Repair Maintenance Of Electrical Installation And Fans , Pump Sets , Wet Riser , Sub Stn . , Pumps , Dg Set , Ac Equipments And Central Ac Plant System At Aaa Govt . Hospital Delhi ( Sh Fixing Of Ac Drain Pipe Of Stac For Proper Drainage From Ou, Aaagh-Delhi
TDR : 26679207
Tender Notice
BOQ
Expired
Aaagh
Delhi
Repair Maintenance Of Electrical Installation And Fans , Pump Sets , Wet Riser , Sub Stn . , Pumps , Dg Set , Ac Equipments And Central Ac Plant System At Aaa Govt . Hospital Delhi ( Sh Fixing Of Ac Drain Pipe Of Stac For Proper Drainage From Ou
Name of Work : RMO EI & Fans, P/Sets,Wet Riser, Sub-Stn., Pumps, DG set, AC equipments & Central AC plant system at AAA Govt. Hospital Delhi (SH: Fixing of AC drain pipe of STAC for proper drainage from outlet of all AC's and Replacement of burnout fittings).
Sl.No.
Item Description
Item Code / Make
Quantity
Units
1
1
Supplying & fixing of 20mm dia CPVC heavy duty drain pipe for connection with suitable nipple / elbow etc. existing drain pipe of split type AC and window type AC to the existing header pipe provided horizontal / vertical to avoid dripping etc as reqd.
1
200
Mtr
2
2
Supplying & fixing of 20mm x 40mm dia reducer with one sided press to fit and other sided with thread matched with existing 40mm dia GI pipe etc as reqd.
2
60
Nos
3
3
P/F of 100mm x 50 mm size rigid PVC trunking with the help of rawl plug, steel screws i/c dressing etc complete as reqd.
3
150
Mtr
4
4
Supplying & fixing of 40mm dia CPVC heavy duty drain pipe for connection existing drain pipe of split type AC and window type AC provided horizontal / vertical to avoid dripping etc as reqd.
4
225
Mtr
5
5
Supplying, installation, testing & commissioning of energy efficient surface/recess mounted type 34W to 42W full window glare free PMMA diffuser LED panel luminaries of size 595mm x 595mm (nominal size) fabricated with MS powder coated white CRCA housing and connections with 3 x 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required including dismantling alongwith credit for worn out luminaries under buy back arrangement. The Total system Lumen of 34W to 42W LED should be minimum 3600 with minimum system efficacy of 100 lumen /watt colour temperature 5500K to 6500K, power factor>0.90, CRI (Ra)>75, THD <10%, with APFC driver having driver efficiency >85%, operating voltage 150-270 volts with minimum 2.5KV surge protection. The luminaries shall be submitted with LM-80 report with a life of 50000 Hours @ L-70 and LED photo biological safety report conforming to IEC 62471 & LED source manufacturer and LM-79 report from NABL accredited Lab. The LED chip should be of Cree, Nichia, Lumiled, Osram, Seoul. Dismantled material to be retianed by the contractor .
5
30
Nos
6
6
Supplying, installation, testing & commissioning of energy efficient surface/recess mounted type 34W to 42W full window glare free PMMA diffuser LED panel luminaries of size 300mm x 1200mm (nominal size) fabricated with MS powder coated white CRCA housing and connections with 3 x 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required including dismantling alongwith credit for worn out luminaries under buy back arrangement. The Total system Lumen of 34W to 42W LED should be minimum 3600 with minimum system efficacy of 100 lumen /watt colour temperature 5500K to 6500K, power factor>0.90, CRI (Ra)>75, THD <10%, with APFC driver having driver efficiency >85%, operating voltage 150-270 volts with minimum 2.5KV surge protection. The luminaries shall be submitted with LM-80 report with a life of 50000 Hours @ L-70 and LED photo biological safety report conforming to IEC 62471 & LED source manufacturer and LM-79 report from NABL accredited Lab. The LED chip should be of Cree, Nichia, Lumiled, Osram, Seoul. Dismantled material to be retianed by the contractor .
6
40
Nos
7
7
SITC of 70 W having IP 66 protection integral LED flood light fitting complete with all accssories on existing pole with suitable arrangement of fixing the same and dismantaling the existing non-functional/burnt out fitting and dismantled should be retained by the contractor i/c connection with 2.5 sqmm FRLS PVC insulated, copper conuctor, single core cable and earthing etc complete as reqd.