Military Engineer Services-MES has published Repair/ Maintenance Of Dg Set , Amf Panel , Bty Charger And Connected Items At Mil Stn Gaya. Submission Date for this Tender is 23-03-2021. Diesel Generators Tenders in Garrison Engineer Gaya Paharpur Mil Stn Gaya Bihar Bihar. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 16-Mar-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 23-03-2021 |
Name of Work: Repair/ maintainance of DG set , AMF panel , Bty Charger and connected works at OTA Gaya | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | M&L Periodical maintenance / servicing / 'B' check and minor repair of DG set 200 KVA all as per manufacturer specification and directions complete all as specified and directed by Engr-in-charge. \nNote : \n(i) Necessary tool for replacement of spares for 'B' check shall be deemed to be inclusive in the rate quoted by the contractor.\n(ii) Spares such as replacement of u/s items incl engine oil, air filter, fuel filter & mobil filter will be measured & paid separately under respective item of Sch. | 2 | Each | |
2 | 2 | Ditto all as per item No 1 above but 100 KVA capacity | 4 | Each | |
3 | 3 | Ditto all as per item No 1 here in before but 25/30 KVA capacity. | 4 | Each | |
4 | 4 | Taking down the radiator assembly of DG sets 200KVA by disconnecting both inlet / outlet hose pipe and foundation nuts and draining out old water including cleaning and dismantling by the parts and cleaning complete fins / tubes / upper & lower tanks with cleaning solution and welding the leakage holes / replacing unserviceable hose pipe and re-assembling the complete parts and fixed back to its original base and testing to the entire satisfaction of Engineer-in-Charge.\nNote :- Coolant will be measured & paid separately under respective item of Sch. | 2 | Each Job | |
5 | 5 | Ditto all as per item No 1 here in before but 100 KVA capacity | 4 | Each Job | |
6 | 6 | Ditto all as per item No 1 here in before but 25/30 KVA capacity. | 2 | Each Job | |
7 | 7 | S&F Engine Oil servo type in 20 Ltrs seal pack 20W/40. Make : HP/BP/Gulf. | 400 | Ltrs | |
8 | 8 | S&F Radiator coolant in 1 Ltrs seal pack. | 40 | Ltrs | |
9 | 9 | S&F Fuel filter cartridge as per sample of DG Set 200 KVA capacity with rubber seal | 2 | Each Set | |
10 | 10 | S&F Mobile filter cartridge as per sample of DG Set 200 KVA capacity with rubber seal. | 4 | Each Set | |
11 | 11 | S&F Air filter cartridge as per sample of DG Set 200 KVA capacity with rubber seal. | 4 | Each Set | |
12 | 12 | S&F Fuel pipe as per sample of DG Set 200 KVA capacity all etc complete. | 2 | Each Set | |
13 | 13 | S&F Fuel filter cartridge as per sample of DG Set 100 KVA capacity with rubber seal | 7 | Each Set | |
14 | 14 | S&F Mobile filter cartridge as per sample of DG Set 100 KVA capacity with rubber seal. | 5 | Each Set | |
15 | 15 | S&F Air filter cartridge as per sample of DG Set 100 KVA capacity with rubber seal. | 7 | Each Set | |
16 | 16 | S&F Fuel pipe as per sample of DG Set 100 KVA capacity all etc complete. | 4 | Each Set | |
17 | 17 | S&F Fuel filter cartridge as per sample of DG Set 25/30 KVA capacity with rubber seal | 3 | Each Set | |
18 | 18 | S&F Mobile filter cartridge primary and secondary as per sample of DG Set 25/30 KVA capacity with rubber seal. | 2 | Each Set | |
19 | 19 | S&F Air filter cartridge as per sample of DG Set 25/30 KVA capacity with rubber seal. | 2 | Each Set | |
20 | 20 | S&F Fuel pipe as per sample of DG Set 25/30 KVA capacity all etc complete. | 2 | Each Set | |
21 | 21 | M&L Silencer assembly complete with mufler of 100 KVA DG Set all as specified and directed. | 1 | Each Set | |
22 | 22 | M&L Silencer assembly complete with mufler of 200 KVA DG Set all as specified and directed. | 1 | Each Set | |
23 | 23 | M&L Replacement of Actuator as per sample of 100 DG Set all etc complete as specified and directed by Engr-in-charge | 1 | Each | |
24 | 24 | M&L Replacement of V-belt of DG Sets 200KVA all as specified and directed by Engr-in-charge. | 2 | Each Set | |
25 | 25 | M&L Replacement of V-belt of DG Sets 100KVA all as specified and directed by Engr-in-charge. | 4 | Each Set | |
26 | 26 | M&L Replacement of V-belt of DG Sets 25/30 KVA all as specified and directed by Engr-in-charge. | 2 | Each Set | |
