India Trade Promotion Organisation-ITPO has published Supply , Installation , Testing And Commissioning Of Supply , Installation , Testing And Commissioning OfNew Air Handling Units Along With The RelatedAccessories For Hvac Plant For Hall No . 8-10 AtPragati Maidan , New Delhi . . Submission Date for this Tender is 11-05-2021. Air Handling Unit Tenders in Pragati Maidan NEW Delhi Delhi. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 15-Apr-2021 | Minutes of Pre-bid Meeting | Other | 26-04-2021 |
2 | 26-Apr-2021 | Corrigendum for extension of date | Date | 11-05-2021 |
Name of Work: SITC of New Air Handling Units along with the related accessories for HVAC Plant for hall no. 8-10 at Pragati Maidan, New Delhi | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Supplying,Installation,Testing,Commissioning of Double skin floor mounted horizontal Air Handling Unit that has 50 mm thick(EU-4) box type pre filter, coil section with 6 row deep chilled water cooling coil, fan section with DIDW centrifugal backward curved fan, drive set with V- belt and motor (IE3) complete with civil works to fix the new AHUs along with dismantling and buy-back of existing AHUs etc as required with the following specification: MAKE: ZECO Aircon/EDGETECH/SYSTEMAIR/ABS AIRTECH 1.Panel: Outer skin: not less than 0.8 mm Pre-coated GI, Inner skin: not less than 0.8 mm Plain GI & Thickness: 25 mm thick,CFC Free PUF injected (Density:40 kg/Cu. m) Frame work : Unit base: Heavy duty GSS & Profile: Thermal Break Aluminium profile. Cooling Coil (Chilled water type): Tube material: Copper, Tube thickness: not less than 0.41 mm, Outside dia.: not less than 12.7 mm, Header Material: MS, Coil casing: GI, Fin material: Plain Aluminium, Fin spacing: 11-13 FPI, Condensing Tray: 22G SS-304, Test Pressure: 21 kg/sq. m. & Insulation material for drain tray: 13 mm thick close cell Nitrile rubber. Filters: Make: Spectrum/Mechmark/Puramatic Fan(DIDW Type): Make: NICOTRA/KRUGER/GREENHECK AC Motor (For DIDW Fans): Make: BHARAT BIJLEE/HAVELLS/ABB/Seimens & Efficiency Factor: IE3 Special features:1. AHUs must be CE certified 2. AHUs should also certified for mechanical and thermal performance as per EN 1886 standard (European Standard) 3.All coils must be AHRI certified as per test standard ARI-410 4. All coils are UL certified for safety. | BI01010001010000077000000515BI0100001112 | ||
2 | 1.01 | 13000 to 15000 CFM size AHU | BI01010001010000000000000534BI0100001113 | 1 | Nos |
3 | 1.02 | 18000 to 20000 CFM size AHU | BI01010001440000000000000515BI0100001114 | 2 | Nos |
4 | 1.03 | 28000 to 30000 CFM size AHU | BI01010001010033300000000515BI0100001115 | 5 | Nos |
5 | 2 | Supplying,Installation,Testing,Commissioning of new M.S. Chilled water Piping complete with all accessories, duly insulated with 32mm Class "O" Nitrile Rubber Insulation, fiber glass clothing and painting after dismentalling and buyback of existing wornout Piping in existing AHU Rooms at various locations etc. as required. MAKE: SAIL/JINDAL/TATA | BI01010001010000765000000515BI0100001124 | ||
6 | 2.01 | 80mm | BI01010001010777000000000515BI0100001116 | 30 | MTR |
7 | 2.02 | 65mm | BI01010001010000000000000515BI0100001117 | 5 | MTR |
8 | 2.03 | 50mm | BI01010001010000066600000515BI0100001118 | 5 | MTR |
9 | 3 | Supplying,Installation,Testing,Commissioning of following dia M.S. Drain Pipe duly insulated with 32mm Class "O" Nitrile Rubber Insulation with fiber glass clothing and painting after dismentalling and buyback of existing wornout Piping in existing AHU Rooms at various locations etc. as required. MAKE: SAIL/JINDAL/TATA | BI01010001010000000222000515BI0100001124 | ||
10 | 3.01 | 40mm | BI01010001010000000005500515BI0100001119 | 25 | MTR |
11 | 3.02 | 32mm | BI01010001010000000045000515BI0100001120 | 15 | MTR |
12 | 4 | Supplying,Installation,Testing,Commissioning of following sizes Manual Butterfly Valve with SS Disc complete with all accessories and duly insulated with 32mm Class "O" Nitrile Rubber Insulation with fiber glass clothing and painting after dismentalling and buyback of existing wornout Valve in existing AHU Rooms at various locations etc. as required. MAKE : SANT/CASTLE/ AUDCO/ ADVANCE/ZOLOTO | BI01010001010000005500000515BI0100001124 | ||
13 | 4.01 | 80mm | BI01010001810000000000000515BI0100001121 | 10 | Nos |
14 | 4.02 | 65mm | BI01010001010000000000000515BI0100001122 | 4 | Nos |
15 | 4.03 | 50mm | BI01010001010000008880000515BI0100001123 | 2 | Nos |
16 | 5 | Supplying,Installation,Testing,Commissioning of following sizes Balancing Valve Valve with SS Disc complete with all accessories and duly insulated with 32mm Class "O" Nitrile Rubber Insulation with fiber glass clothing and painting after dismentalling and buyback of existing wornout Valve in existing AHU Rooms at various locations etc. as required. MAKE : SANT/CASTLE/ AUDCO/ADVANCE/ZOLOTO | BI01010001010000000006700515BI0100001124 | ||
17 | 5.01 | 80mm | BI01010001010000000033300515BI0100001125 | 5 | Nos |
18 | 5.02 | 65mm | BI01010001010000000000000515BI0106001126 | 2 | Nos |
19 | 5.03 | 50mm | BI01010001010000000000009015BI0100001127 | 1 | Nos |
20 | 6 | Supplying,Installation,Testing,Commissioning of following suitable sizes 2 Way / 3 Way Motorized Valve with Actuator, Thermostat and Wiring complete with all accessories, duly insulated with 32mm Class "O" Nitrile Rubber Insulation with fiber glass clothing and painting after dismentalling and buyback of existing wornout Valve in existing AHU Rooms at various locations etc. as required. MAKE: DISTECH/JCI/HONEYWELL/SIEMENS | BI01010001010000000003210515BI0100001124 | ||
21 | 6.01 | Suitable for 80mm CHW Pipe Line | BI01010001010000000000000515BI0100991125 | 5 | Nos |
22 | 6.02 | Suitable for 65mm CHW Pipe Line | BI01010001010000000055500515BI0100001126 | 2 | Nos |
23 | 6.03 | Suitable for 50mm CHW Pipe Line | BI01010001010077000000000515BI0100001127 | 1 | Nos |
24 | 7 | Supplying,Installation,Testing,Commissioning of IP Based BACNet BMS Standalone 32 Bit Controllers suitable for AHU Automation (2 or more AHU Per Controller ) alongwith DDC Panel Enclosure complete with copper conductor Internal Wiring, Power supply and other accessories etc. required for DDC Panel to function in existing AHU Rooms at various locations etc. as required. MAKE: DISTECH/JCI/HONEYWELL/SIEMEN | BI01010044010000000000000515BI0100001127 | 4 | Nos |
25 | 8 | Supplying,Installation,Testing,Commissioning of following add on accessories/modifications for the existing IP Based BACNet BMS Standalone Controllers complete with copper conductor Internal Wiring in existing AHU Rooms at various locations etc. as required. | BI01010001010000000760000515BI0100001124 | ||
26 | 8.01 | Duct type Return Air Temperature. MAKE: DISTECH/JCI/HONEYWELL/SIEMENS/DWYER | BI01010341010000000000000515BI0100001125 | 8 | Nos |
27 | 8.02 | Curent Relay. MAKE: DISTECH/JCI/HONEYWELL/SIEMENS/DWYER | BI01010001010000000770000515BI0100001126 | 8 | Nos |
28 | 8.03 | Accessories in AHU Electrical Starter Panel / necessary modifications to make it compatible for BMS. | BI01010001010023000000000515BI0100001127 | 8 | Nos |
29 | 8.04 | 2C*1.0Sqmm ATC Armoured Signal Control Cables Required for Connecting AHU, Field Devices, Electrical Panel & DDC Enclosure. MAKE: POLYCAB/FUSION POLYMER/BATRA HENLEY | BI01010001010444000000000515BI0100001127 | 2100 | MTR |
30 | 9 | Supplying,Installation,Testing,Commissioning of following accessories with necessary insulation etc. in existing AHU Rooms at various locations etc. as required. | BI01010001010000023000000515BI0100001124 | ||
31 | 9.01 | Temperature Gauge. MAKE : H.GURU/Equivalent | BI01010001010000004400000515BI0100001125 | 16 | Nos |
32 | 9.02 | Pressure Gauge. MAKE : SANT/CASTLE/ AUDCO/ ADVANCE/ZOLOTO | BI01010044010000000000000515BI0100001126 | 16 | Nos |
33 | 9.03 | 25mm Size Drain Valve. MAKE : SANT/CASTLE/ AUDCO/ ADVANCE/ZOLOTO | BI01010333010000000000000515BI0100001127 | 16 | Nos |
34 | 9.04 | Auto Purge Valve. MAKE : SANT/CASTLE/ AUDCO/ ADVANCE/ZOLOTO | BI01010005510066600000000515BI0100001127 | 8 | Nos |
35 | 10 | Repairing of damaged portion of Supply Air Plenum by providing and fixing 20 SWG GI sheet in existing AHU at various locations etc. as required. MAKE: SAIL/JINDAL/TATA | BI01010001010000005555000515BI0100001127 | 12 | Sq.MTR |
36 | 11 | Repairing,Testing,Commissioning of existing VFD for AHUs of 13000 CFM to 30000 CFM capacity including replacement of mother board,display and other all accessories etc. to make VFD functional and integration with mixing valve through New controller in New AHUs at various locations etc. as required. (Repairing of VFD must be done by authorised OEM agency) | BI01010001010003450000000515BI0100001128 | 8 | Nos |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail