Indian Oil Corporation Limited-IOCL has published Supply Installation Testing And Commissioning Of Automated Tank Farm Management System Tank Truck Entry System Pump House Automation Allied Works As Per Fdr For Terminal Automation Systems At Sewree Ii Terminal Under Maharashtra State Office . . Submission Date for this Tender is 08-06-2021. Application Software Tenders in IOCL SEWREE II TERMINAL Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 21-May-2021 | Time Extension | Date | 08-06-2021 |
Name of Work: Supply, installation, testing and commissioning of Automated Tank Farm Management System, Tank Truck Entry System, Pump House Automation, Allied works as per FDR for Terminal Automation Systems at Sewree-II Terminal under Maharashtra State Office | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 10 | SUPPLY COMPONENTS | 1 | ||
2 | 20 | Supply of Complete Terminal Automation Software for LRCS and Operator work Stations with dongle/key, licenses, media, documentation, including equipment fault detection module / software etc complete as per specifications and tender documents. Vendor to provide the complete software to meet the Terminal Automation System as per tender scope of work and requirements. | 3 | 1 | LS |
3 | 30 | Supply of LED monitor of minimum 42" along with required hardware and software for interfacing with TAS for displaying the list of TTs whose invoice has been generated and TT is still inside license area complete in all respect as per tender requirement. | 4 | 1 | EA |
4 | 40 | Supply of weather proof Single line LED display board (Minimmum 1 line x 25 mm Character height x 11 characters per line) for outdoor application near Security Gate for displaying the TT Registration no. bilingual (English + local language) of reported TT whose proximity card has been shown on the PCR adjacent to the display board for TT reporting. | 5 | 1 | EA |
5 | 50 | Supply of intrinsically safe / flameproof type proximity card reader alongwith mounting accessories etc complete as per specifications for mounting atTLF, Security Entry & Exit barrier gates ( 1 no. Per barrier Gate) | 6 | 6 | EA |
6 | 60 | Supply of single phase socket at TLF | 7 | 1 | EA |
7 | 70 | Supply of three phase socket at TLF | 8 | 1 | EA |
8 | 80 | TLF Header line instruments supply of Densitometer on by-pass line of TLF header line with in built display. | 9 | 2 | NO |
9 | 90 | Supply of HART Gateway | 10 | 2 | NO |
10 | 100 | Supply of Restriction Orifice Plate including flages | 11 | 2 | NO |
11 | 110 | Supply of un managed 24 Port Ethernet Switch | 12 | 2 | EA |
12 | 120 | Supply of un managed Ethernet switch - 8 port | 13 | 2 | EA |
13 | 130 | Supply of laser printer | 14 | 1 | EA |
14 | 140 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS, along with FLP double compression gland, TBs. | 15 | ||
15 | 150 | For ROSOVs (A/G product tank's inlet & outlet line- 8 nos. ) | 16 | 8 | EA |
16 | 160 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of DBBVs from LPBS, along with FLP double compression gland, TBs | 17 | ||
17 | 170 | For DBBVs (A/G product tank's inlet & outlet line- 8 nos. ) | 18 | 8 | EA |
18 | 180 | Supply of ESD PUSH BUTTON STATION Installation, Integration, Testing and Commissioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation alongwith mounting structure complete as per specification and tender document. Local ESD Push Button Station | 19 | 4 | EA |
19 | 190 | Supply of Non FLP ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation alongwith mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) | 20 | 3 | EA |
20 | 200 | Supply of Wailing siren along with controller with a provision to operate locally as well as from control room, mounting accessories etc complete as per specification and tender document. | 21 | 1 | LS |
21 | 210 | Supply of Ex-proof and weather proof Hooter cum Beacons along with accessories, mounting structure etc complete as per specification and tender document for audio visual alarm at field in case the MOVs installed at tank dyke drain and tank water draw off line is not fully closed. \nLocation : Near each tank dyke and to be installed outside dyke. | 22 | 3 | EA |
22 | 220 | Supply of MCT block for entire Automation cable entry to Control Room, Admin Building, Invoice Room, Security Room, S&D, Driver's Rest Room with minimum 30% spare MCT blocks for furture cable entry alongwith frame and mounting accessories complete as per specification and tender document. | 23 | 1 | LS |
23 | 230 | Supply of MS structural Steel | 24 | 3 | TON |
24 | 240 | FO Cable -LIU, Media Convertor & All Accessories | 25 | 2 | EA |
25 | 250 | Cabling, JB, Earthing: (Cables, JBs, Cables Trays etc. would be arranged from Other MSO based Locations like JNPT and Miraj. In case any additional cable is essential, to be procured as per actual requirement from Successful bidder based on Finalized rates as per line items below) | 26 | ||
26 | 260 | Note: Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc | 27 | ||
27 | 270 | Supply of FRLS Armoured Copper Power cable as per tender specifications. | 28 | ||
28 | 280 | 3C x 2.5 sqmm | 29 | 10 | RM |
29 | 290 | 4C x 2.5 sqmm | 30 | 10 | RM |
30 | 300 | 8C x 2.5 sqmm | 31 | 10 | RM |
31 | 310 | 10C x 2.5 sqmm | 32 | 10 | RM |
32 | 320 | 12C x 2.5 sqmm | 33 | 10 | RM |
33 | 330 | 24C x 2.5 sqmm | 34 | 10 | RM |
34 | 340 | 3C x 4 sqmm | 35 | 10 | RM |
35 | 350 | 4C x 4 sqmm | 36 | 10 | RM |
36 | 360 | 4C x 6 sqmm | 37 | 10 | RM |
37 | 370 | 4C x 10 sqmm | 38 | 10 | RM |
38 | 380 | Supply of FRLS Armoured Aluminium Power cable as per tender specifications. | 39 | ||
39 | 390 | 3.5C x 120 sqmm | 40 | 10 | RM |
40 | 400 | Supply of FRLS Armoured Copper Control cable as per tender specifications. | 41 | ||
41 | 410 | 2C x 1.5 sqmm | 42 | 10 | RM |
42 | 420 | 3C x 1.5 sqmm | 43 | 10 | RM |
43 | 430 | 4C x 1.5 sqmm | 44 | 10 | RM |
44 | 440 | 6C x 1.5 sqmm | 45 | 10 | RM |
45 | 450 | 8C x 1.5 sqmm | 46 | 10 | RM |
46 | 460 | 10C x 1.5 sqmm | 47 | 10 | RM |
47 | 470 | 12C x 1.5 sqmm | 48 | 10 | RM |
48 | 480 | 16C x 1.5 sqmm | 49 | 10 | RM |
49 | 490 | 18C x 1.5 sqmm | 50 | 10 | RM |
50 | 500 | 20C x 1.5 sqmm | 51 | 10 | RM |
51 | 510 | 24C x 1.5 sqmm | 52 | 10 | RM |
52 | 520 | 32C x 1.5 sqmm | 53 | 10 | RM |
53 | 530 | 36C x 1.5 sqmm | 54 | 10 | RM |
54 | 540 | 48C x 1.5 sqmm | 55 | 10 | RM |
55 | 550 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. | 56 | ||
56 | 560 | 1P x 1.5 sqmm | 57 | 10 | RM |
57 | 570 | 2P x 1.5 sqmm | 58 | 10 | RM |
58 | 580 | 3P x 1.5 sqmm | 59 | 10 | RM |
59 | 590 | 4P x 1.5 sqmm | 60 | 10 | RM |
60 | 600 | 6P x 1.5 sqmm | 61 | 10 | RM |
61 | 610 | 8P x 1.5 sqmm | 62 | 10 | RM |
62 | 620 | 10P x 1.5 sqmm | 63 | 10 | RM |
63 | 630 | 12P x 1.5 sqmm | 64 | 10 | RM |
64 | 640 | 16P x 1.5 sqmm | 65 | 10 | RM |
65 | 650 | 18P x 1.5 sqmm | 66 | 10 | RM |
66 | 660 | 1T x 1.5 sqmm | 67 | 10 | RM |
67 | 670 | 8T x 1.5 sqmm | 68 | 10 | RM |
68 | 680 | Supply of FS Armoured Copper Power cable as per tender specifications. | 69 | ||
69 | 690 | 3C x 2.5 sqmm | 70 | 10 | RM |
70 | 700 | 3C x 4 sqmm | 71 | 10 | RM |
71 | 710 | 4C x 2.5 sqmm | 72 | 10 | RM |
72 | 720 | 4C x 4 sqmm | 73 | 10 | RM |
73 | 730 | Supply of FS Armoured Copper Control cable as per tender specifications. | 74 | ||
74 | 740 | 2C x 1.5 sqmm | 75 | 10 | RM |
75 | 750 | 3C x 1.5 sqmm | 76 | 10 | RM |
76 | 760 | 4C x 1.5 sqmm | 77 | 10 | RM |
77 | 770 | 6C x 1.5 sqmm | 78 | 10 | RM |
78 | 780 | 8C x 1.5 sqmm | 79 | 10 | RM |
79 | 790 | 10C x 1.5 sqmm | 80 | 10 | RM |
80 | 800 | 12C x 1.5 sqmm | 81 | 10 | RM |
81 | 810 | 18C x 1.5 sqmm | 82 | 10 | RM |
82 | 820 | 24C x 1.5 sqmm | 83 | 10 | RM |
83 | 830 | 32C x 1.5 sqmm | 84 | 10 | RM |
84 | 840 | 36C x 1.5 sqmm | 85 | 10 | RM |
85 | 850 | 48C x 1.5 sqmm | 86 | 10 | RM |
86 | 860 | Supply of FS Armoured Copper Signal cable as per tender specifications. | 87 | ||
87 | 870 | 1P x 1.5 sqmm | 88 | 10 | RM |
88 | 880 | 2P x 1.5 sqmm | 89 | 10 | RM |
89 | 890 | 3P x 1.5 sqmm | 90 | 10 | RM |
90 | 900 | 4P x 1.5 sqmm | 91 | 10 | RM |
91 | 910 | 1T x 1.5 sqmm | 92 | 10 | RM |
92 | 920 | Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. | 93 | 10 | RM |
93 | 930 | Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. | 94 | 10 | RM |
94 | 940 | Supply of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. | 95 | ||
95 | 950 | 10 m | 96 | 10 | EA |
96 | 960 | 15 m | 97 | 10 | EA |
97 | 970 | 20 m | 98 | 10 | EA |
98 | 980 | 25 m | 99 | 10 | EA |
99 | 990 | 30 m | 100 | 10 | EA |
100 | 1000 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document | 101 | 10 | RM |
101 | 1010 | Supply of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | 102 | 10 | RM |
102 | 1020 | Supply of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. | 103 | ||
103 | 1030 | 50 mm | 104 | 820 | RM |
104 | 1040 | 100 mm | 105 | 520 | RM |
105 | 1050 | 150 mm | 106 | 370 | RM |
106 | 1060 | 300 mm | 107 | 125 | RM |
107 | 1070 | 600 mm | 108 | 10 | RM |
108 | 1080 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. | 109 | ||
109 | 1090 | 24 ways JB | 110 | 2 | EA |
110 | 1100 | 18 ways JB | 111 | 10 | EA |
111 | 1110 | 12 ways JB | 112 | 2 | EA |
112 | 1120 | 8 ways JB | 113 | 1 | EA |
113 | 1130 | 6 ways JB | 114 | 1 | EA |
114 | 1140 | 4 ways JB | 115 | 1 | EA |
115 | 1150 | Supply of hot dip GI earth strip ( 50 X 6) within earth station. Hot dip galvanizing (800 gm/m2 as per IS 4759) shall be done after all fabrication. | 116 | 300 | RM |
116 | 1160 | Supply of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | 117 | 500 | RM |
117 | 1170 | Earth Pit Supply of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length T45 model/equivalent safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation \nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) | 118 | 6 | EA |
118 | 1180 | Supply of Glands / adopters for each ROSOV/DBBV | 119 | 40 | EA |
119 | 1190 | Supply of 25 HP Pump Star Delta starter in exsisting MCC feeder | 120 | 5 | EA |
120 | 1200 | PART-V PUMP HOUSE | 121 | ||
121 | 1210 | Supply of required Automation for pump House complete as per site requirements. Automation including ESD actuation, pump control as per tank level, pump status and allied work for pump house. Item also includes all the required auxiliary contacts and all other necessary hardware for proper working. -PUMPHOUSE | 122 | 5 | EA |
122 | 1220 | Supply of FLP DC Glands for 3.5C X 120 sq mm cable for pumps | 123 | 5 | EA |
123 | 1230 | Supply of Non FLP Glands for 3.5C X 120 sq mm cable for pumps | 124 | 5 | EA |
124 | 1240 | Supply of Pipe and pipe fittings maximum upto 3" for TLF bay bay modification and Density meter installation | 125 | 1 | LS |
125 | 1250 | Supply of NPT/ET Double Compression FLP Glands (1/2"/ 3/4"/ 1") | 126 | 100 | EA |
126 | 1260 | SERVICE COMPONENTS | 127 | ||
127 | 1270 | Installation, testing and commissioning of double Case Positive Displacement Meter of size 80 mm with Pulse Transmitter in Flameproof and Weather Proof (IP 65) enclosure | 129 | 3 | EA |
128 | 1280 | Installation, Integration, Testing and Commissioning of Strainer cum Air eliminator alongwith differential pressure gauge across the Strainer Cum Air Eliminator along with accessories, SS tubing, needle valves. For product line size 80 mm - TLF\n | 130 | 3 | EA |
129 | 1290 | Installation, Integration, Testing and Commissioning of Multistage Digital Control Valve (DCV). For product line size 80 mm - TLF | 131 | 3 | EA |
130 | 1300 | Installation, Testing and Commissioning of top loading arm of size 80 mm NB along with 1 no. full bore isolation ball valve (80 mm). | 132 | 3 | EA |
131 | 1310 | Integration,Testing and Commissioning of Tank Truck grounding unit (Earthing Relay/Device ) | 133 | 3 | EA |
132 | 1320 | Installation, Integration, Testing and Commissioning of Ex-proof field mounted Remote Interaction Terminal (RIT) alongwith FLP double compression glands and ExProof-plugs | 134 | 3 | EA |
133 | 1330 | Installation, Integration, Configuration, Testing and Commissioning of Microprocessor based Field mounted dual arm Batch Controller | 135 | 3 | EA |
134 | 1340 | Installation, Integration, Testing and Commissioning of intrinsically safe / flameproof type proximity card reader | 136 | 6 | EA |
135 | 1350 | Installation, Integration, Testing and Commissioning of 3M barrier gates.TLF gantry entry gates | 137 | 2 | SET |
136 | 1360 | Installation, Integration, Testing and Commissioning of barrier gate traffic lamps (Red, Amber & Greeen LED Cluster type) | 138 | 2 | SET |
137 | 1370 | Design, Installation, Configuration, Testing & Commissioning of Complete Terminal Automation Software for LRCS and Operator work Stations with dongle/key, licenses, media, documentation, including equipment fault detection module / software etc complete as per specifications and tender documents. Vendor to provide the complete software to meet the Terminal Automation System as per tender scope of work and requirements. | 139 | 1 | LS |
138 | 1380 | Installation, integration, testing and commissioning of LED monitor of minimum 42" along with required hardware and software for interfacing with TAS | 140 | 1 | EA |
139 | 1390 | Installation, integration, testing and commissioning of weather proof Single line LED display board (Minimmum 1 line x 25 mm Character height x 11 characters per line) for outdoor application near Security Gate | 141 | 1 | EA |
140 | 1400 | Installation, Powering, Testing and Commissioning of single phase FLP socket with cover at alternate bay alongwith mounting accessories for powering master meter skid | 142 | 2 | EA |
141 | 1410 | Installation & commissioning of Density meter | 143 | 2 | No |
142 | 1420 | Installtion of HART Gateway | 144 | 2 | No |
143 | 1430 | Installation of Restriction Orifice Plate including flages | 145 | 2 | EA |
144 | 1440 | Installation, Integration, Testing and Commissioning of flameproof cum weather proof, min SIL 2 smart pressure transmitter with display unit, SS manifold,1 no isolation ball valve | 146 | 2 | EA |
145 | 1450 | Installation, Integration, Testing and Commissioning of flameproof cum weather proof, min SIL 2 smart temperature transmitter with display unit, SS manifold,1 no isolation ball valve | 147 | 1 | EA |
146 | 1460 | Tank Farm Management System Installation, Integration, Testing and Commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better | 148 | 4 | EA |
147 | 1470 | Installation, Integration, Testing and Commissioning of pressure transmiter For Water Tanks (2 nos.) | 149 | 2 | EA |
148 | 1480 | Installation, Integration, Testing and Commissioning of Pressure transmiter along with accessories etc for density measurement of the product | 150 | 4 | EA |
149 | 1490 | Installation, Integration, Testing and Commissioning of Tank Side indicator along with mounting accesories etc for TFM system for displaying inventory data complete as per specification and tender document. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) For Vertical Product tanks - (Primary & Secondary Radar Gauges) | 151 | 4 | EA |
150 | 1500 | Installation, Integration, Testing and Commissioning of top mounted minimum SIL2 certified Overspill detector (vibrating fork type) of suitable probe length For Vertical Product tanks | 152 | 4 | EA |
151 | 1510 | Installation, Integration, Testing and Commissioning of parallel redundant Communication Interface Units (CIU) including all accessories etc for tank farm management system complete as per specification and tender document. For Primary Radar gauges, Radar Gauges installed in under ground tank, water tank & Sludge tank | 153 | 2 | SET |
152 | 1520 | Installation, Integration, Configuration, Testing and Commissioning of TFMS Workstation with minimum 23" LED colour monitor, standard keyboard, mouse, Licensed OS(latest supported by TFMS software), Licenced Antivirus, Licenced latest MS Office proffestional, TFMS licensed client software from same Radar Gauge OEM at Control Room | 154 | 1 | EA |
153 | 1530 | Tower type at TM's room | 155 | 1 | EA |
154 | 1540 | Control Room equipments Design, Engineering, Setup, Configuration, Integration with TAS, Installation, Testing & Commissioning of Dual redundant (Parallel/ Hot Standby) Programmable Logic Controller (Process PLC) along with PLC Panels, Marshalling Panels, | 156 | 1 | LS |
155 | 1550 | Design, Engineering, Set-up, Installation, Configuration, testing & Commissioning of two nos. of Load Rack Computers (LRC Servers ) | 157 | 1 | LOT |
156 | 1560 | Installation, Configuration, Integration, Testing and Commissioning of Operator Interface Console Computer (OIC) minimum 23" color LED monitor, standard keyboard, mouse, client software, SCADA, OS, Antivirus, MS office professional | 158 | 2 | EA |
157 | 1570 | Tower mounted type in TM's Cabin and Invoice Room ( 1 no OIC in TM cabin, 1 no. OIC In Invoice room) | 159 | 1 | Ea |
158 | 1580 | Installation, Integration, Configuration, Testing and Commissioning of Terminal servers \nNote: Terminal Server to be configured in Dual Redundant mode. 8 ports at Control Room | 160 | 2 | EA |
159 | 1590 | Installation, Testing and Commissioning of UPS Power Distribution Panel | 161 | 1 | EA |
160 | 1600 | Installation of Ethernet Switch | 162 | 4 | EA |
161 | 1610 | Installtion of printers | 163 | 2 | EA |
162 | 1620 | Push Buttons Outside Dyke Walls Installation, Integration, Testing and Commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for open and close of ROSOVs and DBBVs (tank's inlet and outlet line) | 164 | 16 | EA |
163 | 1630 | ESD PUSH BUTTON STATION Installation, Integration, Testing and Commissioning of Exd/FLP ESD push button stations, mushroom head type, with protection cover to avoid accidental activation alongwith mounting structure complete as per specification and tender document. Local ESD Push Button Station | 165 | 4 | EA |
164 | 1640 | Installation, Integration, Testing and Commissioning of ESD push button stations (for indoor application), mushroom head type with protection cover to avoid accidental activation alongwith mounting structure complete as per specification and tender document. (control room - 1 no., security room - 1 no., TM's cabin - 1 no.) | 166 | 3 | EA |
165 | 1650 | Installation, Configuration, Integration, Testing and Commissioning of Wailing siren | 167 | 1 | LS |
166 | 1660 | Installation, Configuration, Integration, Testing and Commissioning of Ex-proof and weather proof Hooter cum Beacons\nLocation : Near each tank dyke to be installed outside dyke. | 168 | 3 | EA |
167 | 1670 | Installation of MCT block for entire Automation cable entry to Control Room, Security Room with minimum 30% spare MCT blocks for furture cable entry alongwith frame and mounting accessories. | 169 | 1 | LS |
168 | 1680 | Fabrication of MS structural Steel | 170 | 3 | TON |
169 | 1690 | Laying of hot dip GI earth strip ( 50 X 6) within earth station. Hot dip galvanizing (800 gm/m2 as per IS 4759) shall be done after all fabrication. | 171 | 300 | RM |
170 | 1700 | Cabling, JB, Earthing: | 172 | ||
171 | 1710 | Note: laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc | 173 | ||
172 | 1720 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. | 174 | ||
173 | 1730 | 3C x 2.5 sqmm | 175 | 10 | RM |
174 | 1740 | 4C x 2.5 sqmm | 176 | 10 | RM |
175 | 1750 | 8C x 2.5 sqmm | 177 | 10 | RM |
176 | 1760 | 10C x 2.5 sqmm | 178 | 10 | RM |
177 | 1770 | 12C x 2.5 sqmm | 179 | 10 | RM |
178 | 1780 | 24C x 2.5 sqmm | 180 | 10 | RM |
179 | 1790 | 3C x 4 sqmm | 181 | 10 | RM |
180 | 1800 | 4C x 4 sqmm | 182 | 10 | RM |
181 | 1810 | 4C x 6 sqmm | 183 | 10 | RM |
182 | 1820 | 4C x 10 sqmm | 184 | 10 | RM |
183 | 1830 | Laying, glanding, ferruling, termination of FRLS Armoured Aluminium Power cable as per tender specifications. | 185 | ||
184 | 1840 | 3.5C x 120 sqmm | 186 | 10 | RM |
185 | 1850 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. | 187 | ||
186 | 1860 | 2C x 1.5 sqmm | 188 | 10 | RM |
187 | 1870 | 3C x 1.5 sqmm | 189 | 10 | RM |
188 | 1880 | 4C x 1.5 sqmm | 190 | 10 | RM |
189 | 1890 | 6C x 1.5 sqmm | 191 | 10 | RM |
190 | 1900 | 8C x 1.5 sqmm | 192 | 10 | RM |
191 | 1910 | 10C x 1.5 sqmm | 193 | 10 | RM |
192 | 1920 | 12C x 1.5 sqmm | 194 | 10 | RM |
193 | 1930 | 16C x 1.5 sqmm | 195 | 10 | RM |
194 | 1940 | 18C x 1.5 sqmm | 196 | 10 | RM |
195 | 1950 | 20C x 1.5 sqmm | 197 | 10 | RM |
196 | 1960 | 24C x 1.5 sqmm | 198 | 10 | RM |
197 | 1970 | 32C x 1.5 sqmm | 199 | 10 | RM |
198 | 1980 | 36C x 1.5 sqmm | 200 | 10 | RM |
199 | 1990 | 48C x 1.5 sqmm | 201 | 10 | RM |
200 | 2000 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. | 202 | ||
201 | 2010 | 1P x 1.5 sqmm | 203 | 10 | RM |
202 | 2020 | 2P x 1.5 sqmm | 204 | 10 | RM |
