Proving Conceal Internal Electrification On The Newly Constructed 50 Bedded Chc Building At Kumarghat Except Pipe Laying 3Rd Call
Tender Value
41.13 Lakhs
Estimated cost
Bid Submission
05 Apr 2021
0 days left
EMD
41138
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
KUMARGHAT → Tripura
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Proving Conceal Internal Electrification On The Newly Constructed 50 Bedded Chc Building At Kumarghat Except Pipe Laying 3Rd Call
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light/ fan/ exhaust fan/ call bell point with 2x1.5 sq. mm PVC insulated copper conductor cable (FR) in the existing PVC conduitrecessed in slab/ wall complete with 6/10 amp moduler type switch, GIswitch board, cover plate, including necessary connection etc. as required. |
| 2 | Wiring for 2 way controlling light point with 3x1.5 sq. mm PVC insulated copper conductor cable (FR) in the existing PVC conduitrecessed in slab/ wall complete with 10 amp moduler type2 way switch, GI switch board, cover plate, including necessary connection etc. as required. |
| 3 | Wiring for Circuit/Sub-main wiring with the following sizes of PVC insulated copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required. |
| 4 | a. 2 X 1.5 sq mm. |
| 5 | b. 2 X 2.5 sq mm. |
| 6 | c. 2 X 4 sq mm. |
| 7 | d. 2 X 6 sq mm. |
| 8 | d. 4 X 6 sq mm |
| 9 | e. 4 X 10 sq mm. |
| 10 | f. 4 X 16 sq mm |
| 11 | h. 1 X 1.5 sq mm |
| 12 | i. 1 X 2.5 sq mm |
| 13 | Providingearthing systemwith maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 50 kg, terminalsize 32x 6mm i/c accessories with masonry enclosure of CIcover plate size 12\"x 12\" having locking arrangement including CC works etc as required |
| 14 | Proving and fixing / Drawing 4.06 mm dia (8 SWG) copperwire on surface or inexisting G.I / PVC / Polythene pipe for loop earthing as required. |
| 15 | Providng and laying 15mm dia(medium gauge) G.I. pipe for drawing of4.06mm (8SWG) dia G.I./ Copper wire forearth connection from earth electrodes etc as required. |
| 16 | Supply and fixing of the following sizes GIpronewith necessary nuts & bolts etc as required grouted on roof for Lightning protection. |
| 17 | a.G.I Prone 60 cm long. |
| 18 | Supply and fixing of 25 x 5mm GI strip on wall/ floor of the building for horizontal/ vertical run including necessary spacers and porcelain insulators at regular intervals. |
| 19 | Supply and fixing of 30/32 x 6 mm GI strip on walls/ floor of the building for horizontal/ vertical run including necessary spacers and porcelain insulators at regular intervals. |
| 20 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick i/c accessories and providing masonry enclosure withCIcover plate Size 12\"x 12\" having locking arrangement, alongwith20 mm dia (medium gauge) watering pipe including CC work etc as required. |
| 21 | Extra for using salt (12 kg) and charcoal (96kg) for plate earth electrode as required. |
| 22 | Supplying and fixing of the following sizes GI (in recess) and plastic (on surface) modular switch boards etc. as required. |
| 23 | a. 1-2 module GI switch board |
| 24 | b. 6 module GI switch board. |
| 25 | c. 12 module GI switch board. |
| 26 | Supplying and fixing of the following sizes modular type cover plates for GI/plastic modular switch boards etc. as required. |
| 27 | a. 1-2 module. |
| 28 | b. 6 module. |
| 29 | c. 12 module. |
| 30 | Supplying and fixing of the following modular accessories including necessary connection etc. as required. |
| 31 | a. 6/10 amps one way SP switch (1M). |
| 32 | b. 3 pin 6/10 amps socket outlet (2M). |
| 33 | c. 16/20 amps one way SP switch (1M). |
| 34 | d. 3/6 pin 16/20 amps socket outlet (2M). |
| 35 | e. 20/25 amps single phase motor starter switch (2M). |
| 36 | f. Blank plate (1M). |
| 37 | Supplying and fixing of the following ratingsBus bar chamber of copper strip made of sheet steel enclosure with all accessories including drilling holes on the board/MS clamp and necessary connection etc. as required. |
| 38 | a. 100 Amps 415 volts four strip of size (455mmx330mmx120mm) |
| 39 | b. 32 Amps 415 volts four strip of size (300mmx240mmx80mm) |
| 40 | c. 63 Amps 415 volts four strip of size (330mmx280mmx100mm) |
| 41 | Supplying and fixing of the following ratings switch disconnector fuse unit(main switch)made of sheet steel enclosure with all accessories including drilling holes on the board/MS clamp and necessary connection etc. as required. |
| 42 | a. 100 amps TPN 415 volts cubical front handle including HRC/HBC fuse link. |
| 43 | b. 32 amps 415 volts TPN (rewireable) |
| 44 | Supplying and fixing of the following changeover switch made of sheet steel enclosure with all accessories including drilling holes on the board/MS clamp including necessary connection etc. as required. |
| 45 | a. 400 amps FP on load change over (Front handle) |
| 46 | b. 63 amps FP on load change over (Front handle) |
| 47 | Supplying and fixing of powder coated sheet steel enclosure on surface/recess, suitable for 240/415 volts MCB/Isolator/RCCB (SP/SPN/DP/TP/TPN/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connectionas required. |
| 48 | a. 2+4 / 6 way MCB DB (double door). |
| 49 | b. 2+6 / 8 way MCB DB (double door). |
| 50 | c. 2+10 / 12 way MCB DB (double door). |
| 51 | d.4 way TPN MCB DB (double door). |
| 52 | e.6 way TPN MCB DB (double door). |
| 53 | Supplying and fixing of powder coated sheet steel enclosure (Double door) on surface/recess,suitable for 415 volts MCB/MCCB (TP/TPN/FP) incomer complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connectionas required. |
| 54 | a. 4 way vertical TPN MCB DB suitable for MCCB as incomer. |
| 55 | Supplying and fixing of powder coated sheet steel enclosure on surface/recess, suitable for 415 volts MCCB (TP/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connectionas required. |
| 56 | a. 8 way suitable for TP MCCB outgoing & TP MCCB incomer upto 400 amps:- |
| 57 | Supplying, installation, testing & commissioning of powder coated prewired digital meter module complete with ammeter, voltmeter, phase indicator lamp, control fuses, CTs, in the existing panel board including connectionas required. |
| 58 | Supplying, installation, testing & commissioning of powder coated cable alley (1 pair) in the existing panel board including connectionas required. |
| 59 | Supplying & fixing of following ratings MCBB/C curve having breaking capacity10 KA in the existing MCB DB including connectionas required. |
| 60 | a. 6 to 32 amps SP MCB. |
| 61 | b. 6 to 32 amps DP MCB |
| 62 | c. 6 to 32 amps FP MCB. |
| 63 | c. 40 amps FP MCB. |
| 64 | d. 40 amps TP MCB. |
| 65 | e.50/63 amps TP MCB. |
| 66 | f.50/63 amps FP MCB. |
| 67 | Supplying & fixing offollowing ratings TP/FP MCCB having breaking capacity 16/18 KA in the existing MCCB enclosure/ panel board including connection etc as required. |
| 68 | a. 16 to 100 amps TP MCCB. |
| 69 | Supplying & fixing offollowing ratings TP/FP MCCB having breaking capacity 25 KA in the existing MCCB enclosure/ panel board including connection etc as required. |
| 70 | a. 25 to 125 amps TP MCCB. |
| 71 | Supplying & fixing of TP/FP MCCB having breaking capacity 50 KA of following ratings in the existing MCCB enclosure/ panel board including connection etc as required. |
| 72 | a. 400 amps TP MCCB. |
| 73 | Supplying & fixing of 1200 mm sweep white color AC ceilingfan capacitor typedouble ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades, including wiring the down rod with 2x1.5 sqmm PVC insulated copper conductor cable(FR) (ISI Marked, BEE 1 Star/minimum service value 4.0) |
| 74 | Installation, testing and commissioning of ceiling fan i/c wiring the down rod of standard length (up to 30 cm) by 2 x 1.5 Sq.mm PVC insulated copper conductor cable etc as required. |
| 75 | Supplying & fixing of electronic modular 4 step fan regulator in existing switch board including necessary connection etc as required. |
| 76 | Supplying & installation of 400 mm sweep AC wall mounting fan with plastic blade including connection etc as required. |
| 77 | Supplying & installation of 300 mm sweep 900 rpm metalic body exhaust fan including connection etc as required. |
| 78 | Supplying & installation of shutter for 230/300 mm sweep metalic body exhaust fan in the existing hole as required. |
| 79 | Making different sizes of hole in the wall for fixing of exhaust fan including finishing the same with cement plastering and painting etc as required. |
| 80 | Supplying and fixing of the following luminaries (Surface/Recess) including necessary accessories and connection with 2x1.5 sq.mm PVC insulated coper conductor cable(FR) etc. as required. |
| 81 | a. Single box type FTL fittings CRCA sheet steel housing with white reflector cover fitted on the body completewith decorative end cap,36/40 W FTL,electronic ballast, holder. |
| 82 | Supplying and fixing of the following lighting accessories(Lamp, Ballast,Starter,Ignitor etc) and connection etc. as required. |
| 83 | a. 14/15 WRetrofit CFL. |
| 84 | Supplying and fixing of following surface/recess mounting LED luminaries complete with powder coated die cast housing and high efficiency diffuser including necessary connection etc. as required. |
| 85 | a. 12-18 watt (round/square shaped) LED light fixture. |
| 86 | b. 20 watt LED TL fittings. |
| 87 | Supplying and fixing of following outdoor LED luminaries complete with powder coated die cast housing and heat resistant tempered glass/ diffuser including necessary connection etc. as required. |
| 88 | a. 45-48 watt LED street light fixture (IP 66). |
| 89 | b. 60-65 watt LED street light fixture (IP 66). |
| 90 | Supplying & fixing of G.I. pipe (medium gauge) bracket fabricated at suitable angle for fixing of outdoor light on wall/ RCC base with necessary MS clamp, nut, bolt etc as required. |
| 91 | a.50 mm dia. |
| 92 | Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering,shuttering, finishing and reinforcement- 1:2:4 ( 1 Cement: 2 fine sand : 4 graded well burnt brick aggregate 20 mm nominal size) |
| 93 | Centering shuttering including struttings, propping etc. and removal of form work for: Foundations, footings, bases for columns etc. for mass concrete with timber plank. |
| 94 | 6 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete. In cement mortar 1 : 4 ( 1 cement : 4 fine sand ). |
| 95 | Supplying & fixing of digital/ astronomical time switch including necessary connection etc as required. |
| 96 | Supplying & fixing of following power contactors including necessary connection etc as required. |
| 97 | a. 18-25 amps 3 pole power contactors. |
| 98 | Supplying and laying of the following XLPE insulated PVC sheathed alluminum armoured cable including connection etc as required. |
| 99 | a. 2 core 4 Sq mm. |
| 100 | b.3.5 core 50 Sq mm. |
| 101 | c. 3.5 core 300 Sq mm. |
| 102 | Supplyingandfixingoffollowing alluminum terminal ends. |
| 103 | a. 25 sq mm |
| 104 | b. 50 sq mm |
| 105 | c. 150 sq mm |
| 106 | d. 300 sq mm. |
| 107 | Supplyingandfixingoffollowing copper terminal ends. |
| 108 | b. 10 sq mm |
| 109 | c. 16 sq mm |
| 110 | Excavation of earth for cable tranch of 800mm depth & 300mm width in all kinds of soil including back filling of cable trench with the excavated soil with 20cm layer of sand, 3.5 nos bricks/ metre for protection including ramming, consolidating to the original shape as required. |
| 111 | Drawing of armoured/un-armoured cable with proper saddeling etc as required. |
| 112 | Supplying and fixing of the following PVC conduit (medium gauge) with all accessories on slab/ recessed on wall etc as required. |
| 113 | a. 20 mm dia |
| 114 | b. 25 mm dia |
AI Tender Summary
Tender Timeline
Mar 20, 2021
11:30 IST
Tender Published
Tender notice published.
CompletedApr 05, 2021
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedApr 06, 2021
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender