Providing And Installation Of Air Conditioners At Drugs Testing Laboratory , Cfdl Building , Lawrence Road Industrial Area , Delhi . - 1 Wiring For Circuit / Submain Wiring Alongwith Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Steel Conduit As Required. Na ) 2 X 10 Sq. Mm + 1 X 6 Sq. Mm Earth Wire N 2 B ) 2 X 16 Sq. Mm + 1 X 6 Sq. Mm Earth Wire 3 Supplying And Fixing Following Way, Single Pole And Neutral, Sheet Steel, Mcb Distribution Board, 240 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator ) Na ) 12 Way, Double Door N 4 B ) 8 Way, Double Door 5 Supplying & Fixing 5 A To 32 A Rating 240 / 415 V C Curve Mcb Suitable For Inductive Load Of Following Poles In The Existing Mcb Db With Connections, Testing, Commissioning Etc. As Reqd. Na ) Single Pole N 6 B ) Single Pole And Neutral 7 Sitc Of Energy Efficient Hi-Wall Split Type Ac Unit Of 1.5 Tr Capacity 5 Star / ( Invertor Based Technology ) Bee Rating Year 2020, Nominal Cooling Capacity Of Minimum 5100 Watt, Suitable For Operation On Single Phase, 220V, 50 Hz, Ac Supply I / C Electronic Remote Control, Comprising Of Both Indoor And Outdoor Unit With Copper Condensor Coil, Eco-Friendly Gas, Ms Angle Iron Stand For Outdoor Unit Including 6 Meter Length, 4 Core 2.5 Sq.Mm.Wire, 4 Mtr. Copper Tube Of Suitable Size, Wall Thickness 0.8Mm Duly Insulated With 9Mm Nitrile Insulation, 5 Mtr. Pvc Drain Pipe Of Size 25Mm I / C Elbow, Tee, Socket, Cement Solvent Etc. Complete As Reqd. 8 Sitc Of Energy Efficient Hi-Wall Split Type Ac Unit Of 2.0 / 2.2 Tr Capacity 5 Star / ( Invertor Based Technology ) Bee Rating Year 2020, Nominal Cooling Capacity Of Minimum 5500-6000 K.Cal. / Per Hr., Suitable For Operation On Single Phase, 220V, 50 Hz, Ac Supply I / C Electronic Remote Control, Comprising Of Both Indoor And Outdoor Unit With Copper Condensor Coil, Eco-Friendly Gas, Ms Angle Iron Stand For Outdoor Unit Including 6 Meter Length, 4 Core 2.5 Sq.Mm.Wire, 4 Mtr. Copper Tube Of Suitable Size, Wall Thickness 0.8Mm Duly Insulated With 9Mm Nitrile Insulation, 5 Mtr. Pvc Drain Pipe Of Size 25Mm I / C Elbow, Tee, Socket, Cement Solvent Etc. Complete As Reqd. 9 Supplying, Installation, Testing & Commissioning Of Copper Wound Automatic Voltage Stabilizer Having Input Voltage Range Of 150-270 Volt And Output Of 195-245 Volt ± 5% Ffor Including Fixing, Connections Of Following Rating Etc. As Reqd. Na ) 5 Kva N 10 Supplying & Fixing Of 4 Kva Capacity Automatic Voltage Stablizer With Time Delay Relay And High / Low Voltage Trip Facility Input Voltage 150V To 290V And Output Voltage 220+10% With Copper Flexible Cable Connection Etc. As Required At Site. 11 Providing And Fixing Of Hard Drawn Pvc Drain Pipe Line Of 25Mm Dia For Drain Out Condensed Water Etc In Surface Or Recesses As Required At Site. 12 Supplying And Fixing Of Refrigerant Copper Pipes Of Following Sizes Along With 1 / 2 Nylon Insulation Tube Complete With 3 Core 2.5 Sq.Mm Copper Cable, Clipping On Wall Surface I / C Testing And Commissioning Etc. As Reqd. Na ) 1 / 4 & 1 / 2 N 13 B ) 3 / 8 & 5 / 8 14 Providing And Fixing Of U-Pvc Trunking System Of Following Size With Flexible Cover, Cover Joint , Base Joint , End Caps, Tee, Bend, Joints, Angles, Provision Of Partition If Reqd. , Suitable For Drawing Of Wires And Cables On Surface Of Wall / Existing Mounting Etc. As Required. Na ) 105Mm X 50Mm N 15 B ) 32 Mm X 20 Mm