27 | 27 | M&L Taking out self starter from DG sets 200KVA for servicing / repairs / rewinding of starter, including repair/replacement of following unservieable items all as specified and directed by Engr-in-charge :- \n(i) Re-winding of self starter armature.\n(ii) Replacement of cumutator and brushes\n(iii) Replacement of bentex complete | 2 | Each Job | |
28 | 28 | M&L Taking out self starter from DG sets 100KVA for servicing / repairs / rewinding of starter, including repair/replacement of following unservieable items all as specified and directed by Engr-in-charge :- \n(i) Re-winding of self starter armature.\n(ii) Replacement of cumutator and brushes\n(iii) Replacement of bentex complete | 4 | Each Job | |
29 | 29 | M&L Taking out self starter from DG sets 25/30KVA for servicing / repairs / rewinding of starter, including repair/replacement of following unservieable items all as specified and directed by Engr-in-charge :- \n(i) Re-winding of self starter armature.\n(ii) Replacement of cumutator and brushes\n(iii) Replacement of bentex complete | 2 | Each Job | |
30 | 30 | M&L Taking out dynemo cum alternator from DG sets 200KVA for servicing / repairs / rewinding of dynemo, including repair/replacement of following unservieable items all as specified and directed by Engr-in-charge :- \n(i) Re-winding of dynemo \n(ii) Replacement of circuit panel. | 1 | Each Job | |
31 | 31 | M&L Taking out dynemo cum alternator from DG sets 100KVA for servicing / repairs / rewinding of dynemo, including repair/replacement of following unservieable items all as specified and directed by Engr-in-charge :- \n(i) Re-winding of dynemo \n(ii) Replacement of circuit panel. | 2 | Each Job | |
32 | 32 | M&L Taking out dynemo cum alternator from DG sets 25/30KVA for servicing / repairs / rewinding of dynemo, including repair/replacement of following unservieable items all as specified and directed by Engr-in-charge :- \n(i) Re-winding of dynemo \n(ii) Replacement of circuit panel. | 1 | Each Job | |
33 | 33 | M&L Replacement of battery charger cap 180 AH, 12 Volt capacity, single phase 240 volt incl Amp meter, voltmeter and on off switch, indicator lamp (red and green) complete all as specified and directed by Engr-in-charge | 2 | Each | |
34 | 34 | M&L Replacement of lead acid battery of cap 180 AH, 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 4 | Each | |
35 | 35 | M&L Replacement of lead acid battery of cap 150 AH, 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 2 | Each | |
36 | 36 | M&L Replacement of lead acid battery of cap 100 AH, 12V, complete all as specified and directed. Make : Exide New Xpress or its equivalent Tata | 2 | Each | |
37 | 37 | M&L Replacement of AMF Gen Set controller for 200/100 KVA DG set as per sample complete all as specified and directed. | 1 | Each | |
38 | 38 | M&L Replacement of Automatic Voltage Regulator for 200/100 KVA DG set as per sample complete all as specified and directed. | 1 | Each | |
39 | 39 | S&F in replacement of all broken door hinges with new MS hinges of length 4” screwed/welded with door and made the door operational condition of DG Set any capacity all as directed by Engineer-in-Charge. | 2 | Each Job | |
40 | 40 | Taking out of LT panel/change over panel Including all fittings complete from the site as directed by Engr-in-Charge. | 1 | Each | |
41 | 41 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 800 amps rated aluminium bus bar for neutral complete with the following accessories incl Cable Gland & PCC Foundation and Coping taking down old all as specified and directed (Location -HQ Generator Panel )\nNote-MCCB and onload changeover switch will be measured and paid saparately against respective item of schedule. | 1 | Each Job | |
42 | 41.01 | (a) Incoming | |||
43 | 41.02 | (i) On load change over switch 400 Amps, 04 Pole, 415V, front operated Qty-01 No, Make : Schneider / L&T/Havells/HPL | |||
44 | 41.03 | (ii) MCCB 04 Pole 50 kA, 400 Amp,415 Volts (Qty 01 No)\n | |||
45 | 41.04 | (b) Out goings | |||
46 | 41.05 | (i) MCCB 04 Pole 36 KA, 250 Amp, 415 Volts, (Qty - 02 Nos)\n | |||
47 | 41.06 | (ii) MCCB 04 Pole 25 KA, 160 Amp, 415 Volts, (Qty - 02 Nos)\n | |||
48 | 41.07 | (iii) MCCB 04 Pole 25 KA, 100 Amp, 415 Volts, (Qty - 02 Nos)\n | |||
49 | 41.08 | (iv) Aluminium bus bar suitable size 3 phase, 4 wire 600 Amp,415 V | |||
50 | 41.09 | (v) Digital Volt meter 0-500V with slector switch, make-AE/L&T | |||
51 | 41.1 | (vi) Digital Amp meter 0-600 amp with CT and selector switch. make-AE/L&T | |||
52 | 41.11 | (vii) Indicating lamp (Blue, Yellow &Red-1 set)LED Type make-AE/L&T/ Havells | |||
53 | 42 | M&L Earthing complete with galvenized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 m below normal ground level (with top edge of earth plate not less than 1.5m below ground level) connected to GI strip 32mm x 6mm main earthing lead by means of galvenized bolts, nuts & washers all as shown in electrical plate no 3 of MES sch part-I (2009) with connected to earth test point & to main switch board etc with and an incl ediquate quantity of charcole dust and common salt around earth plate, PCC 1:3:6 type C1 using 20 mm graded stone agreegate for earth pit with precast RCC (1:2:4) type B1 using 20mm graded stone agreegate 40mm thick cover reinforce with 8mm dia TMT bars 3 nos both way with 20mm dia MS round bar handle, GI light grade watering pipe 20mm dia with funnel and wire mess and 40mm dia GI light grade earth lead protection pipe complete all as specified and directed. | 4 | Each Set | |
54 | 43 | M&L Dismantling of unserviceable DG Set 25 KVA installed at Signal Centre with all connections and deposit it to to MES E/M yard all as specified and directed by Engr-in-charge. Note :- The quoted rate shall be of all inclusive viz disconnecting and transportation to E/M yard store. | 1 | Each Job | |
55 | 44 | M&L Replacement of 3 pole power contactors of capacity 200Amps, Make : L&T, model : MCX 33, all etc complete as specified and directed by Engr-in-charge. | 1 | Each | |
56 | 45 | S&F Replacement of MCCB 04 pole, 50 KA 400 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 1 | Each | |
57 | 46 | S&F Replacement of MCCB 04 pole, 36 KA 250 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 1 | Each | |
58 | 47 | S&F Replacement of MCCB 04 pole, 25 KA 160 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 2 | Each | |
59 | 48 | S&F Replacement of MCCB 04 pole, 25 KA 125 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 2 | Each | |
60 | 49 | S&F Replacement of MCCB 04 pole, 25 KA 100 Amps, AC 415 Volts complete all as specified and directed.\nMake:-HPL/Havells/L&T Lexic/Legrand/C&S Electric Ltd/ABB | 2 | Each | |
61 | 50 | Taking down unserviceable street light timer panel all etc complete as specified and directed by Engr-in-charge | 10 | Each | |
62 | 51 | S&F Street light control panel for security light incl digital timer astromical, contractor, TPN MCB 63 Amps and contactor rating 63 Amps TP and Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including proper mounting arrangement, providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location . Make : Havells, 63 Amps, Phase/230V-Digital Catlog, Model No :IHXSS0912A, Make : Havells | 10 | Each | |
63 | 52 | Taking out unserviceable cable any type/size from trenches,pole, road,duct etc including necessary joints,U/S fittings and pipes etc complete all as directed. | 580 | RM | |
64 | 53 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 10 Sq mmx 4 Core complete alongwith proper thimbling and cable gland as per requirement of site all as specified and directed . | 450 | RM | |
65 | 54 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 35 Sq mmx 3.5 Core complete alongwith proper thimbling and cable gland as per requirement of site all as specified and directed . | 130 | RM | |
66 | 55 | Excavation in trenches not. exc. 1.5m wide and not exc. 1.5 in deep and getting out in soft/loose soil complete all as specified and directed. | 100 | Cum | |
67 | 56 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in soft/loose soil. | 65 | Cum | |
68 | 57 | Removing surplus soil to a distance not exc 50m and depositing where directed at a level not exc. 1.5m above the starting point. | 35 | Cum | |
69 | 58 | M&L Sand cushioning for under ground cable with locally available sand for protection of cable including spreading and consolidations, complete all as specified and directed. | 32 | Cum | |
70 | 59 | Supply and laying in trenches dry well burnt locally available sub class “B” bricks over sand cushioning for protection of cable complete all as per specified and directed. | 3.2 | Per 1000 Nos |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy