Finance Department has published External Electrification And Sub Station Works At Food Craft Institute Almora . . Submission Date for this Tender is 05-04-2021. Electrification Work Tenders in almora Uttarakhand. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 25-Mar-2021 | CORRIGENDUM | Other | 05-04-2021 |
Name of Work:CONSTRUCTION OF PROPOSED SUB STATION EQUIPMENTS AT FOOD CRAFT INSTITUTE ALMORA | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | TWO POLE STRUCTURE\nSupplying, installing, structural steel tubular pole conforming to IS-2713, 410 SP-51, 164 Kg weight with base plate of 300 mm x 300 mm x 6 mm for erecting 11 KV two pole structure comprising of 11 Mtr. pole, i/c welding, cutting, revetting, bolting and painting the entire structures with red oxide primer and two coats of synthetic enamel paint and necessary foundations including excavation and earth work for the steel structure with PCC 1:2:4 with following accessories. | BI01010001010000000000000515BI0100001127 | ||
2 | 1.01 | Supplying, installing 11 KV 9 KA discharge current single pole lightning arrestor with insulated base and necessary hardware. - 3 Nos. | BI01010001010000000000000515BI0100001128 | ||
3 | 1.02 | Supplying & installing 11 KV single pole strain insulators complete with all necessary hardware for termination. - 3 Nos. | BI01010001010000000000000515BI0100001129 | ||
4 | 1.03 | Supplying & installing 11 KV 3 phase, 200 Amp. Vertical type gang operated switch with hot dip galvanised channels post type, insulator, tinned copper contacts, arcing horns, GI pipe gang operating handle, limit switch etc. (wiring with 4 x 2.5 sq.mm PVC insulated copper wire upto HT breaker laid in GI pipe of 40mm dia) locking arrangements etc. complete in all respects. - 1 Set. | BI01010001010000000000000515BI0100001130 | ||
5 | 1.04 | Supplying & installing 11 KV post type insulators for jumper supports. - 3 Nos. | BI01010001010000000000000515BI0100001131 | ||
6 | 1.05 | 11 KV, 3 phase 200 Amp dropout fuse unit with 60 Amp fuses. Hot dip galvanished channel, post type insulator, tinned copper contacts bakelite fuse, carriers etc. complete in all respects. - 1 Set. | BI01010001010000000000000515BI0100001132 | ||
7 | 1.06 | Supplying & installing of "DOG" 6 /. 186 Al. Plus 7 / 0.062 Steel ACSR overhead conductor - 10 Mtrs. | BI01010001010000000000000515BI0100001133 | ||
8 | 1.07 | Cross arms of shape and size as shown on drawing and made out of M.S. channels 100mmx50mm with flats and fixed to poles with M.S. clamps, GI bolts, nuts and washers and all hardware, jumpers & thimbles etc. of required size. | BI01010001010000000000000515BI0100001134 | ||
9 | 1.08 | Anti Climbing devices on each pole made out of 2 mm barbed wire coiled alongwith pole. | BI01010001010000000000000515BI0100001135 | ||
10 | 1.09 | Danger Notice Boards with Skull & Bones in red colour made out of 14 SWG sheet in Hindi & English with voltage indicated. | BI01010001010000000000000515BI0100001136 | ||
11 | 1.1 | Supplying & installing 150 mm dia GI pipe - 10 Mtr. | BI01010001010000000000000515BI0100001137 | ||
12 | 1.11 | Earthing & GI Strips. | BI01010001010000000000000515BI0100001138 | ||
13 | 1.12 | Stay Assembly. | BI01010001010000000000000515BI0100001139 | 1 | Set |
14 | 2 | Supplying, installation, testing & commissioning of single panel with VCB totally enclosed, indoor sheet steel clad floor mounting, vermin proof, vertical isolation, horizontal drawout, extensible type air insulated metal clad switchgear having motorised mechanism SPMX, complete with circuits detailed as below The switchboard would be complete with necessary busbars and integral earthing facility through bus bar for the entire switchboard, small wiring labels, cable eyes, cable box to receive XLPE cables suitable for operation on 11 KV, three phase, 50 cycle, earthed system with a rupturing capacity of 350 MVA at 11 KV. | BI01010001010000000000000515BI0100001140 | ||
15 | 2.01 | Supplying, installation, testing & commissioning of single panel with VCB totally enclosed, indoor sheet steel clad floor mounting, vermin proof, vertical isolation, horizontal drawout, extensible type air insulated metal clad switchgear having motorised mechanism SPMX, complete with circuits detailed as below The switchboard would be complete with necessary busbars and integral earthing facility through bus bar for the entire switchboard, small wiring labels, cable eyes, cable box to receive XLPE cables suitable for operation on 11 KV, three phase, 50 cycle, earthed system with a rupturing capacity of 350 MVA at 11 KV. | BI01010001010000000000000515BI0100001141 | ||
16 | 2.02 | 1) One. Incoming panel equipped with air insulated Metal clad 630 Amps. Housing. | BI01010001010000000000000515BI0100001142 | ||
17 | 2.03 | 2) A set of three phase PVC insulated 630 Amp busbars. | BI01010001010000000000000515BI0100001143 | ||
18 | 2.04 | 3) One triple pole draw out truck mounted 350 MVA 630 amps, Vacuum Circuit Breaker fitted with all necessary vacuum interrupters. | BI01010001010000000000000515BI0100001144 | ||
19 | 2.05 | 4) One trip free, motor charged, spring released closing mechanism fitted with shunt trip suitable for 24 V DC operation complete with necessary auxiliary switches, emergency hand trip device and mechanical ON and OFF indicators. | BI01010001010000000000000515BI0100001145 | ||
20 | 2.06 | 5) 3 Nos 100/50/5A ratio, 15 VA, class 1.0 resin cast current transformer for metering purpose and 15 VA, class 5P10 resin cast current transformer for protection purposes. | BI01010001010000000000000515BI0100001146 | ||
21 | 2.07 | 6) One three phase horizontal draw out type resin cast line type potential transformer of 11KV/110 V, 100 VA burden per phase class 1.0 accuracy connected star/star on HV & LV sides with HV and LV fuses, isolating plugs, for HV side and LV connection. | BI01010001010000000000000515BI0100001147 | ||
22 | 2.08 | 7) One strip heater to prevent absorption of moisture. | BI01010001010000000000000515BI0100001148 | ||
23 | 2.09 | 8) IDMT relay having 2 over current & 1 no. Earth fault relay | BI01010001010000000000000515BI0100001149 | ||
24 | 2.1 | INSTRUMENT PANEL | BI01010001010000000000000515BI0100001150 | ||
25 | 2.11 | 1) One 144 sq.mm, scaled 0-15000V, flush type, digital voltmeter with 3 way and OFF selector switch. | BI01010001010000000000000515BI0100001151 | ||
26 | 2.12 | 2) One 144 sq.mm, scaled 0-200 Amps, flush type, digital ammeter with 3 way and OFF selector switch. | BI01010001010000000000000515BI0100001152 | ||
27 | 2.13 | 3) One 144 sq.mm digital PF meter. | BI01010001010000000000000515BI0100001153 | ||
28 | 2.14 | 4) One no. Electronic Trivector Meter. | BI01010001010000000000000515BI0100001154 | ||
29 | 2.15 | 5) One triple pole very inverse definite mean time over-current and earth fault relay two outer elements connected for over current protection and the middle element for earth fault protection with over current setting of 50-200%,and earth fault setting 10 to 40% and short circuit setting of 200-800%. | BI01010001010000000000000515BI0100001155 | ||
30 | 2.16 | 6) One no. trip circuit supervision relay. | BI01010001010000000000000515BI0100001156 | ||
31 | 2.17 | 7) One no. Master trip relay. | BI01010001010000000000000515BI0100001157 | ||
32 | 2.18 | 8) Annunciation circuit for fault tripping of HT panels with 8 Window annunciation with windows. | BI01010001010000000000000515BI0100001158 | ||
33 | 2.19 | 9) One set of Red/Green/Indication lamps for check and open protection. | BI01010001010000000000000515BI0100001159 | ||
34 | 2.2 | 10) One Amber indicating lamp for trip circuit healthy | BI01010001010000000000000515BI0100001160 | ||
35 | 2.21 | 11) One set of white phase indication lamps for phase. | BI01010001010000000000000515BI0100001161 | ||
36 | 2.22 | OUTGOING | BI01010001010000000000000515BI0100001162 | ||
37 | 2.23 | 1) Outgoing Panel equipped with air insulated Metal clad 630 Amps. Housing | BI01010001010000000000000515BI0100001163 | ||
38 | 2.24 | 2) A set of three phase PVC insulated 630 Amp busbars. | BI01010001010000000000000515BI0100001164 | ||
39 | 2.25 | 3) One triple pole draw out truck mounted 350 MVA 630 amps, Vacuum Circuit Breaker fitted with all necessary vacuum interrupters. | BI01010001010000000000000515BI0100001165 | ||
40 | 2.26 | 4) One trip free, motor charged, spring released closing mechanism fitted with shunt trip suitable for 24 V DC operation complete with necessary auxiliary switches, emergency hand trip device and mechanical On and OFF indicators. | BI01010001010000000000000515BI0100001166 | ||
41 | 2.27 | 5) 3 Nos 50/30/5 A ratio, 15 VA, class 1.0 Resin cast current transformer for metering purpose and 15 VA class 5P10 resin cast current transformer for protection purposes. | BI01010001010000000000000515BI0100001167 | ||
42 | 2.28 | 6) One strip heater to prevent absorption of moisture. | BI01010001010000000000000515BI0100001168 | ||
43 | 2.29 | 7) One 144 sq.mm, scaled 0-30Amps, flush type, digital ammeter with 3 way and OFF selector switch. | BI01010001010000000000000515BI0100001169 | ||
44 | 2.3 | 8) One no. trip circuit supervision relay. | BI01010001010000000000000515BI0100001170 | ||
45 | 2.31 | 9) One no. Master trip relay | BI01010001010000000000000515BI0100001171 | ||
46 | 2.32 | 10) One set of Red/Green/Indication lamps for check and open protection. | BI01010001010000000000000515BI0100001172 | ||
47 | 2.33 | 11) One amber indicating lamp for trip circuit healthy. | BI01010001010000000000000515BI0100001173 | ||
48 | 2.34 | 12) One set of white phase indication lamps for phase. | BI01010001010000000000000515BI0100001174 | ||
49 | 2.35 | 13) Suitable cable boxes with double compression brass glands suitable to receive 3 Core 11KV XLPE cable. | BI01010001010000000000000515BI0100001175 | ||
50 | 2.36 | 14) Annunciation circuit for fault tripping of HT panels with 8 Window annunciation with windows. | BI01010001010000000000000515BI0100001176 | ||
51 | 2.37 | 15) IDMT relay having 2 over current & 1 no. Earth fault relay | BI01010001010000000000000515BI0100001177 | 1 | Set |
52 | 3 | Supplying, installing, testing & commissioning of O.L.T.C. 400 KVA Dry Type Transformer with copper winding having 400 KVA rating 11 KV / 433 V, 3 Phase, 50 Hz Vector Group Dyn-11, having cable end box on HV side suitable for 11 KV XLPE cable & on 433 Volt side suitable for XLPE cable.The Transformer shall have on load tap changing links on HV side, for +7.5% to -7.5% in steps of 2.5% with locking arrangement. It shall also have Thermistor Type Sensor for high temperature Alarm & Trip contacts, Earthing Terminal, Lifting hooks, base channels skid type suitable for mounting on floor and plinth. The enclosure of transformer shall be sheet steel enclosure type IP33 for indoor installation complete as required. | BI01010001010000000000000515BI0100001178 | 1 | set |
53 | 4 | Supplying, installing, testing & commissioning of Trickle Boost Charger of 24 Volt complete with automatic trickle charger, change over complete with voltmeter, ammeter 50 Hz. AC supply & DC ammeter / voltmeter complete with 12 Nos. 2 Volt batteries, 40 AH etc. as required. | BI01010001010000000000000515BI0100001179 | 1 | Set |
54 | 5 | 150 KVAR CAPACITOR PANEL | BI01010001010000000000000515BI0100001180 | ||
55 | 5.01 | Supplying, installing, testing & commissioning of compartmentalised wall mounted / floor mounted cubicle board made from 2mm thick CRCA sheet dust & vermin proof duly phosphatized & powder coated inclusive of suitable size 4 strip Al. Busbar complete with interconnection providing Lugs, inter-earthing, painting etc. i/c providing & fixing below noted accessories: | BI01010001010000000000000515BI0100001181 | ||
56 | 5.02 | INCOMING : | BI01010001010000000000000515BI0100001182 | ||
57 | 5.03 | 200 Amp 415 V FP MCCB having breaking capacity - 50 KA, with Rotary Handle operating Mechanism - 1 Nos. | BI01010001010000000000000515BI0100001183 | ||
58 | 5.04 | (0-200 A) Digital Ammeter with selector switch & 200/5 C.T.'s - 1 Set | BI01010001010000000000000515BI0100001184 | ||
59 | 5.05 | 0 - 500 Volt Voltmeter with selector switch - 1 Set | BI01010001010000000000000515BI0100001185 | ||
60 | 5.06 | RYB Indication lamps with Backup fuses - 1 Set of three | BI01010001010000000000000515BI0100001186 | ||
61 | 5.07 | Power factor meter - 1 Set | BI01010001010000000000000515BI0100001187 | ||
62 | 5.08 | 8 step APFC relay with aux. Contactor and timer - 1 Set | BI01010001010000000000000515BI0100001188 | ||
63 | 5.09 | OUTGOING : | BI01010001010000000000000515BI0100001189 | ||
64 | 5.1 | 80 Amp 415 V TP MCCB having breaking capacity - 35 KA, with Ics=Icu=35 KA, with Rotary Handle operating Mechanism - 5 Nos. | BI01010001010000000000000515BI0100001190 | ||
65 | 5.11 | 63 A TP Contactor - 5 Nos. | BI01010001010000000000000515BI0100001191 | ||
66 | 5.12 | 25 KVAR Capacitor banks - 5 Sets (MPP type Normal Duty) | BI01010001010000000000000515BI0100001192 | ||
67 | 5.13 | Push button for START / STOP - 5 Set | BI01010001010000000000000515BI0100001193 | ||
68 | 5.14 | AUTO / MANUAL Selector switch - 1 No. | BI01010001010000000000000515BI0100001194 | 1 | Set |
69 | 6 | Supplying, installing, testing & commissioning of 630 amp. Ready to intall factory fabricated automatic transformer switch (ATS) to manage the automatic change over between two supply lines (one from transformer & the other from D.G. Set) along with enclosure CRCA sheet steal duly power coated after derusting, degreasing & phosphetising etc. complete with electronic control box, inverted mounting plate and 2 nos. 630 amp. MCCB's 70 KA, connection, interconnection, lungs etc. as required. | BI01010001010000000000000515BI0100001195 | 1 | Set |
70 | 7 | FEEDER PILLAR - 1 (out door cubical panel) | BI01010001010000000000000515BI0100001196 | ||
71 | 7.01 | Supply and creation of factory fabricated and wired metal clad dust and vermin proof floor mounting panel MCCB switch board complete with the following MCCB , MCB and instrument chamber etc. complete in all respects. the instrument chamber shall be separate and shall comprise of digital type ammeter. Voltmeter, selector switches for ammeter and voltmeter instrument, fuses current transformer etc. The Board shall have suitable capacity electrolytic aluminum bus-bars as per IS:8623 insulated with heat shrink sleevings and mounted on non hygroscopic supports such as CMC/DMC supports with detachable side covers and shall be suitable for extension on the sides. The switches shall be complete with suitable cable end boxes, cable sockets, compression glands and indicating lamp on incoming etc.The switch board shall be fabricated with CRCA sheet with a minimum thickness of 1.6mm/2mm cubical type. \n.\n\n | BI01010001010000000000000515BI0100001197 | ||
72 | 7.02 | INCOMING : | BI01010001010000000000000515BI0100001198 | ||
73 | 7.03 | 100 Amp 415 V FP MCCB having breaking capacity - 25 KA, with Ics=Icu=25 KA, with Rotary Handle operating Mechanism - 1 No. | BI01010001010000000000000515BI0100001199 | ||
74 | 7.04 | (0- 100A) Digital Ammeter with selector switch, 100/5A C.T.'s - 1 Set | BI01010001010000000000000515BI0100001200 | ||
75 | 7.05 | (0-500 V) Digital Voltmeter with selector switch - 1 Set | BI01010001010000000000000515BI0100001201 | ||
76 | 7.06 | Indication lamp R/Y/B with backup fuses - 1 Set of Three | BI01010001010000000000000515BI0100001202 | ||
77 | 7.07 | 150A strip Al. bus bars with heat shrinkable colored PVC sleeves 1 Set | BI01010001010000000000000515BI0100001203 | ||
78 | 7.08 | OUTGOING | BI01010001010000000000000515BI0100001204 | ||
79 | 7.09 | 63 Amp 415 V TP MCCB having breaking capacity - 25 KA, with Ics=Icu=25 KA, with Rotary Handle operating Mechanism - 7 No. | BI01010001010000000000000515BI0100001205 | ||
80 | 7.1 | 63A FP MCCB -1 No. | BI01010001010000000000000515BI0100001206 | ||
81 | 7.11 | 40A FP CONTACTOR - 1 No. | BI01010001010000000000000515BI0100001207 | ||
82 | 7.12 | 40A TP Isolater -2 No. | BI01010001010000000000000515BI0100001208 | ||
83 | 7.13 | Timer for 24 hours | BI01010001010000000000000515BI0100001209 | 1 | Set |
84 | 8 | Supplying of following size of 11 KV cable circular aluminium conductor, conductor screened, XLPE insulated, insulation screened with extruded semi-conducting compound in combination with copper tape (short ckt. rating (350MVA for 1 sec). Aluminium round wire armoured and overall PVC sheathed cable conforming to IS:7098/II/85 with latest amendments complete as reqd. | BI01010001010000000000000515BI0100001210 | ||
85 | 8.01 | 3 core 185 sq.mm. | BI01010001010000000000000515BI0100001211 | 50 | Mtr |
86 | 8.02 | 3 core 120 sq.mm. | BI01010001010000000000000515BI0100001212 | 25 | Mtr |
87 | 9 | Supplying and making INDOOR cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required. | BI01010001010000000000000515BI0100001213 | ||
88 | 9.01 | 120 sq. mm | BI01010001010000000000000515BI0100001214 | 3 | Nos |
89 | 9.02 | 185 sq. mm | BI01010001010000000000000515BI0100001215 | 2 | Nos |
90 | 10 | Supplying and making OUTDOOR cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor .cable of 11 KV grade as required: | BI01010001010000000000000515BI0100001216 | ||
91 | 10.01 | 185 sq. mm | BI01010001010000000000000515BI0100001217 | 1 | Nos |
92 | 11 | Laying of one number PVC insulated and PVC but not exceeding 11 KV of size exceeding 120 sq. mm but not exceeding 400 sq. mm dirct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. | BI01010001010000000000000515BI0100001218 | 25 | Mtr |
93 | 12 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade (XLPE type) at a depth of 750mm below ground lever over a cushion of 75 mm. thick sand around and protect with burnt bricks on sides and on top. as directed by he Engineer-armouring of by he cable shall be properly connected with the earth conductor by clamps etc. | BI01010001010000000000000515BI0100001219 | ||
94 | 12.01 | 3.5 x 185 sq.mm. | BI01010001010000000000000515BI0100001220 | 50 | Mtr |
95 | 12.02 | 3.5 x 300 sq.mm. | BI01010001010000000000000515BI0100001221 | 40 | Mtr |
96 | 13 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1. KV grade as required : | BI01010001010000000000000515BI0100001222 | ||
97 | 13.01 | 3.5 x 185 sq.mm. | BI01010001010000000000000515BI0100001223 | 2 | Nos |
98 | 13.02 | 3.5 x 300 sq.mm. | BI01010001010000000000000515BI0100001224 | 4 | Nos |
99 | 14 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement :2 fine sand) including testing of joints etc. complete. | BI01010001010000000000000515BI0100001226 | ||
100 | 14.01 | 250 mm dia. R.C.C. pipe | BI01010001010000000000000515BI0100001227 | 30 | Mtr |
101 | 15 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick Including accessoires, & providing masonary enclosure with cover plate having locking arrangement & watering pipe etc. (but without charcoal or coke and salt) as required. | BI01010001010000000000000515BI0100001228 | 6 | Set |
102 | 16 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick Including accessories, & providing masonary enclosure with cover plate having locking arrangement & watering pipe etc. (but without charcoal or coke and salt) as required. | BI01010001010000000000000515BI0100001229 | 4 | Set |
103 | 17 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode, as required. | BI01010001010000000000000515BI0100001230 | 75 | Mtr. |
104 | 18 | Providing & fixing 25 mm X 5 mm G.I strip on surface or in recess for connections etc. as required. | BI01010001010000000000000515BI0100001231 | 80 | Mtr. |
105 | 19 | Providing and fixing M.V danger notice plate of 200 mm x 150 mm, made mild steel, atleast 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.st 2mm thick & vitreous enamelled white on both sides & with inscription in single red colour on front side as required. | BI01010001010000000000000515BI0100001232 | 4 | Set |
106 | 20 | DANPLHV P/F H.V. danger notice plate: each\nProviding and fixing H.T danger notice plate of 250 x 200 mm, made mild steel, atleast 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. | BI01010001010000000000000515BI0100001233 | 2 | Set |
107 | 21 | Supplying and making cable route marker with cement concrete 1.2.4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) of size 60 cm x 60 cm at the bottom and 50 cm x 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. | BI01010001010000000000000515BI0100001234 | 40 | set |
108 | 22 | Providing, installing, testing and commissioning of Diesel Generating set having prime power rating of 125 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system and consisting of the following: | BI01010001010000000000000515BI0100001235 | ||
109 | 22.01 | Diesel Engine | BI01010001010000000000000515BI0100001236 | ||
110 | 22.02 | Diesel Engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at site condition and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour in any 12 hours duration. The engine will be fitted complete with all the reqd. acc. including the following accessories: | BI01010001010000000000000515BI0100001237 | ||
111 | 22.03 | Flywheel to suit flexible coupling | BI01010001010000000000000515BI0100001238 | ||
112 | 22.04 | Flexible coupling | BI01010001010000000000000515BI0100001239 | ||
113 | 22.05 | Exhaust gas turbo charger | BI01010001010000000000000515BI0100001240 | ||
114 | 22.06 | Automatic safety control in case of high water temperature | BI01010001010000000000000515BI0100001241 | ||
115 | 22.07 | Automatic safety control in case of low lubrication oil pressure | BI01010001010000000000000515BI0100001242 | ||
116 | 22.08 | Automatic over speed trip protection | BI01010001010000000000000515BI0100001243 | ||
117 | 22.09 | Lubrication oil pump | BI01010001010000000000000515BI0100001244 | ||
118 | 22.1 | Lubrication oil filter | BI01010001010000000000000515BI0100001245 | ||
119 | 22.11 | Lubrication oil pan | BI01010001010000000000000515BI0100001246 | ||
120 | 22.12 | Lube oil By-Pass filter | BI01010001010000000000000515BI0100001247 | ||
121 | 22.13 | Fuel pump | BI01010001010000000000000515BI0100001248 | ||
122 | 22.14 | Fuel filter | BI01010001010000000000000515BI0100001249 | ||
123 | 22.15 | Hoses for fuel tank | BI01010001010000000000000515BI0100001250 | ||
124 | 22.16 | Air intake manifold | BI01010001010000000000000515BI0100001251 | ||
125 | 22.17 | Air cleaner dry type | BI01010001010000000000000515BI0100001252 | ||
126 | 22.18 | Electronic Governor | BI01010001010000000000000515BI0100001253 | ||
127 | 22.19 | Self Starter | BI01010001010000000000000515BI0100001254 | ||
128 | 22.2 | Alternator for battery charging | BI01010001010000000000000515BI0100001255 | ||
129 | 22.21 | Flexible pipe for silencer | BI01010001010000000000000515BI0100001256 | ||
130 | 22.22 | Engine mounted Instrument Panel fitted with and having digital display for following: | BI01010001010000000000000515BI0100001257 | ||
131 | 22.23 | Start-stop switch with key | BI01010001010000000000000515BI0100001258 | ||
132 | 22.24 | Water temperature indication | BI01010001010000000000000515BI0100001259 | ||
133 | 22.25 | Lubrication oil pressure indication | BI01010001010000000000000515BI0100001260 | ||
134 | 22.26 | Lubrication oil temperature indication | BI01010001010000000000000515BI0100001261 | ||
135 | 22.27 | Battery charging indication | BI01010001010000000000000515BI0100001262 | ||
136 | 22.28 | RPM indication | BI01010001010000000000000515BI0100001263 | ||
137 | 22.29 | Over speed indication | BI01010001010000000000000515BI0100001264 | ||
138 | 22.3 | Low lub. Oil trip indication | BI01010001010000000000000515BI0100001265 | ||
139 | 22.31 | Engine Hours indication | BI01010001010000000000000515BI0100001266 | ||
140 | 22.32 | Alternator: | BI01010001010000000000000515BI0100001267 | ||
141 | 22.33 | Synchronous alternator rated at 125 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at site condition. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722 / BS 2613 suitable for tropical conditions and with class-F/H insulation. | BI01010001010000000000000515BI0100001268 | ||
142 | 22.34 | Base Frame & Foundation: | BI01010001010000000000000515BI0100001269 | ||
143 | 22.35 | Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. | BI01010001010000000000000515BI0100001270 | ||
144 | 22.36 | Fuel Tank: | BI01010001010000000000000515BI0100001271 | ||
145 | 22.37 | Daily service fuel tank of 990 liters capacity fabricated out of 3mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required. | BI01010001010000000000000515BI0100001272 | ||
146 | 22.38 | Exhaust System: | BI01010001010000000000000515BI0100001273 | ||
147 | 22.39 | Dry exhaust manifold with hospital exhaust silencer and catalytic converter. | BI01010001010000000000000515BI0100001274 | ||
148 | 22.4 | Starting System: | BI01010001010000000000000515BI0100001275 | ||
149 | 22.41 | 12V / 24 V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation. Complete with suitable nos. of batteries. | BI01010001010000000000000515BI0100001276 | ||
150 | 22.42 | Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. | BI01010001010000000000000515BI0100001277 | 1 | Set |