Manning And Operation Including Repair Maintenance Of Clarifier Drinking Water Supply Installation And Fire Pump House Including Dg Set At Site E Under Ge Sb Karwar, CWE NAVY VASCO-Goa

Military Engineer Services-MES has published Manning And Operation Including Repair Maintenance Of Clarifier Drinking Water Supply Installation And Fire Pump House Including Dg Set At Site E Under Ge Sb Karwar. Submission Date for this Tender is 08-03-2021. Diesel Generators Tenders in CWE NAVY VASCO Goa. Bidders can get complete Tender details and download the document.




Tender Notice

26733011
Corrigendum : Manning And Operation Including Repair Maintenance Of Clarifier Drinking Water Supply Installation And Fire Pump House Including Dg Set At Site E Under Ge Sb Karwar
Open Tender
Indian
Goa
CWE NAVY VASCO
08-03-2021

Tender Details

Manning And Operation Including Repair Maintenance Of Clarifier Drinking Water Supply Installation And Fire Pump House Including Dg Set At Site E Under Ge Sb Karwar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 15-Feb-2021 DATECORRI Date 01-03-2021
2 22-Feb-2021 BOQCORRI Other 01-03-2021
3 01-Mar-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 08-03-2021

Key Value

Document Fees
INR 1000 /-
EMD
INR 166000.0 /-
Tender Value
Refer document

BOQ Items

NAME OF WORK :- MANNING AND OPERATION INCLUDING REPAIR/MAINTENANCE OF CLARIFIER , DRINKING WATER SUPPLY INSTALLATION AND FIRE PUMP HOUSE INCLUDING DG SET AT SITE 'E' UNDER GE (SB) KARWAR
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Manning and Operation of water supply installation at clarified water sump and pump house NK Bail in three shifts of 8 hours each on all days including Sundays and Holidays including minor maintenance / checks, all as specified and as directed.The installation comprises of following equipments :- 11 Per Month
2 1.1 (a) Water pump vertical turbine type Hp-100 ,Head- 80 m, discharge - 200 cum/Hr Make-Kirloskar Brothers , coupled with Induction motor 3 phase, 415 volt Rpm-1475 Hp-100 ,Make- Alsthom -2 Nos.\n(b) Drain water Lifting pump Hp-1.5 ,Head- 11.5mtr discharge - 10 cum/Hr Make-Kishor pumps coupled with Induction motor 3 phase, 415 volt Rpm-1415 Hp-1.5,Make- Crompton Greaves - 2 Nos.\n(c) Main Electric control panel with SFU TPN -02 Nos, starters 45kw 3 phase 415 volt-04 Nos, starters 0.37 kw 3 phase 415 volt-03 Nos, push buttons, selector switches ,volt & Amp meters ,control wiring & accessories local push button stations -1 set\n(d) Pressure sand Filter back wash Air compressor,pressure-1.2 kg/cm 2 capacity - 400 cum/Hr Make-Usha compressors coupled with Induction motor 3 phase, 415 volt Rpm-1450,10 HP, -02 Nos .Make- Laxmi motors\n(e) Pressure Sand Filter cap-300 cum / Hr with butter fly valves pressure gauges and piping accessories - 03 Nos\n(f) C.I./ D.I. piping Network with sluice valves -01 set\n(g) Air blowers of capacity -12.5 HP Make: Thermax - 02 Nos\n\n\n\n\n\n\n
3 2 Manning and Operation of drinking water pump house at NK Bail (CF Area) in 03 (three) shifts of 8 hours each on all days including Sundays and Holidays including minor maintenance / checks, all as specified and as directed. The installation comprises of following equipments :- 11 Per Month
4 2.1 (a) Water pump Hp-30 ,Head- 60 m discharge - 50 cum/Hr Make-Kirloskar Brothers , coupled with Induction motor 3 phase, 415 volt Rpm-1475 Hp-30, Make- Crompton Greaves -06 Nos\n(b) Chlorine dozing pump model G6402, pressure -8Kg/Sq cm , discharge 160 LPM, Make –Milton Roy coupled with Induction motor 3 phase, 415 volt, RPM-1360, HP -0.5, Make - Crompton Greaves – 4 Nos. with connected accessories and 1000 ltr cap PVC storage tank – 04 Nos.\n(c) Drain water lifting pump HP-1.5, Head -11.5 m, discharge 10 Cum/hr Make Kishor pumps coupled with Induction motor 3 phase, 415 volt, RPM-1415 , HP-1.5, Make –Crompton Greaves – 2 Nos\n(d) Main Electric control panel – 200 Amp SFU, 415 volt, 3 phase -01No, starters -06Nos 3 phase, 415 volts -22 KW-06 Nos, 0.37KW – 05 Nos, push buttons selector switches, volt & Amp meters, control wiring & accessories, local push button stations 90 KVAR-08 Nos – 1 set.\n(e) C.I./ D.I.piping Network with sluice valves covering entire area of Coman facilities, Admin Bldg, NAD & MTP including Magzine /Misiles Bldgs area.\n(f) Water received from clarified water sump to GLR of Cap 45,00,000 ltr\n
5 3 Manning and operation of fire pump house installation at NK Bail (MTP Area) in three shifts of 8 hours each on all days including Sundays and Holidays including minor maintenance/checks all as specified and directed. \nThe installation comprises of the following equipments:-\n(a) Fire water pump Head – 88 m, discharge – 273 cum/hr. Make – Kirloskar Ltd, coupled with diesel engine, 415 volt, RPM – 1488, HP – 156, Make – Kirloskar Ltd – 1 No. (b) Fire water pump Head – 88 m, discharge – 273 cum/hr, coupled with induction motor, 415 volt, RPM – 1488, HP – 150, Make – CG – 1 No\n(c) Jockey pump Head – 88 m, discharge – 30 cum/hr, coupled with induction motor 3 phase, 415 volt, RPM – 2945, HP – 30, Make – CG – 2 Nos.\n(d) Drain water lifting pump HP-1.5, Head – 11.5 m, discharge – 10 cum/hr, Make – Kishor pumps, coupled with induction motor 3 phase, 415 volt, RPM – 1450, HP – 1.5, Make – Kirloskar Ltd – 2 Nos.\n(e) Main electric control panel 630 Amp SFU with starters, push buttons, selector switches, volt & Amp meters, control wiring & accessories local push button stations- 1 set.\n(f) Starters for motor – 04 Nos\n(g) GLR of 2x350 cum of capacity – 01 No\n(h) C.I/D.I piping network with sluice valves – 01 set\n 11 Per Month
6 4 Manning and operation of fire pump house installation at NK Bail (NAD Area) in three shifts of 8 hours each on all days including Sundays and Holidays including minor maintenance/checks all as specified and directed. The installation comprises the equipments same as mentioned in Item No 3 here in before. 11 Per Month
7 4.1 Notes for Item Nos.1 & 4:-\n(a) Contractor has to employ minimum following staff for manning & operation of the Clarifier , Drinking water installations and Fire pump house at Item Nos 1& 4 above :-\n (i) One skilled electrician/ Fitter general mechanic operator per shift of 08 hours (Total 06 shifts per day i.e 3 shifts per day for each water supply installation at Sl No.1 & 4 above) havining minimum ITI qualification in respective trade from Govt recognised institute with adequate knowledge with minimum two years experience in maintenance & operation of water supply installation. The operator must be competent to carry out the minor Maintenance of water supply installation all as directed by Engineer-in-Charge.\n(ii) One skilled Valve operator per shift of 08 hours (Total 04 shifts per day i.e 2 shifts per day for each water supply installation at Item Nos 1 & 2 above & One skilled Valve operator per shift of 08 hours (Total 06 shifts per day i.e 3 shifts per day for each water supply installation at Item Nos 3 & 4 above having minimum ITI qualification in respective trade from Govt recognised institute with adequate knowledge with minimum two years experience in maintenance & operation of water supply pipes & valves. The operator must be competent to carry out the minor maintenance of water supply pipe line & valves all as directed by Engineer-in-charge.\n(b) The rates quoted shall be inclusive of all taxes ,cess, levies etc as applicable including GST\n(c) The prevailing rate,wage,contribution etc shall be as applicable as on the bid submission end date.\n
8 4.2 (d) In view of COVID-19 alerts various restrictive instructions issued concerned authorities from time to time. Hence additional precautions essential for the work shall be taken by the contractor by way of provisioning of masks, hand sanitizers, gloves etc to workmen and all local instructions issued by the Concerned Authorities and Station Authorities shall be complied with all relevant safety precautions covered under Model Rules for the protection of health and sanitary arrangement for workmen (Annexure ‘C’ of IAFW-2249) shall be strictly followed. Nothing extra is admissible on this account \n(e) The contractor shall also deploy additional man power as relief against weekly off,leave,holidays etc all as per existing Labour Act and shall substitute the operator accordingly for which no extra payment admissible. The unit rate quoted against items in Schedule ‘A’/BOQ shall be inclusive of this provision also.\n(f) The contractor shall pay the wages to the operator through e-payment i.e Aadhar linked bank accounts and Credit to their bank account. The wages shall not be less than prevailing minimum wages fixed by state Govt or central Govt whichever is more. \n\n
9 4.3 (g)Chemicals for chlorination/dozing will be measured & paid separately under respective items here in below as "Supply only" however cost of labour is deemed to be included in the unit rate quoted against Item No 1 to 4 above.\n(h) The unit rate quoted shall be deemed to include for daily minor maintenance like checking and rectification of any water leakage ,loose connection, cleaning and general up keep of pump room/ GLR/HTR and area around it\n(j) Power supply for operating the installation and diesel for running the DG set shall be made available by the department free of cost.\n(k) The Contractor shall not employ same tradesman continuously for more than 11 months during the Contract period of 11 months. \nl) The unit rate quoted shall deemed include for maintenance for earth pits, cutting & removing of vegetation and upkeep of the surrounding area, all around the bldg upto 6m from the plinth protection all as directed by Engineer-in-Charge. In case of failure, a penalty of Rs 2000/- per month will be levied and recovered from dues.\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n\n(d) Power supply for operating the installation will be made available by the department free of cost.\n(e) The Contractor shall not employ same tradesman continuously for more than 11 months during the Contract period of 11 months. \n\n\n\n\n\n\n
10 4.4 (m) The contractor shall provide 02 uniforms to each operators & helper and design of uniform shall be got approved from GE. In case of failure, a penalty of Rs 100/- per day per operator will be levied and recovered from dues.\n(n) The rate quoted shall deemed to be inclusive of safety gear & required tools for minor maintenance. In case of failure to provide tools kit & safety kit (Gum boots-02 pairs, hand gloves), a penalty of Rs 3000/- will be recovered and levied \n(o) The Contractor shall maintain proper records of all kinds of daily, weekly, monthly, quarterly, half yearly and yearly or whatsoever maintenance is carried out during contract period in a binded book / register and shall obtain the signature of Engineer-in-Charge every fortnightly. \n(p) In the case of absence of operator, penalty will be charged as doubled as quoted rate or Rs 1000/-per shift whichever is higher besides any loss/damages occurring during the period which will have to be made good by the contractor without any extra cast.
11 4.5 (q) It is responsibility of contractor to deposit the employees provident fund (EPF) to the concerned authority as per the prevailing scales as laid down by the Ministry of labour for all Electrician/operator/helper (as applicable) and necessary proof to this regard shall be submitted to Engineer-in-Charge for verification and records. The quoted rate shall be deemed to be included of above provisions. In case contractor fails to produce the proof of EPF, he shall be liable for action as deemed fit. Decision of GE in this regard shall be final and binding.\n(r) The contractor shall maintain all the registers under various labour law rules, 2017 and shall be produced to GE and as well as officers detailed by labour department. \n
12 5 Supply only following chemicals for chlorination / filtration of water :-
13 5.1 (a) Alum lump grade Ist quality 1212 Kg
14 5.2 (b) Calcium based granular disinfectant having chlorine concentration 65%-70% 900 Kg
15 6 M & L for cleaning of RCC ground level reservoir drinking water at NAD/ MTP area of 3,00,000 ltrs capacity including mouths of connected pipes etc by dewatering the sumps by using a portable pump set of suitable capacity, removing all sludge/ mud/ dirt etc manually, pouring fresh water in sump through another pump set, rinsing and dewatering the sumps including removing sludge/ dirt particle manually, wash the sump using fresh water mixed with sodium hypochlorite & drain out water by a pump set and finally applying one coat of antibacterial sodium hypochlorite solution to inner surface & writing date of cleaning complete all as specified and as directed. 2 Each Job
16 7 M & L for taking down, transportation to workshop and back to site, dismantling electric motor of any make three phase 415 Volts, opening the motor, cutting / removing the existing burnt winding and rewinding using super enamelled copper wire of suitable gauge to match with the existing winding including varnishing & drying and reassembling the motor, connecting with pump set with proper alignment and testing complete all as specified and directed of following capacities:\n\n\n\n
17 7.1 (a) 100 HP 2 Each Job
18 7.2 (b) 30 HP 5 Each Job
19 7.3 (c) 1.5 HP 4 Each Job
20 8 M&L for servicing of mono block / split casing centrifugal type pump set by removing & dismantling pump and connected pipes & electrical connections etc and replacing of unserviceable parts with new gland packing set, gun metal bushes, bearing, water seal packing complete cleaning of impeller, greasing etc reassembling and re fixing in original position complete with packing and necessary nuts and bolts etc including testing for smooth functioning etc all as specified and as directed for following capacities:\n\n\n\n
21 8.1 (a) Clarifier drinking pump of capacity 200 cum/hr vertical turbine type. 2 Each Job
22 8.2 (b) Drinking water pump at NAD / MTP area of capacity 30 cum/hr 5 Each Job
23 9 S&F in repairs rotational moulded polythyne water storage tank of capacity 1000 ltrs, double layered, ISI marked (cylindirical vertical with closed top) hoisted and fixed in position all as specified and as directed. 2 Each
24 10 M & L for repair to unserviceable starter of capacity 30 HP by disconnecting it from the main panel, transporting it to workshop and back to site, making arrangement for new copper lugs, new contactor, switch fuses, replacement of old wiring with new one all as specified and as directed. 2 Each Job
25 11 S & F in repair cast iron butterfly valve of size 200 mm including checking for any leakages all as specified and as directed. 2 Each
26 12 S & F in repair cast iron butterfly valve of size 150 mm including checking for any leakages all as specified and as directed. 2 Each
27 13 S & F in repair cast iron butterfly valve of size 50 mm including checking for any leakages all as specified and as directed. 1 Each
28 14 M&L for taking down carefully existing old unserviceable 30 HP DOL starter and supply, installation, testing and commissioning of 30 HP DOL starter panels of size 500 mm x 500 mm x 300 mm, dust, moisture and vermin proof totally enclosed IP-55 factory made fabricated from 1.6 mm thick CRCA sheet duly powder coated in existing indoor LT panels floor mounted comprising of following accessories with incoming and outgoing connections as per site requirement complete all as specified and as directed :- 3 Each
29 14.1 (a) 63A 3P 25 KA MCCB, TMD Release, type : easy pact CVS -01 No. \n(b) Standard extended rotary handle for easy pact CVS 100/160/250 A. - 01 No. \n(c ) 6A 1P 10KA C curve MSB, type : xC60 - 01 No. \n(d) AC3: 50 AC1:70A 3P Power contactor, coil : AC, Aux. Contact : 1 NO+1NC - 01 No. \n(e) 37-50A Thermal overload relay Type IRE - 01 No. \n(f) Auxiliary contact block, front mounting, contacts : 2NO+2NC for LC1E06-E630/LC1E0600-LC1E9500. \n(g) Red, yellow, blue indicating lamps (LED) 230 V AC - 03 Nos. \n(h) Control fuse 2 A - 04 Nos of Reputed make.\n\n\n\n\n
30 14.2 (j) Ammeter 5 A AC Input - 01 No. \n(k) Voltmeter 480V, AC input - 01 No. \n(l) 60/5A 1VA Acc CL-3 ABS insulated Current Transformer - 03 Nos. \n(m) Red mushroom head (40 mm) Trigger type, press to lock turn to release 22.5 mm push button (plastic)- 01 No. \n(n) Green Flush type 22.5 mm Push Button (Plastic) + NO - 01 No. \n(p) Red Flush type 22.5 mm Push Button (Plastic) + NC - 01 No. \n(q) ON/OFF/TRIP indication lamp- 03 Nos. \n(r) 0.5 Sqmm FR insulated 1 core unsheathed industrial flexible cable-35 RM. \n(s) 10 Sqmm FR insulated 1 core unsheathed industrial flexible cable-10 RM. \n(t) 2.5 Sqmm Feed thru screw clamp TB - 10 Nos. \n(u) 16 Sqmm Feed thru screw clamp TB - 08 Nos. \n\n\n\n\n\n
31 15 S&F in repair MCCB 400 Amps 3 Pole 50 KA breaking capacity, 415 volts AC with adjustable thermal magnetic release complete all as specified and as directed. 2 Each
32 16 S&F in repair MCCB 250 Amps 3 Pole 36 KA breaking capacity, 415 volts AC with adjustable thermal magnetic release complete all as specified and as directed. 3 Each
33 17 S&F in repair MCCB 160 Amps 3 Pole 25 KA breaking capacity, 415 volts AC with adjustable thermal magnetic release complete all as specified and as directed. 5 Each
34 18 S&F in repair MCCB 125 Amps 3 Pole 25 KA breaking capacity, 415 volts AC with adjustable thermal magnetic release complete all as specified and as directed. 6 Each
35 19 S&F in repair HRC fuses of blade tag type of 2 to 16 Amps rated at 415 volts AC with breaking capacity of 80 KA all as specified and as directed. 16 Each
36 20 S&F in repair HRC fuses of blade tag type of 20 to 32 Amps rated at 415 volts AC with breaking capacity of 80 KA all as specified and as directed. 18 Each
37 21 S&F in repair HRC fuse link 100 Amps, 415 Volt all as specified and as directed 10 Each
38 22 S&F in repair HRC fuse link 250 Amps, 415 Volt all as specified and as directed. 12 Each
39 23 S&F in repair HRC fuses holder for HRC fuses all as specified and as directed. 12 Each
40 24 S&F in repair soft starter for 100 HP motor, 140-150 Amps, 415 Volt complete all as specified and as directed. 2 Each
41 25 S&F in repairs MCB TPN, 50 to 63 Amps, ''C'' series 415 Volts, 3 phase, 10 KA breaking capacity of complete all as specified and as directed. 10 Each
42 26 S&F in repairs MCB SPN, 6 to 32 Amps, ''C'' series 230 Volts, single phase, 10 KA breaking capacity complete all as specified and as directed. 25 Each
43 27 S&F in repairs cast iron sluice valve of size 80 mm flanged PN-1.6 ISI conforming to IS :14846 hand wheel operated, stainless steel stem with gun metal parts flanged driller to IS: 1538 non rising stem PN-1.6 all as specified and as directed. 5 Each
44 28 All as per Item No 27 here in before but of size 100 mm dia all as specified and as directed. 8 Each
45 29 M&L for dismantling and taking out carefully defective spindle from sluice valve of size 80 mm dia and removing the old gate stud by grinding and making it to a shape by brass welding and turning & polishing, greasing, servicing as per original gate stud and re fixing the same at position and testing complete all as specified and as directed. 12 Each Job
46 30 All as per Item No 29 here in before but of size 100 mm dia all as specified and as directed. 14 Each Job
47 31 All as per Item No 29 here in before but of size 150 mm dia all as specified and as directed. 15 Each Job
48 32 S&F in repairs gland packing for pump of size 30 HP/ fire hydrant valves complete all as specified and as directed. 58 Each
49 33 Supply only grease for pump bearings all as specified and as directed. 30 Kg
50 34 S&F in repairs mild steel nuts, bolts, washer & flange etc all as specified and as directed. 30 Kg
51 35 M&L for taking sample of water from MES pump house/selected area at Naval Base Karwar and send it to any govt approved lab for carryout the following test periodically or required basis and test report to be produce to Engineer in Charge all as specified and as directed. \n(a) PH\n(b) Total Hardness\n(c) Iron (As Fe Mg/I)\n(d) Turbidity (NTU)\n(e) Sulphate(As SO2 Mg/I)\n(f) Magnesium(As Mg/I)\n(g) E coil or thermo tolerant (coil from bacteria) 8 Each Job
52 36 Supply,laying,jointing and testing of LT XLPE insulated screened PVC bedded armoured heavy duty electric cable with stranded aluminium conductor,1100 volts grade of cross sectional area 25 sqmm 3.5 core conforming to IS-7098 (Part-I) of 1958 laid in pipe/ducts/wall/floors etc fixed with saddle and clamps complete with proper thimbles,nuts,bolts and washers all as specified and as directed 315 RM
53 37 Supply only engine oil grade 15W-40 for routine maintenance and topping up all as specified and as directed. 20 Ltr
54 38 M&L for cleaning of RCC Ground level reservoir of fire pump house of 2x350 cum (7,00,000.00 ltrs) capacity including mouths of connected pipes etc by dewatering the sumps by using a portable pump set of suitable capacity, removing all sludge/ mud/ dirt etc manually, pouring fresh water in sump through another pump set, rinsing and dewatering the sumps including removing sludge/ dirt particle manually, wash the sump using fresh water mixed with sodium hypochlorite & drain out water by a pump set and finally applying one coat of antibacterial sodium hypochlorite solution to inner surface & writing date of cleaning complete all as specified and as directed. 2 Each Job
55 39 M&L for opening the LT Panel board cubical type for pump sets located at NAD/MTP pump house, cleaning the bus duct chamber, inspect the complete panel, tighten the all nut, bolts of incoming, outgoing ACBs/MCCB s/ SFU of different capacity and heating up for removal of moisture, record its IR value with the help of 1.1 KV megger and applying thick coating of Z931 strippex B and Z 955 Strippex (SL) of stanac product for preventing from flush over and fire hazard, including replacement of 3mm thick gasket, closing of all holes complete all as directed.\n 2 Each Job
56 40 M&L for taking down electric motor of any make three phase 415 Volts, transportation to workshop, opening the motor, cutting / removing the existing burnt winding and rewinding using super enamelled copper wire of suitable gauge to match with the existing winding including varnishing & drying and reassembling the motor, connecting with pump set with proper alignment and testing complete all as specified and directed of following capacities:
57 40.1 (a) 1.5 HP 2 Each Job
58 40.2 (b) 30 HP 2 Each Job
59 40.3 (c) 150 HP 1 Each Job
60 41 M&L for taking down centrifugal pump sets / vertical turbine pumps 3 phase 415 volts for overhauling of following capacities and shifting at civil workshop by transport, opening up the pump set, cleaning inside & out side thoroughly, including replacement of gland packing, rubber insertion, replacement of bearings - 2 Nos (DE/NDE), repair impeller and testing complete all as specified and as directed.
61 41.1 (a) HP – 30, Head – 88 m, discharge – 30 cum/hr, RPM – 2945 at MTP/NAD area 2 Each Job
62 41.2 (b) HP – 150, Head – 88 m, discharge – 273 cum/hr, RPM – 1488 at MTP/NAD area 2 Each Job
63 42 M&L for repair to fire hydrant valves of size 80/100 mm dia and shifting at civil workshop by transport, opening up the defective valves and taking out spindle and gate from sluice valve and removing the old threads by grinding and making a new threads by brass welding, turning & polishing to the spindle at civil workshop on grinding machine as per original threads and re fixing the same at position and testing complete all as specified and as directed 20 Each
64 43 S&F in repair spindle wheel of fire hydrants complete all as specified and as directed. 20 Each
65 44 M&L for repairs to sluice valves of size 80 mm by taking out defective spindle, repairing the same in lathe by grinding, turning, cutting to make fresh grooves and refix the same in its original position and testing for leakage all as specified and as directed. 2 Each
66 45 All as per Item No 44 here in before but of size 100 mm dia all as specified and as directed. 2 Each
67 46 All as per Item No 44 here in before but of size 150 mm dia all as specified and as directed. 1 Each
68 47 All as per Item No 44 here in before but of size 200 mm dia all as specified and as directed. 1 Each
69 48 M & L for preparation of existing painted surfaces of motor, pump, water pipe lines etc at fire water pump house NAD/MTP, filling of cavities etc and applying one coat of synthetic enamel paint using spray gun/machine as per colour code including writing SM & MES No on pump & motor, indication marking etc complete all as specified and as directed. 2 Each Job
70 49 S&F in repairs of battery of 12 volts 45 AH battery all as specified and as directed. 2 Each
71 50 S&F in repairs blank cap for fire hydrant of size 63/75/80 mm complete with chain and connected items all as specified and as directed 30 Each
72 51 S&F in repair MCCB 100 Amps rupturing capacity 25 KA 4 Pole 415 volts AC with adjustable thermal setting complete all as specified and as directed 1 Each
73 52 S&F in repairs battery charging system meant for charging 12 Volts, 45 AH battery complete all as specified and as directed. 1 Each
74 53 S&F in repairs bearing No : 6309 ZZ all as specified and as directed. 1 Each
75 54 S&F in repairs bearing No : 6314 ZZ all as specified and as directed. 1 Each
76 55 M&L for repair to unserviceable starter of capacity 30 HP by disconnecting it from the main panel, transporting it to workshop, making arrangement for new copper lugs, new contactor, switch fuses, replacement of old wiring with new one all as specified and as directed 1 Each Job
77 56 S&F in repairs of oil filter suitable for Diesel Engine of capacity 156 HP all as specified and as directed. 1 Each
78 57 S&F in repairs of fuel filter suitable for Diesel Engine of capacity 156 HP all as specified and as directed. 1 Each
79 58 S&F in repairs LED flood light luminaire 160 watt with secondary optics made in pressure die cast housing and heat sink in aluminium extruction with IP66 protection all as specified and as directed. 3 Each
80 59 S&F in repairs pressure switch suitable for 1-16 Kg/Sqcm complete all as specified and as directed. 2 Each
81 60 S&F in repairs rubber expension joint angle arch of size 50 to 100 mm dia all as specified and as directed. 2 Each
82 61 S&F in repairs water pressure gauge dial type of range 0-21 Kg/Sqcm all as specified and as directed. 1 Each
83 62 M&L for taking down copper/aluminium conductor cable of size 16/25 Sq mm 4 core of any type and Supply, laying, jointing and testing of PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 volts grade of cross-sectional area 16 Sq mm 4 core laid in existing pipe/ducts/wall/floors etc, fixed with saddle, clamps, proper copper lugs/thimbles, nuts, bolts and washers etc complete all as specified and as directed. 90 RM
84 63 M&L for preparation of old surface by scraping down old pealed off paint using sand paper, removing dirt/dust from fire hydrant and painting to fire hydrant (1.20 m long approx) with applying two coats of synthetic aluminium paint including marking the fire hydrant number etc complete all as specified and as directed. 50 Each Job
85 64 M&L in repairs to earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth 32 x 6mm GI strip by means of bolts, nuts, check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit, charcoal common salt, earthing lead 32x6 mm up to 7.5m, 20mm dia medium grade GI watering pipe, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, PCC pit cover including earth work etc as shown in electrical plate No-3 of SSR-2014 (Part-I) complete all as specified and as directed. 1 Each
86 65 S&F in repairs cast iron sluice valve of size 80 mm flanged PN-1.6 ISI conforming to IS :14846 hand wheel operated, stainless steel stem with gun metal parts flanged driller to IS: 1538 non rising stem PN-1.6 all as specified and as directed. 1 Each
87 66 All as per Item No 65 here in before but of size 100 mm dia all as specified and as directed. 1 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy