| 1 | 1 | SITC of Single Skin Centrifugal Cabinet Type Fan complete with DIDW- forward curved belt driven centrifugal blower Rotaion of fan 1435 RPM, Epoxy/ galvanized steel sheet cabinet with service access doors, Inlet & outlet drilled flanges 3.7 KW, 4 pole, IE - 2, IP -55 Standard 3Ph/415V/50 hz Motor(Make: ABB/Cromptom) with Fixed base, common base frame with spring isolators,Flange at inlet and outlet are provided to facilitate duct connection necessary hanging/supporting members,water prof VFD Panel for Fan's Speed control etc. Sound level-65 dba. Capacity 70mmwg Static pressure, 4000 CFM, (Nikotra/ Elta/ Wolter) | BI01010001010000000000000515BI0100001112 | 2 | Nos |
|---|
| 2 | 2 | SITC of 10 Micron Pre Filter with Frame, it will be fitted on Centrifugal Exhust fan & on the Fresh air Damper (Make: Spectrum/ Priyanka Engg./ AFI) | BI01010001010000000000000515BI0100001113 | 8 | Nos |
|---|
| 3 | 3 | SITC of 0.3 Micron Hefa Filter,it will be fitted on Centrifugal Exhust fan.(Make: Spectrum/ Priyanka Engg. Spectrum/ AFI) | BI01010001010000000000000515BI0100001114 | 5 | Nos |
|---|
| 4 | 4 | SITC of Motorized Duct Damper for out side Fresh air Control & AC Machine Air Control.(Make: Primier/ AFI/ Spectrum) | BI01010001010000000000000515BI0100001115 | 6 | Nos |
|---|
| 5 | 5 | Fabrication and erection of duct fabricated out of 22 SWG GI sheet complete with necessary flange connections, FRP flexible connections, GI brackets / hanger supports, to suit site condition & design layout. Exhaust Ducting,Supply ducting,Exhaust rille, Make: TATA,SAIL,JINDAL\n\n | BI01010001010000000000000515BI0100001116 | 110 | Sq.Mtr |
|---|
| 6 | 6 | Fabrication and erection of duct fabricated out of 24 SWG GI sheet complete with necessary flange connections, FRP flexible connections, GI brackets / hanger supports, to suit site condition & design layout. Exhaust Ducting,Supply ducting,Exhaust rille, Make: TATA,SAIL,JINDAL\n\n | BI01010001010000000000000515BI0100001117 | 450 | Sq.Mtr |
|---|
| 7 | 7 | Supply & Pasting Al. Foil face 9mm thick Nitrile rubber insulation on duct by adhesive gum. | BI01010001010000000000000515BI0100001118 | 450 | Sq.Mtr |
|---|
| 8 | 8 | Supply & Pasting open cell 9mm thick Nitrile rubber insulation under duct by adhesive gum. | | 90 | Sqmt. |
|---|
| 9 | 9 | SITC of 16A Limit switch for control the Fresh air Motorized Damper(Fresh air damper Will be Closed when open the Door.Fresh Air Damper will be Open when Close the Door) | | 8 | Nos |
|---|
| 10 | 10 | Supply & laying 4 Core 4.0 Sq.mm Copper Cable with 15Amp. For Power line of Exhaust Fan | | 70 | Mtr |
|---|
| 11 | 11 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required for 4x84/0.3 (6 sqmm) + 2x56/0.3 (4 sqmm) as ECC | | 50 | Mtr |
|---|
| 12 | 12 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. | | | |
|---|
| 13 | 12.01 | 6 Sqmm | | 12 | Set |
|---|
| 14 | 12.02 | 4 Sqmm | | 8 | Set |
|---|
| 15 | 13 | Supply & laying 3 Core 1.5 Sq.mm Copper Cable with 15 Amp. Plug Top For Power line of Motorized dumper | | 120 | Mtr |
|---|
| 16 | 14 | Supply and Fixing of Silicon on the window inside the room for air titening | | 1 | Item |
|---|
| 17 | 15 | Charges for Lifting & Shifting of Fan | | 1 | Lot |
|---|
| 18 | 16 | SITC of Discrite Powder Coaed Al. Grill with VCD (Make:Primier/AFI/Air Primier) | | 12 | Sqmt. |
|---|
| 19 | 17 | SITC of Discrite Powder Coaed Al. Grill without VCD (Make:Primier/AFI/Air Primier) | | 12 | Sqmt. |
|---|
| 20 | 18 | SITC of 40 Micron Pre Filter,it will be fitted on return Grill.(Make: Spectrum/ Priyanka Engg./ AFI) | | 12 | Sqmt. |
|---|
| 21 | 19 | Supply & Fixing of Bird Screen as per direction of E.I.C. | | 8 | Nos |
|---|
| 22 | 20 | Supply and fixing of UVC EMIITTER for the above fan's for prevention of fungus , The minimum UV intensity in the coils shall be 700-800 UW-SEC/CM2. The unit shall be UL.Listed (UL-1995) and it should be suitable to fix the same in Fan's Duct. | | 8 | Nos |
|---|
| 23 | 21 | Supplying, fabrication & fixing 2 Nos. M.S. u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making Base Frame table type for installation of Exhuast Fan incl. drilling 2 nos holes in each channel. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm as per direction of E.I.C. | | 8 | Nos |
|---|
| 24 | 22 | Supply of Microprocessor based air cooled 11.0TR Floor Mounting/ Ceiling Suspended ductable type Split Air Conditioner having nominal cooling capacity of 132000 BTU/hr.with 1 nos.or 2nos. Scroll/Rotary Compressor ISI condition suitable for operation on 415V, + 5% - 50 Hz. - 3Ph AC supply. (Make : Hitachi/ OGeneral/ Daikin/Carrier/Bluestar) as per direction of E.I.C. | | 4 | Nos |
|---|
| 25 | 23 | Supply of Microprocessor based air cooled 8.5TR Floor Mounting / Ceiling Suspended ductable type Split Air Conditioner having nominal cooling capacity of 102000 BTU/hr.with 1 nos.or 2 nos. Scroll/Rotary Compressor ISI condition suitable for operation on 415V, + 5% - 50 Hz. - 3Ph AC supply. (Make : Hitachi/ OGeneral/ Daikin/Carrier/Bluestar) as per direction of E.I.C. | | 4 | Nos |
|---|
| 26 | 24 | Installation, testing & commissioning of the above-said 11.0/ 8.5 ton ductable as per direction of E.I.C. | | 8 | Nos |
|---|
| 27 | 25 | Supply & laying Drain Water piping work out of PVC / HDPE hard pipes of following sizes incl. fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchors. Of 25 mm dia. | | 80 | Rmt |
|---|
| 28 | 26 | Supply, installation & commissioning Copper Refrigeration pipe line for liquid and suction line with supports & brackets (For Twin circuit11.0 Ductable split AC) for Liquid Line (1/2\" OD HD Copper Pipe with 0.6mm thick) | | 95 | Rmt |
|---|
| 29 | 27 | Supply, installation & commissioning Copper Refrigeration pipe line for liquid and suction line with 9mm thick Nitrile Rubber Inuslatin, supports & brackets (For Twin circuit11.0 Ductable split AC) for Suction line (7/8\" OD HD Copper Pipe with 0.7mm thick) | | 95 | Rmt |
|---|
| 30 | 28 | Supply, installation & commissioning Copper Refrigeration pipe line for liquid and suction line with supports & brackets (For single circuit11.0 Ductable split AC) for Liquid Line (5/8\" OD HD Copper Pipe with 0.6mm thick) | | 70 | Rmt |
|---|
| 31 | 29 | Supply, installation & commissioning Copper Refrigeration pipe line for liquid and suction line with 9mm thick Nitrile Rubber Inuslatin, supports & brackets (For Single circuit11.0 Ductable split AC) for Suction line (1 1/8\" OD HD Copper Pipe with 0.7mm thick) | | 70 | Rmt |
|---|
| 32 | 30 | Control copper Cabling from ODU Unit to IDU unit of Concealed Split AC of 3 Core 2.5sq. mm. Communication Cable | | 160 | Rmt |
|---|
| 33 | 31 | Control copper Cabling from ODU Unit to IDU unit of Concealed Split AC of 4 Core 2.5sq. mm. Power Cable | | 160 | Rmt |
|---|
| 34 | 32 | Supplying, fabrication & fixing 2 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making Base Frame table type for installation of AC ODU incl. drilling 2 nos holes in each channel. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm as per direction of E.I.C. | | 8 | Nos |
|---|
| 35 | 33 | Supply & Fixing of Canvass Connection of Ductable AC | | 16 | Nos |
|---|
| 36 | 34 | Supply & fixing of ACP Board with all supporting accerise to coverred the IDU | | 50 | Sqmt. |
|---|
| 37 | 35 | Supply & fixing of IDU trap door by Wall angle & ACP Boad | | 8 | Nos |
|---|