sq.mm on wall surface 100 Meters
34 21 Less credit of following electrical accessories etc. complete as required under buy back arrangement.\n(a) DBs (assorted size) 4 Nos.
35 21.01 (b) MCBs (assorted size) 62 Nos.
36 21.02 (c) SPN Industrial type Socket Outlet 10 Nos.
37 21.03 (d) 1200/1400mm sweep size Ceiling Fan 35 Nos.
38 21.04 (e) Wall Fan 10 Nos.
39 21.05 (f) Fresh Air Fan 10 Nos.
40 21.06 (g) 300/380mm sweep size Exhaust Fan 20 Nos.
41 21.07 (h) Assorted light fittings 50 Nos.
42 21.08 (i) Bulk head light fittings 10 Nos.
43 21.09 (j) Flood light fittings 5 Nos.
44 21.1 (k) Assorted material like switches, sockets, plates, wire, cable, scrap iron, conduit, MS boxes etc. 1 Lot