203 | 2030 | 3P x 1.5 sqmm | 205 | 10 | RM |
204 | 2040 | 4P x 1.5 sqmm | 206 | 10 | RM |
205 | 2050 | 6P x 1.5 sqmm | 207 | 10 | RM |
206 | 2060 | 8P x 1.5 sqmm | 208 | 10 | RM |
207 | 2070 | 10P x 1.5 sqmm | 209 | 10 | RM |
208 | 2080 | 12P x 1.5 sqmm | 210 | 10 | RM |
209 | 2090 | 16P x 1.5 sqmm | 211 | 10 | RM |
210 | 2100 | 18P x 1.5 sqmm | 212 | 10 | RM |
211 | 2110 | 1T x 1.5 sqmm | 213 | 10 | RM |
212 | 2120 | 8T x 1.5 sqmm | 214 | 10 | RM |
213 | 2130 | Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. | 215 | ||
214 | 2140 | 3C x 2.5 sqmm | 216 | 10 | RM |
215 | 2150 | 3C x 4 sqmm | 217 | 10 | RM |
216 | 2160 | 4C x 2.5 sqmm | 218 | 10 | RM |
217 | 2170 | 4C x 4 sqmm | 219 | 10 | RM |
218 | 2180 | Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. | 220 | ||
219 | 2190 | 2C x 1.5 sqmm | 221 | 10 | RM |
220 | 2200 | 3C x 1.5 sqmm | 222 | 10 | RM |
221 | 2210 | 4C x 1.5 sqmm | 223 | 10 | RM |
222 | 2220 | 6C x 1.5 sqmm | 224 | 10 | RM |
223 | 2230 | 8C x 1.5 sqmm | 225 | 10 | RM |
224 | 2240 | 10C x 1.5 sqmm | 226 | 10 | RM |
225 | 2250 | 12C x 1.5 sqmm | 227 | 10 | RM |
226 | 2260 | 18C x 1.5 sqmm | 228 | 10 | RM |
227 | 2270 | 24C x 1.5 sqmm | 229 | 10 | RM |
228 | 2280 | 32C x 1.5 sqmm | 230 | 10 | RM |
229 | 2290 | 36C x 1.5 sqmm | 231 | 10 | RM |
230 | 2300 | 48C x 1.5 sqmm | 232 | 10 | RM |
231 | 2310 | Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. | 233 | ||
232 | 2320 | 1P x 1.5 sqmm | 234 | 10 | RM |
233 | 2330 | 2P x 1.5 sqmm | 235 | 10 | RM |
234 | 2340 | 3P x 1.5 sqmm | 236 | 10 | RM |
235 | 2350 | 4P x 1.5 sqmm | 237 | 10 | RM |
236 | 2360 | 1T x 1.5 sqmm | 238 | 10 | RM |
237 | 2370 | laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. | 239 | 10 | RM |
238 | 2380 | laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. | 240 | 10 | RM |
239 | 2390 | laying, glanding, ferruling, termination of Pre fab CAT 6 Ethernet un-armoured cable as per tender specifications and instructions of Engineer in charge. | 241 | ||
240 | 2400 | 10 m | 242 | 10 | EA |
241 | 2410 | 15 m | 243 | 10 | EA |
242 | 2420 | 20 m | 244 | 10 | EA |
243 | 2430 | 25 m | 245 | 10 | EA |
244 | 2440 | 30 m | 246 | 10 | EA |
245 | 2450 | laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document | 247 | 10 | RM |
246 | 2460 | Fabrication , cutting , laying & connection of GI strip ( 25mm X 3mm) with Hot dip galvanizing (800 gm/m2 as per IS 4759) along with accessories required for complete Terminal Automation System as per Standard Design Engineering, specification and tender document. | 248 | 10 | RM |
247 | 2470 | Laying of anodized Aluminium perforated cable trays (2.5mm Thick and 25mm edge height), tray covers (1.5mm Thick and 10 mm edge height) along with structural steel for mounting of the cable tray. Complete as per specifications / tender documents. | 249 | ||
248 | 2480 | 50 mm | 250 | 820 | RM |
249 | 2490 | 100 mm | 251 | 520 | RM |
250 | 2500 | 150 mm | 252 | 370 | RM |
251 | 2510 | 300 mm | 253 | 125 | RM |
252 | 2520 | 600 mm | 254 | 10 | RM |
253 | 2530 | Installation of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. | 255 | ||
254 | 2540 | 24 ways JB | 256 | 2 | EA |
255 | 2550 | 18 ways JB | 257 | 10 | EA |
256 | 2560 | 12 ways JB | 258 | 2 | EA |
257 | 2570 | 8 ways JB | 259 | 1 | EA |
258 | 2580 | 6 ways JB | 260 | 1 | EA |
259 | 2590 | 4 ways JB | 261 | 1 | EA |
260 | 2600 | Laying of 50 mm HDPE pipe of minimum 2.5 mm thick along with accessories as per tender specifications and instructions of Engineer in charge. | 262 | 500 | RM |
261 | 2610 | Earth Pit Installation, Testing and Commissioning of Maintenance Free CPRI approved Earth pit ( Ashlok /Equivalent make ) as per IS : 3043 with 100 mm dia of minimum 3mtr length T45 model/equivalent safe earthing electrode with Pipe-in-pipe technology consisting of two mild steel pipes one inside the other, hot dip galvanized (80-100 microns), filled with high conductive & corrosion resistance crystalline mixture and backfilling compound around electrode, 25 mm dia G.I. watering pipe with funnel, test link, brick masonry earth pit including plastering in CM 1:4, 600x600 mm C.I. Manhole chamber including providing suitable earth bus for interconnection etc. Equivalent make shall be approved by client / consultants. Procedure recommended by chemical earth supplier and IS code to be finally adopted. Item also includes provision of earth station flags with pit nos and date of inspection and the next due date of inspection. Job also includes provision of test certificate of earthing station from a licensed electrician as per the format of the Corporation \nAll Instruments, JBs, Equipments in Field and CCR shall be earthed by 6 mm2 PVC insulated copper cable to nearest Insulated copper Earth Bus bar ( minimum size 25 mm x 6 mm ) and this earth bar shall be connected to earth pit by redundant Multi stranded copper cable (Min 25 mm2 ). Signal and Power earth shall be separate as per specification) | 263 | 10 | EA |
262 | 2620 | Installation of Glands / adopters for each ROSOV/DBBV | 264 | 40 | EA |
263 | 2630 | PUMP HOUSE | 265 | ||
264 | 2640 | Installation, Testing & Commissioning of required Automation for pump House as per site requirements. | 266 | 1 | LS |
265 | 2650 | Installation, glanding & Termination (1/2"/ 3/4" / 1") of supplied FLP Glands | 267 | 1 | LS |
266 | 2660 | Comphrehensive AMC | 268 | ||
267 | 2670 | Comprehensive Annual Maintenance Contract for a period of Seven years for entire Terminal Automation System after successful completion of SAT as described Technical Bid. \nCost of all the required spares, hardwares, software modification, tools and tackles, ladders, labours, Preventive & Breakdown maintenance Service, calibration of instruments, proving & stampings of metering equipments, rectification/ replacement of faulty TAS equipment etc required for running and maintenance of the entire Terminal Automation System to the desired performance level throughout the contract period of CAMC is included in the item rates and the same has to be borne by the Vendor. \nThe scope also includes posting of Resident Engineer (s) to take care of running and maintenance of the entire Automation System complete as per the tender document. | 269 | ||
268 | 2680 | CAMC for First Year @4% of the CAPEX cost including GST | 270 | 1 | EA |
269 | 2690 | CAMC for Second Year @4% of the CAPEX cost including GST | 271 | 1 | EA |
270 | 2700 | CAMC for Third Year @7% of the CAPEX cost including GST | 272 | 1 | EA |
271 | 2710 | CAMC for Fourth Year @7% of the CAPEX cost including GST | 273 | 1 | EA |
272 | 2720 | CAMC for Fifth Year @10% of the CAPEX cost including GST | 274 | 1 | EA |
273 | 2730 | CAMC for Sixth Year @6% of the CAPEX cost including GST | 275 | 1 | EA |
274 | 2740 | CAMC for Seventh Year @12% of the CAPEX cost including GST | 276 | 1 | EA |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy