Military Engineer Services-MES has published Repair Maint Of Electric Supply , Electrical Appliances And External Water Supply Line Incl Rectification Of Day To Day Complaints In Office , Guest House And Md Accn Of Pcda Office Complex , Pcda Colony And Guest House Jaipur Mil Stn Under Ge ( S ) . Submission Date for this Tender is 06-02-2021. Electrification Work Tenders in JAIPUR Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 30-Jan-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 06-02-2021 |
Name of Work: REPAIR & MAINT OF ELECTRIC SUPPLY, ELECTRICAL APPLIANCES AND EXTERNAL WATER SUPPLY LINE INCL RECTIFICATION OF DAY TO DAY COMPLAINTS IN OFFICE, GUEST HOUSE AND MD ACCN OF PCDA OFFICE COMPLEX, PCDA COLONY AND GUEST HOUSE AT JAIPUR MIL STN UNDER GE (S) JAIPUR | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down carefully aluminium Point wiring (light fan socket or power) complete fittings such as switches, ceiling rose, pendants fan regulators, tube light fittings etc and making good disturbed surfaces of wall floors etc. | 290 | Point | |
2 | 2 | M&L Point wiring using approved colour coding as per IS, with stranded copper conductor 1.5 Sq. mm (nominal area), single core, FRLS insulated, PVC insulated and unsheathed stranded cable 1100 volts grade, confirming to IS-694/ISI marked in and including PVC casing caping, medium grade, ISI marked, with mild steel sunken boxes with earth dolly zink coated and including mounting frame and over cover plate, including PVC insulated stranded copper conductor 1.5 Sqmm (nominal area) single core cable as earth continuity conductor to common earth and connected to earth dolly. | |||
3 | 2.01 | One light / fan / bell controlled by one, one way switch. | 140 | Point | |
4 | 2.02 | One 3 pin 5 Amp socket out let on the same board with other switches | 40 | Point | |
5 | 2.03 | One 5 Amp socket independent controlled by one, one way switch. | 50 | Point | |
6 | 3 | Description all as per item No 2 here in befor but with 1100 volts grade copper standard conductor cable of size 2.5Sqmm for 3 pin switch socket outlet15Amp independent board complete all as specified and directed by Engineer in charge . | 60 | Per\nPoint | |
7 | 4 | S&F switch, piano type 230/250 volts :- make: anchor/Cona/Plaza. | |||
8 | 4.01 | Single pole, one way 5 Amp rating | 210 | Each | |
9 | 4.02 | Single pole, one way 15 Amp rating | 60 | Each | |
10 | 4.03 | Bell push, one way 5 Amp rating | 20 | Each | |
11 | 5 | S&Fixing Socket outlet 3 pin 5 Amp 2 in 1 flush type, 230/250 Volts grade on top covers (catered in point wiring above) :- | 90 | Each | |
12 | 6 | S&Fixing Socket outlet 3 pin 15 Amp flush type, 230/250 Volts grade on top covers (catered in point wiring above) :- | 60 | Each | |
13 | 7 | M/L for Ceiling rose surface bakelite 65 mm x50 mm three terminal AC 230 volts flush type complete all as specified and directed by Engineer in charge | 90 | Each | |
14 | 8 | M & L Electric bell, A/C, 230 volts, single pole, Multi Musical type. | 20 | Each | |
15 | 9 | M/L for Ceiling fan regulator 100 watt electronic type suitable for 1200mm /1400mm weep complete all as specified and directed by Engineer in charge. | 60 | Each | |
16 | 10 | Supply & fix in repair T5 integrted batten LED Light fittings 1 x 20 W ,240 volt( size-4 feet/1136 mm) long life, surface/wall mounting IP 20, luminaire per watt (Minium) extruded alluminium housing with frosted PMMA diffuser with high brightness LEDs complete with all accessories pre-wired twin core twisted flexible copper conductor cable with suitable size. Make - C&S Cat No LTTB4F20WLED/Wor equivelent model in Bajaj/Wipro/ Philips/CG /Surya roshni | 225 | Each | |
17 | 11 | All as per item No 10 here in before, but LED light fitting 1 x 10 W ,240 volt( size-2 feet) \nMake - Siska Cat part No. SSK-ALB-10W or equivelent model in Bajaj/Wipro/ Philips | 40 | Each | |
18 | 12 | Supply & Fixing in repair Retro LED T-8 tubular lamp IP 20 linear LED T8 20 watt with extruded aluminium/ PC body and PC diffuser complete with inbuilt driver. Make - Crompton cat pt No- LTT8-20 or equivelent model in Bajaj/Havells/ Philips | 100 | Each | |
19 | 13 | Supply & Fixing in repair Decorative box type fitting,Blue coured end caps complete for Retro LED T-8 tubular lamp IP 20 complete. with all accessories pre-wired twin core twisted flexible copper conductor cable with suitable size. Make - Crompton cat pt No- DMLN1LT8-16 or equivelent model in Bajaj/Havells/ Philips | 100 | Each | |
20 | 14 | Supply & fix in repair LED surface downlighte Square ( Economy range ) 6500K/3000 K with electronic driver LED fittings 1 x 18 W complete with all accessories pre-wired twin core twisted flexible copper conductor cable with suitable size Make - Syska cat Pt No SSK-SDS-18W-N or equivelent model in Bajaj/Wipro/ Philips/Crompton | 10 | Each | |
21 | 15 | Supply & fixing in repair Energy saving new generation 10 W LED IP -65 Bulkhead energy efficient wall mounted made of dia cast aluminium wiht with opal diffuser complete with all accessories pre-wired twin core twisted flexible copper conductor cable with suitable size Make - Halonix Cat No HLBH-02-10CW 10W LED or equivelent model in Wipro/ Philips/Havells | 10 | Each | |
22 | 16 | Supply & fix in repair wall Bracket light asthetically designed with B22d & E27 lamp holder including 10W LED Lamp with all accessories pre-wired twin core twisted flexible copper conductor cable with suitable size. Make - Halonix cat Pt No- HLBW-01-B22 or equivelent model in Bajaj/ Philips/Syska | 40 | Each | |
23 | 17 | S&F in repair Fancy light fitting weather proof corrosion wall mounted opel colour decorative ovale shape engineering with pc cover suitable for1x9 w LED Bulb etc complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size.(Make ;- Bajaj or equivelent model inPhilips/crompton greaves | 25 | Each | |
24 | 18 | M & L in repair for LED Energy saving 60 watt fitting IP 66 flood light luminaire of pressure die cast aluminium housing with anodised Al reflector & enclosed with toughned glass including provision of fixing arrangement made out of MS flat 25x4 mm with suitable size nut,bolt and washer in existing pole/biulding including welding in pole /grouting work in wall complete all as specified and directed by Engr-in-Charge. \nMake- Halonix HLFLD-ML12-60CWL or equivalant in Phillips ,HAVELLS, SYSKA, C&G and Wipro | 10 | Each | |
25 | 19 | Supply and Fixing in repair security lights LED 45 W Energy saving & Environmental friendly long life versatile pressure die cast aluminium IP 66 LED Wall mounted Light Luminaries are made of die casted aluminium body and toughened glass cover for uniformlight spread cames LED technology of Britelite. including bracket made out of suitable size of GI medium grade tubing and fixed with clamps nuts and bolts, washer complete all as specified . Make- CG cat Pt No-LSTS-45-CDL-M or equivalant in HAVELLS ,Syska and Phillips | 15 | Each | |
26 | 20 | M&L in repair 2 tier LED garden light conical shape with top cover at bottom, round shape and top cover at top with pointed bolt opal finish glass made up of polycabonate body suitable for B-22 Base (retrofit) with 9 watt LED lamp complete all as per sample | 20 | Each | |
27 | 21 | M&Lin repair decorative LED Globe Gate light (Moon prismetic ) made up of high grade unbreakable poluycarbonate material suitable for B-22 Base (retrofit) with 14 watt LED lamp complete all as per sample Make : Havells Cat No LHFXBO1TN6F035 or equivalent make of C&S/Bajaj/Halonix. | 8 | Each | |
28 | 22 | Supply and fix in repair button holder insulated body with back plate for batten fittings all as specified and directed. Make-SSK & equivalanet in anchor/Cona/wall including 10 LED lamp complete | 50 | Each | |
29 | 23 | Supply & Fixing in repair LED Lumeno 10 W Bulb E27 WW Ball Lamp suitable for Lumen output 1020, (lm) complete Make- Havells cat pt No-LHLDEBHEMD8 X010 or equivelent model in Bajaj/Wipro/ Philips | 150 | Each | |
30 | 24 | Supply & fixing in repair LED Lumeno 15 W Bulb E27 WW Ball Lamp suitable for Lumen output 1380, (lm) complete Make- Havells cat pt No-LHLDEBHEMD8Z015 or equivelent model in Bajaj/Wipro/ Philips | 100 | Each | |
31 | 25 | Taking down of Old exiting U/S submain PVC insulated aluminium conductor wiring with PVC conduit. | 100 | RM | |
32 | 26 | M & L Sub main wiring with following sizes cable single multi stranded copper conductor FRLS PVC insulated but unsheathed cable 1100 volts grade drawn through existing PVC conduit/ duct/ trunking etc fixed on surfece of wall or ceiling all as per IS earth continuity conductor to common earth and connected to earth dolly. | |||
33 | 26.01 | Two run of 6 sqmm and one run of 6.0 sqmm cable. | 100 | RM | |
34 | 27 | S&F factory made, sheet distribution board, double door, protection class IP 42 suitable for mounting MCB/MCCB, confirming to IS-13032, IS-8623, BS-5484 with minumum 200 amps, copper bus bar of the under mentioned rating:- | |||
35 | 27.01 | SPN 4 way | 2 | Each | |
36 | 27.02 | SPN 12 way | 3 | Each | |
37 | 27.03 | SPN 8 way | 5 | Each | |
38 | 27.04 | TPN 4 ways | 4 | Each | |
39 | 28 | S&F MCB 10 KA , C series rupturing capacity of the under mentioned type and rating :- MAKE- Havells(Std)/Polycab/HPL/Havells/Legrand/L&T | |||
40 | 28.01 | SP 5 to 32 amps | 70 | Each | |
41 | 28.02 | SPN 32 to 63 amps. | 20 | Each | |
42 | 28.03 | TPN 32 to 63 amps. | 10 | Each | |
43 | 29 | S&F MCCB 4P 100 Amp, 25 KA rating HPL/ABB/Legrand/Havells /C & S | 4 | Each | |
44 | 30 | Supply and fix sheet metal enclosure complete with metallic plug and socket heavy duty moduler type 3 pin (2P + Earth), 32 amp rating single phase 240 volts complete with MCB SP 32 amp “C” series including taking down (Make : L&T/havells). | 4 | Each | |
45 | 31 | Earthing complete with galvanized steel plate electrode 60cmx60cmx 6.3mm thick buried directly in ground earth pit not less than 2.25 meter deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead GI strip 25x4mm by means of bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 5 of SSR Part-I connected to continuous earth wire on pole all as specified and testing on completion, including provision of earth wire protected by 40mm dia GI light grade protection pipe from test Point to main board and 20mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as directed at site. | 5 | Each | |
46 | 32 | S&F in reapir casing & caping with accessories for make some power point make: Tirupati/Plaza/Supreme/Richa. | 150 | RM | |
47 | 33 | S & F in reapir Plug top 3 pin 15 Amps, 230 Volt AC, ISI marked Make Anchor / Plaza | 40 | Each | |
48 | 34 | S & F in reapir Plug top for 3 pin 5 Amps, 230 Volt AC, ISI marked complete all as specified and directed. (Make Anchor / Plaza) | 20 | Each | |
49 | 35 | S&F in reapir Gang box for make power point make ISI Marked | 25 | Each | |
50 | 36 | S&F in reapir capacitor AC for 440 volts 50 Hz of capacity 2/2.5 Mfd incl PVC claimp connector etc.Make Bajaj/ | 100 | Each | |
51 | 37 | S& F in reapir LED rod 20 watt suitable for 40 watt FTL/ 20 watt LED fitting. Make- Bajaj,Syska,Crompton | 150 | Each | |
52 | 38 | S&F in reapir LED rod 10 watt suitable for 10 watt LED/20 watt FTL fitting Make - Wipro/ Bajaj/Philips. | 40 | Each | |
53 | 39 | Taking down old /defective fan (ceiling or exhaust ) from hook in wall and dismantling all parts of fans taking out old burnt copper winding of starter mortar and re-winding with superior quality super enamelled copper wire of existing gauge including varnishing of winding replacement and reassembling of all parts of fan including testing complete & refixing to existing hook or hole of following size of fan including painting of fan as per existing colour:- | |||
54 | 39.01 | Ceiling fan size 1200mm sweep. | 100 | Each | |
55 | 39.02 | Exhaust fan size 300 mm | 40 | Each | |
56 | 40 | Supply only ball bearing No 6201or equivalent size | 60 | Each | |
57 | 41 | Supply only ball bearing No 6202 or equivalent size | 40 | Each | |
58 | 42 | Supply only ball bearing No 6203 or equivalent size | 20 | Each | |
59 | 43 | Supply only ball bearing No 6204 or equivalent size | 30 | Each | |
60 | 44 | Dismantling/taking down unservisable air conditioner 1.5TR/2TR capacity window type from any place and install the AC at location at the proper repairand testing complete all as directed. | 3 | Each Job | |
61 | 45 | All as per serial item No. 44 here in before but AC 1.5/2 TR split type | 3 | Each Job | |
62 | 46 | M&L for servicing of 2TR/1.5TR capacity window type AC unit by cleaning with air pressure,tighting of bolts and nuts, arresting all leakages with necessary brazing/welding ensuring leak proof cleaning of condensor ,water line, checking of serviceability of fan ,motor ,compressor,relay ,capacitors thermostat,control circuit remote,sensor indicator electric circuits,replacing of unserviceable parts except compressor and charging of refrigerant gas and submit the report complete all as specified and as directed by Engr-in-charge. (Note : ( i) Replacement of compressor shall be measured and paid separately ( ii) Spare Parts required for replacement shall be measured separately under replacement items given here-in-after .( iii) (Gas will be measured and paid separately). | 7 | Each Job | |
63 | 47 | All as per serial item No 46 here in before but for AC 2TR/1.5TR capacity split type | 6 | Each Job | |
64 | 48 | M/L for disconnecting and removing U/S sealed compressor unit from 1.5 TR capacity window type AC including supply connecting with original sealed refrigeration compressor unit all as specified and as directed by Engr-in-charge(Make:- TECUMESH / KIRLOSKAR / CARRIER) | 2 | Each | |
65 | 49 | All as per serial item No 48 here in before but for AC 1.5TR capacity split type | 2 | Each | |
66 | 50 | All as per serial item No 48 here in before but for AC 2 TR capacity split type | 2 | Each | |
67 | 51 | Supply only Running capacitor 45 to 50 MFD 230 volts, 50 Hz for window/split Ac(Make : KELTRON / USHA / SIEMENS) | 8 | Each | |
68 | 52 | Supply only Starting capacitor 100 to 120 MFD 230 volts, 50 Hz for window/split Ac (Make : KELTRON / USHA / SIEMENS) | 8 | Each | |
69 | 53 | Supply only Box type relay suitable for Window type AC 1.5 ton capacity(Make : SRIRAM Model SR 1622 or equivalent of Ranutrol) | 3 | Each | |
70 | 54 | Supply only Thermostatic switch with knob suitable for window type AC 1.5 TR.(Make : INDFOS / RENUTRAL ) | 3 | Each | |
71 | 55 | Supply only Capacitor 4 MFD, 230 volts, 50 Hz(Make : KELTRON / USHA / SIEMENS) | 8 | Each | |
72 | 56 | Supply only Blower Motor, single phase 230 Volts 1500 RPM, suitable for 1.5 TR Window type Air Conditioner (Make : AUE / USHA) | 2 | Each | |
73 | 57 | Supply only Blower Motor, single phase 230 Volts 1500 RPM, suitable for 1.5 TR Split type Air Conditioner (Make : AUE / USHA) | 2 | Each | |
74 | 58 | Supply only Blower Motor, single phase 230 Volts 1500 RPM, suitable for 2 TR Split type Air Conditioner (Make : AUE / USHA) | 2 | Each | |
75 | 59 | Supply only gas Mafron-22 in sealed cylinders. (Cylinders shall be return after use). | 16 | Kg | |
76 | 60 | Supply only gas R-134 A in sealed cylinder. (Cylinders shall be return after use). | 6 | Kg | |
77 | 61 | Labor only for Gas Charging for AC 1.5/2 Ton and testing complete.(Gas will be paid and measured separately). | 8 | Each Job | |
78 | 62 | supply only remote complete for split type ACs 1.5 to 2 ton capacity including necessary testing of the equipment complete all as directed by the Engr in Charge . | 6 | Each | |
79 | 63 | Supply only PCB suitable for 1.5/ 2 ton split type AC,s of make LG/Carrier/Blue Star/Voltas/Fedder Lloyd | 5 | Each | |
80 | 64 | Supply only contactor suitable for Split type AC capacity 1.5/2.0 Make:-Carrier | 2 | Each | |
81 | 65 | Supply only fan blade suitable for out door unit of Split type AC capacity 1.5/2.0 Make:-Carrier/voltas | 2 | Each | |
82 | 66 | Supply only blower complete with fins suitable for in door unit of Split type AC capacity 1.5/2.0 Make:-Carrier/voltas | 2 | Each | |
83 | 67 | Disconnecting electrical connection and dismantling/ taking out indoor and out door unit of split type air conditioning of any make and capacity from any place and installation, commissioning and testing to another location including transportation from existing bldg to another bldg all as spacified and directed. | 2 | Each Job | |
84 | 68 | M & L for Supplying, laying, connecting and testing in trenches, under floors/ roads or on walls Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armored, electric power cables (heavy duty) ISI marked with stranded aluminium conductor, 1100 volts grade, of size 35 sqmm, 3.5 core . | 150 | RM | |
85 | 69 | All as per item No 68 but 10 sqmm 2 core | 200 | RM | |
86 | 70 | Excavation in trenches n.exc 1.5 metre wide and n.exc 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables errection of poles / struts/stays etc n.exe 10 Sqm on plan not exceeding 1.5 metre in depth and getting out in any type of soil.\nE/M - 76\nW/S - 15 | 91 | Cum | |
87 | 71 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm in any type of soil.\nE/M - 49\nW/S - 12 | 61 | Cum | |
88 | 72 | Removing of excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50metre above the starting point\nE/M - 27\nW/S - 03 | 30 | Cum | |
89 | 73 | M & L Sand cushioning to PVC under ground cable with screened and washed sand and punning to provide a required cover. | 23 | Cum | |
90 | 74 | M&L bricks for protection cover to under ground cable (with old size sub class `B` bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10 mm as directed by Engineer in-charge | 2 | Per 1000 Nos | |
91 | 75 | Repair of Desert Cooler- M & L for Repairs / Servicing of Desert cooler 4000 cum/hrs air flow capacity single phase 230 Volts of various make after disconnecting incoming and outgoing electric/water connection drain out water and carry out minor repair work such as repairing of internal worn out wires, motor ,Pump, Fan vicket, Lead wire , switch regulator , PVC Pipe Name plate , and replacement of unserviceable parts including testing complete all as specified and directed by Engr-in-charge (Note “ Spares required for Replacement shall be measured and paid separately as supply only in respective items) | 90 | Each Job | |
92 | 76 | Supply only wooden shelving pad for Desert cooler each set weighting not less than 500 grams all as directed of size 75 Cms x 60 Cms. | 90 | Each | |
93 | 77 | Supply only Front Grill Air Divertor of PVC with Selector Switch and 2 Nos. indicator for Desert Cooler 3500 / 5000 Cum/Hr | 40 | Each | |
94 | 78 | Supply only Fan vickret Blade PVC/iron body with nut Bolt washer for 4000 cum/Hr Desert Cooler of various makes all as per existing one all as specified and directed by Engr-in-charge Make:- KHAITAN / SUMMER KING | 35 | Each | |
95 | 79 | Supply only Fan motor for Desert cooler of various makes all as per existing one all as directed Make :- KHAITEN / SUMMER KING/Shakti | 50 | Each | |
96 | 80 | Supply only Submerssible Vertical pump with suitable head for Desert coolers all as spacified and directed. Make :- KHAITEN / SUMMER KING/Shakti | 70 | Each | |
97 | 81 | Supply only Desert Cooler Fan regulator for 4000 cum/Hr Desert Cooler capacity of various makes all as per existing one all as specified and directed by Engr-in-charge Make:- KHAITAN / SUMMER KING/Shakti | 30 | Each | |
98 | 82 | Supply only PVC Lead wire 1.5 sqmm stranded copper conductor 3 core ISI Marked all as specified and directed.Make : Finolux,Havells | 90 | RM | |
99 | 83 | Supply only PVC flexible pipe (from vertical pump to distributer and distributer to panele ) 15mm dia for Desert cooler including 3 way distributor junction tee set complete. | 60 | Each\nSet | |
100 | 84 | Supply only PVC pipe connection, both end screwed 18” long 15mm dia with brass nuts and neoprene washers for water cooler/ desert coolers complete all as specified and directed. | 40 | Each | |
101 | 85 | S & F Painting of Desert cooler with two coats of enamel paint after surface preparation including painting of alphabets 5 cm height, 5 cm thick not more than 50 Alphabets complete all as specified and directed. | 25 | Each | |
102 | 86 | S &F ceiling fan 1200 mm sweep complet 5 star rating with aerodynamic blades all as specified and directed including taking out U/s ceiling fan and removing from site. Make: kaitan/Usha/CG/Bajaj. | 30 | Each | |
103 | 87 | M & L for exhaust fan 300 mm sweep compete all as specifed and directed including taking out U/s exhaust fan and removing from site. Make: kaitan/Usha/CG/Bajaj | 20 | Each | |
104 | 88 | Supply and fix Louver made of galavnised iron 300 mm including fixing with suitable fastner complete all as specifed and directed including taking out U/s Louver and removal from site. | 20 | Each | |
105 | 89 | Supply and fix wall fans 400 mm sweep, copper motor, 50 watt, rated air delivery 70 CMM complete all aa specified and directed including taking out U/s wall fan and removal from site. Make Bajaj/Usha/Crompton/Khaitan. | 10 | Each | |
106 | 90 | S & Fix Water heater storage type, electrical supplied and installed complete of capacity 25 ltrs complete with provn of hold fastener of suitable size including drilling and fixing complete including taking out U/s wate heater and removal from site.. Make Bajaj, Crompton, Racold | 10 | Each | |
107 | 91 | Labour charges for attending and checking electrical fault as on requirement basis inluding minor rectification or identifying the major fault in OTM and Md accn of PCDA in their office complex and Ajay Meru complex all as directed by engineer-in charge.\nNote :- This job will not include labour charges for repalcement of unsv items. These items will be measured and paid as per the respective items of BOQ here in before.\n | 600 | Each JOb | |
108 | 92 | WATER SUPPLY\nM & L Taking out submersible pump set of Capacity 7.5 HP to 10 HP, 1/3 phase, 230/415 volts, 50Hz, AC supply along with column pipe of any size from the bore well after disconnecting electric connection, dismantling of pump and motor for repairing/ replacing defective parts as ordered, oiling, greasing as required and re-assembling and testing including replacing worn out nuts, bolts, washers complete and lowering the same after repairing and making electrical and delivery pipe connections complete all as specified and directed.\nNote : - (i) The spare part required for replacement shall be measured & paid for separately as supply only under item | 1 | Job | |
109 | 92.01 | Supply only, gun metal impeller with neck key, distance bush. | 1 | Each | |
110 | 92.02 | Supply only Shaft bush. | 4 | Each | |
111 | 92.03 | Cutting of burnt winding and rewinding the stator with supper enamelled copper wire of suitable size and class of insulation including insulation paper, sleeves, thimbles etc. | 1 | Job | |
112 | 93 | Replacement of following sizes existing sluice valves,class PN 1.6 of undermentioned type and size with cast iron body , non rising type and cast iron wheel head, both ends flanged, IS-14846 marked comlete with neoprene rubber gasket ,jointing material and incl nuts/bolts/washer of suitable size etc complete all as specified and directed including taking down old unsv :- | |||
113 | 93.01 | 80 mm bore | 1 | Each | |
114 | 93.02 | 100 mm bore | 1 | Each | |
115 | 94 | S&F in repair of 50 mm dia GI column pipe both side flanged Medium grade ISI marked ( Each of 6 m length) including taking out old corroded column pipe both side flanged complete all as specified and directed. \nMake; Tata/ Jindal/ Surya Prakash/Swattik Pipe Ltd (TT Swastik) | 3 | Each | |
116 | 95 | S & F submersible copper cable PVC insulated over all sheethed flat ISI marked of 1100 volts grade of 6 sqmm 3 core. (Make:- Finolex/L&T/Havells) including taking out old U/s cable. | 30 | RM | |
117 | 96 | M&L for leakage rectification by cutting of existing pipe and making threading for repair/ replacement of U/S fittings etc., pipe in short lengths (1 to 2 meter pipe) or addition / alteration of the following size. Replacement of of above GI pipe and including fittings like tee, Elbow/Sockets/Union/Nipple etc and making serviceable including necessary execavation as required complete all as specified and directed.\n | |||
118 | 96.01 | 15 mm bore of pipe | 6 | Each JOb | |
119 | 96.02 | 20 mm bore of pipe | 6 | Each JOb | |
120 | 96.03 | 25 mm bore of pipe | 5 | Each JOb | |
121 | 96.04 | 50 mm bore of pipe | 5 | Each JOb | |
122 | 96.05 | 80 mm bore of pipe | 2 | Each JOb | |
123 | 97 | M&L for galvanised steel tubes "medium grade " (ISI marked) with all fitting( ISI marked) and fixed complete to walls and ceilings or laid in floors/trenches and under road, complete all as specified and directed of the following sizes :-\nMake; Tata/ Jindal/ Surya Prakash/Swattik Pipe Ltd (TT Swastik) | |||
124 | 97.01 | 15 mm bore of pipe | 24 | RM | |
125 | 97.02 | 25 mm bore of pipe | 24 | RM | |
126 | 97.03 | 50 mm bore of pipe | 12 | RM | |
127 | 98 | Supply and fix in repair DOL starter,20HP(MU1) suitable for upto 20 HP 3 phase, 415 volts AC supply motor complete all as specified and directed. \n | 1 | Each | |
128 | 99 | Supply and fix in repair MCCB TPN 100 Amp , 415 volts, 50 Hz 25KA complete all as specified and directed. \nMake:- Legrand / L&T/Schneider / Havells india ltd /ABB/ SEIMENS | 1 | Each | |
129 | 100 | S & F in repair detachable joints suitable for CI/DI pipe complete with cast iron ring , rubber rings nut, bolts, excavation and earthwork, cutting of pipe etc of following sizes complete all as specified and directed .\n | |||
130 | 100.01 | 50 mm bore | 2 | Each Set | |
131 | 100.02 | 80 mm bore. | 2 | Each Set | |
132 | 101 | Dewatering of OH Tank cap 20000 Gln and cleaning by using bleaching powder first and then with the plain water complete all as specified and directed.\n | 1 | Job | |
133 | 102 | Labour only for checking the srviceability of the different spares/ component/ parts of the starter and motor pump set/ panel of any capacity at any site complete all as directed by Engr-in-charge | 2 | Each JOb | |
134 | 103 | Replacement of existing U/S level indicator for OH water tank/Underground sump . S&F electronic water level indicator operating on magnetic float system to indicate 4 levels of water in 6 mtr deep water tank including wiring from single phase power point complete with rain water guard on mounting housing recommended by manufature cable top to grround of tank (Approx 30 mtr) complete all as specified and directed Make delta Modle No DOP-B07S411 or new upgraded DOP-107CV | 1 | Each JOb | |
135 | 104 | M&L for gun metal gate valve/forged valve with iron wheel head, screwed both ends for jointing iron pipes, non rising, forged brass spindle class-1, IS778 marked of following sizes including taking down old unsv :- | |||
136 | 104.01 | 15mm dia | 4 | Each | |
137 | 104.02 | 20mm dia | 4 | Each | |
138 | 104.03 | 25mm dia | 2 | Each | |
139 | 104.04 | 50mm dia | 1 | Each |