Indian Oil Corporation Limited-IOCL has published Supply , Installation And Commissioning Of Radar Level Gauges In Place Of Existing Magnetic Level Gauges Of Lpg Above Ground Bullets ( 3 Nos . ) At Ujjain Lpg Bottling Plant Supply , Installation And Commissioning Of Radar Level Gauges In Place Of Ex. Submission Date for this Tender is 12-02-2021. Radar System Tenders in LPG Bottling Plant, Ujjain Madhya Pradesh. Bidders can get complete Tender details and download the document.
Name of Work: Supply, Installation & Commissioning works of Radar Level Guages in place of existing magnetic level guages of LPG Above Ground Bullets at Ujjain BP Note:- 1) Rates quoted shall be inclusive of all taxes and duties, but exclusive of Goods and Services tax (GST). Bidders are advised to make themselves fully conversant with applicable GST Law. 2) GST rate is considered @18% and will be paid extra at the time of billing as per Government Directives. 3) The Price Bid / Price Schedule shall be read with all other sections of this Tender Document. 4) The Tenderer is deemed to have studied the tender terms and conditions, specifications and details of works to be done within the Time Schedule and acquainted himself on the conditions prevailing at the locations. 5) This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. 6) The bidders shall quote only in coloured cells in Column F and also indicate their name in coloured cell in row 8 of the sheet. 7) Bidder should quote by selecting EXCESS or LESS in the dropdown box and thereafter filling the percentage rate in figures only without any condition. In case bidder is intending to quote “at Par”, bidder must quote “0” in the space provided. Name of bidder must also be provided at appropriate place in price bid. Leaving the designated space for quoting percentage rate blank shall be taken as quoted “Not Quoted”. The party in their own interest should tally the quoted rate in words and quoted amount (in figures) which is displayed at the bottom of price bid sheet and calculated as per % rate quoted by the party. Name of bidder must also be provided at appropriate place in price bid. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1.01 | Supply, Installation, Testing and Commissioning of CCOE approved Radar type Level Gauge for LPG Above Ground Bullets\nAccuracy : ± 1mm\nProduct Application : LPG\nItem also includes Transmitter Head with JB, Vapour Pressure Sensor with Ball Valve Kit Analog input Card. | 3 | Nos. | |
2 | 1.02 | Supply, Installation, Testing and Commissioning of CCOE approved of Tank side indicator | 3 | Nos. | |
3 | 1.03 | Supply,laying, testing and commissioning of Armoured 3C x 2.5 sq. mm FR Copper XLPE cable (from PMCC to JB) as per cable schedule or requirement | 500 | Meter | |
4 | 1.04 | Supply, laying, testing and commissioning of Armoured 2P x 1.5 sq. mm FR Copper XLPE cable (from JB to Control Room) as per cable schedule or requirement | 500 | Meter | |
5 | 1.05 | Supply, laying, testing and commissioning of Armoured 6P x 1.5 sq. mm FRLS cable ( from JB to Pump House) as per cable schedule or requirement | 600 | Meter | |
6 | 1.06 | Supply and laying of Perforated Aluminium Cable Tray with cover of size 100mm inclusive of tray inside riser, Outside riser, bend, coupler plates along with bolts for support etc | 100 | Meter | |
7 | 1.07 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets & dressing of sides, ramming of bottoms,depth upto 1.5m including getting out excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing surplus excavated soil as directed, within or outside site at unobjectionable place IN ALL KIND OF SOIL) Pipes, Cable etc. > 80mm < 300m dia | 400 | Meter | |
8 | 1.08 | Supplying and Local sand filling within the grading zone V of fine aggregates specified in table 3.1 , clause 3.1.3 of attached specifications, in plinth, under floors etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming watering and dressing complete | 50 | Cub.M | |
9 | 1.09 | Brick duct for cables, 225mm wide (16 Bricks & 0.0195 cum per Mtr) as per specifications and direction of Engineer in charge. | 400 | Meter | |
10 | 1.1 | Making necessary modifications in 3X150 MT Bullets if any for Radar gauge including supply, fabrication and fixing of required fitting/pipes, DPT of weld joints and Radiography and other necessary tests. | 1 | Lumpsum | |
11 | 1.11 | TPI and PESO Work: TPI stage wise inspection including preparation of documents, Procedure , Drawings for modification and modification in nozzles if required, For supply and fixing of radar gauges and all connected works as per site requirements in total including Preparation of all procedures and related documents, submission to PESO before commencing the works and after completion of works duly vetted by TPI agency, all NDT activities, Checking of weld joints, Witnessing and Review of Radiography film , Witness of Hydro test of all 3 Vessels (Three Bullets) if required, preparation of all documents as per SMPV rules, duly witnessed and certified by approved TPI agency, submission to CCOE and co-ordination with CCOE and obtaining approvals. | 3 | Nos. | |
12 | 1.12 | To conduct “HYDROTESTING” of vessel if modification done or if required for installation of radar gauge and obtain Rule 19 as per SMPV(U) Rule. | 3 | Nos. | |
13 | 1.13 | Hooking up with existing Tank Farm Management Software including required field interface and host interface | 1 | Lumpsum |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy