Tripura State Electricity Corporation Limited-TSECL has published Distribution System Improvement Turnkey Contract For Supply And Construction Of New / Augmentation Of 33Kv / 11Kv / Lt Lines In Tripura -Package Ii- Lot 3. Submission Date for this Tender is 03-07-2021. Overhead Line Tenders in Across the State of Tripura Tripura. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 19-May-2021 | Corrigendum for Online Pre Bid Meeting | Other | 18-06-2021 |
2 | 21-May-2021 | Corrigendum Tech1 | Technical Bid | 18-06-2021 |
3 | 02-Jun-2021 | Corrigendum for Time Extension | Date | 25-06-2021 |
4 | 07-Jun-2021 | BoQ Corrigendum | BOQ | 25-06-2021 |
5 | 23-Jun-2021 | Time Extension2 | Date | 03-07-2021 |
6 | 29-Jun-2021 | Technical Bid Corrigendum | Technical Bid | 03-07-2021 |
7 | 30-Jun-2021 | Modified Corrigendum | Technical Bid | 03-07-2021 |
Sl. No. | Item Description |
1 | Sch-A2 :Schedule of Quantities for 11 kV UG Cable Lines ( New and Conversion of Existing OH Lines) |
2 | 6.35/11 kV (E)grade,Al conductor, TR-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 3-core/ 240 Sqmm |
3 | Termination kit for11 kV Grade, 3-core, 240 Sq.mm, Al conductor, Tr-XLPE insulated, screened, armoured, PVC sheathed power cable,outdoor / heat-shrinkable type including screen and armour earth kits, all accessories andlugs. |
4 | Straight through jointing kit for 11 kV Grade, 3-core, 240 Sq.mm,Al conductor, Tr-XLPE insulated , screened, armoured, PVC sheathed power cable,cold-shrink type including termite proofing mesh and all accessories |
5 | 125 mm dia HDPE pipe, PE-100 material grade, SDR 19, wall thickness 7.4 mm (min) inclusing coupling as required. |
6 | GI pipe , medium class, 125 mm dia. (For Road Crossings) |
7 | Duct sealing material / kit for duct dia 125 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables . |
8 | RCC Cable Protection Tiles 500 X 250X 35mmwith"DANGER - ELECTRICITY" mark |
9 | Cable route marker, plate type 100 mm dia with 60 cm shaft with helix, Marking " 11 kV Cable" and direction arrows. |
10 | Cable Termination at Substations / DTR on existing single / double pole structures |
11 | 11 kV lightning Arrestertor (Distribution Class), 9 kV, 10 KA with earth lead disconnector and GI mounting frame, GI bolts and nuts and all accessories |
12 | G.I. Channel cross arm 100x50x6x2200 mm |
13 | UPG Clamp for ACSR Racoon conductor |
14 | G.I. Earth pipe, 40mm dia x 2.5 mt. Longwith earth conductor clamp including eathing compound for earth pit backfill |
15 | G.I. Wire 8 SWG for earthing |
16 | Corrugated flexible protection conduit for electrical cables, 125 mm dia, polyamide or other UV andabrasion-resistant material, including cable glands |
17 | GI pipe , medium class, 125 mm dia. |
18 | C-clamp for GI Pipe, 50x5 mm, 125 mm Dia |
19 | G.ITop Pole Clamp- Type C11-1 |
20 | G.I. Nuts & bolts with spring washers- assorted sizes |
21 | Mandatory Spares, tools and instruments |
22 | 6.35/11 kV (E)grade,Al conductor, TR-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 3-core/ 240 Sqmm |
23 | Duct sealing material / kit for duct dia 125 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables . |
24 | Schedule A3 : Schedule of Quantities for construction of new 33 kV Covered Conductor Single Circuit Lines |
25 | Galvanized Steel Tubular Pole 540 SP-66 - 12 mtrs (For Cradle Guarding for line crossing ) |
26 | Galvanized Steel Tubular Pole 540 SP-57 - 11 mtrs |
27 | G.I. Channel cross arm 100x50x6x3150 mm |
28 | GI Channel top bracket, 100x50×6×310mm (for top pin insulator) |
29 | G.I Channel cross arm 100x50x6x1570 mm |
30 | Cross arm bottom Support GI V bracket , Type C12-V (for single pole cross arm) |
31 | 33 kV Composite (Polymer) Tension Insulator, 45 kN with all accessories |
32 | 33 kV Composite Insulator Tension Hardware, 45 kN suitable for stringing covered conductor including all accessories |
33 | Insulating Piercing Connector - 33 kV CC to CC (100 sqmm) |
34 | 33KV Composite (Polymeric) Pin Insulatortie top type including all accessories |
35 | Non-metallic helical ties for covered conductor |
36 | Insulating Piercing Connector for 33 kV CC (100 sqmm CC- 8 SWG GI wire for LA ) |
37 | Lightning Arrester (Distribution Class) with polymer housing (suitable for CC),30 kV , 10 KA, with earth lead disconnector and channel mounting brackets. MCOV : 25 kV or as recommended by CC manufacturer |
38 | Insulated Tension Mid Span Joint /Repair Sleeve for 33 kV Covered Conductor (100 sqmm) |
39 | Insulating Piercing Connector for 33 kV CC (100 sqmm) to Bare ( 75-150 sqmm) |
40 | 33 kV 100 sqmm Covered Conductor End Seal Caps, heat or cold shrink type |
41 | 33KVCovered Conductor Triple Layer Type with AAAC 100 Sqmm (or 99 sqmm) conductor |
42 | 33 kV G.I Cross Bracing Set made of G.I angles 65x 65x 6 mm , X-type, single Tier (Type : C12-XB) |
43 | G.I. Earth pipe, 40mm dia x 2.5 mt. Longwith earth conductor clamp including eathing compound for earth pit backfill |
44 | G.I. Wire 8 SWG for earthing |
45 | H.T. galvanized stay setincluding anchor plate (300x300x8), nut bolts,turn buckles,1.8 m long 20 mm dia. Solid GS Stay Rod, Thimble complete |
46 | H.T. Guy insulator 88KN |
47 | G.I Stay wire 7/10 SWG |
48 | 33KV Danger plate with clamps |
49 | G.ITop Pole Clamp- Type C12-1 |
50 | G.IMiddle Pole Clamp - Type C12-2 |
51 | G.IBottom Pole clamp - Type C12-3 |
52 | G.I Stay Clamp - Type C12-S |
53 | G.I. Nuts & bolts with spring washers- assorted sizes |
54 | G.I Barbed wire 12 SWG |
55 | Stone Pad, 450x450x50 mm |
56 | Concreting Materials, M15 Grade, 0.35 cum per pole including muffling above GL 300 mm |
57 | Concreting Materials, M15 Grade, 0.2 cum per stay |
58 | Painting Materials for pole numbering per pole (Area 150 x 200 mm) |
59 | MANDATORY SPARE PARTS |
60 | Insulated Tension Mid Span Joint /Repair Sleeve for Covered Conductor (100 sqmm) |
61 | 33KVCovered Conductor AAAC 100 Sqmm (or 99 sqmm) |
62 | Insulating Piercing Connector for 33 kV CC- CC to CC (100 sqmm) |
63 | Insulating Piercing Connector for 33 kV CC -100 sqmm- Earthing (8 SWG) |
64 | Insulating Piercing Connector for 33 kV CC (100 sqmm) to Bare ( 75-150 sqmm) |
65 | Lightning Arrester (Distribution Class) with polymer housing (suitable for CC),30 kV , 10 KA, with earth lead disconnector and channel mounting brackets. MCOV : 25 kV or as recommended by CC manufacturer |
66 | SSchedule A4 : Schedule of Quantities for new11 kV Covered Conductor S/C Lines including existing line replacements |
67 | Galvanized Steel Tubular Pole 540 SP-57 - 11 mtrs |
68 | G.I. Channel cross arm 100x50x6x2200 mm |
69 | GI Channel top bracket, 100x50×6×310mm (for top pin insulator) |
70 | G.I Channel cross arm 100x50x6x1570 mm |
71 | Cross arm bottom Support GI V bracket , Type C11-V (for single pole cross arm) |
72 | 11 kV Composite (Polymer) Tension Insulator, 45 kN with all accessories |
73 | 11 kV Composite Insulator Tension Hardware, 45 kN suitable for stringing covered conductor including all accessories |
74 | Insulating Piercing Connector for 11 kV CC to CC (70 sqmm) |
75 | 11KV Composite (Polymeric) Pin Insulatortie top type including all accessories |
76 | Non-metallic helical ties for covered conductor |
77 | Insulating Piercing Connector for 11 kV CC : 70 sqmm CC- 8 SWG GI wire for LA |
78 | Lightning Arrester (Distribution Class) with polymer housing (suitable for CC),9 kV , 10 KA, with earth lead disconnector and channel mounting brackets. MCOV : 7.65 kV or as recommended by CC manufacturer |
79 | Insulated Tension Mid Span Joint /Repair Sleeve for 11 kV Covered Conductor (70 sqmm) |
80 | Insulating Piercing Connector for 11 kV CC (70 sqmm) to Bare ( 75-150 sqmm) |
81 | 11KVCovered Conductor Triple Layer Type with AAAC 70 Sqmm conductor |
82 | 11 kV 70 sqmm Covered Conductor End Seal Caps, heat or cold shrink type |
83 | 11 kV G.I Cross Bracing Set made of G.I angles 65x 65x 6 mm , X-type, single Tier (Type : C11-XB) |
84 | G.I. Earth pipe, 40mm dia x 2.5 mt. Longwith earth conductor clamp including eathing compound for earth pit backfill |
85 | G.I. Wire 8 SWG (for earthing) |
86 | H.T. galvanized stay setincluding anchor plate (300x300x8 mm), nut bolts,turn buckles,1.8 m long 20 mm dia. Solid GS Stay Rod, Thimble complete |
87 | H.T. Guy insulator 88KN |
88 | G.I Stay wire 7/10 SWG |
89 | 11 kV Danger plate with clamps |
90 | G.ITop Pole Clamp- Type C11-1 |
91 | G.IMiddle Pole Clamp - Type C11-2 |
92 | G.IBottom Pole clamp - Type C11-3 |
93 | G.I Stay Clamp - Type C11-S |
94 | G.I. Nuts & bolts with spring washers- assorted sizes |
95 | G.I Barbed wire 12 SWG |
96 | Stone Pad, 450x450x50 mm |
97 | Concreting Materials, M15 Grade, 0.35 cum per pole including muffling above GL 300 mm |
98 | Concreting Materials, M15 Grade, 0.2 cum per stay |
99 | Painting Materials for pole numbering per pole (Area 150 x 200 mm) |
100 | ADDITIONAL ITEMS FORCRADLE GUARDING FOR LINE CROSSING (0.5X0.33 m GI wire mesh, Double Pole Section - 50 MTR) - 01 NO PER 6 CKM |
101 | G.I. Guard Angles (65×65x6mm-2.2 m) |
102 | G.I. Flat back clamp (50x6xmm - 2.2 m) |
103 | G.I. Eye Bolt-16 mm |
104 | G.I . Turn Buckle |
105 | G.I. Wire 8 SWG (for guarding and grounding ) |
106 | G.I. wire 6 SWG (for guarding) |
107 | MANDATORY SPARE PARTS |
108 | Insulated Tension Mid Span Joint /Repair Sleeve for 11 kV Covered Conductor (70 sqmm) |
109 | 11KVCovered Conductor Triple Layer Type with AAAC 70 Sqmm conductor |
110 | Insulating Piercing Connector for 11 kV CC to CC (70 sqmm) |
111 | Insulating Piercing Connector for 11 kV CC : 70 sqmm CC- 8 SWG GI wire for earthing |
112 | Insulating Piercing Connector for 11 kV CC (70 sqmm) to Bare ( 75-150 sqmm) |
113 | 11 kV Covered Conductor End Seal Caps, heat or cold shrink type |
114 | Lightning Arrester (Distribution Class) with polymer housing (suitable for CC),9 kV , 10 KA, with earth lead disconnector and channel mounting brackets. MCOV : 7.65 kV or as recommended by CC manufacturer |
115 | Schedule A5 : Schedule of Quantities for New LT ABC Lines and Conversion of existing LT lines to AB Conductor Lines |
116 | Galvanized Steel Tubular Pole 540 SP-33 - 9 mtrs |
117 | 1.1 kV XLPE/Al Cable with one Street LTG conductor and AAAC insulated messenger neutral - 3x70 sqmm + 1x50 sqmm + 1x16 sqmm |
118 | Anchoringclamp wedge type for ABC -3x70+1x50+1x16 sqmm (for terminations, large angles & branch lines) |
119 | Suspension clamp for ABC - 3x70+1x50+1x16 sqmm |
120 | Eye Hook for ABC anchoring / suspension clamps |
121 | GI Pole Clamps / Double SS straps for fixing Eye Hook to existing 8 m PCC Poles including GI B&N / Strap Buckles |
122 | GI Pole Clamps / Double SS straps for fixing Eye Hook to 8 m STP Poles including GI B&N / Strap Buckles |
123 | Pre- insulated mid span jointing sleeves - 1 set forABC - 3x70+1x50+1x16 sqmm |
124 | Pre-moldedpush on type end capsfor ABC - 3x70+1x50+1x16 sqmm |
125 | Insulated piercing connector for main - main connections, 25-95 / 25-95 sqmm |
126 | Insulated piercing connector 16-35 /16-35 sqmm (for street light conductor main-main connection) |
127 | Single phase LTABC Distribution Box1 incoming / 6 outgoing including accessories and GI clamps /SS straps for fixing with STP/PCC pole |
128 | Three phase LTABC Distribution Box 1 incoming / 4 outgoing including accessories and GI clamps /SS straps for fixing with STP/PCC pole |
129 | Insulated piercing connector for main - service taps, 25-95 / 6-35 sqmm |
130 | Insulated piercing connector for main - st lighting taps / earthing 16 -95 / 4-35 sqmm |
131 | 1x25 sqmm Al/PVC cable |
132 | 1x35 sqmm Al/PVC cable |
133 | Outdoor Three Phase Fuse-Switch-Disconnector with HRC fuse linksrated as recommended for thermal capacity of AB cable and solid link for neutral, pole mounting type with pole mounting brackets / double SS strapsfor STP / PCC poles |
134 | Pre-insulated lugs with bolts and nuts for 70 sqmm Al Conductors for terminating ABC cables at DTR bushing terminals or Dist. Boards |
135 | Pre-insulated lugs with bolts and nuts for 50 sqmm Al Conductors for terminating ABC cables at DTR bushing terminals or Dist. Boards |
136 | Pre-insulated lugs with bolts and nuts for 16 sqmm Al Conductors for terminating ABC cables at DTR bushing terminals or Dist. Boards |
137 | 2Cx6 sqmm Al/ PVC/PVC service cable |
138 | 4Cx10 sqmm Al/ PVC/PVC service cable |
139 | L.T. galvanized stay setincluding anchor plate (300x300x8), nut bolts,turn buckles,1.8 m long 16 mm dia. Solid GS Stay Rod, Thimble complete |
140 | L.T. Guy insulator |
141 | G.I Stay wire 7/12 SWG |
142 | GI Stay Clamps for 8 m STP / PCC Poles including bolts & Nuts |
143 | G.I Barbed wire 12 SWG |
144 | 20 mm dia, 1.8 mtr long GI Earth Rod includingconnecting clamps , bolts & nuts etc. |
145 | G.I. Wire 8 SWG (for earthing) |
146 | Stone Pad, 300x300x50 mm |
147 | Concreting Materials, M15 Grade, 0.25 cum per pole including muffling above GL 300 mm |
148 | Concreting Materials, M15 Grade, 0.2 cum per stay |
149 | Painting Materials for pole numbering per pole (Area 100 x 150 mm) |
150 | MANDATORY SPARE PARTS |
151 | Insulated piercing connector for main - main connections, 25-95 / 25-95 sqmm |
152 | Insulated piercing connector 16-35 /16-35 sqmm (for street light conductor main-main connection) |
153 | Insulated piercing connector for main - service taps, 25-95 / 6-35 sqmm |
154 | Insulated piercing connector for main - st lighting taps, 16 -95 / 4-35 sqmm |
155 | Pre- insulated mid span jointing sleeves - 1 set forABC - 3x70+1x50+1x16 sqmm |
156 | Single phase LTABC Distribution Box1 incoming / 6 outgoing including accessories and clamps for fixing with STP/PCC pole |
157 | Three phase LTABC Distribution Box 1 incoming / 4 outgoing including accessories and clamps for fixing with STP/PCC pole |
158 | Pre-moldedpush on type end capsfor ABC - 3x70+1x50+1x16 sqmm |
159 | Outdoor Three Phase Fuse-Switch-Disconnector with HRC fuse links rated as recommended for thermal capacity of AB cable, pole mounting type with pole mounting brackets / double SS strapsfor STP / PCC poles |
160 | Insulated Operating Rod for Outdoor Three Phase Fuse-Switch-Disconnector |
161 | HRC fuse links with blade contacts with fuse rating as per ABC manufacturer recommendations |