| 1 | 1 | PART-I\nVariable Refrigerant Volume System \nSupply Installation Testing and Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor Units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based controller, Top discharge type condensing units with R-410A refrigerant, vibration isolators with suitable foundation complete etc. as required. The unit shall deliver the rated capacity at AHRI conditions and work even at 50 Deg C ambient temperature without tripping. The unit shall be suitable to work on 400 V+/-10% 3 phase, 50 Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.6 and IEER not less than 6.5\nOutdoor Unit-\n | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 1.01 | 14 HP ( Squash Courts -1) | BI01010001010000000000000515BI0100001113 | 14 | HP |
|---|
| 3 | 1.02 | 14 HP ( Squash Courts -2) | BI01010001010000000000000515BI0100001114 | 14 | HP |
|---|
| 4 | 1.03 | 30 HP (Table Tennis Court) (20 HP x 1 No.+ 10 HP x 1 No.) | BI01010001010000000000000515BI0100001115 | 30 | HP |
|---|
| 5 | 1.04 | 64 HP (Badminton Court) (20 HP x 2 Nos.+ 12 HP x 2 Nos.) | BI01010001010000000000000515BI0100001116 | 64 | HP |
|---|
| 6 | 1.05 | 14 HP for treated fresh air unit (badminton court ) | BI01010001010000000000000515BI0100001117 | 14 | HP |
|---|
| 7 | 2 | Air handling Units (Ceiling Suspended Type)\nSupply, installation, testing and commissioning of double skin airhandling units ceiling suspended type with 24Ga pre coated G.I. outer skin & 24 Ga G.I. inner sking with 40 mm thick PUF insulation of density 42+2 kg/m3 horizontal type AHU complete with DIDW fan, fan motor drive, 6 row deep DX cooling coil, MERV-8 pre filters, mixing box, device, with fire rated canvass connection between CSU and supply air duct, thermal break profile, vibration isolator pad, Expansion Kit, communication Kit and wired remote controller as per specifications and drawings.\nCost shall also include supply, installation, testing and commissioning of DOL Starter Panel with indicating lights and auto selector switch for the AHU along with Necessary cabling upto 10 mtrs, earthing and termination from starter panel till AHU motor. | BI01010001010000000000000515BI0100001118 | | |
|---|
| 8 | 2.01 | 4,000 cfm, 10 TR 6 row coil cooling, 40 mmwg E.S.P. (for Squash Court & Badminton Court) | BI01010001010000000000000515BI0100001119 | 6 | Each |
|---|
| 9 | 3 | Air handling Units (Ceiling Suspended Type)\nSupply Installation, Testing and Commissioning of following minimum capacity VRF High wall type Indoor unit equipped with washable synthetic media pre filter fan section with low noise fan/ dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet cord less remote control, drain pan necessary accessories etc suitable for operation on 230 V +- 10% 50 Hz single phase AC supply complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of Indoor Unit will be at air inlet conditions of 27 Deg C DB and 19 deg C WB temperature. | BI01010001010000000000000515BI0100001120 | | |
|---|
| 10 | 3.01 | 2 TR (for Table Tennis Court) | BI01010001010000000000000515BI0100001121 | 12 | Each |
|---|
| 11 | 4 | Air handling Units (Ceiling Suspended Type)\nSupply Installation Testing and Commissioning of variable refrigerant flow distribution couplings with insulation for refrigerant piping (Y branches) in copper piping. | BI01010001010000000000000515BI0100001122 | 13 | Each |
|---|
| 12 | 5 | Air handling Units (Ceiling Suspended Type)\nSupply, fixing and commissioning of imported refrigerant joint/ Branch distributors between Outdoors complete with nitrile rubber insulation, supporting etc.,\n | BI01010001010000000000000515BI0100001123 | 3 | Each |
|---|
| 13 | 6 | Refrigerant Piping \nSupply Installation Testing and Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRF/VRV system, complete with fittings, with suitable adjustable ring type hanger supports, jointng/brazing including accesories insulated with XLPE Class O tubular insulation/with Class O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specification etc as required: | BI01010001010000000000000515BI0100001124 | | |
|---|
| 14 | 6.01 | 9.5 mm dia (OD) (soft drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001125 | 80 | Mtr. |
|---|
| 15 | 6.02 | 12.7 mm dia (OD) (soft drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001126 | 150 | Mtr. |
|---|
| 16 | 6.03 | 15.86 mm dia (OD) (soft drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001127 | 80 | Mtr. |
|---|
| 17 | 6.04 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001128 | 126 | Mtr. |
|---|
| 18 | 6.05 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001129 | 25 | Mtr. |
|---|
| 19 | 6.06 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001130 | 148 | Mtr. |
|---|
| 20 | 6.07 | 34.9 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation | BI01010001010000000000000515BI0100001131 | 120 | Mtr. |
|---|
| 21 | 7 | Drain piping \nSupply, installation testing & commissioning of rigid UPVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation. \n | BI01010001010000000000000515BI0100001132 | | |
|---|
| 22 | 7.01 | 25 mm dia ( with 6 mm nitrile rubber Insulation) | BI01010001010000000000000515BI0100001133 | 65 | Mtr. |
|---|
| 23 | 7.02 | 32 mm dia ( with 6 mm nitrile rubber Insulation) | BI01010001010000000000000515BI0100001134 | 52 | Mtr. |
|---|
| 24 | 7.03 | 50 mm dia ( with 6 mm nitrile rubber Insulation) | BI01010001010000000000000515BI0100001135 | 60 | Mtr. |
|---|
| 25 | 8 | Ducting \nSupply Installation Testing and Commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.\n | BI01010001010000000000000515BI0100001136 | | |
|---|
| 26 | 8.01 | 0.63 mm (24 Gauge) | BI01010001010000000000000515BI0100001137 | 295 | Sq. Mtr |
|---|
| 27 | 8.02 | 0.80mm (22 Gauge) | BI01010001010000000000000515BI0100001138 | 70 | Sq. Mtr |
|---|
| 28 | 9 | Ducting \nSupply and fixing of following thickness duly laminated aluminum foil finish closed cell Nitrile rubber (Class 'O') insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3mm thick self-adhesive Nitrile rubber insulation complete as per specifications etc as required. | BI01010001010000000000000515BI0100001139 | | |
|---|
| 29 | 9.1 | 25 mm | BI01010001010000000000000515BI0100001140 | 520 | Sq. Mtr |
|---|
| 30 | 10 | Ducting \nSupply and fixing of acoustic lining for supply air duct/ duct plenum with 13 mm open cell nitrile rubber after applying suitable adhesive.\n | BI01010001010000000000000515BI0100001141 | 60 | Sq. Mtr |
|---|
| 31 | 11 | Ducting \nSupplying, installation and fixing fire retardant non porous double layer flexible connection between each AHU and supply air duct/ return air duct.\n | BI01010001010000000000000515BI0100001142 | 6 | Sq. Mtr |
|---|
| 32 | 12 | Grills/ Diffuser \nSupplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. | BI01010001010000000000000515BI0100001143 | 16 | Sq. Mtr |
|---|
| 33 | 12.01 | Grills/ Diffuser \nSupplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. | BI01010001010000000000000515BI0100001144 | 34 | Sq. Mtr |
|---|
| 34 | 13 | Volume Control Damper \nSupply & Installation of extruded aluminium volume control damper with blades, adjustable lever, frame etc for Supply Air and Fresh Air Connected to AHU as per specifications and drawings as complete as required.\n | BI01010001010000000000000515BI0100001145 | 12 | Sq. Mtr |
|---|
| 35 | 14 | Cable Tray \nSupplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. | BI01010001010000000000000515BI0100001146 | | |
|---|
| 36 | 14.01 | 150mm x 50 mm x 1.6 mm thick | BI01010001010000000000000515BI0100001147 | 50 | Mtr. |
|---|
| 37 | 14.02 | 300 mm x 50 mm x 1.6 mm thick | BI01010001010000000000000515BI0100001148 | 120 | Mtr. |
|---|
| 38 | 15 | Supply & installation of control cum transmission wiring of 2 core x 1.5 sq mm copper in suitable pvc conduits between indoor and out door unit. | BI01010001010000000000000515BI0100001149 | 660 | Mtr. |
|---|
| 39 | 16 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required | BI01010001010000000000000515BI0100001150 | | |
|---|
| 40 | 16.01 | 20 mm Size | BI01010001010000000000000515BI0100001151 | 360 | Mtr. |
|---|
| 41 | 17 | Supply of Power cable of following sizes XLPE insulated aluminiumarmoured conductor cable to VRF outdoor unit from main electrical panal. The cost shall include all necessary supports clamps etc as necessary as required. | BI01010001010000000000000515BI0100001152 | | |
|---|
| 42 | 17.01 | 4C x 25 sq mm | BI01010001010000000000000515BI0100001153 | 120 | Mtr. |
|---|
| 43 | 18 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. | BI01010001010000000000000515BI0100001154 | | |
|---|
| 44 | 18.01 | Upto 35 sq. mm (clamped with 1mm thick saddle) | BI01010001010000000000000515BI0100001155 | 100 | Mtr. |
|---|
| 45 | 19 | Supplying, making end termination with brass compression gland and aluminium lugs for following sizes of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | BI01010001010000000000000515BI0100001156 | | |
|---|
| 46 | 19.01 | 4C x 25 sq mm | BI01010001010000000000000515BI0100001157 | 32 | Mtr. |
|---|
| 47 | 20 | Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing as required. | BI01010001010000000000000515BI0100001158 | 140 | Mtr. |
|---|
| 48 | 21 | SITC of dust, damp and vermin proof, outdoor type double door feeder pillar IP 55 protection fully compartmentalized minimum 450 mm deep sheet steel panel suitable suitable for operation of use on 415V +/- 10% volts, 3 Phase, 4 wire, 50 HZ made out of 2 mm thick CRCA Sheet i/c cleaning and finishing complete with 7 tank process with powder coating in approved shade having TPN as mentione below Al. alloy bus bars of high conductivity DMC/SMC bus bar supports with short circuit withstand capacity of 31 MVA for 1 second. The entire panels shall have a continuous, common copper earth bar inter connection with solid copper conductor wire/ Al. strip neutral link i/c control wiring with 2.5 sq mm PVC insulated, copper conductor FRLS copper conductor single core cable, cable alley, cable gland plates etc including providing detachable gland plate of 3 mm thick for incoming and outgoing cables entry, complete with painting, interconnections, earthing etc complete as required. The feeder pillar shall be installed 300mm above floor level by means of MS angle. (50 mm x 50mm x 6 mm thick legs.) | BI01010001010000000000000515BI0100001159 | | |
|---|
| 49 | 21.01 | For Squash 300 Amp | BI01010001010000000000000515BI0100001160 | 2 | Sq. Mtr |
|---|
| 50 | 21.02 | For TT 300 Amp | BI01010001010000000000000515BI0100001161 | 2 | Sq. Mtr |
|---|
| 51 | 21.03 | For Badminton 400 Amp | BI01010001010000000000000515BI0100001162 | 2.5 | Sq. Mtr |
|---|
| 52 | 22 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/MCCB/Isolator) | BI01010001010000000000000515BI0100001163 | | |
|---|
| 53 | 22.01 | 6 way (4 + 18), Double door | BI01010001010000000000000515BI0100001164 | 9 | Nos. |
|---|
| 54 | 23 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. | BI01010001010000000000000515BI0100001165 | | |
|---|
| 55 | 23.01 | 63 A | BI01010001010000000000000515BI0100001166 | 18 | Nos. |
|---|
| 56 | 24 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. ( For Hi Wall Units) | BI01010001010000000000000515BI0100001167 | 12 | Nos. |
|---|
| 57 | 25 | Supplying Installation Testing & Commissioning of following Switch gears/Electrical accessories in the existing LT Panel i/c making connection etc. complete as required. | BI01010001010000000000000515BI0100001168 | | |
|---|
| 58 | 25.01 | 150 A 4P MCCB 50 KA with Microprocessor based release (S/C & O/L) protection or suitable capacity contactor with suitable timer, controls, NO-NC Contacts, sw. | BI01010001010000000000000515BI0100001169 | 2 | Nos. |
|---|
| 59 | 25.02 | 250 A 4P MCCB 50 KA with Microprocessor based release (S/C & O/L) protection or suitable capacity contactor with suitable timer, controls, NO-NC Contacts, sw. | BI01010001010000000000000515BI0100001170 | 1 | Nos. |
|---|
| 60 | 25.03 | MNX 20, 3 pole Power Contactor | BI01010001010000000000000515BI0100001171 | 7 | Nos. |
|---|
| 61 | 25.04 | Single phase preventor | BI01010001010000000000000515BI0100001172 | 7 | Nos. |
|---|
| 62 | 25.05 | Thermal Over load relay suitable for MNX 20 Power contactor | BI01010001010000000000000515BI0100001173 | 7 | Nos. |
|---|
| 63 | 25.06 | Push Button | BI01010001010000000000000515BI0100001174 | 14 | Nos. |
|---|
| 64 | 25.07 | Digital Voltmeter CL-1.0 (0-500 V) | BI01010001010000000000000515BI0100001175 | 7 | Nos. |
|---|
| 65 | 25.08 | 10 A Voltmeter Selector Switch | BI01010001010000000000000515BI0100001176 | 7 | Nos. |
|---|
| 66 | 25.09 | Digital Ammeter CL-1.0 ( 0-30 amp) | BI01010001010000000000000515BI0100001177 | 7 | Nos. |
|---|
| 67 | 25.1 | Ammeter Selector Switch | BI01010001010000000000000515BI0100001178 | 7 | Nos. |
|---|
| 68 | 25.11 | CTs 250/5A, CL-1, 15 VA, Cast Resin for metering | BI01010001010000000000000515BI0100001179 | 4 | Nos. |
|---|
| 69 | 25.12 | On/ Off indicating lamps | BI01010001010000000000000515BI0100001180 | 24 | Nos. |
|---|
| 70 | 25.13 | LED Phase Indicating Lamps | BI01010001010000000000000515BI0100001181 | 9 | Nos. |
|---|
| 71 | 25.14 | CTs 150/5A, CL-1, 15 VA, Cast Resin for metering | BI01010001010000000000000515BI0100001182 | 12 | Nos. |
|---|
| 72 | 26 | Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. | BI01010001010000000000000515BI0100001183 | 6 | Set |
|---|
| 73 | 27 | Supplying and laying 25 mm x 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I nut, bolt, spring, washer etc. as required. (jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) | BI01010001010000000000000515BI0100001184 | 18 | Mtr. |
|---|
| 74 | 28 | Part - II\nComprehensive Maintenance of Complete installation as per provided in Part-I for first year after completion defect liability period as per terms and conditions attached complete etc as required. | BI01010001010000000000000515BI0100001185 | 12 | Month |
|---|
| 75 | 29 | Comprehensive Maintenance of Complete installation as per provided in Part-I for next year after completion item No. 28.00. | BI01010001010000000000000515BI0100001186 | 12 | Month |
|---|
| 76 | 30 | Comprehensive Maintenance of Complete installation as per provided in Part-I for next year after completion item No. 29.00. | BI01010001010000000000000515BI0100001187 | 12 | Month |
|---|
| 77 | 31 | Comprehensive Maintenance of Complete installation as per provided in Part-I for next year after completion item No. 30.00. | BI01010001010000000000000515BI0100001188 | 12 | Month |
|---|