Repair/Maint Of Distribution Network Of Extg 500 Kva Transformer Installed At Arch And Replacment Of Genr Wiring At Shokhuvi, ARTC and School 3rd mile dimapur-Nagaland

Assam Rifles-AR has published Repair/Maint Of Distribution Network Of Extg 500 Kva Transformer Installed At Arch And Replacment Of Genr Wiring At Shokhuvi. Submission Date for this Tender is 08-02-2021. Electrification Work Tenders in ARTC and School 3rd mile dimapur Nagaland. Bidders can get complete Tender details and download the document.




Tender Notice

26731040
Repair/Maint Of Distribution Network Of Extg 500 Kva Transformer Installed At Arch And Replacment Of Genr Wiring At Shokhuvi
Open Tender
Indian
Nagaland
ARTC and School 3rd mile dimapur
08-02-2021

Tender Details

Repair/Maint Of Distribution Network Of Extg 500 Kva Transformer Installed At Arch And Replacment Of Genr Wiring At Shokhuvi

Key Value

Document Fees
INR 500 /-
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work:REPAIR/MAINT OF DISTRIBUTION NETWORK OF EXTG 500 KVA TRANSFORMER INSTALLED AT ARCH AND REPLACMENT OF GENR WIRING AT SHOKHUVI
Sl. No. Item Description Item Code / Make Quantity Units
1 1 REPAIR/MAINT WORKS
2 1.01 Supply, installation, testing & commissioning of factory made cubical flour mounted outdoor distribution feeder pillar box with built-in APFC 100 KVAR for 500 KVA transformer , totally enclosed dust and vermin proof, front side opening with locking arrangement made of angle iron frame work of size 50mmx 50mmx6mm thick and 2.00 mm thick MS sheet duly powder coated , suitable for 800 amp capacity aluminum bus bar , size of the panel board should be not less than 2250 (W)x1600(W) x 900 mm (D) with stand height of 450 mm and internal wiring should be copper multistrained conductor including cooper Nuts& bolts, terminal Lugs comprising as follows:- 1 Job
3 1.02 (i) ACB, 4 pole , 50 KA,800 Amps, MO Thermal magnetic release with Digital Voltmeter and ammeter with selector switch , LED indicator Lamp, CT 800/5A with MCB SP 06 Amps - 01 Set (Incoming) \n(ii) MCCB, 4P,35 KA,250 Amps, spreader link and direct rotary handle 250 A,4Pole, MCCB - 04 Set (Outgoing Complete) 1 Job
4 1.03 (iii) For 100 KVAR APFC: MCCB, TP,200 Amps Spreader link for 200 Amps,TP, MCCB spreader link and direct rotary handle for 200 Amps MCCB , LED indicator lamp, CT 200/5 Amps, 6 Amps,SP,MCB 8 th stage APFC relay MNX 9 Contactor with auto manual selector switch , cooling fan,thermostat 6 Amps DP MCB 10 DP, MCB with Fixed APFC Bank of 10 KVAR , 2x5 KVAR Banks, 2x 10 KVAR Banks and 03 x 20 KVAR Banks with all connected items as per direction of Deptt . Installation including foundation base in all complete all as direction of Engr-In-Charge . (MCCBs :SIEMENS/L&T/Havells) (Panel : CPRI approved manufacturer)\n 1 Job
5 1.04 Dismantling of existing UNSV LT feeder pillar panel complete incl disconnection of wiring complete with necessary connection complete with taking out subject panel board incl UNSV UG cable and deposted to store yard of ARCH at Shokhuvi. 1 Job
6 1.05 Earthing of machinery/equipment Installed at power house/substation, using 25 x 3 mm copper strip and copper plate of size 300 x 300 x 3 mm, as earth electrode. 2 Set of 02
7 1.06 Dismantling of existing distribution feeder incl re- Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above upto 400 sq. mm Cable. 30 RMtr
8 1.07 Supply and fix double compression copper stain less steel gland for fixing armoured cable in panel of size cable of size 3 .5 core 400 SQMM size 1 Each
9 1.08 but for cable of size 3.5 core 95 sq mm to 120 sqmm size 4 Each
10 1.09 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit and all connected works 1.5 sq.mm. FR PVC insulated copper conductor singlecore cable etc as required and as directed at site. (92 Qtrsx3 Points (2x light pts and 1xfan Points) 276 Pts
11 1.1 Wiring for circuit/ submain wiring along with earth wire with the 1.5 Sqmmx 3 wires FR PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit as required (main DB to User DB) 1350 RMtr
12 1.11 S/F MCB DB 12 way SPN,240 Volts complete 14 Each
13 1.12 S/F MCB SP 6 Amps,240 Volts AC complete 92 Each
14 1.13 Supplying and fixing DP PVC Box enclosure on surface/ recess along with 6 amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required. 92 Each
15 1.14 Supplying and fixing PVC batten/ angle holder including connection etc. as required. 184 Each
16 1.15 Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. 92 Each