| 1 | 1 | Taking out of LT panel/Feeder Pillar box Including all fittings completed from the site completed as per directed by Engr-in-Charge. | | 15 | Each |
|---|
| 2 | 2 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 600 amps (03 Nos 600 Amps for Phase and 01 No 300 Amps for neutral) rated aluminium bus bar for neutral complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : Gate No 03. Note : The quoted rate shall be of all inclusive.\n(a) Incoming\n(i) MCCB 04 Pole 50 kA, 400 Amp,415 Volts (Qty 01 No)\n(b) Out goings\n(i) MCCB 04 Pole 36 KA, 250 Amp, 415 Volts, (Qty - 02 Nos)\n(ii) MCCB 04 Pole 36 KA, 125 Amp, 415 Volts, (Qty - 01 Nos)\n(iii) Aluminium bus bar suitable size 3 Phase, 4 wire 600 Amp, 415 V\n(iv) Digital volt meter 0-500V with slector switch, Make-AE/L&T\n(v) Digital Amp meter 0-600 Amp with CT and selector switch, \nMake-AE/L&T\n(vi) Indicating lamp (Blue, Yellow & Red - 01 set) LED type \nMake-AE/L&T/Havells | | 1 | Each |
|---|
| 3 | 3 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 400 amps (03 Nos 400 Amps for Phase and 01 No 200 Amps for neutral) rated aluminium bus bar for neutral complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : Khetrapal Bn & Batra Bn. Note : The quoted rate shall be of all inclusive.\n(a) Incoming\n(i) MCCB 04 Pole 36 KA,415 Volts (Qty 01 No)\n(b) Out goings\n(i) MCCB 04 Pole 25 KA, 125 Amp, 415 Volts, (Qty - 03 Nos)\n(ii) MCCB 04 Pole 25 KA, 100 Amp, 415 Volts, (Qty - 03 Nos)\n(iii) Aluminium bus bar suitable size 3 Phase, 4 wire 1200 Amp, 415 V\n(iv) Digital volt meter 0-500V with slector switch, Make-AE/L&T\n(v) Digital Amp meter 0-1000 Amp with CT and selector switch, \nMake-AE/L&T\n(vi) Indicating lamp (Blue, Yellow & Red - 01 set) LED type \nMake-AE/L&T/Havells | | 2 | Each |
|---|
| 4 | 4 | Supply ,installation,commisioning and testing LT Feeder piller box outdoor type double door and single shutter from open including locking arrangement system made out of MS sheet of 3.00 mm CRCA sheet 0.6x0.6x0.3 Mtr and double door,canopy dust proof,bottom cable entry plate and gland for cable size 95/70/50/35/25/16/10 Sqmm 3.5 core suitable MS angle iron 40x40x5 mm with alluminium busbar rating capacity 400 Amps (03 Nos 400 Amps for phase & 01 No 200 Amps for neutral) system mounted on hygroscopic insulators bus bar connected with MCCB 04 Pole 36 KA 250 Amps,415 volt(as incomer) including powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : Batra Bn | | 1 | Each |
|---|
| 5 | 5 | Supply ,installation,commisioning and testing LT Feeder piller box outdoor type double door and single shutter from open including locking arrangement system made out of MS sheet of 3.00 mm CRCA sheet 0.6x0.6x0.3 Mtr and double door,canopy dust proof,bottom cable entry plate and gland for cable size 95/70/50/35/25/16/10 Sqmm 3.5 core suitable MS angle iron 40x40x5 mm with alluminium busbar rating capacity 200 Amps (03 Nos 200 Amps for phase & 01 No 100 Amps for neutral) system mounted on hygroscopic insulators bus bar including powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Batra Bn & Khetrapal Bn. | | 2 | Each |
|---|
| 6 | 6 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 400 amps (03 Nos 400 Amps for Phase and 01 No 200 Amps for neutral) rated aluminium bus bar for neutral complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : GC Mess. Note : The quoted rate shall be of all inclusive.\n(a) Incoming\n(i) MCCB 04 Pole 36 KA, 250Amp, 415 Volts (Qty 01 No)\n(b) Out goings\n(i) MCCB 04 Pole 25 KA, 125 Amp, 415 Volts, (Qty - 04 Nos)\n(ii) MCCB 04 Pole 25 KA, 100 Amp, 415 Volts, (Qty - 02 Nos)\n(iii) Aluminium bus bar suitable size 3 Phase, 4 wire 400 Amp, 415 V\n(iv) Digital volt meter 0-500V with slector switch, Make-AE/L&T\n(v) Digital Amp meter 0-400 Amp with CT and selector switch, \nMake-AE/L&T\n(vi) Indicating lamp (Blue, Yellow & Red - 01 set) LED type \nMake-AE/L&T/Havells | | 1 | Each |
|---|
| 7 | 7 | Supply ,installation,commisioning and testing LT Feeder piller box outdoor type double door and single shutter from open including locking arrangement system made out of MS sheet of 3.00 mm CRCA sheet 0.6x0.6x0.3 Mtr and double door,canopy dust proof,bottom cable entry plate and gland for cable size 95/70/50/35/25/16/10 Sqmm 3.5 core suitable MS angle iron 40x40x5 mm with alluminium busbar rating capacity 150 Amps (03 Nos 150 Amps for phase & 01 No 100 Amps for neutral) system mounted on hygroscopic insulators bus bar connected with MCCB 04 Pole 16 KA 100 Amps,415 volt(as incomer) including powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : Swimming Pool | | 1 | Each |
|---|
| 8 | 8 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 600 amps (03 Nos 600 Amps for Phase and 01 No 300 Amps for neutral) rated aluminium bus bar for neutral complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : Demo Coy. Note : The quoted rate shall be of all inclusive.\n(a) Incoming\n(i) MCCB 04 Pole 50 KA,400Amp, 415 Volts (Qty 01 No)\n(b) Out goings\n(i) MCCB 04 Pole 36 KA, 250 Amp, 415 Volts, (Qty - 02 Nos)\n(ii) MCCB 04 Pole 36 KA, 200 Amp, 415 Volts, (Qty - 04 Nos)\n(iii) MCCB 04 Pole 25 KA, 100 Amp, 415 Volts, (Qty - 02 Nos)\n(iv) Aluminium bus bar suitable size 3 Phase, 4 wire 600 Amp, 415 V\n(v) Digital volt meter 0-500V with slector switch, Make-AE/L&T\n(vi) Digital Amp meter 0-600 Amp with CT and selector switch, \nMake-AE/L&T\n(vii) Indicating lamp (Blue, Yellow & Red - 01 set) LED type \nMake-AE/L&T/Havells | | 1 | Each |
|---|
| 9 | 9 | Supply , installation ,fabrication, testing and commissioning LT Panel board,Factory made cubical type, Outdoor type, floor mounted, factory made out of 40mm x 40mmx4mm angle iron frame and 3 .15mm inner CRCA steel sheet side covers with front and back hinged doors with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof, powder coated including suitable rated aluminium bus bar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of 600 amps (03 Nos 600 Amps for Phase and 01 No 300 Amps for neutral) rated aluminium bus bar for neutral complete powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge. Location : GC Area. Note : The quoted rate shall be of all inclusive.\n(a) Incoming\n(i) MCCB 04 Pole 50 KA,400Amp, 415 Volts (Qty 01 No)\n(b) Out goings\n(i) MCCB 04 Pole 36 KA, 250 Amp, 415 Volts, (Qty - 02 Nos)\n(ii) MCCB 04 Pole 36 KA, 125 Amp, 415 Volts, (Qty - 04 Nos)\n(iii) Aluminium bus bar suitable size 3 Phase, 4 wire 600 Amp, 415 V\n(iv) Digital volt meter 0-500V with slector switch, Make-AE/L&T\n(v) Digital Amp meter 0-600 Amp with CT and selector switch, \nMake-AE/L&T\n(vi) Indicating lamp (Blue, Yellow & Red - 01 set) LED type \nMake-AE/L&T/Havells | | 2 | Each |
|---|
| 10 | 10 | Supply, installation,commisioning and testing LT feeder pillar box out door type double door and single shutter front open including locking arrangement system made out of MS sheet of 3.00 mm CRCA sheet of size 0.6x0.6x0.3 mtr and double door ,canopy,dust proof,bottom cable entry plate and gland for cable size95/70/50/25/16/10 sqmm 3.5 core suitable MS angle iron 40x40x5 mm with aluminium busbar size 800Amps system mounted on hygroscopic insulators bus bar including suitable nut, Bolt and Washer(16 Nos) , & including powder coated paint with and providing necessary foundation/plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland, thimbling and proper finshing as per existing surface complete all as specified and directed by Engr- in- Chanrge | | 4 | Each |
|---|
| 11 | 11 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 25 Sq mmx 4 Core complete all as specified and directed . | | 500 | RM |
|---|
| 12 | 12 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 35 Sq mmx 3.5 Core complete all as specified and directed . | | 400 | RM |
|---|
| 13 | 13 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 50 Sq mmx 3.5Core complete all as specified and directed . | | 400 | RM |
|---|
| 14 | 14 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 70 Sq mmx 3.5 Core complete all as specified and directed . | | 300 | RM |
|---|
| 15 | 15 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 95 Sq mmx 3.5 Core complete all as specified and directed . | | 200 | RM |
|---|
| 16 | 16 | Supply and laying in trenches /laid in floor/duct/drawn through conduit XLPE insulated,screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 120 Sq mmx 3.5 Core complete all as specified and directed . | | 125 | RM |
|---|
| 17 | 17 | Taking out unserviceable cable any type/size from trenches,pole, road,duct etc including necessary joints,U/S fittings and pipes etc complete all as directed. | | 1925 | RM |
|---|
| 18 | 18 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m deep and getting out in soft/loose soil complete all as specified and directed | | 438 | Cum |
|---|
| 19 | 19 | Returning, filling in, incfluding spreading, watering and well ramming in layers not exc 25 cm in soft/loose soil | | 135 | Cum |
|---|
| 20 | 20 | Removing suplus soil to a distance not exc 50m and depositing where directed at a level not exc 1.5 m above the starting point | | 303 | Cum |
|---|
| 21 | 21 | Material and labour for sand cushioning for under ground cable with locally available sand for protection of cable including spreading and consolidations complete all as specified and directed | | 131 | Cum |
|---|
| 22 | 22 | Supply and laying in trenches dry well burnt locally available sub Class \"B\" bricks over sand cushioning for pretection of cable complete all as specified and directed | | 13 | Per 1000 Nos |
|---|
| 23 | 23 | M&L Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground.(earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr. Below ground level connecting to GI Strip 25X4 mm dia size by means of bolts, check nuts and washers of GI and earth wire protected by provision of GI pipe light grade, 15 mm bore including provn of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded crushed stoned aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 25x25 x3mm with lughs 2 Nos and with 6mm dia MS bar handle made to shape, GI medium grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge plate, common salt and charcoal filling, test pont made out of phosphorous bronze with fixing arrangement, funnel, wiremesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 mtr, all as per electrical plate No 3 of SSR 2009 Part-I and connection all as specified and testing on completion. | | 20 | Each Set |
|---|
| 24 | 24 | M&L 50mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, complete all as specified and directed including clamps, nut bolts and washers incl taking down old pipe completed all as specified and directed | | 24 | RM |
|---|
| 25 | 25 | Boring under road and foot path for inserting 50mm bore GI tubing for drawing UG cable, complete all as per specified and directed | | 12 | RM |
|---|
| 26 | 26 | Material & Labour Cutting out concrete blocks, slabs,brick-work or stone masonry (in alternate course),forming toothings for and bonding new work in mortar into old work,including new materials entering old wall for PCC 1:2:4 type B1 using 20mm graded crushed stone aggregate as in complete finishing surfaces. | | 6 | Sqm |
|---|