Chandigarh Administration Engineering Department has published Maintenance Of Electrical Installation In Non Residential Building At Chandigarh ( Repair/ Servicing Of Ht , Vcb , Lt Acb And Servicing Of Transformer In Various Sub Stations In The Jurisdiction Of Sde E-6 , Chandigarh ) .. Submission Date for this Tender is 21-01-2021. Electrical Maintenance Tenders in Chandigarh Chandigarh. Bidders can get complete Tender details and download the document.
Name of Work:-MTC. OF E.I. IN NON RESIDENTIAL BUILDING AT CHANDIGARH (REPAIR/ SERVICING OF HT VCB, LT ACB AND SERVICING OF TRANSFORMER IN VARIOUS SUB STATION IN THE JURISDICTION OF SDE E-6, CHANDIGARH). | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | DSR Item No. 9.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | |||
2 | 1.01 | 3½ X 35 sq. mm (32mm) | 1 | Each | |
3 | 1.02 | 3½ X 50 sq. mm (35mm) | 1 | Each | |
4 | 1.03 | 3½ X 70 sq. mm (38mm) | 1 | Each | |
5 | 1.04 | 3½ X 95 sq. mm (45mm) | 1 | Each | |
6 | 1.05 | 3½ X 185 sq. mm (57mm) | 1 | Each | |
7 | 1.06 | 3½ X 240 sq. mm (62mm) | 1 | Each | |
8 | 1.07 | 3½ X 400 sq. mm (82mm) | 1 | Each | |
9 | 2 | DSR Item No.9.3Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | |||
10 | 2.01 | 3½ X 35 sq. mm | 1 | Each | |
11 | 2.02 | 3½ X 50 sq. mm | 1 | Each | |
12 | 2.03 | 3½ X 70 sq. mm | 1 | Each | |
13 | 2.04 | 3½ X 95 sq. mm | 1 | Each | |
14 | 2.05 | 3½ X 185 sq. mm | 1 | Each | |
15 | 2.06 | 3½ X 240 sq. mm | 1 | Each | |
16 | 2.07 | 3½ X 400 sq. mm | 1 | Each | |
17 | 3 | DSR Item No.10.3Supplying and making straight through cable jointing with castresin compound, including ferrule and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : | |||
18 | 3.01 | 50/ 70 sq. mm | 2 | Each | |
19 | 4 | DSR Item No.10.4Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : | |||
20 | 4.01 | 50/ 70 sq. mm | 2 | Each | |
21 | 5 | Repair and servicing of HT-OCB’s / VCB’s of 400 Amps. to 800 Amp. 350 MVA of various types of make. The job includes the dismantling of OCB’s/ VCB’s & reinstallation of the same in the control panel unit. The cost also includes cleaning the 11KV contacts of HT OCB/ VCB, Lubrication of movable parts of mechanism of the panel units, replacements of minor pars during the servicing job being done at site. The job also includes servicing & the cost of minor parts & other petty material required to complete the job i.e. OCB shunt trip coil, mechanism greasing etc. The job includes the guarantee. | 4 | Each | |
22 | 6 | Repairing & Servicing of various type of ACB’s of various ratio from 630 A to 1600 Amp. of various types of make. The job includes dismantling of ACB’s from L.T. panel, re-installation of the same after servicing in the LT control panel unit. The cost also includes lubrication of movable parts, replacement of minor parts during the serving job being done at site. The job includes doing the repair of U/V coil, Shunt coil etc. | |||
23 | 6.01 | Servicing of LT ACB’s 1000/1250 Amp | 5 | Each | |
24 | 7 | Supply and filling of transformer oil (Dehydrate oil) in the existing transformer. The job includes the cost of all petty material require to complete the job. | 500 | per Ltr | |
25 | 8 | Dehydration of Transformer oil. The job includes the cost of labour and material required to complete the job. | 1800 | per Ltr | |
26 | 9 | Drain out of transformer oil, opening of transformer part and replacement of gasket, oil seal and silica zel, breather of 800 KVA / 1000 KVA transformer to stop of the leakage of oil as required at site, refilling of oil after complete the job to the entire satisfaction of Engineer-in-charge. | 1 | Each Job | |
27 | 10 | S/E rubber mat of size 6’x3’x12 mm thick (ISI mark) wide of superior quality of approved make as approved by the Engineer-in-charge to be laid on floor in HT room in front of panels and transformers. | 8 | Each | |
28 | 11 | S/E/T/C of Stationary Battery charger set comprising of 2 Nos. 12volts 100AH maintenance free batteries of make Exide, Amaron duly houses in cabinet of size (LxWxD) 36”x24”x18” made of 14 gauge CRCE sheet having 4 Nos. legs of 8” length made of M.S. angle of size 50 x 50 x 6mm. The complete cabinet inner and outer side is powder coated of gray paint. The cabinet should have one open able door on front side with locking arrangement complete in all respect. | |||
29 | 11.01 | The battery charger should be suitable for boost mode and trickle mode with display of input & output voltage and current. | |||
30 | 11.02 | Suitable Miniature circuit breaker shall be provided for protection at input supply and output of the battery charger. | 1 | Each set | |
31 | 12 | Dismantling, refilling & re-erection of modular type ceiling mounted fire extinguisher 10kg capacity the job includes the cost of new fastener and L-shape bracket if required as per site requirement. The job includes cost of other petty material and labour etc as required to complete the job to the entire satisfaction of Engineer-in-charge. | 3 | Each | |
32 | 13 | S/E of fire extinguishers ISI marked duly erected hung on wall with hooks including the cost of hook with all material and labour required to complete the job in all respect upto the entire satisfaction of the engineer in charge of work. | |||
33 | 13.01 | CO2 type of 9 kg capacity fire extinguishers conformation to relevant IS | 4 | Each | |
34 | 14 | S/E of shocks treatment chart written in Hindi English and local language duly framed in wood frame with glass complete as required. | 2 | Each | |
35 | 15 | S/E medium size first aid box made of 16 gauge MS sheet of size 14’’x7’’x5’’ with 6 wound dressing 3 burns dressing 13 gms absorbent cotton wool one dressing scissor one bottle of sprit of sal volatile 1 tube of burn ointment. | 2 | Each | |
36 | 16 | S/E of 4 nos. sand buckets of 10 ltr. Capacity each made out of 24 gauge G.I. pipe sheet the bucket with sand shall be reected on suitable size of angle iron stand fabricated out 1 ½ x 1 ½ x 1/8’’ angle iron having hooks for hanging the buckets in two rows. | 2 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy