Provision Of Apfc Panel At Second Stage And Third Stage Pump House At Lansdowne, GE LANSDOWNE-Uttarakhand

Military Engineer Services-MES has published Provision Of Apfc Panel At Second Stage And Third Stage Pump House At Lansdowne. Submission Date for this Tender is 20-03-2021. Power Factor Panel Tenders in GE LANSDOWNE Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

27166687
Corrigendum : Provision Of Apfc Panel At Second Stage And Third Stage Pump House At Lansdowne
Open Tender
Indian
Uttarakhand
GE LANSDOWNE
20-03-2021

Tender Details

Provision Of Apfc Panel At Second Stage And Third Stage Pump House At Lansdowne

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Mar-2021 Corrigendum BOQ 13-03-2021
2 13-Mar-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-03-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 20600.0 /-
Tender Value
INR 10.30 Lakhs /-

BOQ Items

Name of Work: PROVISION OF APFC PANEL AT SECOND STAGE AND THIRD STAGE PUMP HOUSE AT LANSDOWNE
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, installation, testing & commissioning of power factor improvement out door capacitor bank having aggregate capacity 125 KVAR in 10 stages, with microprocessor along with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of stainless steel (SS) SL 316 sheet 2.00 mm thick & frame SS channel having bush bar of aluminium 200 Amps capacity , three phase and one nutral fixed on insulator and bus bar insulated by coloured heat shrinkable shleeve & housed in specified compartment both side openable.Including powder coating internally externally the entire steel surfaces. All the cover shall have with suitable locking arrangements, fully internally wired with suitable size of thimbles. Incoming/outgoing internal connection with PVC insulated PVC sheathed multi stranded copper wire of suitable size all as directed. And comprising the following:-\n(1) Main incoming MCCB 200 Amps 25KA 4 Pole Make L&T/Legrand - 01 No\n(2) Power factor corrector relay 10 stage Make L&T/Trinity. \n(3) Capacitor duty contactor for 25 KVAR, Make: L&T- 02 Nos\n(4)Capacitor duty contactor for 20 KVAR, Make: L&T- 01 Nos.\n(5) Capacitor duty contactor for 15 KVAR, Make: L&T- 01Nos.\n(6) Capacitor duty contactor for 10 KVAR, Make: L&T- 02 Nos.\n(7) Capacitor duty contactor for 05 KVAR, Make: L&T- 02 Nos.\n(8) Capacitor duty contactor for 03 KVAR, Make: L&T- 01 Nos.\n(9) Capacitor duty contactor for 02 KVAR, Make: L&T- 01 Nos.\n(10) MCCB 100 A, 25 KA,TP Make L&T/Legrand - 01 No.\n(11)MCB 63 A,TP Make:L&T - 01 No.\n(12) MCB 40 A,TP Make:L&T - 01 No.\n(13) MCB 32 A,TP Make:L&T - 01 No.\n(14)MCB 25 A,TP Make:L&T - 01 No. \n(15) MCB 16 A,TP Make:L&T - 01 No.\n(16) A/M Selector Switch, Make: L&T - 01 No.\n(17) ON/OFF Push Button, Make: L&T - 07 Nos.\n(18) Aux contactor 4 NO + 4 NC, Make: L&T-02 Nos Contd........ 2 Each Job
2 1.01 (19) Indicating light ON-OFF, Make: L&T-08 Sets.\n(20) Power capacitor 50 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, confirmed to IS 13340, Make: L&T- 01 No.\n(21) Power capacitor 25 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, confirmed to IS 13340, Make: L&T- 01 No.\n(22)Power capacitor 20 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, confirmed to IS 13340, Make: L&T- 01 No.\n(23)Power capacitor 15 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, confirmed to IS 13340, Make: L&T- 01 No.\n(24)Power capacitor 10 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, confirmed to IS 13340, Make: L&T- 01 No.\n(25)Power capacitor 05 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, confirmed to IS 13340, Make: L&T- 01 No.\n(26)Voltmeter 0-500 V with VSS,Make: L&T - 01 set.\n(27) Ammeter 0-500 Amps with ASS, Make: L&T- 01 set.\n(28) C.T. 150/5 Make: Trinity - 01 Set.\n(29) Protection MCB 6 Amps, Make: HPL - 04 Nos.
3 1.03 Notes for Supply, installation, testing, commissioning of electronic based APFC Item No 1 :-\n1. Panal manufacturers should have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing/ water rinsing/ de-rusting/ water rinsing/ activation/ phosphating/ water rinsing / passivation).\n2. Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel.\n3. The panel manufacturer should have following certification:-\n(i) CPRI certificate Degree of protection IP-54 (should have IEC: 61439-1-2 & IEC: 60529 tests)\n(ii) CPRI certificate short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA.\n(iii) CPRI certificate rated current not less than 5000A\n4. MCCB (microprocessor based) should be capable for on line setting of the current.\n5. All the electrical switch gear like MCCBs and MCBs should be of same make.\n6. Drawing of panel board should be got approved from GE before fabrication.\n7. Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2.\n8. Any item technically required for proper functioning of APFC panel but not mentioned in the item is deemed included in item rate quoted by the firm.\n\n
4 2 Supply, laying, connecting and testing of 1.1 KV grade XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty ) 11000 Volts (Earthed) grade with stranded aluminium conductor cross sectional area 185 sqmm 3.5 core ISI marked laid in cable duct/trenches/surface/wall complete all as specified and directed. Make :- Havells/KEI/Gloster\n 265 RM
5 3 Excavation in trenches not exceeding 1.5 mtr wide and not exc.1.5 mtr in depth for poles /laying of electric underground cables and GI tubing (where provided for protection of cables) and getting out trimmimg the sides, forming bottom surface to required level in any type of soil complete all as specified and directed. 48 Cum
6 4 Returning filling in any type of soil including spreading, leveling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed. 36 Cum
7 5 Removing of excavated soil to a distance n. exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting points in soil complete all as specified and directed. 26 Cum
8 6 M&L for fine dry sand cushing for under ground cable by providing layers of sand 8cm deep before laying and 15cm deep after laying the cable including streching the cable complete all as specified and directed . Note :- For payment purpose Punned (consolidated ) thickness of sand will be measured . 16 Cum
9 7 Supply and laying factory cast , unreinforced precast concrete cable cover factory made embossed the mark "LT CABLE " class LV Type 1 , ISI marked flat size 250x150x40mm laid in trenches as specified and directed . 1400 Each
10 8 Supplying, laying & jointing GI water tubing, 80 mm bore, light grade as in sleeving etc laid in trenches / pole post incl clamps nut bolts etc /under culvert/ under road etc. complete all as specified and directed . 20 RM
11 9 M& L, for earthing with galvanised steel earth plate of size 600 x 600 x 6 mm thick burried directly in ground not less than 2.5 mtr below groud level with top edge of earth plate not less than 1.5 meters below ground level connected by 25x4 mm GI strip as earth lead by means of brass nuts and bolt, thimbles, check nuts, washers including concrete chamber of PCC 1:3:6 type C1 using 20 mm graded stone aggregate, with fair finish, inetrnal surface of concrete chamber shall be given internal dia 300mm X 300mm , 15 mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320 x 320 x 80 mm size (1:2:4) type B1 using 20 mm graded stone aggregate, adequate quantity of common salt, charcoal etc all, as shown in electrical plate No 3 of MES SSR Part-1(2009) and specified incuding and provision of GI strip upto 7.5 mtr long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, Medium grade, including all excavation and earthn work and connecting the earth strip to an earthing test point/panel including testing on completion complete alll as specified and directed by Engr-in-charge\nNote:-(1) RCC pit cover shall be precast of RCC (1:2:4) type B1, 80 mm thick reinforced with XPM weighting not less than 4 Kg/Sqm in lieu of CI cover \n(2) Cost of addtional GI strip more than 7.5 mtr will be measured and paid seperately under relevant item 4 Each