Provision Of Addl 12 Nos ( 2X6 ) Mortuary Chambers Including Pre-Fab Housing ( 8X5 Mtr ) And Other Connected B/R And E/M Works At Base Hospital Under Ge ( E/M ) Base Hospital Delhi Cantt-10, GE E/M BASE HOSPITAL DELHI CANTT-Delhi

Military Engineer Services-MES has published Provision Of Addl 12 Nos ( 2X6 ) Mortuary Chambers Including Pre-Fab Housing ( 8X5 Mtr ) And Other Connected B/R And E/M Works At Base Hospital Under Ge ( E/M ) Base Hospital Delhi Cantt-10. Submission Date for this Tender is 17-05-2021. Laboratory Cooling Equipment Tenders in GE E/M BASE HOSPITAL DELHI CANTT Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

27811979
Corrigendum : Provision Of Addl 12 Nos ( 2X6 ) Mortuary Chambers Including Pre-Fab Housing ( 8X5 Mtr ) And Other Connected B/R And E/M Works At Base Hospital Under Ge ( E/M ) Base Hospital Delhi Cantt-10
Open Tender
Indian
Delhi
GE E/M BASE HOSPITAL DELHI CANTT
17-05-2021

Tender Details

Provision Of Addl 12 Nos ( 2X6 ) Mortuary Chambers Including Pre-Fab Housing ( 8X5 Mtr ) And Other Connected B / R And E / M Works At Base Hospital Under Ge ( E / M ) Base Hospital Delhi Cantt-10

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-May-2021 AMENDMENT Other 17-05-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 98000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: PROVN OF ADDL 12 NOS (2X6) MORTUARY CHAMBERS INCLUDING PRE-FAB HOUSING (8X5 MTR) AND OTHER CONNECTED B/R AND E/M WORKS AT BASE HOSPITAL UNDER GE (E/M) BASE HOSPITAL, DELHI CANTT-10
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, installation commissioning and testing of york mortury chamber for capacity of 6 body having dimensions 2946mm wide, 2362mm deep, 1745 mm high unitary type refrigeration system, temperature range 2 to 6 °C, Power supply 230 Volts, vapour-proof incandescant lamp, electronic temperature indicator cum controller lamp,pre painted GI sheet for exterior and interior and stainless steel front finish complete all as specified and directed. Make: Blue Star/ iLABOT/ YATHERM SCIENTIFIC/ Carrier.\nNote: The Contractor shall be responsible for carrry out comprehensive maintenance for BOQ item No 1 above including replacement of all parts required to be replaced for the one year from the date of completion of work. The Contractor shall submit a letter from OEM in this regards to Engr-in-Charge with copy to User duly endorsed mobile No of the authorised rep to whom the complaints can be logged. The unit rates quoted against this item shall deemed to be including above provision and nothing shall be paid extra on this account. 2 Each Set
2 2 M&L point wiring for modular switches with 1.5 sqmm , single core , multi stranded copper conductor PVC insulated and unsheathed (FRLS) cable 1100 Volts grade, drawn through concealed Conduit as requirement of site including cadmium plated screws as per ISS, including replacement of 3 mm thick phenolic laminated sheet top covers on and including sunk type CI/steel terminal boxes concealed in wall including 1.5 Sqmm size pvc insulated unsheathed copper earth continuity conductor to common earth and connecting to earth dolly for One light point controlled by one switch 5 Amps one way single polecomplete all as specified and directed. 8 Per Point
3 3 All as per item No. 2 above but one fan point controlled by one switch 5 Amps one way single pole. 4 Per Point
4 4 All as per item No. 2 above but one three pin 5 Amps socket out let on same board. 1 Per Point
5 5 All as per item No. 2 above but point wiring of copper cable multi stranded 2.5 Sqmm size for 15 Amps socket outlet on independent board with 2.5 Sqmm size of earth conductor complete all as specified and directed. 1 Per Point
6 6 All as per item No. 2 above but point wiring of copper cable multi stranded 4.00 Sqmm size for AC point wiring with 4.0 Sqmm size of earth conductor complete all as specified and directed. 2 Per Point
7 7 S & F ceiling rose, PVC/ polycarbonate, isolated body type three terminal, 240 volt complete all as specified and directed. 8 Each
8 8 S&F Modular switch, flush button type, single pole, one way 10 Amps complete all as specified and directed. 11 Each
9 9 S&F in repair Modular switch, flush button type, single pole , one way 15 Amps complete all as specified and directed. 1 Each
10 10 S&F in repair Modular socket outlet 3 pin and 2 pin, 10 Amps, flush type complete all as specified and directed. 1 Each
11 11 S&F in repair Modular socket outlet 2-in-1, 3 pin, 10 and 20 Amps , flush type complete all as specified and directed. 1 Each
12 12 S&F sheet metal enclosure with socket plug top, single pole and neutral enclosure with a two pin earth plug and socket complete with one MCB of capacity 32 Amps, 240 Volts complete all as specified and directed. 2 Each
13 13 M & L Sub main wiring using two single core PVC insulated FRLS cable 4 sqmm copper conductor multi stranded and 4.0 sqmm copper conductor insulated cable using as earth wire and drawing in to PVC conduit 25mm dia complete all as specified and directed. \nNote: Two runs of 4sqmm copper FRLS cable & one run of 4.0 sqmm copper cable in and including 25mm PVC conduit medium grade will be measured as one unit. 20 RM
14 14 M & L Sub main wiring using two single core PVC insulated FRLS cable 6 sqmm copper conductor multi stranded and 6.0 sqmm copper conductor insulated cable using as earth wire and drawing in to PVC conduit 25mm dia complete all as specified and directed.. \nNote: Two runs of 6 sqmm copper FRLS cable & one run of 6.0 sqmm copper cable in and including 25 mm PVC conduit medium grade will be measured as one unit. 10 RM
15 15 M & L submain wiring using four run PVC insulated FRLS Copper conductor 10 sqmm with rigid non metalic PVC conduit of size 32 mm dia medium grade inclusive of boxes (junction/terminal) all tees, bends, elbows, reducers bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hook including all fixtures /fittings fixed on wall/ceiling with saddles PVC with earth continuity wire copper conductor PVC insulated unsheathed 10 Sq mm etc complete all as specified & directed.\nNote: four runs of 10 sqmm copper FRLS cable & one run of 10 sqmm copper cable in and including 32 mm PVC conduit medium grade will be measured as one unit. 10 RM
16 16 S & F load line distribution board double door type, TPN, vertical, 4 way, IP-43 complete suitable for MCB with incomming frame three pole, including bus bar, neutral link, blanking plates etc complete all as specified and directed.\nMake : Legrand Model: 507730 or equivalent model of Make Seimens/ Schneider/ ABB. 1 Each
17 17 S & F in repair MCB SP, 240 Volts, 63 Amps complete all as specified and directed. Make- Legrend Model No 408598 or equivalent model of make ABB/ Seimens/ Schneider 2 Each
18 18 S & F in repair MCB SP, 240 Volts, 6-32 Amps complete all as specified and directed. Make- Legrend model No 408587 to 408595 or equivalent model of make ABB/ Seimens/ Schneider 4 Each
19 19 S & F energy efficient LED light fitting 18/20 Watt,230 Volt of 1200 mm ± 50 mm length along with fixture, heat sink, environmental friendly, energy efficient, wall mounted batten integrated electronic driver complete all as specified and directed. \n 8 Each
20 20 M&L for Earthing complete with galvanised GI earth plate eletrode 600x600x6mm thick,burried directly in ground (earth pit not less than 2.25mtrdeep below GL) with top edge of the plate n.less than 1.5mtr below normal.GL surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all round the plate using 4mm dia GI wire as earth wire electrode welded and revetted to earth plate at one end connected to main DBs of Bldg at another end GI earth wire encased in and including 15mm dia GI light grade pipe through upper end of earth plate upto main DB of bldg with 20mm bore GI pipe light grade as water pipe from earth chamber to upper edge of earth plate MS funnel with wire mesh fixed on water pipe and Provn of PCC pit in PCC 1:2:4 type B-1 chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1 duly reinforeced with MS bars 8mm dia @ 150mm C/c with both ways complete with lifting handle all as shown in electrical plate no 5 of SSR of Part-I complete all as specified and directed. 2 Each
21 21 S& F exhaust fan PVC type 300 mm dia sweep, 900 RPM, 240 Volt with louver shutter and brackets, connection with flexible PVC copper cable 3 core of size 1.5 Sqmm of length from ceiling rose to exhaust fan including nut bolt and washers of suitable size complete all as specified and directed. 2 Each
22 22 S&F modular white cover plate with frame, 2 module complete all as specified and directed. 1 Each
23 23 S&F modular white cover plate with frame, 3 module complete all as specified and directed. 1 Each
24 24 S&F modular white cover plate with frame square type, 12 module complete all as specified and directed. 1 Each
25 25 S&F modular metal flush box, 2 module complete all as specified and directed. 1 Each
26 26 S&F modular metal flush box, 3 module complete all as specified and directed. 1 Each
27 27 S&F modular metal flush box, 12 module complete all as specified and directed. 1 Each
28 28 Supply, installation, testing and commissioning Diesel Engine driven generating set of 50 KVA capacity, 3 phase, 4 wire, 415 V, 1500 RPM, AC power supply with power factor 0.8, coupled directly to alternator, mounted on a common base plate complete with integral acoustic enclosures (shall have salient features) modular bolted construction & pure polyester based coating to ensure long life in all weather conditions & for outdoor application/ installation, integrated design thereby facilitating/ easy handling. The design of integral acoustic enclosure shall be approved by National Physical laboratory as per central pollution control board (CPCB) latest regulation / norms with fuel tank, battery & standard accessories, tools & spares as provided by manufacturer complete with necessary PCC foundations including excavation and earth work with block measonary work and plastering complete with following specifications at Srl 28.01 to 28.07 complete all as specified and as directed:- 1 Each
29 28.01 (A) ENGINE: Water cooled diesel engine at 1500 RPM, of capacity to match the 50 KVA alternator under NTP conditions with provision of 10 % over load for 1 hour in every 12 hours running confirming to BS 5514/ IS 10001/ 10002. The Engine shall consist of the following:-
30 28.02 (a) Fly wheel with starter ring\n(b) Flexible coupling with guard \n(c) Cooling fan \n(d) Radiator with guard and water pump engine mounted \n(e) Dynamo of suitable capacity\n(f) Air cleaner heavy duty dry \n(g) Fuel injection pump \n(h) Radiator fan ( Blower type ) with guard \n(j) Mechanical governor \n(k) Fuel filter (Mounted)\n(l) Lubricating oil filters ( mounted) \n(m) 12 v self regulating alternator belt driven by engine \n(n) Exhaust silencer heavy duty residential type \n(o) Corrosion resistor /scale inhibitor \n(p) Starter 12 V DC\n(q) Lubricating oil cooler \n(r) Lubricating oil pump (Gear type )\n(s) Turbo charger\n(t) Exhaust piping shall be insulated with asbestos rope duly cladded with aluminium sheet.\n
31 28.03 (u) Instrument panel complete with :-\n(v) Auto manual Starting switch with key\n(w) Lubricating oil temperature gauge \n(x) Lubricating oil pressure gauge \n(y) Water temperature gauge \n(z) Battery charging ammeter\n(aa) Battery charging indicating lamp \n(ab) Hour meter with RPM indicator \n(ac) Safety control against high temperature of water.\n(ad) Safety control against low lubricating oil pressure .\n(ae) Over speed stop with double driven adopter .\n
32 28.04 (B) BRUSH LESS ALTERNATOR \n(i) Alternator coupled to engine indigenous make through a flexible coupling mounted on sturdy steel fabricated base frame suitable for mounting on a permanent foundation brushless alternator shall be confirming to BS -2613 or relevant of IS-4722/ IS 13364.\n(ii) Type :- Self excited self regulated with automatic voltage regulator.\n(iii) Rating :- 50 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition.\n(iv) Speed :- 1500 RPM\n(v) System :- 415 V +/- 2.5 % AC 3 phase 4 wire 50 Hz.\n(vi) Connection :- 4 wire star connected.\n(vii) Enclosure :- Screen protected drip proof.\n(viii) Ventilation :- Self ventilated.\n(ix) Insulation :- Insulation class H\n
33 28.05 (C) CONTROL PANEL \nThe control panel with aluminium bas bar, bottom entry and exit of cable, current transformer, set of control fuses, Multifunctional Meter, it should display time and date, Volts, Frequency, Current, KW, KWH, PF, RPM, Cumulative Run Hours, Oil Pressure, Coolant Temp, Charging current (DC Amp Meter). Emergency off, factory made floor mounted, totally enclosed, epoxy powder coated suitable for 50 KVA DG Set including all necessary operating controlled devices as stated above and MCCBs as out going with protection fuse for panel instruments duly wired with flexible copper conductor cable and cable connection with lugs/thimbles complete as per latest IS/BS complete all as specified and directed.
34 28.06 (D) ONE SET OF ACCESSORIES COMPRISING OF:-\n(i) Level indicator.\n(ii) drain plug .\n(iii) MS class 'C' piping for inlet from pump to tank to engine.\n(iv) Fuel strainer.\n(v) Air vent.\n\n(E) SEALED MAINTENANCE FREE BATTERY:-\nHeavy duty battery two nos: 24 plates 12 v 180 AH connected to the system fully charged including lead and battery terminal's complete . \n\n(F) BASE PLATE:- Fabricated out of MS channel's ISMC of suitable size suitable for fixing of DG set all specified by the manufacturer.
35 28.07 (G) AMF PANEL:-\nSupply, fixing, testing and commissioning Auto main failure (AMF) panel, 15 SWG, 50 KVA DG Set Cubical consist of sheet steel enclosure of 2.00 mm thick totally enclosed dust and water proof duly painted with powder coated, fully wired up and ready to connect load & control lines in comprising the followings:- \na) Indication lamp LED type Green (IL1)- 01 No.\nb) Indication Lamp LED type Green (IL2) – 01 No.\nc) Control Supply ON/OFF switch (TS1) - 01 No.\nd) Canopy light ON /OFF Toggle switch ( TS2) - 01 No.\ne) Generator Controller unit (GCU) - 01 No\nf) Power contactor, AC-01 Duty, With Wide Band Coil (230AC), 2 NO + 2 NC Auxiliary contacts - 01 NO.\ng) Fuse link - 02 Set \nh) Fuse Holder & Base - 02 Set\ni) Current transformer - 03 Nos\nj) DC Ammeter - 01 No\nk) Hotter – 01 No.\nl) HTR,CFAR,GCR & MCR Relay - 01 Set\nm) Glass fuse holder - 08 Nos.\nn) Glass Fuse - 07 Nos\n(o) Battery Charger - 01 No.\n(p) Control Terminals - 02 Nos\n(q) Miniature Circuit Breaker ( MCB) - 01 No\n(r) Aluminium Busbar 40 x 10 mm - 01 set\n(s) Control Connector - 03 Nos\n(t) ECD Card - 01 No\n(u) Control Connector with suitable terminals - 01 Set
36 29 M&L Earthing complete with galvanised Iron earth plate electrode 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25mtrdeep below GL) with top edge of the plate not less than 1.5 metre below normal ground level, surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all round the plate with using 32X6 mm GI earth strip electrode welded and revetted to earth plate up to a distance of 7.5 mtr long, GI earth strip encased in and including 40mm bore GI light grade pipe, with 20mm bore GI pipe light grade as water pipe from earth chamber to upper edge of earth plate, MS funnel with wire mesh fixed on water pipe including excavation earth work, Provn of PCC pit in PCC 1:2:4 type B-1 chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type BI duly reinforced with MS bars 8mm dia @ 150 mm centre to centre, both ways complete with lifting handle all as shown in electrical plate No 3 of SSR of part-I complete all as specified and as directed. 10 Each
37 30 M&L 40mm bore GI tubing, light grade including all fittings for earthing lead protection and cable protection complete all as specified and directed. 4 RM
38 31 Supply, laying, connecting & testing, 95 Sqmm 3.5 core, XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT underground cable ISI marked with aluminium multistranded conductor 1100 volt grade, laid in trenches/duct, passing through pipe/duct or fixed on pole complete all as specified & directed. 50 RM
39 32 Supply, laying, connecting & testing, 50 Sqmm 3.5 core, XLPE insulated, PVC inner sheathed, armoured with galvanised steel strip or wire, heavy duty, LT underground cable ISI marked with aluminium multistranded conductor 1100 volt grade, laid in trenches/duct, passing through pipe/duct or fixed on pole complete all as specified & directed. 30 RM
40 33 Supply, installation, testing & commissioning LT outdoor switch gear panel board , manufactured by CPRI approved factory, platform mounted, totally enclosed dust and vermin proof, made out of 50 x 50 x 6 mm thick MS angle iron frame and CRCA sheet of not less than 2 mm thick and legs of size 0.5m long as per IS 5039, cubical type, front and rear side openable, provision of air vent and provision of cable alley, with 300 Amps Aluminium rated bus bar for phases and 150 amps rated bus bar for neutral, duly painted with powder coated paint of approved shade after seven tank treatment process. The panel shall be suitable for 415 Volts, 50 Hz 3 Phase, 4 wire system and bus bars shall be fixed on porcelain or PVC insulators, thimbles, glands of brass and shall be complete including necessary earth work and PCC foundation, with following accessoriescomplete all as required at site, as specified and as directed: -\n(a) Incomming : MCCB 250A 35 KA - 01 No. \n(b) Metering and Indication - 01 No.\n(i) Digital Multifunction Meter - 01 No.\n(ii) CT for Meter CI -1.0,15VA - 01 No.\n(iii) RYB phase Indication light - 01 Set\n(v) Control MCB SP 6 Amp 3 Nos\n(vi) BUS Bar chamber 300 Amp ,3 strips & N/L 150 A aluminium \n(c) Out Goings -\n(i) 4 pole MCCB thermal Magnetic Based release -125A,25 KA -02 Nos \n(ii) 4 pole MCCB thermal Magnetic Based -100A,25 KA -01 Nos \n(iii) 4 pole MCCB thermal Magnetic Based -63A,25 KA -01 Nos 1 Each
41 34 Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth for foundation / fixing pole / laying cable and pipe line etc or for man hole etc not exc 10 Sqm on plan and getting out in soft / loose soil complete all as specified and as directed. 12.96 Cum
42 35 Returning filling in including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick complete all as specified and as directed. 8.28 Cum
43 36 Removing excavated Soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. 4.68 Cum
44 37 M&L for providing dry river sand as in sand cushioning to under ground electric cable including punning down of sand in layer complete all as specified and as directed. \nNote: For measurement purpose punned thickness of sand shall only be considered. 3.89 Cum
45 38 Supply and Laying burnt old size bricks as in protection to cable complete all as specified and directed. 400 Each
46 39 S&F Steel work in tubular trusses, purlins, rafter, vertical post and similar works including special shaped washer etc complete using ERW or induction butt welded tubes confirming to IS- 1161-1979 gde SI-240 including one shop coat of zinc chromate primer paint incl preparation of surface at contractor workshop before fabrication complete all as specified and directed. 150 Kg
47 40 S & F plain MS plate including cutting / welding & drilling (Fe 410- w Gde-E 250 Quality A) complete all as specified & directed. 40 Kg
48 41 S & F framed bracket of angles or tees with web and flanges cut to shape, drilled and counter, sunk for screw, including bending and welding, as necessary gusset plates, riveting etc not exc 10 kg each bracket, confirming to Fe 290 grade E 165 complete all as specified and directed. 80 Kg
49 42 M&L shade covering with galvanised, corrugated mild steel sheeting of thickness 0.80mm with two corrugations of side lap, fixed with L type and J type hook and washers, in roofs wall with grade of zinc coating 275 complete all as specified and directed. 38 Sqm
50 43 M&L PCC (1:3:6) type C-2 using 40 mm graded stone aggregate as in foundation/bed and for filling in post hole for column etc complete all as specified and directed. 10 Cum
51 44 S& F Metallic, heavy duty Exhaust fan 380 mm dia sweep, 900 RPM, 240 Volt heavy duty with louver shutter and brackets, connection with flexible PVC copper cable 3 core of size 1.5 Sqmm of length from ceiling rose to exhaust fan including nut bolt and washers and making suitable size of hole in brick/PCC block/ Stone masonary wall built in cement mortar and making good disturbed surface incl white washing complete all as specified and directed. 2 Each
52 45 M & L for construction of pre-fabricated portable hut of size (8.00 Mtr x 5.00 Mtr) complete all as per manufacture instructions complete all as specified and directed along with following specification:-\nMake: M/s Porta Cabin Engrs Pvt Ltd/ Shree Porta Builders Pvt Ltd/ M/s Startrek Structures/ M/s Makeover Interiors 1 Each Job
53 45.01 Walls: Wall shall be 50mm Thick Panels fabricated with Cement Fiber Board of 6mm shall be pasted on either side of thermocole. These panels shall be joined together with galvanised iron H-section to complete wall.
54 45.02 Roof: Pre-Painted galvanised iron Sheet of 0.50mm thickness fixed with self-tapping screws of 75mm over mild steel Hollow Pipes (25x50, 50x50) Section Grid. Grid size shall be 60Cm x 120Cm covered by 6mm thick Cement Fibar board underneath. Trusses & purloins and vertical post shall be welded or fixed together with the help clamps washers as required complete. Roof is to be laid to a minimum slope of 1:20. Trusses purlins and vertical post shall be fixed together with the help of clamps washers as required complete. Ridges shall be made of 0.50mm thickness plain pre painted GI Sheet fixed with self tapping screws of 75mm. Height from floor level to bottom of truss shall be 2.40 mt and ridge to be placed according to maintain required slope. Roof shall have projection of 300mm.
55 45.03 Structures: Purlins, principles etc. for structures made out of MS Pipes(25x50, 50x50) & 90 dig, 112 dig for walls + roof supports.
56 45.04 Exterior Painting: External surface of walls with 3 coats of Asian apex white or as required color.\nInterior Painting: Internal surface shall be provided with 2 coats of oil bond distemper (OBD).
57 45.05 Door: Door shall be provided in aluminium powder coated of size 2.50 x 2.50 Mtr with locking arrangement and two number aluminium handles.
58 45.06 Sliding Window: Aluminium Powder Coated Sliding Window in Aluminium Frame size 900 x 900 mm with aluninium frame of size 2.5”x1.5” slider section size 1”x.5” with plain glass of 5mm.
59 45.07 Modular Floor: The framework of platform shall be made of Rectangular Hollow Section of MS Steel (50x25mm) Confirming to grid of 600x600mm. The floor platform shall be made mainly 16mm Cement Fiber Board. The entire structure shall be raised above ground by 8” using steel support (Iron Joists). Superior Quality Vinyl shall be pasted on top.
60 46 S&F GI powder coated snap grid frame work for false ceiling (Size of grid 605X605 mm) complete all as specified and directed. 40 Sqm
61 47 S&F 4 mm thick Eco building board fixed or laid/inserted to GI/ Aluminium framework with screws complete all as specified and directed. 40 Sqm
62 48 M&L for cement concrete 1:4:8 type D2 using 40 mm graded stone aggregate as in foundations filling, sub base and mass concrete filling, etc complete all as specified and directed. 4 Cum
63 49 M&L for 7mm to 8mm thick ceramic joint free non skid tiles coloured of area exc 0.11 Sqm but nexc 0.18 Sqm (400x400mm) in flooring set and jointed in neat cement slurry and pointed in coloured cement to match with tiles laid over and including 15mm thick cement screed in cement mortar (1:4) over 25 mm thick PCC 1:2:4 type B-1 (Using 20mm graded stone aggregate) as levelling course complete all as specified and as directed. 40 Sqm
64 50 M&L for cement concrete (1:3:6) type C-1 (using 20mm graded stone aggregate) as in foundations, filling and mass concret etc complete all as specified and directed. 8 Cum