Establishment Of Cng Based Cremation Units At Seemapuri Cremation Ground Under Edmc. S.H.:- Design, Supply, Installation, Testing, Commissioning And Maintenance Of Compressed Natural Gas (C.N.G) Based Cremation Units, Office of the Ex Engineer (E and M )-Delhi

East Delhi Municipal Corporation has published Establishment Of Cng Based Cremation Units At Seemapuri Cremation Ground Under Edmc. S.H.:- Design, Supply, Installation, Testing, Commissioning And Maintenance Of Compressed Natural Gas (C.N.G) Based Cremation Units. Submission Date for this Tender is 04-05-2021. Cremetorium Tenders in Office of the Ex Engineer (E and M ) Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

27715719
Establishment Of Cng Based Cremation Units At Seemapuri Cremation Ground Under Edmc. S.H.:- Design, Supply, Installation, Testing, Commissioning And Maintenance Of Compressed Natural Gas (C.N.G) Based Cremation Units
Open Tender
Indian
Delhi
Office of the Ex Engineer (E and M )
04-05-2021

Tender Details

Establishment of CNG based cremation units at Seemapuri Cremation Ground under EDMC. S.H.:- Design, Supply, Installation, Testing, Commissioning and maintenance of compressed natural gas (C.N.G) based Cremation units

Key Value

Document Fees
INR 2000 /-
EMD
INR 323350.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Establishment of CNG based cremation units at Seemapuri Cremation Ground under EDMC. S.H.:- Design, Supply, Installation, Testing, Commissioning and maintenance of compressed natural gas (C.N.G) based Cremation units.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Design, supply, installation, testing and commissioning of 2 Nos. of CNG fired cremator ( Cremation Furnace) at designated location as per details below and Technical Specification BI01010001010000000000000515BI0100001112
2 2 CNG Cremation Furnace casing:-\nThe Cremation furnace designed, supply, installation, testing and commissioning with following technical specification : (a) each furnace would take 12 to 15 bodies in a day.(b) maximum temperature of 900° C to 1200 C can be brought . (c) operating temperature required is 550° C (d) double chambers One primary other secondary and 2 burners are required for each furnace\n(e)Overall Size :- 3500 mm (L) x 3600 mm (H) x 2100 mm (W)\n(f) Working Chamber Size (inside) :- 2725 mm (L) x 830 mm (H) x 900 mm (W)\nFrame make with MS Steel Structural with U channel :- 75 mm x 5 mm\n(g)Foundation of the furnace make with red bricks and RCC bottom to plinth level:- 750 m depth filling with high insulation bricks etc. as required BI01010001010000000000000515BI0100001113 2 each
3 3 Front Doors mechanical drive system and counter weight etc.\nThe front doors made of SS 304 in front side duly fabricate the frame of MS angel/channel fill with high complete insulation material with fiber insulation and SS rod 8 mm inside for hold the insulation door operation material Consist of front door handle of 190 mm (dia) chrome plated handle and 16 mm thickness Consist of front gate screws and cast irons nuts having 350 mm length x 40 mm diameter Provided with gate pulleys 2 Nos having diameter 300 mm x 25 mm thick x 50 mm ID . key nays of 10x5 mm Provided with big Gears duplex 250 mm diameter x 30 mm thk Provided with small gear bottom side with 100 mm x 30 thk Consist of main shaft of 2250 mm long x 50 mm dia with keys ways , and plummer block having sizes of 50 mm and 30 mm etc. as required BI01010001010000000000000515BI0100001114 2 each
4 4 Refractory lining of the furnace and insulation.\nHot face insulation bricks, Ceramic fibre, dead body support will be CNG furnace with dual chamber primary and secondary. Highly efficient insulation to maintain the temperature with 6 step in be used of 70% fire brick, 40% fire bricks good quality, light weight insulation bricks, 1” fibber insulation board quality, red bricks with plaster and frame work with fibber insulation and 1.5 mm MS sheet with red oxide and heat resistance aluminium paint of proper thickness that is 570 mm shall be provided in order to operate the furnace with minimum gas consumption and lost the temperature burner block and dead body supporter should be used ( Burner Block Size :- 225 mm x 225 mm or 300 mm x 300 mm) (dead Body supporter Size:- 600 mm x 300 mm x 75 mm) etc. as required BI01010001010000000000000515BI0100001115 2 each
5 5 CNG GAS FULLY Automatic Burner for primary and secondary chamber\nIn belt blower single phase, auto ignition electrode, Auto Sequence Controller\n With Flame Failure sensor, Air Detecting Pressure Switch, Slow Opening & amp ; First Closing solenoid Valve & amp; Diffuser Firing Head Blast Tube With Mounting Flange CI, MS Sheet Powder Coated Body etc. as required\n BI01010001010000000000000515BI0100001116 2 each
6 6 Heat Recovery unit\nThe unit outlet of chamber with control dumper fitted in outlet duct and chamber should be 2.5 mm MS Sheet angle frame with 70% bricks insulation and with cover etc. as required BI01010001010000000000000515BI0100001117 2 each
7 7 Electrical Control Panel for CNG Furnace for auto ignition\nControl panel with 3 Phase Over load MCB , individual 3 Phase MCB, Control MCB, I.D. Fan Contractor & amp ; Over load Relay, Water Feeding motor Contractor, Gas High- pressure Cut On/ Off Switch, Indication LED , Flame Failure Buzzer Burner AUTO/MANUAL Relay, Volt/ Ampere/ Hz. Indicator , Temperature Controller 0-120 deg. Centrigrade, Thermocouple and Compensating lead , Out Put Warring etc as required\n BI01010001010000000000000515BI0100001118 2 each
8 8 Track and Charging Trolley\n Made by section of size 100 mm x 50 m x 5 mm channel provided with complete arrangements for uplift and lowering of body, provided with C.I. wheels side plate assembly 1000 mm long x 50 mm width having wheel plats of size 190 mm x 10 mm the provided with guided wheels size 80 mm x 20 (thk) complete with pins. BI01010001010000000000000515BI0100001119 2 each
9 9 Chimney\nFoundation for Chimney Size :- 2300 mm (W) x 4200 mm (L) x 500 mm (H) for 2 units.\nFoundation Bolts L –type:- 36 mm (dia) x 1500 (L)) with double nuts and washer x 150 mm long thread.\nCone\nMS Cone 1200 mm bottom dia x 10 mm thickness x 3000 mm height\nBase plate:- 1800 mm x 1800 mm x 25 mm thick\nTop size of cone weided with 25 mm thick flange suitable for fixing with pipe.\nService window 600 mm x 600 mm.\nRibs :- 15 Nos: 600 mm x 200 mm x 10 mm\nPipe 300 mm dia x 6 mm thick with 18 mm flange Welded Both Sides, having 20 mm dia holes suitable for fixing 18 mm dia high tensile bolts.\nHaving 15 Nos. of ribs 125 mm x 100 mm x 10 mm thick.\n\nLadder with Safety cage\nMonkeys type ladder with 50x 6 MS angle.\nPlate Form 02 Nos. for Smoke testing.\nBase made of 4mm wire mesh having spring std 1000 mm (H) x 1400 mm (W) etc. as required BI01010001010000000000000515BI0100001120 2 each
10 10 SS Wet Scrubber for Gases and Pollution control size 800 x 500 x 500 total 2450 mm (L) with SS 304 horizontal round shape.\nWet scrubber will be provided for gases and pollution control size of based dia 800 mm x 2.5 mm thick x 1200 mm (L) cone 500 10” NB x 8 mm SS 304 Sprikler 5 mm 8 Nos. with copper fitting and SS Socket 2 Nos. baffle plat 2 Nos. 800 mm x 25 mm hole x 50 mm pitch thick 2.5 mm Outlet pipe lines, valves and necessary pumping unit fitted on water tank, minimum 1000 Lt capacity PVC over head tank for each unit furnace. BI01010001010000000000000515BI0100001121 2 each
11 11 Ducting from Scrubber to Chimney : 300 mm dia x 6 mm thick with fire bicks 40% insulation covered under ground BI01010001010000000000000515BI0100001122 2 each
12 12 Internal Gas Pipe Lines\nAll the internal gas pipelines 2” seamless 3.5mm should be flange mounted and welded with air tight gasket as per the norms of IGL. Piping of gas line from IGL souce to furnace with Power failure Safety value and by-pass system.\nGas Train\nGas train would be fitted in Main gas pipeline to reduce the pressure by fitting the regulator, gauges, Hose pipe, steel nipples, S.S. Valves, Pressure Switch etc.\n BI01010001010000000000000515BI0100001123 2 each
13 13 2. Diesel fired Power Generating Set
14 14 Providing , installation, testing & commissioning of silent type Diesel Generating set along with prime power rating of 20 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 Phase system & consisting of the following: (a) Diesel Engine: Diesel Engine water cooled , electric start of minimum 16 BHP at 1500 RPM. The engine will be fitted complete with all the required accessories. (b) Suitable engine mounted instrument panel. (c) Alternator, Synchronous alternatore rated at 20 KVA, 415 V at 1500 RPM, 3 phase 50 Hz, AC supply with 0.85 lagging power factor. The alternator shall be brushlessm self excited & self regulated through AVR. (d) Base frame (e) Fuel tank: Daily service fuel tank of suitable capacity complete with all standard accessories & fuel piping b/w fuel tank & diesel engine. Complete with valves, level indications & accessories as reqd. (f) Suitable Exhaust system. (g) Electrical Starting system. (h) Acoustic & weather proof enclosure with arrangement for fresh air intake for cooling the engine & alternator, extraction, discharging hot air in the atmosphere. (i) Exhaust piping : 3 m exhaust MS B class piping of 50 mm dia with glass wool, wire mesh & aluminum cladding. (j) Automatic mains failure control panel suitable for 20 KVA silent type DG sets complete with relays, timers, sets of CTs for matering & protection & energy analyzer to indicate currents, phase & line voltaes, frequency, PG, KWH, KVARH & provision of overload , short circuit, estricted earth fault, under frequency complete as reqd. As per CPWD DG sets specifications including availing the approval of the total inspector and pollution board for energizing the DG Set. BI01010001010000000000000515BI0100001125 1 each
15 15 Supply of XLPE insulated PVC sheathed AL Conductor armoured cable for working voltage upto 1.1kv confirming to IS: 7098 of following sizes: (a) 3.5 C x 50 sq mm BI01010001010000000000000515BI0100001126 50 Mtr.
16 16 Supply of PVC sheathed XLPE insulated copper conductor armoured control cable of 1.1 KV grade as per IS : 7098 (part-1) 1988 of 6 C x 2.5 sq mm size as reqd. BI01010001010000000000000515BI0100001127 50 Mtr.
17 17 Laying of one number PVC insulated & PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as reqd. (a) up to 35 sq mm. BI01010001010000000000000515BI0100001128 15 Mtr.
18 18 (b) above 35 sq mm and upto 95 sq mm BI01010001010000000000000515BI0100001129 15 Mtr.
19 20 Laying of one number PVC insulated & PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/metal pipe as reqd. (a) upto 35 sq mm. BI01010001010000000000000515BI0100001130 15 Mtr.
20 21 Above 35 sq mm and upto 95 sq mm BI01010001010000000000000515BI0100001131 15 Mtr.
21 22 Laying & fixing of one number PVC insulated & PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as reqd. (a) up to 35 sq mm (clamped with 1 mm thich saddle(s) BI01010001010000000000000515BI0100001132 20 Mtr.
22 23 Above 35 sq mm and upto 95 sq mm (clamped with 25x3 mm flat clamp) BI01010001010000000000000515BI0100001133 20 Mtr.
23 24 Earthing with GI plate 600 mm x 600 mm thick i/c accessories & provind masonry with cover plate having locking arrangement and watering pipe 2.7 m long etc. with charcoal/coke & salt etc, as reqd. BI01010001010000000000000515BI0100001134 4 Mtr.
24 25 P/F 25 mm x 5 mm GI strip in 40 mm dia GI pipe from earh electode i/c connection with GI nut, bolt, spring, washer excavation & refelling etc. as reqd. BI01010001010000000000000515BI0100001135 12 Mtr.
25 26 P/F 25 mm x 5 mm GI strip on surface or in recess for connections etc. as reqd. BI01010001010000000000000515BI0100001136 40 Mtr.
26 27 P/F 6 SWG dia GI wire on surface or in recess for loop earthing along with existing cable as reqd. BI01010001010000000000000515BI0100001137 100 Mtr.
27 28 Supplying & making end termination with brass compression gland & aluminum lugs for following sizes of PVC insulated & PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as reqd : 3.5 x 50 sq mm (35 mm) BI01010001010000000000000515BI0100001138 4 Mtr.
28 29 Providing & lying in position cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) in foundation of pump, GD set etc. i/c form work etc. as reqd. BI01010001010000000000000515BI0100001139 2 Cum
29 30 Supplying & fixing of light class GI pipe of 50 mm dia (nominal) 3 m length along the pole for protection of U/G cable as reqd. BI01010001010000000000000515BI0100001140 2 Mtr.
30 31 3. Fire fighting equipments
31 32 supply and fixing of 4.5 Kg CO2 fire extinguisher (wall mounting type) as per BIS specifications (conforming to IS: 2878) BI01010001010000000000000515BI0100001142 1 each
32 33 Supplying and installing at approved location approved make 4 nos. fire buckets of 24 gauge galvanized steel , painted white inside as red outside and back on the bottom, inscribed with letter "FIRE" in black and gold including stand fabricated out of sheet metal (16 gauge) shade, platform and associated civil works, painting etc. as approved by the fire authority. BI01010001010000000000000515BI0100001143 1 Set
33 34 Supply and fixing of 4.5 Kg DCP with CO2 fire extinguisher (wall mounting type) cartridge fire extinguisher dry type (conforming to IS: 2171 with cylinder fully charged) BI01010001010000000000000515BI0100001144 1 each
34 35 3. OMC Support for 4 years after defect liability period of one year
35 36 OMC support for first year, Operation & comprehensive maintenance support for the 2 Nos. CNG Furnaces, chimney, scrubber and DG set for first year (by providing at least one trained manpower at all time of the day during the whole year and minimum 2 services during first year and as and when required). This also includes all spare parts, consumbles such as diesel, lubricants for gen set etc. and any other incidental expenditure. BI01010001010000000000000515BI0100001146 1 Per Year
36 37 OMC support for second year, Operation & comprehensive maintenance support for the 2 Nos. CNG Furnaces, chimney, scrubber and DG set for second year (by providing at least one trained manpower at all time of the day during the whole year and minimum 2 services during second year and as and when required). This also includes all spare parts, consumbles such as diesel, lubricants for gen set etc. and any other incidental expenditure. BI01010001010000000000000515BI0100001147 1 Per Year
37 38 OMC support for third year, Operation & comprehensive maintenance support for the 2 Nos. CNG Furnaces, chimney, scrubber and DG set for third year (by providing at least one trained manpower at all time of the day during the whole year and minimum 3 services during third year and as and when required). This also includes all spare parts, consumbles such as diesel, lubricants for gen set etc. and any other incidental expenditure. BI01010001010000000000000515BI0100001148 1 Per Year
38 39 OMC support for fourth year, Operation & comprehensive maintenance support for the 2 Nos. CNG Furnaces, chimney, scrubber and DG set for fourth year (by providing at least one trained manpower at all time of the day during the whole year and minimum 3 services during fourth year and as and when required). This also includes all spare parts, consumbles such as diesel, lubricants for gen set etc. and any other incidental expenditure. BI01010001010000000000000515BI0100001149 1 Per Year
Disclaimer :