Military Engineer Services-MES has published Repair/Maintenance And Improvement To Earthing Of Ht/Lt Distribution System And Lightning Protection And Allied Works At Ahrr Under Ge E/M Rr Hospital Delhi Cantt10 Ca No Ge/H 36/2020-21. Submission Date for this Tender is 06-02-2021. Electrification Work Tenders in GE E/M RR HOSP DELHI CANTT 10 Delhi. Bidders can get complete Tender details and download the document.
Name of work: REPAIR/MAINTENANCE AND IMPROVEMENT TO EARTHING OF HT/LT DISTRIBUTION SYSTEM AND LIGHTNING PROTECTION AND ALLIED WORKS AT AHRR UNDER GE E/M RR HOSPITAL DELHI CANTT-10. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Dismantling of old u/s earthing complete with accessories all as directed | BI01010001010000000000000515BI0100001113 | 64 | Each |
2 | 2 | M & L Earthing complete with galvanized steel earth plate electrode 60cmx60cmx60cm thick buried directly in ground(earth) pit not less than 2.25 meter deep below normal ground level) with top edge of earth plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical palte No 3 of SSR Pt-I connected earthing test point/panel all as specified including GI PCC earth chamber using PCC(1:3:6) Type C-2 using, graded stone aggregate, 50mm thick cast iron frame with CI cover, funnel and wire in mesh excavation and earth work complete all as specified and directed. | BI01010001010000000000000515BI0100001114 | 6 | Each Set |
3 | 3 | M & L Earthing complete with galvanized steel earth plate electrode 60cmx60cmx60cm thick buried directly in ground(earth) pit not less than 2.25 meter deep below normal ground level) with top edge of earth plate not less than 1.5mtr below normal ground level connected to galvanized earth strip of size 25 mm x 4 mm by means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical palte No 3 of SSR Pt-I connected earthing test point/panel all as specified including PCC earth chamber using PCC(1:3:6) Type C-2 using, graded stone aggregate,50mm thick cast iron frame with CI cover, funne and wire in esh excavation and earth work complete all as specified and directed. | BI01010001010000000000000515BI0100001115 | 20 | Each Set |
4 | 4 | Earthing complete with copper plate 60×60cm ×3.15mm thick electrode, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 20×3 mm copper stripby means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical palte No 5 of SSR Pt-I connected earthing test point/panel all as specified including PCC earth chamber using PCC(1:3:6) Type C-2 using, graded stone aggregate,50mm thick cast iron frame with CI cover, funne and wire in esh excavation and earth work complete all as specified and directed | BI01010001010000000000000515BI0100001116 | 25 | Each set |
5 | 5 | M&L for Borewell Earthing by drilling 150mm bore hole with DTH bore machine and in any type of strata providing 50 mm dia medium duty GI pipe duly drilled all around 15mm dia hole at a distance of 200mm from hole to hole upto 30 meter depth and providing charcol/ salt mixture all around the pipe and connecting top edge of pipe with galvanised earth strip of size 32 x 6mm upto 7.5 meter upto test point including PCC earth chamber using PCC(1:3:6) Type C-2 using, graded stone aggregate,50mm thick cast iron frame with CI cover, funne and wire in esh excavation and earth work complete all as specified and directed,\nNote :- Quoted rated are deemed to included suitable size PCC pit RCC reinforced cover of suitable size and providing 150mm bore MS pipe medium grade upto 3 mtr depth from top level, Earth results should not be more than 1 (one ) Ohm. | BI01010001010000000000000515BI0100001117 | 6 | Each |
6 | 6 | M&L for Borewell Earthing by drilling 150mm bore hole with DTH bore machine and in any type of strata providing 50 mm dia medium duty GI pipe duly drilled all around 15mm dia hole at a distance of 200mm from hole to hole upto 25 meter depth and providing charcol/ salt mixture all around the pipe and connecting top edge of pipe with galvanised earth strip of size 32 x 6mm upto 7.5 meter upto test point, complete all as specified including PCC earth chamber using PCC(1:3:6) Type C-2 using, graded stone aggregate,50mm thick cast iron frame with CI cover, funne and wire in esh excavation and earth work complete all as specified and directed:- Quoted rated are deemed to include suitable size PCC pit RCC reinforced cover of suitable size and providing 6" dia MS pipe medium grade upto 3 mtr depth from top level, Earth results should not be more than 1 (one ) Ohm. | BI01010001010000000000000515BI0100001118 | 7 | Each |
7 | 7 | M& L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 20mmx3mm copper strip all as specified. | BI01010001010000000000000515BI0100001119 | 60 | RM |
8 | 8 | All as per item No 07 above but for aluminium strip of size 25mmx 3mm all specified. | BI01010001010000000000000515BI0100001120 | 120 | RM |
9 | 9 | M& L for Tubes, 'light grade' galvanised, with all fitting and fixed to walls and ceilings or laid in floor of size 40 mm bore complete all as specified. | BI01010001010000000000000515BI0100001121 | 30 | RM |
10 | 10 | Material & labour and fixing Copper Earth strip of size 32mmx6mm buried in ground fixed on poles/MS flat iron clamps of suitable size in trenches including necessary fixing arrangement such as fasteners, nut bolts and washer etc complete including dismantling of old unserviceable GI strip all as specified and directed by the Engineer-in-Charge | BI01010001010000000000000515BI0100001122 | 50 | RM |
11 | 11 | M& L for Tubes, 'medium grade' galvanised, with all fitting and fixed to walls and ceilings or laid in floor of size 40 mm bore all complete as specified. | BI01010001010000000000000515BI0100001123 | 10 | RM |
12 | 12 | Ditto all as per item ser Np 11 but for 32 mm bore | BI01010001010000000000000515BI0100001124 | 100 | RM |
13 | 13 | Ditto all as per item ser Np 11 but for 25 mm bore | BI01010001010000000000000515BI0100001125 | 150 | RM |
14 | 14 | Ditto all as per item ser Np 11 but for 20 mm bore | BI01010001010000000000000515BI0100001126 | 100 | RM |
15 | 15 | Ditto all as per item ser Np 11 but for 15 mm bore | BI01010001010000000000000515BI0100001127 | 60 | RM |
16 | 16 | M&L bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for 20 mm bore iron pipe or for brass ferrule and fixed all as speicifed | BI01010001010000000000000515BI0100001128 | 94 | Each |
17 | 17 | M&L for Gun-metal, globe or gate valves of 25 mm, with iron wheel head, screwed both ends for iron pipe and fixed all as specified | BI01010001010000000000000515BI0100001129 | 10 | Each |
18 | 18 | ditto all as per item Ser No 17 but for 32 mm dia | BI01010001010000000000000515BI0100001130 | 5 | Each |
19 | 19 | ditto all as per item Ser No 17 but for 40 mm dia | BI01010001010000000000000515BI0100001131 | 1 | Each |
20 | 20 | M& L for making PCC earth pit with suitable ratio including dismantling exting broken surface and fixing of CI cover fixed with iron frame all as specified. | BI01010001010000000000000515BI0100001132 | 15 | Each Job |
21 | 21 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75mmx75mmx25mm drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screw including necessary cutting and welding wk as directed by Engr In Charge | BI01010001010000000000000515BI0100001133 | 30 | Each |
22 | 22 | Dismantling of old unserviceable earthing strips of any description complete whereas directed by Engr In Charge | BI01010001010000000000000515BI0100001134 | 230 | RM |
23 | 23 | Excavation in trenches in soft / loose soil not exceeding 1.5 meter depth and not exceeding 1.5 meter wide and getting out complete all as directed. | BI01010001010000000000000515BI0100001135 | 27 | Cum |
24 | 24 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick complete all as directed. | BI01010001010000000000000515BI0100001136 | 12 | Cum |
25 | 25 | Removal of excavated material not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meter above the starting point complete all as directed. | BI01010001010000000000000515BI0100001137 | 15 | Cum |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy