Special Repair Replacement Of Lt Overhead Line With Ug Cable Including Allied Works In Zone O And Conversion Of Conventional Light Fittings Qty 48 Into Led Ultra Light High Bay 120W Light Fittings In Bldg No P 260 In Zone J At Mil Stn Agartala-Tripura

Military Engineer Services-MES has published Special Repair Replacement Of Lt Overhead Line With Ug Cable Including Allied Works In Zone O And Conversion Of Conventional Light Fittings Qty 48 Into Led Ultra Light High Bay 120W Light Fittings In Bldg No P 260 In Zone J At Mil Stn Agartala. Submission Date for this Tender is 16-04-2021. Overhead Line Tenders in Tripura. Bidders can get complete Tender details and download the document.




Tender Notice

27398859
Corrigendum : Special Repair Replacement Of Lt Overhead Line With Ug Cable Including Allied Works In Zone O And Conversion Of Conventional Light Fittings Qty 48 Into Led Ultra Light High Bay 120W Light Fittings In Bldg No P 260 In Zone J At Mil Stn Agartala
Open Tender
Indian
Tripura
16-04-2021

Tender Details

Special Repair Replacement Of Lt Overhead Line With Ug Cable Including Allied Works In Zone O And Conversion Of Conventional Light Fittings Qty 48 Into Led Ultra Light High Bay 120W Light Fittings In Bldg No P 260 In Zone J At Mil Stn Agartala

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Apr-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-04-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 50800.0 /-
Tender Value
INR 25.40 Lakhs /-

BOQ Items

Name of Work: SPL REPAIR /REPLACEMENT OF LT OVERHEAD LINE WITH UG CABLE INCLUDING ALLIED WORKS IN ZONE ‘O’ AND CONVERSION OF CONVENTIONAL LIGHT FITTINGS QTY-48 INTO LED ULTRA LIGHT HIGH BAY 120W LIGHT FITTINGS IN BLDG NO P-260 IN ZONE ‘J’ AT MIL STN AGARTALA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches not exceeding 1.50 m wide and n.exc1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil etc complete all as specified and directed. 330 Cum
2 2 Returning, filling in, of soil including spreading leveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and directed . 187.2 Cum
3 3 Removing excavated material to a distance n. exc. 50M and deposited/ spreaded where directed at a level n. exc 1.5 M above the starting point complete all as specified and as directed . 142.8 Cum
4 4 Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of under ground cable including spreading and punning down complete all as specified and as directed.\n(Punned down thickness shall be measured) 112.2 Cum
5 5 Materials and labour for brick protection cover to underground cables with sub class ‘B’ over burnt brick of size 23 X 11.5 X 7.5 cm, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10mm complete all as specified and directed. 10920 Each
6 6 Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured LT electric power UG cable (heavy duty with stranded aluminum conductor) of size 120 Sqmm, 3.5 core, 1100 Volts(Earthed) grade, confirming to IS-7098 (Part-I) laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs complete all as specified and as directed.\nNote : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under respective item. 270 RM
7 7 .-Ditto- all as per item No 6.00 here-in-before but of size 95 Sqmm 3.5 core and -ditto-. 405 RM
8 8 .-Ditto- all as per item No 6.00 here-in-before but of size 35 Sqmm 3.5 core and -ditto-. 85 RM
9 9 .-Ditto- all as per item No 6.00 here-in-before but of size 25 Sqmm 3.5 core and -ditto-. 85 RM
10 10 .-Ditto- all as per item No 6.00 here-in-before but of size 16 Sqmm 2 core and -ditto-. 60 RM
11 11 .-Ditto- all as per item No 6.00 here-in-before but of size 10 Sqmm 2 core and -ditto-. 700 RM
12 12 Supply and fixing PVC insulated aluminium conductor cable, 1100 Volt grade, heavy duty served with inner sheathing of PVC tape armoured with galvanized steel wire or tape and overall PVC sheathed, twin core stranded conductor flat or circular, 4 Sqmm, nominal cross sectional area, drawn in suitable size conduit by using clamp, nut & bolts from junction box to street light fitting and testing complete all as specified and as directed.\n\n 120 RM
13 13 Dismantling of existing unserviceable/undersize ACSR conductor (of any size) , jumper from overhead line, removing unserviceable materials from site of work complete all as specified and as directed.\n 2.95 Qtl
14 14 Dismantling of unserviceable insulator of any size/type, complete all as specified and as directed. 90 Each
15 15 Dismantling of undersize / defected cross arms of M.S. channel or angle of any sections complete all as specified and as directed. 1.85 Qtl
16 16 Dismantling of old unservicable earth continuity conductor/craddle guard / craddle guard supporting wire of any type and size complete all as specified and as directed. 0.16 Qtl
17 17 Taking down old unserviceable LT UG/ service cable of size upto 25mm sqmm from trenches/ road/ floor/ poles/ wall complete all as specified and as directed. 50 RM
18 18 Supply, installation, testing & commissioning of cubical type CPRI approved Feeder pillar box of suitable size (approx 600 x 600 x 500 mm), double door, outdoor type, mounted on suitable size PCC foundation, totally enclosed factory made, vermin and weather proof front opening with locking arrangement made of MS angle iron frame work of size 40mm x 40mm x 6 mm and CRCA sheet of 3.00 mm thick as per IS-5039 duly painted with powder coated paints and canopy type roof 15cm extended in all side and two leaf hinged door in front side with locking arrangement and gasket arrangement with 1 Nos, 7 lever pad lock with 3 Nos keys and back side fixed with nuts & gasket, suitable for 415 Volts, 50Hz, 3 phase 4 wire system including provision of one set of bus bar of 400 Amps ( 4 Nos. aluminium strip of size 40mm x 10mm of 50 cm long and povision of 4 Nos hole for incoming and outgoing cable connection) fixed on porcelain insulator and carry out internal wiring of accessories with suitable size PVC copper lugs, nut, bolts & washers, gaskets etc., and providing cable glands at cable entry into panel, making all electrical connection of incoming and outgoing including painting with two coat of powder coated paint complete all as specified and directed with the following accessories:-\n(a) For incoming/Outgoing: MCCB 4 Pole, 415 Volt AC, Ics=100%Icu, 50 Hz, of 250 Amps with breaking capacity 25 KA - 01 Nos. with suitable size aluminium connection bus bar covered with PVC sleeves for incoming & outgoing sides of MCCB's.\n(b) Aluminium strip should be in RYB colour code with heat shrinkable PVC sleeves and hole in bus bar strip.\nNote:- Quoted rates are inclusive of following:-\n(i) Contractor will get approved the drawing of panel from AGE(I).\n(ii) PCC foundation of suitable size. 1 Each
19 19 Supply, installation, testing & commissioning of cubical type CPRI approved Feeder pillar box of suitable size (approx 800 x 800 x 500 mm), double door, outdoor type, mounted on suitable size PCC foundation, totally enclosed factory made, vermin and weather proof front opening with locking arrangement made of MS angle iron frame work of size 40mm x 40mm x 6 mm and CRCA sheet of 3.00 mm thick as per IS-5039 duly painted with powder coated paints and canopy type roof 15cm extended in all side and two leaf hinged door in front side with locking arrangement and gasket arrangement with 1 Nos, 7 lever pad lock with 3 Nos keys and back side fixed with nuts & gasket, suitable for 415 Volts, 50Hz, 3 phase 4 wire system including provision of one set of bus bar of 200 Amps ( 4 Nos. aluminium strip of size 40mm x 10mm of 70 cm long and povision of 6 Nos hole for incoming and outgoing cable connection) fixed on porcelain insulator and carry out internal wiring of accessories with suitable size PVC copper lugs, nut, bolts & washers, gaskets etc., and providing cable glands at cable entry into panel, making all electrical connection of incoming and outgoing including painting with two coat of powder coated paint complete all as specified and directed with the following accessories:-\n(a) For incoming/Outgoing: MCCB 4 Pole, 415 Volt AC, Ics=100%Icu, 50 Hz, of 100 Amps rating with breaking capacity 25 KA - 01 Nos. with suitable size aluminium connection bus bar covered with PVC sleeves for incoming & outgoing sides of MCCB's.\n(b) Aluminium strip should be in RYB colour code with heat shrinkable PVC sleeves and hole in bus bar strip.\nNote:- Quoted rates are inclusive of following:-\n(i) Contractor will get approved the drawing of panel from AGE(I).\n(ii) PCC foundation of suitable size. 3 Each
20 20 Supply and fixing of busbar chamber in cable junction boxes of size 255mm x 355mm x 122mm including terminals having IP-66 degree of protection for outdoor installation with metric knock out for cable entry of 35-50 sqmm size with colour code with RYB-B including fixed with suitable size of clamp nuts, bolt washer for fixing on pole complete all as specified and directed. 5 Each
21 21 Supply and fixing of busbar chamber in cable junction boxes of size 205mm x 255mm x 112mm including terminals having IP-66 degree of protection for outdoor installation with metric knock out for cable entry of 10-25 sqmm size with colour code with RYB-B including fixed with suitable size of clamp nuts, bolt washer for fixing on pole complete all as specified and directed. 2 Each
22 22 Supply and fixing of busbar chamber in cable junction boxes of size 130mm x 180mm x 77mm including terminals having IP-66 degree of protection for outdoor installation with metric knock out for cable entry of 4-10 sqmm size with colour code with RYB-B including fixed with suitable size of clamp nuts, bolt washer for fixing on pole complete all as specified and directed. 15 Each
23 23 Supply and fixing as in repair for street light panel, outdoor type, vermin and weather proof of 3 phase digital 24 hour timer of contactor rating 40A, TP, 230V including fixing with necessary clamps, nuts, bolts complete all as specifed and directed. \n 1 Each
24 24 Material and labour for PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and as directed. 1.12 Cum
25 25 Supply and laying GI tubing 50mm bore light grade with fittings laid in trenches or in road crossing for protection of LT underground cables including taking up/down unserviceable pipe complete all as specified and as directed.\n 14 RM
26 26 Supply and laying GI tubing 40mm bore light grade with fittings laid in trenches or in road crossing for protection of LT underground cables including taking up/down unserviceable pipe complete all as specified and as directed.\n 14 RM
27 27 Supply and laying GI tubing 25mm bore light grade with fittings laid in trenches or in road crossing for protection of LT underground cables including taking up/down unserviceable pipe complete all as specified and as directed.\n 24 RM
28 28 Material and labour for boring of hole under roads with mechanical arrangement for 80 mm dia GI tubing without disturbing the top surface of the road for passing the cable across the road complete all as specified and as directed.\n 15 RM
29 29 Material and labour for boring of hole under roads with mechanical arrangement for 40 mm dia GI tubing without disturbing the top surface of the road for passing the cable across the road complete all as specified and as directed.\n 14 RM
30 30 Supply and fixing as in repair 120 watt LED ultra light high bay, aluminium alloy pressure die casted housing with electronic driver, 240V, Power factor = 0.95, 5700K, 15600 lm, IP-65 complete fixed with all accessories to ceiling and connecting to celling rose with twin core 0.75mm flexible copper conductor wire/cable complete all as specified and as directed. \n 48 Each
31 31 Material and labour as in repair for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.25 metre below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt, earth electrode GI strip 25 x 4 mm dia connected to GI earth plate electrode by means of bolts, nuts, check nuts and washers of galvanized iron and thimbles and other end of earth wire connected to main switch board and protected by galvanized iron light grade 40mm bore and GI pipe 20mm bore medium grade with funnel and wire mesh for watering including necessary excavation and earth works. concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) and all as shown in Electrical Plate No. 3 of SSR (Part-1)of 2009. all as specified.\nNotes:-\n(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. \n(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. 3 Each set
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail