Provision Of Exhaust Fans And Ceiling Fans Against Deficiency Of Inf Bn-Ii And Electric Energy Meter , Dbs And Allied Works In Bldg No P-213 Of Klp-Ii At Mil Stn Fazilka, Fazilka Mil Stn-Punjab

Military Engineer Services-MES has published Provision Of Exhaust Fans And Ceiling Fans Against Deficiency Of Inf Bn-Ii And Electric Energy Meter , Dbs And Allied Works In Bldg No P-213 Of Klp-Ii At Mil Stn Fazilka. Submission Date for this Tender is 31-05-2021. Energy Meter Tenders in Fazilka Mil Stn Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

27804688
Corrigendum : Provision Of Exhaust Fans And Ceiling Fans Against Deficiency Of Inf Bn-Ii And Electric Energy Meter , Dbs And Allied Works In Bldg No P-213 Of Klp-Ii At Mil Stn Fazilka
National Competitive Bid
Indian
Punjab
Fazilka Mil Stn
31-05-2021

Tender Details

Provision Of Exhaust Fans And Ceiling Fans Against Deficiency Of Inf Bn-Ii And Electric Energy Meter , Dbs And Allied Works In Bldg No P-213 Of Klp-Ii At Mil Stn Fazilka

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-May-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 31-05-2021
2 24-May-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 31-05-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 19040.0 /-
Tender Value
INR 9.52 Lakhs /-

BOQ Items

Name of Work : Provn of exhaust fans and ceiling fans against deficiency of Inf Bn-II and electric energy meter, DBs and allied works in Bldg No P-213 of KLP-II at Mil Stn Fazilka
Sl. No. Item Description Item Code / Make Quantity Units
1 1 M & L point wiring complete with 1.5 Sqmm (nominal area) PVC FRLS insulated unsheathed copper stranded conductor cable with colour code in and including medium grade rigid PVC conduit with tees, bends, elbows, couplers, MS junction boxes concealed after cutting chases in wall, floor etc and making good to match with existing surface including sunken iron terminal box, 3mm thick bakelite sheet cover, clips, pipe hooks, brass screws, washers and 1.5 Sqmm single core stranded / solid copper conductor 1100 volts grade PVC insulated and unsheathed cable as earth continuity conductor to common earth and connecting to earth dolly for One light /bell point/ fan point controlled by one, one way switch all as specified and directed at site by Engineer – in – Charge. 207 Per Point
2 2 All as per item No. here in before but for socket out let 3 pin 5 amp on same board all as specified and directed by Engineer - in - Charge 2 Per Point
3 3 All as per item No. here in before but for socket out let 3 pin 5 amp on independent board all as specified and directed by Engineer - in - Charge 2 Per Point
4 4 M & for point wiring complete with 2.5 Sqmm single core multi stranded copper conductor of 1100 volts grade PVC FRLS insulated and unsheathed cable for one multipurpose switch socket outlet 6 pin, 15 Amps on independent board including 1.5 Sqmm single core stranded / solid copper conductor 1100 volts grade PVC insulated and unsheathed cable as earth continuity conductor to common earth and connecting to earth dolly. 5 Per point
5 5 S & F ceiling rose 65 x 50mm three terminals PVC/ polycorbonate, isolated body all as specified and directed by Engineer - in - Charge . 156 Each
6 6 S & F switch piano flush type single pole one way 5 Amp all as specified and directed by Engineer - in – Charge.\nMake : Anchor/Havells/Legrand 211 Each
7 7 S & F piano type socket two in one, 3 pin 5 Amps 230 VAC supply\nMake : Anchor/Havells/Legrand 2 Each
8 8 S & F switch piano flush type single pole one way 15 Amp all as specified and directed by Engineer - in – Charge. 5 Each
9 9 S & F piano type socket two in one, 6 pin 5 Amps 230 VAC supply\nMake : Anchor/Havells/Legrand 5 Each
10 10 Supply and fix microprocessor based single phase electronic temper proof energy meter of rating 10 to 60 Amps with optical communication port, conforming to IS:13779 3 Each
11 11 S & F of Ceiling fan of 1200mm sweep monted in suitable arrangement for operation on 230 Volts, single phase, 50 cycle phase, 50 cycle per second, AC supply with electronic type regulator and connecting accessories BEE 5 Star rating and connecting up including three core PVC insulated PVC sheated copper conductor flexible cable from ceiling rose to fan fixing in ceiling complete and making the surface good after fixing the fan complete all as specified and directed.\nMake : BAJAJ/HAVELLS/ORIENT 115 Each
12 12 S & F heavy duty exhaust fan of 450mm sweep mounted in suitable opening arrangement with louvers siitable for operation on 230 Volts, single pase, 50 cycle per second, AC supply and connecting up including three core PVC insulated PVC sheated copper conductor flexible cable 24/0.2mm deawn in flexible PVC conduit fixing in wall and making suitable hole for exhaust fan with necessary finishing of the surface good after fixing the fan complete all as specified and directed by Engr-In-Charge.\nMake : BAJAJ/HAVELLS/ORIENT 38 Each
13 13 S & F isolator single pole 40 Amp 240 volt all as specified and directed by Engineer – in – Charge . 60 Each
14 14 S & F of MCB suitable for 240 Volts AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA and 16 to 32 Amps all as specified and directed. 42 Each
15 15 S & F MCB distribution board of sheet metal single pole and neutral 8 way, single door, with 200 Amp rated bus bar 240 volt all as specified and directed by Engineer-in- Charge. 12 Each
16 16 S & F sheet metal enclosure distribution board triple pole and neutral 4 way, double door, with 200 Amp rated bus bar 440 volt all as specified and directed by Engineer-in- Charge. 12 Each
17 17 S & F sheet metal enclosure distribution board triple pole and neutral 4 way, double door, with 200 Amp rated bus bar 440 volt with incoming MCCB of rating 100 Amps all as specified and directed by Engineer-in- Charge. 1 Each
18 18 S & F of MCB suitable for 415 Volts AC supply, TPN with over load and short circuit protection and rupturing capacity not less than 10 KA and 63 Amps all as specified and directed. 5 Each
19 19 S & F of MCB suitable for 240 Volts AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 KA and 40 Amps all as specified and directed. 12 Each
20 20 S & F of MCCB suitable for 415 Volts, 4 Pole, AC supply and short circuit protection and rupturing capacity not less than 16 KA and 100 Amps all as specified and directed. 6 Each
21 21 S & F of MCCB 4 Pole 125 Amps suitable for 415 Volts AC supply, with over load and short circuit protection and repturing capacity not less than 10 KA all as specified and directed. 2 Each
22 22 S & F of MCCB 4 Pole 63 Amps suitable for 415 Volts AC supply, with over load and short circuit protection and repturing capacity not less than 10 KA all as specified and directed. 3 Each
23 23 Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations or laying cables/ pipes etc and getting out in soft / loose soil all as specified and directed by Engineer - in - Charge. 27 Per Cum
24 24 Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge. 18.9 Per Cum
25 25 Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge. 8.1 Per Cum
26 26 M & L sand cushioning for under ground cable 23 cm thick (one layer of 8 cm thickness before laying the cable and other layer of 15 cm thickness after laying the cable) all as specified and directed by Engineer-in-Charge. 8.1 Per Cum
27 27 Supply, laying, jointing and testing and commissioning 25 sqmm, 4 core XLPE insulated, screened, PVC bedded galanised steel strip or wire armoured electric power cable heavy duty multi stranded aluminium conductor and PVA sheathed LT cable 1100 Volts grade conforming to IS-7098 laid in trenches/ducts/fixed on poles/wall/laid under roads/paths/drain/culverts or passing through pipes complete all as specified and directed by Engr-In-Charge 100 RM
28 28 S & F in repairs submain wiring with two single core cables PVC FRLS insulated unsheathed 6 Sqmm stranded copper conductor drawn in and including PVC conduit with and including PVC insulated 6.0 Sqmm stranded copper conductor cable as earth continuity conductor and connecting complete all as specified and directed by Engineer - in - Charge.\nNote : PVC cables two single core and one single core of sizes as mentioned will considered as one unit. 220 Per \nRM
29 29 M & L as in repairs submain wiring with two single core cables PVC FRLS insulated unsheathed 4 Sqmm stranded copper conductor drawn in and including PVC conduit with and including PVC FRLS insulated 4.0 Sqmm stranded copper conductor cable as earth continuity conductor and connecting complete all as specified and directed by Engineer - in – Charge.\nNote : PVC cables two single core and one single core of sizes as mentioned will considered as one unit. 170 Per\nRM
30 30 S & F submain wiring with four single core cables PVC FRLS insulated unsheathed 10 Sqmm stranded copper conductor drawn in and including PVC conduit with and including PVC FRLS insulated two single core cables 6.0 Sqmm stranded copper conductor cable as earth continuity conductor and connecting complete all as specified and directed by Engineer - in - Charge.\nNote : PVC cables two single core and one single core of sizes as mentioned will considered as one unit. 20 Per \nRM
31 31 Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations or laying cables/ pipes etc and getting out in soft / loose soil all as specified and directed by Engineer - in - Charge. 13.5 Per Cum
32 32 Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge. 6.95 Per Cum
33 33 Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge. 6.55 Per Cum
34 34 M & L sand cushioning for under ground cable 23 cm thick (one layer of 8 cm thickness before laying the cable and other layer of 15 cm thickness after laying the cable) all as specified and directed by Engineer-in-Charge. 4.05 Per Cum
35 35 Labour for boring hole across the road/plinth/floor for cable passing without damaging the road/plinth/floor complete including necessary T&P all as specified and directed. 5 Per \nRM
36 36 M & L brick protection using old size sub class ‘B’ bricks, laid flat, across the cable i.e. length perpendicular to the axis of cable all as specified and directed by Engineer-in-Charge. 1.35 Per 1000 Nos
37 37 Supply and fix GI pipe 40 mm bore light grade for protection of cable including provision of clamps, nuts, bolts etc required for fixing pipe along pole/wall/laid under the road/laid under the floor or in trenches complete all as specified and directed by Engr-In-Charge 5 Per \nRM
38 38 Supplying, installation, commissioning in repairs of LT penels board not less than 100cmx100cmx50cm made out of 3.15 mm thick CRCA sheet vermin proof, including painting with sysnthetic enamelled paint, CPRI approved with colour code PVC sleeves for bus bar, front opened with locking arrangement, closed bus bar chamber, angle iron frame of ize 50x50x6mm for skeleton and support embeded in concrete foundation comprising of the following :\nIncoming :-\n(a) Aluminium bus bar 400 Amps for phase and neutral - 01 Set\n(b) MCCB FP, 415 V, 250 Amps, 25 KA - 01 No (I/C)\n(c) MCCB FP 100 Amps, 415 V, 16 KA - 03 No (O/G)\n(d) Voltmeter 0-500 volts range with selector switch digital type - 01 Set\n(e) Ammeter 0-100 Amps range with selector switch & CT coils - 01 Set\n(f) Indicator lamp with holder for RYB - 01 Set\n(g) Time switch single phase 20 Amps - 01 No\n(h) Three phase microprocessor based CT operated electronic temper proof static energy meter of rating 60 Amps - 01 No\n\n 1 Each job
39 39 Supplying and laying XLPE cable, PVC insulated, armoured, heavy duty multi stranded aluminium conductor, electric cable LT, 1100V grade of size 50 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-charge. 80 Per \nRM