| 1 | 1 | Taking down carefully any type of point wiring (light, fan, socket bell or power) complete with all fitting such as batten, switch, ceiling rose, pendant, regulator, socket and brackets switch fuse etc removing materials from site and making good disturbed surfaces of walls, floors etc to match the existing surface all as directed . | 1 | 545 | PER POINT |
|---|
| 2 | 2 | M & L for point wiring for one light/ fan point/call bell controlled by one switch with 1100 volt grade PVC insulated FRLS 1.5 Sq mm multi stranded copper conductor cable with continuous earth wire of 1.5 Sq mm multi stranded copper conductor cable PVC insulated-unsheathed, drawn in & including concealed rigid non metallic PVC conduit medium grade with fittings (ISI marked) not less than 20 mm dia & sunken anodized pressed sunken boxes made out of not less than 1.0 mm thick sheet, covered with 2.8 mm thick laminated insulated cover make sheet for housing/fixing switches etc complete all as specified and directed. | 2 | 270 | PER POINT |
|---|
| 3 | 3 | All as per item No 2 above but 1.5 Sq mm for 5 Amp socket outlet on same board with 1.5 Sq mm earth wire complete. | 3 | 50 | PER POINT |
|---|
| 4 | 4 | All as per item No 2 above but 1.5 Sq mm for 5 Amp switch socket combination on independent board with 1.5 Sq mm earth wire complete. | 4 | 100 | PER POINT |
|---|
| 5 | 5 | All as per item No 2 above but 2.5 Sq mm for 15 Amp switch socket combination on independent board with 2.5 Sq mm earth wire complete. | 5 | 125 | PER POINT |
|---|
| 6 | 6 | Supply and fix ceiling rose three terminals PVC/ Polycarbonate, isolated body complete all as specified. | 6 | 250 | EACH |
|---|
| 7 | 7 | S & F socket outlet 2 in 1, 5 pin 5 Amp flush type 230 volt, flush type universal, complete all as specified. | 7 | 100 | EACH |
|---|
| 8 | 8 | S & F switch piano type 5 Amp 230 volt one way flush type complete all as specified and as directed. | 8 | 370 | EACH |
|---|
| 9 | 9 | S & F socket outlet 2 in 1, 3 pin 5 and 15 Amp flush type 230 volt, flush type universal, complete all as specified. | 9 | 125 | EACH |
|---|
| 10 | 10 | S & F switch piano type 15 Amp 230 volt one way flush type, universal, complete all as specified and as directed. | 10 | 125 | EACH |
|---|
| 11 | 11 | S & F angle holder complete all as specified and as directed. | 11 | 300 | EACH |
|---|
| 12 | 12 | S & F LED lamp 9 Watts, complete all as specified and as directed. | 12 | 300 | EACH |
|---|
| 13 | 13 | S&F Fan regulator electronic type 5 step, 230 volt complete all as specified. | 13 | 100 | EACH |
|---|
| 14 | 14 | S&F call bell Ding dong, AC 230 volts, single pole complete all as specified. | 14 | 20 | EACH |
|---|
| 15 | 15 | S&F bell push flush type 5 amp AC 230 volts, single pole complete all as specified. | 15 | 20 | EACH |
|---|
| 16 | 16 | S & F in repair LED tube light batten suitable for LED T-8 lamps (Cat part No- DMLN1T8-16) pre-wired with LED tube rod 16 W ( Cat part No- LTT8-16) with extruded aluminium body PC diffuser and inbuilt driver of Crompton Greaves or equivalent model of Philips/ Wipro/GE including electrical connection from ceiling rose to light fitting by PVC flexible wire 23/.0076 mm size including earth connection complete. | 16 | 85 | EACH |
|---|
| 17 | 17 | S & F in repair LED bulk head fitting 15 W with LED lamp , powder coated with die cast housing Code : SSK-BH-15W of SYSKA LED or equivalent model of Philips/ Bajaj including electrical connection from ceiling rose to light fitting by PVC flexible wire 23/.0076 mm size including earth connection complete. | 17 | 4 | EACH |
|---|
| 18 | 18 | M & L Sub main wiring two single core 4.0 Sqmm PVC insulated FRLS multistanderd copper conductor cable and one run of 4.0 Sqmm PVC insulated unsheathed FRLS multistanderd copper conductor cable for earth wire drawn in & including concealed rigid non metallic PVC conduit medium grade with fittings (ISI marked) not less than 20 mm dia including taking down of existing conduit or batten complete and making good disturbed surface wall complete all as specified and as directed. \nNote : - Not : 2 runs of 4 Sqmm cable and 1 run of earth wire 4 sqmm shall be measured as one unit length. | 18 | 245 | RM |
|---|
| 19 | 19 | S & F in repair sheet metal enclosures for DBs single pole & neutral 4 way double door with 200 Amp rated bus bar suitable to accommodate MCB and necessary electric cable connection through suitable lugs by crimping and making good disturbed area of wall complete all as specified and as directed. | 19 | 15 | EACH |
|---|
| 20 | 20 | S & F in repair sheet metal enclosures for DBs single pole and neutral 8 way double door with 200 Amp rated bus bar suitable to accommodate MCB and necessary electric cable connection through suitable lugs by crimping and making good disturbed area of wall complete all as specified and as directed. | 20 | 14 | EACH |
|---|
| 21 | 21 | S & F in repair sheet metal enclosures for DBs single pole & neutral 12 way double door with 200 Amp rated bus bar suitable to accommodate MCB and necessary electric cable connection through suitable lugs by crimping and making good disturbed area of wall complete all as specified & as directed. | 21 | 5 | EACH |
|---|
| 22 | 22 | S & F in repair MCB single pole 6 to 32 Amp 240 V, ‘B’ Series, 10 KA, complete all as specified and as directed. | 22 | 250 | EACH |
|---|
| 23 | 23 | S & F in repair MCB SPN, 20 to 40A 240V, ‘B’ Series, 10 KA complete all as specified and as directed. | 23 | 75 | EACH |
|---|
| 24 | 24 | Taking down old unserviceable tube light fitting of any type from wall/ceiling and refixing the same in the existing or other position after repairing all the defects at site. Note: Spares, including fixing for repair works are are to be included in quoted rates. | 24 | 500 | EACH |
|---|
| 25 | 25 | S & F LED tube rod 18 Watts with electrical connections as required including testing complete, complete all as specified and as directed. | 25 | 360 | EACH |
|---|
| 26 | 26 | Supply in repair 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular stranderd conductor 16 Sq mm including testing complete all as specified and directed. | 26 | 350 | RM |
|---|
| 27 | 27 | M&L ,for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanised earth lead wire 4.00 mm dia by means of bolts, nuts check nuts & washers of galvanised iron or steel, protected by GI pipe 15 mm bore (light grade) and watering pipe 20 mm bore GI pipe (light grade) and PCC of chamber and coping shall in 1:3:6 type C-1 using 20 mm graded stone aggregate including excavation and earth work and removal of surplus soil and filling with black cotton soil upto ground level complete all as shown in electrical plate No 3 of SSR Pt-I, 2009 with CI cover 10mm thick of size 300x300mm with charcoal dust and common salt complete and earth lead connected to panel including testing complete all as specified and directed. \nNote : Earth test result should not less than one ohm. | 27 | 4 | EACH |
|---|
| 28 | 28 | S & F 3M surface mounted with SP MCB 25 Amp & plug top with indicator (Cat Part No. PU3M-BT) of Make North West or its equivalent, for AC protection, complete all as specified and as directed. | 28 | 4 | EACH |
|---|
| 29 | 29 | S & F metering panel of size 800x600x200 mm, manufacturing cubical type body made out of 1.6 mm CRCA/HR sheet, totally enclosed, dust and vermin proof indoor type suitable for operation on 03 phase and neutral 415 V, 50 Hz AC system (04 metres) including testing and refixing of meters, complete all as specified and as directed inclusive of the following:- Incoming: (a) 63A 4 pole 16 kA MCCB adjustable type thermal magnetic setting - 01 No. (b) Rotary handle extended - 01 No. (c)3 Phase 4 wire digital type voltmeter - 01 No. (d) 3 Phase 4 wire digital type Amperemeter - 01 No. (e) R-Phase indicator Lamp 'RED' (f) Y- Phase indication Lamp 'YELLOW' (g) B - Phase indication Lamp 'BLUE' - 01 No. (h) Tape wound CT-60/5A, Class:I, 5VA, ID:35 - 03 Nos. Outgoing (a) Compartment Feeder - 4 Nos (b) 32 A 2 Pole MCB - 04 Nos (c) (Busbar) Electrolytic tined copper strip for 100 A TPN with R,Y,B & N Colour coding heat shrinkable sleeves.- SET, (d) Nuts, Bolts, washers, ferrule numbers, cable ties, tie base, copper PVC control wire power wire, copper thimbles, panel locks, I-Hooks, PVC tape, insulators E-type, L-Type, round type, MCB, Channel, PVC, Channel connector, channel, connector etc. - One SET. Note: Contractor must submit GA drawings for approval with OEM manufacturer prior to commencement of work. Make: Indo Asian/Procom/L&T/C&S | 29 | 6 | EACH |
|---|