Construction Of 02Nos . Of 33/11Kv 3 . 15Mva S/S ( Rural Type ) Jhamburi And Siwera And Associated 33Kv Line , 11Kv I/C Of 11Kv Feeders Under S/D Abu Road Rural And Sirohi Respectively , Division Abu Road And Sirohi , Circle Sirohi On Lrc-2020 Basis, Sirohi-Rajasthan

Jodhpur Vidyut Vitaran Nigam Limited has published Construction Of 02Nos . Of 33/11Kv 3 . 15Mva S/S ( Rural Type ) Jhamburi And Siwera And Associated 33Kv Line , 11Kv I/C Of 11Kv Feeders Under S/D Abu Road Rural And Sirohi Respectively , Division Abu Road And Sirohi , Circle Sirohi On Lrc-2020 Basis. Submission Date for this Tender is 27-01-2021. Feeder Pillar Tenders in Sirohi Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

26623759
Construction Of 02Nos . Of 33/11Kv 3 . 15Mva S/S ( Rural Type ) Jhamburi And Siwera And Associated 33Kv Line , 11Kv I/C Of 11Kv Feeders Under S/D Abu Road Rural And Sirohi Respectively , Division Abu Road And Sirohi , Circle Sirohi On Lrc-2020 Basis
Open Tender
Indian
Rajasthan
Sirohi
27-01-2021

Tender Details

Construction Of 02Nos . Of 33/11Kv 3 . 15Mva S/S ( Rural Type ) Jhamburi And Siwera And Associated 33Kv Line , 11Kv I/C Of 11Kv Feeders Under S/D Abu Road Rural And Sirohi Respectively , Division Abu Road And Sirohi , Circle Sirohi On Lrc-2020 Basis

Key Value

Document Fees
INR 2950 /-
EMD
Refer document
Tender Value
INR 29.15 Lakhs /-

BOQ Items

Name of Work: Construction of . 02 Nos. of 33/11 KV 3.15 MVA Sub-Station (Rural Type) Jhamburi and Siwera and associated 33 KV line , 11 KV inter connection of 11 KV Feeders under Sub-Divison Abu Road Rural and Sirohi respectively, Division Abu Road and Sirohi, Circle Sirohi on Labour rate basis
Sl. No. Item Description Item Code / Make Quantity Units
1 1 PART - (A):Construction of 02 No. of 33/11 Kv 3.15 MVA Sub-Station Jamburi and Siwera BI01010001010000000000000515BI0100001112
2 2 Grass cutting and surface dressing including removal of unwanted/rubbish plants with roots from open ground /yard and other Nigam premises with stacking of grass/plants at desired place near the ground. BI01010001010000000000000515BI0100001113 720 Sq. mtr.
3 3 ( 1.3 ) Levelling of ground BI01010001010000000000000515BI0100001114
4 4 Levelling of ground up to 30 cm.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting) BI01010001010000000000000515BI0100001115 720 Sq. mtr.
5 5 Levelling of ground above 30 cm.to 90 CM.depth. with tractor and T&P required as per condition of ground including removal of rubbish plants from ground & marking of boundary with lime powder.(Including all lead & lifting) BI01010001010000000000000515BI0100001116 720 Sq. mtr.
6 6 (2.1) Excavation of pit in soil (ordinary) to erect various supports and stay sets including stacking of excavated soil from the edge of excavation.(15 % extra shall be payble for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13) BI01010001010000000000000515BI0100001117
7 7 (A) Height of poles/R.S.Joist/M.S. Rail /Size of pit BI01010001010000000000000515BI0100001118
8 8 9 Mtr/ 1.2mx0.6mx1.50 m deep BI01010001010000000000000515BI0100001119 88 Pit
9 9 (2.5) Earth work excavation and foundation of platfrom of transformers and brakers including dressing of sides and ramming of bottoms .Liftup to 1.5 Meter including taking out the excavated soil and depositing and refilling of jhiri, watering and ramming and disposal of surplus excavated soil as directed with in a lead of 50 Meter. 01(PT) 05 (Brekr) BI01010001010000000000000515BI0100001120
10 10 Soft /loose soil BI01010001010000000000000515BI0100001121 102 Cum
11 11 Providing and laying cement concrete including compaction etc, complete using stone aggregate 40 mm nominal size (hand broken ) in foundation plinth excluding the cost of shuttering using 1 cement:5 sand:10 aggregate mix. Note: 1. The rates are all lead of cement,lime,ballast, sand,surkhi and grit etc.at site of work 2. For all concrete work coarse sand shall be used no extra will be paid 3. Concrete mix prepared by power driven mechanical mixer shall be used 4. Under exceptional coditions, where mechanical mixer and vibrator are not used(with the approval of Engineer Incharge reduced by 3% for mechanical mixer and 2% for Vibrator 5. Thickness of the cement concrete should not exceeed 100 mm BI01010001010000000000000515BI0100001122 56 Cum
12 12 Plaster on new surface on walls in cement ,sand mortar 1:6 including racking of joint etc. complete fine finsh 25 mm thick. Note: 1. The rates for complete work including racking of joints,curing,grinding,mixing and finishing T&P and scaffolding material and cost of material with all lead and lift 2. The rates cover protection of all place and things,requiring protection and cleaing such places and thing of all droppings and splashes of mortar etc 3. Cement concrete flooring grade 1:2:4 (1-cement :2- coarse sand :4-graded stone aggregate ) rounding off edges etc.but excluding cost of nosing of steps etc. complete BI01010001010000000000000515BI0100001123 176 Sq. M
13 13 (2.8) Cement concrete flooring grade 1:2:4 (1-cement :2- coarse sand :4-graded stone aggregate ) rounding off edges etc.but excluding cost of nosing of steps etc. complete BI01010001010000000000000515BI0100001124
14 14 75 mm thick with 20 mm thick nominal size aggregate. BI01010001010000000000000515BI0100001125 60 Sq. M
15 15 (2.11) Masonry for foundation and plinth BI01010001010000000000000515BI0100001126
16 16 Randon Rubble stone masonry for foundation and plinth in cement sand mortar 1:6(1 Cement : 6 Sand) including labour charges. BI01010001010000000000000515BI0100001127 40 Cum
17 17 (3.1) Safe carriage of PCC poles including loading / un-loading BI01010001010000000000000515BI0100001128
18 18 (a) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole BI01010001010000000000000515BI0100001129
19 19 Within 10 Kms. BI01010001010000000000000515BI0100001130 18 Pole
20 20 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001131 18 Pole
21 21 c) 9 Mtr.long 200 Kg. PCC pole BI01010001010000000000000515BI0100001132
22 22 Within 10 Kms. BI01010001010000000000000515BI0100001133 43 Pole
23 23 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001134 43 Pole
24 24 (3.2) Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site BI01010001010000000000000515BI0100001135
25 25 Within 10 Kms. BI01010001010000000000000515BI0100001136 33.23 MT
26 26 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001137 33.23 MT
27 27 (3.3) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. BI01010001010000000000000515BI0100001138
28 28 Within 10 Kms. BI01010001010000000000000515BI0100001139 2.8 MT
29 29 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001140 2.8 MT
30 30 (3.4) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site. BI01010001010000000000000515BI0100001141
31 31 Within 10 Kms. BI01010001010000000000000515BI0100001142 8.54 MT
32 32 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001143 8.54 MT
33 33 (3.5) Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading.from store to site (These charges will be 1.5 times for both sides ) BI01010001010000000000000515BI0100001144
34 34 b) 25 & 40 KVA BI01010001010000000000000515BI0100001145
35 35 Within 10 Kms. BI01010001010000000000000515BI0100001146 2 Nos.
36 36 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001147 2 Nos.
37 37 (3.12) Safe carriage of breakers/kiosks etc. including loading/ unloading and stacking in Nigam stores BI01010001010000000000000515BI0100001148
38 38 Within 10 Kms. BI01010001010000000000000515BI0100001149 9 Nos.
39 39 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001150 9 Nos.
40 40 (4.2) Safe loading of power/ distribution transformer. BI01010001010000000000000515BI0100001151
41 41 (A) 33/11 KV power transformer. BI01010001010000000000000515BI0100001152
42 42 Above 1.6 MVA & upto 3.15 MVA BI01010001010000000000000515BI0100001153 2 Nos.
43 43 (B) 11/.4 KV Distribution Transformer BI01010001010000000000000515BI0100001154
44 44 25 & 40 KVA BI01010001010000000000000515BI0100001155 2 Nos.
45 45 (4.3.1) Safe unloading of power/distribution transformers BI01010001010000000000000515BI0100001156
46 46 (A) 33/11 KV power transformer. BI01010001010000000000000515BI0100001157
47 47 Above 1.6 MVA & upto 3.15 MVA BI01010001010000000000000515BI0100001158 2 Nos.
48 48 (B) 11/.4 KV Distribution Transformer BI01010001010000000000000515BI0100001159
49 49 25 & 40 KVA BI01010001010000000000000515BI0100001160 2 Nos.
50 50 Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. BI01010001010000000000000515BI0100001161 60 Cum
51 51 Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station. BI01010001010000000000000515BI0100001162 8 MT
52 52 Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 nos .disc.& 1set of H/W) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001163 147 Nos.
53 53 Fixing of 33kv pin insulator with pins. BI01010001010000000000000515BI0100001164 52 Nos.
54 54 (6.16) Assembly. Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories completein all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001165
55 55 (B) G.O. switch . without earthing blade. BI01010001010000000000000515BI0100001166
56 56 33kv G.O.switch BI01010001010000000000000515BI0100001167 4 Set
57 57 11kv G.O.switch BI01010001010000000000000515BI0100001168 13 Set
58 58 (6.17) Assembly and installation of Horn Gap fuse set (set of 3nos) on erected structure as per design, complete in all respectwith post insulator including jumpering on both ends for connection with the system. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001169
59 59 33kv Horn Gap fuse set. BI01010001010000000000000515BI0100001170 2 Set
60 60 11kv Horn Gap fuse set. BI01010001010000000000000515BI0100001171 8 Set
61 61 (6.19) Installation of lightening arrestors on erected structure /support (1 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & boltswill be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, BI01010001010000000000000515BI0100001172
62 62 (A) Sub-station type BI01010001010000000000000515BI0100001173
63 63 33 KV L.A.(each) BI01010001010000000000000515BI0100001174 6 Set
64 64 11 KV L.A. .(each) BI01010001010000000000000515BI0100001175 24 Set
65 65 (6.20) Installation testing as per Nigams norm & commissioning of 11/.4 KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire /strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates, BI01010001010000000000000515BI0100001176
66 66 Above 25 KVA & up to 40 KVA BI01010001010000000000000515BI0100001177 2 Nos.
67 67 Installation of LT MCB (Distribution Box) on sub -station structure .The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates,including connection on both ends with suitable lugs duly crimped (lugs & cable will be supplied by Nigam) BI01010001010000000000000515BI0100001178 2 Nos.
68 68 Fixing of danger plates on supports/structure BI01010001010000000000000515BI0100001179 88 Nos.
69 69 Fixing of PG clamp of Dog /Racoon Conductor BI01010001010000000000000515BI0100001180 140 Nos.
70 70 Assembly,installation & commisioning of 11 KV Roaster switchs on erected structures with stting for accurate operation including fixing of allied accessories completed in all respect with post insulators and jumpering on both ends for connection with systm.The nuts & bolts will be supplied by contractor for which payment will be made as per prevailing Dicom store issue rates. BI01010001010000000000000515BI0100001181 8 Nos.
71 71 Three nos. Earthing of each 11/0.4 KV distribution transformer /sub-station with M.S.Rod 20mm dia 3 meter long and driving them into earth by mechanical means at a distance as per approved design & drawing & specification.The work includes flattening of top ends of M.S.rod drilling a hole of 9/16" dia.at flattened top and tightening of M.S.flat 50x6mm/25x3mm/(having 3 hole 2ends and 1mm middle) with nuts and bolts with M.S.rods top end hole.The flat will also be welded with M.S.rod.The end will be connected to equipments as under in sequence. BI01010001010000000000000515BI0100001182 6 Per Earthing
72 72 (8.3) Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.asunder: BI01010001010000000000000515BI0100001183
73 73 (8.3.1) Excavation of trench of 0.65Mtrs.depth and 0.5Mtr.width BI01010001010000000000000515BI0100001184
74 74 (a) Normal soil BI01010001010000000000000515BI0100001185 162.5 Cum
75 75 Laying of MS flat /MS rod in 0.65Mtr.deep excavated trench and welding of MS flat/rod continuosly with 100 mm overlaping for straight joint including coating of MS flat joints with molten bitumen and covering joint with bitumen impregnated tape to protect from rust. BI01010001010000000000000515BI0100001186 500 Mtr.
76 76 Shaping of MS flat for connecting the equipments with earthmesh .The work includes the welding of MS flat with equipments/structure and also with earth mesh.The work also includes coating of MS flat joint with molten bitumen and covering jointwith bitumen impregnated tape to protect from rust. BI01010001010000000000000515BI0100001187 200 Mtr.
77 77 (8.3.4) Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr.length as per design and requirment to be driven in earth by mechanical means and Providing & .fastening of suitable clampswith the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil: BI01010001010000000000000515BI0100001188
78 78 (a) Where drilling is not required BI01010001010000000000000515BI0100001189 34 Per Nos.
79 79 Filling of trench with available excavated muck in layers of 20cm (Max.)consolidating each deposited layer by ramming & watering with lead up to 50 Mtr, and lift up to 1.5 Mtr. BI01010001010000000000000515BI0100001190 300 R.Mtr
80 80 Pipe Earthing for Power Transformer at 33 / 11 KV S/S:- Supply & erection of earthing electrode shall consist of G.I. Pipe 100 mm,of 3 Mtr Length. The electrode shall be buried as far as practicable 3 meters below ground level. Wherever possible, earth electrodes shall be located as near the water tap, water drain or near down take pipe. Earth electrodes shall not be installed in proximity to a metal fence. It shall be kept clear of the buildings foundations and in no case it shall be nearer than 2 meters from the outer face of the wall. The electrode shall be surrounded with layer of charcoal dust and salt mixture through out the length. The 100 mm GI pipe shall be provided with holes of 12 mm dia. drilled at 75 mm interval upto 2.5 meters length from bottom. The top of the pipe shall be provided with a G.I. threaded cap for watering the earth through a pipe. A Clamp with Pati of 12" of M.S. Flat of size 50X6 mm shall be fixed (Bolted) on the top edge of the pipe which in turn shall be connected to Neutral / Body of the Power Transformer through M.S. Flat size 50X6 mm. The G.I. cap over the GI pipe shall be housed in a masonry chamber, approximately 300 mm x 300 mm x 300 mm deep. The masonry chamber shall be provided with a RCC inspection cover resting over a RCC frame, embedded in masonry. BI01010001010000000000000515BI0100001191 4 Per Earthing
81 81 (10.2) Erection of PCC poles in excavated pit in alignment after checking the same with plumb line as per approved design & drawing of 33/11kv sub-station.The pit should be back filled with the soil with proper ramming below 30cm ground level and then muffed above 15cm average ground level with cement concrete ratio1:3:6.The charges for muffing will be paid extra as per chapter code no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made at the prevailing store issue rates. BI01010001010000000000000515BI0100001192
82 82 (B) In rural area BI01010001010000000000000515BI0100001193
83 83 PCC Poles 9 Mtr. Long BI01010001010000000000000515BI0100001194 61 Nos.
84 84 (10.3) Laying / stringing of bus bar with ACSR Dog & jumper connection using tie rod ,33KV /11KV insulator strings,required hardware,P.G.clamps/T clamps etc.as per requirement including Y-connections at bus bar jumpering point as per the direction of engineer in-charge. BI01010001010000000000000515BI0100001195
85 85 ACSR DOG/RABBIT BI01010001010000000000000515BI0100001196 1000 Mtr.
86 86 (11.1) Erection of OCB/Kiosk/VCB complete with accessories including use of special tools & conducting all pre-commissioning test before energization,filling oil etc. complete in all respect with erection & grouting of structure (excluding civil works). The relays will be tested by Discom. BI01010001010000000000000515BI0100001197
87 87 11 KV VCB (Outdoor ) BI01010001010000000000000515BI0100001198 9 Nos.
88 88 (11.12) Installation of metering points on 11 KV Out going feeder at 33/11 KV S/S. BI01010001010000000000000515BI0100001199 9 Nos.
89 89 The installation work to be carried out as per drawing/design, under the supervision of concerned Assistant Engineer BI01010001010000000000000515BI0100001200
90 90 (a) Mounting structure BI01010001010000000000000515BI0100001201
91 91 The requisite steel members will be supplied by contractor including the hardware. Contractor shall joint/weld the members to form the mounting structure as per drawing. Necessary tools, welding, machines, lifting devices etc. shall be arranged by contractor. BI01010001010000000000000515BI0100001202
92 92 (b) Civil works BI01010001010000000000000515BI0100001203
93 93 Erection of lattices in alignment including excavation and concreting of structure foundation including cement, sand and grit 20 mm size (crusher broken) having ratio 1:3:6 and grit 40 mm size for ratio 1:5:10 and curing for period as required (21 days). Area of concreting will be as per the drawing. BI01010001010000000000000515BI0100001204
94 94 ( c ) Metering Equipments: BI01010001010000000000000515BI0100001205
95 95 The requisite metering equipments (CTPT set, meter,meter box & suitable conductors for jumpers), will be provided by the concerned Assistant Engineer in healthy condition at site. The cables from CTPT set to meter box laid down in 50 mm GI pipe with suitable bends & nipples, shall be provided by contractor alongwith the consumable items such as PVC tapes, petroleum jelly etc. The cable should be PVC multi strand copper 4 core 2.5/4 Sq. mm ISI marked and firm & tight connections shall be made by suitable connector e.g. at CTPT sets by using clamps and at meter/TTB by suitable lugs etc. The CTPT sets so installed shall be earthed by means of the MS Flat (size 50x6 mm) by joining it with the nearest earthing available at the sub-station. Requisite earthing material shall be made available by the contractor. BI01010001010000000000000515BI0100001206
96 96 (d) Meter: BI01010001010000000000000515BI0100001207
97 97 Meters should be fixed firmly inside the tamper proof box, as per drawing. All the meter fixture will be provided by contractor including all consumables. BI01010001010000000000000515BI0100001208
98 98 (e) Meter Box BI01010001010000000000000515BI0100001209
99 99 The meter box shall be provided by the concerned Assistant Engineer. However, hardware or any other items required to fix the meter inside the meter box will be provided by contractor. The meter box will be fixed firmly with sufficient strength at a place as per drawing. The test terminal block(TTB) link type shall be provided by contractor in the meter box. BI01010001010000000000000515BI0100001210
100 100 (f) Painting: BI01010001010000000000000515BI0100001211
101 101 All surfaces interior and exterior of lattice structure shall be white aluminum painted. BI01010001010000000000000515BI0100001212
102 102 (g) Commissioning of Metering Equipments: BI01010001010000000000000515BI0100001213
103 103 Installed meters inside the box and metering equipments duly mounted on the mounting structure will be powered up by connecting load in the presence of the concerned Assistant Engineer who will arrange the necessary shut down. The completion certificate shall be furnised by contractor.be filled accordingly. Since the work involves higher A.C. voltage level, the contractor shall take full care regarding safety norms, so as to avoid any accidental hazards. BI01010001010000000000000515BI0100001214
104 104 Safe Loading of new/old 11 KV CT PT sets (all sizes) BI01010001010000000000000515BI0100001215 9 Set
105 105 Safe unloading of new /old 11 KV CT PT set (all sizes ) BI01010001010000000000000515BI0100001216 9 Set
106 106 (24.6)Transportation of 33 KV or 11 KV CT/PT/CTPT Set (All sizes)for replacement at 33/11 KV S/S along with their loading & unloading.. BI01010001010000000000000515BI0100001217
107 107 33 KV or 11 KV CT/PT/ CTPT set BI01010001010000000000000515BI0100001218
108 108 a) Within 10 Kms BI01010001010000000000000515BI0100001219 9 Nos.
109 109 b) Above 10 Kms & upto 30 Kms .Add for each Km or part thereof BI01010001010000000000000515BI0100001220 9 Nos.
110 110 (25(B)) Installation, testing as per Nigam norms and commissioning of new CT/PT set on erected supports including jumpering wiring crimping of lugs clamping earth connection of body and conducting pre commissioning test before energisation and satisfactory operation in all respect. CTPT set shall be provided by Nigam from concern sub-div stores. BI01010001010000000000000515BI0100001221 9 Nos.
111 111 PART - (B): Erection of 33KV line for 33/11KV S/S Jamburi and Siwera (29+7.40)KM BI01010001010000000000000515BI0100001222
112 112 Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. BI01010001010000000000000515BI0100001223 36.4 Km
113 113 Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line. BI01010001010000000000000515BI0100001224 182 Per tree/plant
114 114 (2.1) Excavation of pit in soil (ordinary) to erect various supports and stay sets including stacking of excavated soil from the edge of excavation.(15 % extra shall be payble for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13) BI01010001010000000000000515BI0100001225
115 115 (A) Height of poles/R.S.Joist/M.S. Rail /Size of pit BI01010001010000000000000515BI0100001226
116 116 9 Mtr/ 1.2mx0.6mx1.50 m deep BI01010001010000000000000515BI0100001227 544 Pit
117 117 (B) Lattice Tower /Size of pit BI01010001010000000000000515BI0100001228
118 118 11.4/10.8 Mtr/ 1.5mx1.5m x1.80 m deep BI01010001010000000000000515BI0100001229 38 Pit
119 119 (C) Stay set/Depth of pit BI01010001010000000000000515BI0100001230
120 120 8'x 3/4" -0.75x0.5x1.6 m BI01010001010000000000000515BI0100001231 1 Pit
121 121 (2.4) Excavation of pit in ordinary rock which does not require blasting/murrad (In Jodhpur Discom) to erect various supports and stay sets including stacking of excavated muck from the edge of excavation/pit. BI01010001010000000000000515BI0100001232
122 122 (A) Height of poles/R.S.Joist/M.S. Rail /Size of pit BI01010001010000000000000515BI0100001233
123 123 9 Mtr/ 1.2mx0.6mx1.50 m deep BI01010001010000000000000515BI0100001234 182 Pit
124 124 (B) Lattice Tower /Size of pit BI01010001010000000000000515BI0100001235
125 125 11.4/10.8 Mtr/ 1.5mx1.5m x1.80 m deep BI01010001010000000000000515BI0100001236 13 Pit
126 126 (C) Stay set/Depth of pit BI01010001010000000000000515BI0100001237
127 127 8'x 3/4" -0.75x0.5x1.6 m BI01010001010000000000000515BI0100001238 1 Pit
128 128 (3.1) Safe carriage of PCC poles including loading / un-loading BI01010001010000000000000515BI0100001239
129 129 A) 9/10/11 Mtr. Long-400 Kg /11 Mtr. PCC pole BI01010001010000000000000515BI0100001240
130 130 Within 10 Kms. BI01010001010000000000000515BI0100001241 726 Pole
131 131 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001242 726 Pole
132 132 (3.2) Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site BI01010001010000000000000515BI0100001243
133 133 Within 10 Kms. BI01010001010000000000000515BI0100001244 343.48 MT
134 134 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001245 343.48 MT
135 135 (3.3) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. BI01010001010000000000000515BI0100001246
136 136 Within 10 Kms. BI01010001010000000000000515BI0100001247 26.93 MT
137 137 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001248 26.93 MT
138 138 (3.4) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site. BI01010001010000000000000515BI0100001249
139 139 Within 10 Kms. BI01010001010000000000000515BI0100001250 20.243 MT
140 140 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001251 20.243 MT
141 141 (5.1) Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. BI01010001010000000000000515BI0100001252
142 142 Lattice Structure BI01010001010000000000000515BI0100001253 20.243 MT
143 143 (5.2) Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates. BI01010001010000000000000515BI0100001254
144 144 (B) Rural Area BI01010001010000000000000515BI0100001255
145 145 PCC Poles 9 Mtr. Long (400 Kg) BI01010001010000000000000515BI0100001256 584 Nos.
146 146 (5.3) Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates. BI01010001010000000000000515BI0100001257
147 147 PCC Poles 9 Mtr. Long(400 Kg.)/11Mtr.long BI01010001010000000000000515BI0100001258 142 Nos.
148 148 (5.4) Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire BI01010001010000000000000515BI0100001259
149 149 8"x3/4" with 7/8 SWG stay wire BI01010001010000000000000515BI0100001260 640 Nos.
150 150 Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base. BI01010001010000000000000515BI0100001261 5.184 CUM
151 151 Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station. BI01010001010000000000000515BI0100001262 1.9 MT.
152 152 Fixing of 11kv B&S/T&C type disc insulator for 33kv lines (each unit consiting of 3 nos .disc.& 1set of H/W) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001263 1566 Nos.
153 153 Fixing of 33kv pin insulator with pins. BI01010001010000000000000515BI0100001264 2163 Nos.
154 154 Fixing of danger plates on supports/structure BI01010001010000000000000515BI0100001265 106 Nos.
155 155 Fixing of PG clamp of Dog /Racoon Conductor BI01010001010000000000000515BI0100001266 51 Nos.
156 156 (7.1) Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. BI01010001010000000000000515BI0100001267
157 157 (B) In rural area BI01010001010000000000000515BI0100001268
158 158 ACSR DOG BI01010001010000000000000515BI0100001269 110.8 Km/cond.
159 159 (7.3) Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001270
160 160 (B) In rural area BI01010001010000000000000515BI0100001271
161 161 G.I.Earth wire 6 SWG BI01010001010000000000000515BI0100001272 6.49 Km/wire
162 162 (7.4) Drawing & stringing of G.I. 4 wire over the guarding bracket for guarding of road crossing /P&T crossing /Railway track crossing (for one span only)with cross G.I.wire laces at an interval of two meter each or required as per location using EYE bolt, nuts and bolts with washers etc.including binding .The EYE bolts and other nuts and bolts will be provided by thecontractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001273
163 163 (B) For 4 wire stringing BI01010001010000000000000515BI0100001274
164 164 6 SWG with laces of 8 SWG BI01010001010000000000000515BI0100001275 1 Span
165 165 (7.5)Fixing of G.I. Laces on Guard wire at an interval of one meter each or required as per location using EYE bolt ,nuts and bolts with washers etc.including binding,if required .The EYE bolts and other nuts and bolts will be provided by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001276
166 166 For 2 Guard wire BI01010001010000000000000515BI0100001277 1 Nos./laces
167 167 Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discomstore issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom) BI01010001010000000000000515BI0100001278 34 Nos.
168 168 (15.23)Fixing of extension pieces/ brackets for raising of pole height including fixing of pin insulators with pins & rebinding etc. BI01010001010000000000000515BI0100001279
169 169 33 KV line BI01010001010000000000000515BI0100001280 1 Nos.
170 170 PART - (C): Erection of 11KV inter connection of 11KV feeder (0.12+7.1) Km for 33/11KV S/S Jambudi and Siwera BI01010001010000000000000515BI0100001281
171 171 Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations. BI01010001010000000000000515BI0100001282 7.22 Km
172 172 Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line. BI01010001010000000000000515BI0100001283 36 Per tree/plant
173 173 (2.1) Excavation of pit in soil (ordinary) to erect various supports and stay sets including stacking of excavated soil from the edge of excavation.(15 % extra shall be payble for the designated desert area panchayat samities of Jodhpur Discom in pursuance to JdVVNL order No. 1240 dt. 18.07.13) BI01010001010000000000000515BI0100001284
174 174 (A) Height of poles/R.S.Joist/M.S. Rail /Size of pit BI01010001010000000000000515BI0100001285
175 175 9 Mtr/ 1.2mx0.6mx1.50 m deep BI01010001010000000000000515BI0100001286 109 Pit
176 176 (C) Stay set/Depth of pit BI01010001010000000000000515BI0100001287
177 177 6'x 5/8" -0.75x0.5x1.35 m BI01010001010000000000000515BI0100001288 42 Pit
178 178 (2.2)Excavation of pit in Hard Soil BI01010001010000000000000515BI0100001289
179 179 (A) Height of poles/R.S.Joist/M.S. Rail /Size of pit BI01010001010000000000000515BI0100001290
180 180 9 Mtr/ 1.2mx0.6mx1.50 m deep BI01010001010000000000000515BI0100001291 37 Pit
181 181 (C) Stay set/Depth of pit BI01010001010000000000000515BI0100001292
182 182 6'x 5/8" -0.75x0.5x1.35 m BI01010001010000000000000515BI0100001293 14 Pit
183 183 (3.1) Safe carriage of PCC poles including loading / un-loading BI01010001010000000000000515BI0100001294
184 184 c) 9 Mtr.long 200 Kg. PCC pole BI01010001010000000000000515BI0100001295
185 185 Within 10 Kms. BI01010001010000000000000515BI0100001296 146 Pole
186 186 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001297 146 Pole
187 187 (3.2) Safe carriage of steel( fabricated and unfabricated) I.e.M.S. Rails, R.S.Joists, M.S.Channels, M.S.Angles, M.S.Flat, G.I.Stay Sets, G.I. Stay Wire, G.I.Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site BI01010001010000000000000515BI0100001298
188 188 Within 10 Kms. BI01010001010000000000000515BI0100001299 7.16 M.T.
189 189 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001300 7.16 M.T.
190 190 (3.3) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc. BI01010001010000000000000515BI0100001301
191 191 Within 10 Kms. BI01010001010000000000000515BI0100001302 1.22 M.T.
192 192 Above 10 Km. & upto 30 Km. add for each Km. or part thereof BI01010001010000000000000515BI0100001303 1.22 M.T.
193 193 (5.2) Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates. BI01010001010000000000000515BI0100001304
194 194 (B) Rural Area BI01010001010000000000000515BI0100001305
195 195 PCC Poles 9 Mtr. Long(400Kg.) BI01010001010000000000000515BI0100001306 1 Nos.
196 196 PCC Poles 9 Mtr. Long(200Kg.) BI01010001010000000000000515BI0100001307 134 Nos.
197 197 (5.3) Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates. BI01010001010000000000000515BI0100001308
198 198 PCC Poles 9 Mtr. Long(200 Kg.) BI01010001010000000000000515BI0100001309 12 Nos.
199 199 (5.4) Erection & fixing of G.I.Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming.The work includes fixing of stay clamps.Stay insulator with stay wire at both ends with proper tension.Size of stay set/stay wire BI01010001010000000000000515BI0100001310
200 200 6"x5/8" with 7/10 SWG stay wire BI01010001010000000000000515BI0100001311 56 Nos.
201 201 (6.7) Fixing and assembly of disc.point channel pair with pilot plates&clamps on erected double pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001312
202 202 11 KV line BI01010001010000000000000515BI0100001313 6 Nos.
203 203 Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 1nos.disc.& 1set of H/ W ) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001314 102 Nos.
204 204 Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 2 nos.disc.& 1set of H/ W ) on terminal point including fixing of hardware and strips. BI01010001010000000000000515BI0100001315 102 Nos.
205 205 Fixing of 11 KV pin insulator with pins. BI01010001010000000000000515BI0100001316 318 Nos.
206 206 Fixing of danger plates on supports/structure BI01010001010000000000000515BI0100001317 24 Nos.
207 207 (7.1) Laying ,jointing , stringing, tensioning and clamping of conductor with proper sag as directed , using bolted type hardware including binding on pin insulators,jumpering on section points with binding wire / P.G.clamps.Aluminium jointing sleeves will be used for jointing the conductor.The line must stand at proper voltage on charging.The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate. BI01010001010000000000000515BI0100001318
208 208 (B) In rural area BI01010001010000000000000515BI0100001319
209 209 ACSR WEASEL BI01010001010000000000000515BI0100001320 21.69 Km/cond
210 210 (7.3) Laying , jointing,stringing,tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc.including proper binding at each end.The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates. BI01010001010000000000000515BI0100001321
211 211 (B) In rural area BI01010001010000000000000515BI0100001322
212 212 G.I.Earth wire 8 SWG BI01010001010000000000000515BI0100001323 6.49 Km/wire
213 213 Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod 20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discom store issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom) BI01010001010000000000000515BI0100001324 26 Nos.
214 214 Note-1.Dismentaling, if any: Dismentaling charges for all the items will be 60% of item rates of erection charges. However, charges for transportation of the material from works site in the Nigam/sub division store shall be paid as item rate of that material(Chapter-III, Transportation of material). The payment will be made after issuance of certificate by Engineer In Charge that all the dismentaled material has been safely received in the Nigam/sub division store Note-2. The nut & bolts will be provided/supplied by the contractor which will confirm to relevant ISS & payment will be made as per prevailing Discom store issue rate. Note-3. The quality of material supplied by the contractor be got checked & approved by the circle SE. Note-4. In case of pole upper end of the GI wire provided for earthing shall be bolted with cross arm. Note-5. The qty mentioned for normal soil/ordinary rock. Hard soil which does not required drilling and Hard Rock/ CC road which required drilling are tentative & shall be payble as per actual site condition and due verification by Engineer In Charge. Note-6. Safe Carriage of PCC poles/other material including Loading/un-loading as per actual distance of work-site from place of lifting & shall be payble as per actual distance and due verification by Engineer In Charge.. BI01010001010000000000000515BI0100001325