| 1 | 1 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. | | | |
|---|
| 2 | 1.1 | 3 x 1.5 sq. mm | | 160 | Metre |
|---|
| 3 | 1.2 | 3 x 2.5 sq. mm | | 390 | Metre |
|---|
| 4 | 1.3 | 3 x 4.0 sq. mm | | 30 | Metre |
|---|
| 5 | 1.4 | 6 x 4.0 sq. mm | | 40 | Metre |
|---|
| 6 | 1.5 | 6 x 6.0 sq. mm | | 80 | Metre |
|---|
| 7 | 2 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. | | | |
|---|
| 8 | 2.1 | 20 mm | | 200 | Metre |
|---|
| 9 | 2.2 | 25 mm | | 300 | Metre |
|---|
| 10 | 2.3 | 32 mm | | 200 | Metre |
|---|
| 11 | 2.4 | 40 mm | | 50 | Metre |
|---|
| 12 | 3 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. | | | |
|---|
| 13 | 3.1 | 5/6 amps switch | | 30 | Each |
|---|
| 14 | 3.2 | 15/16 amp switch | | 20 | Each |
|---|
| 15 | 3.3 | 3 pin 5/6 amp socket outlet | | 10 | Each |
|---|
| 16 | 3.4 | 6 pin 15/16 amp socket outlet | | 20 | Each |
|---|
| 17 | 3.5 | Telephone socket outlet | | 2 | Each |
|---|
| 18 | 4 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. | | | |
|---|
| 19 | 4.1 | 1 or 2 Module (75mmX75mm) | | 2 | Each |
|---|
| 20 | 4.2 | 3 Module (100mmX75mm) | | 12 | Each |
|---|
| 21 | 4.3 | 4 Module (125mmX75mm) | | 22 | Each |
|---|
| 22 | 4.4 | 6 Module (200mmX75mm) | | 5 | Each |
|---|
| 23 | 4.5 | 8 Module (125mmX125mm) | | 4 | Each |
|---|
| 24 | 4.6 | 12 Module (200mmX150mm) | | 2 | Each |
|---|
| 25 | 5 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) | | | |
|---|
| 26 | 5.1 | 6 Way, Double door | | 8 | Each |
|---|
| 27 | 6 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) | | | |
|---|
| 28 | 6.1 | 6 way (4 + 18), Double door | | 1 | Each |
|---|
| 29 | 7 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10KA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. | | | |
|---|
| 30 | 7.1 | Single pole | | 50 | Each |
|---|
| 31 | 7.2 | Triple pole | | 10 | Each |
|---|
| 32 | 7.3 | Triple pole and neutral | | 10 | Each |
|---|
| 33 | 8 | Supplying and fixing following rating, 415 volts, \"C\" curve, 10KA breaking capacity, FP miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. | | | |
|---|
| 34 | 8.1 | 40/63 Amp Tripple pole | | 15 | Each |
|---|
| 35 | 8.2 | 40/63 Amp Four pole | | 15 | Each |
|---|
| 36 | 9 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, Provision for MCCB as incommer as required . | | | |
|---|
| 37 | 9.1 | 8 way Double door (Provision for 125A MCCB as incommer) | | 1 | Each |
|---|
| 38 | 9.2 | 8 way Double door (Provision for 250A MCCB as incommer) | | 1 | Each |
|---|
| 39 | 10 | Supply and erection, testing and commissioning of DOL starter of following overload relay range in SS enclosure complete with all accessories I/c overload relay, 230V coil type 50HZ . The job includes supply & fixing of double wooden switch board and 3mm thick bakelite sheet of switch board on which the starter to be fixed. | | | |
|---|
| 40 | 10.1 | 14 - 23 Amp. (Three phase) | | 2 | E. Job |
|---|
| 41 | 11 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. | | | |
|---|
| 42 | 11.1 | 125 Amp, 36 KA FP MCCB | | 3 | Each |
|---|
| 43 | 11.2 | 200 Amp, 36 KA FP MCCB | | 1 | Each |
|---|
| 44 | 11.3 | 250 Amp, 36 KA FP MCCB | | 1 | Each |
|---|
| 45 | 12 | Supply and fixing of MCCB following encloser box (sheet steel, 2mm /14 SWG) on the wall in surface / conceal fashion including mounting arrangement of MCCB complete in all respects. | | | |
|---|
| 46 | 12.1 | For four pole 125/160 DPX MCCB | | 2 | nos |
|---|
| 47 | 12.2 | For four pole 250A DPX MCCB | | 1 | nos |
|---|
| 48 | 13 | Supplying and fixing of modular type recess mounted RJ 45 socket outlet with coverplate and back box including connection of CAT VI wire | | 7 | Each |
|---|
| 49 | 14 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required. | | | |
|---|
| 50 | 14.1 | 1 run of cable | | 120 | Mtr |
|---|
| 51 | 15 | Supplying and drawing following pair 0.5 sq mm FRLSPVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. | | | |
|---|
| 52 | 15.1 | 2 Pair | | 200 | Metre |
|---|
| 53 | 16 | Supply of 1.1 KV grade following PVC insulated Armoured cable confirming the IS 7098 (Part 1) 1988 specification:- | | | |
|---|
| 54 | 16.1 | 4 Core16 sq.mm. copper cable | | 150 | P.Mtr |
|---|
| 55 | 16.2 | 4 Core 35 sq.mm. copper cable | | 120 | P.Mtr |
|---|
| 56 | 16.3 | 3.5 Core 70 sq.mm. copper cable | | 120 | P.Mtr |
|---|
| 57 | 16.4 | 3.5 Core 300 sq.mm. Al. Cable. | | 180 | P.Mtr |
|---|
| 58 | 17 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. | | | |
|---|
| 59 | 17.1 | Upto 35 sq. mm (clamped with 1mm thick saddle) | | 270 | Metre |
|---|
| 60 | 17.2 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | | 120 | Metre |
|---|
| 61 | 17.3 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | | 180 | Metre |
|---|
| 62 | 18 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. | | | |
|---|
| 63 | 18.1 | Upto 35 sq. mm (clamped with 1mm thick saddle) | | 200 | Metre |
|---|
| 64 | 18.2 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | | 100 | Metre |
|---|
| 65 | 18.3 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | | 90 | Metre |
|---|
| 66 | 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | | | |
|---|
| 67 | 19.1 | 3½ X 300 sq. mm (70mm) | | 6 | Set |
|---|
| 68 | 19.2 | 3½ X 70 sq. mm (38mm) | | 20 | Set |
|---|
| 69 | 19.3 | 4 X 16 sq. mm (28mm) | | 24 | Set |
|---|
| 70 | 19.4 | 4 X 35 sq. mm (32mm) | | 16 | Set |
|---|
| 71 | 20 | Finishing of end termination with proper size of pin / ring type copper solderless socket by crimping method of following sizes PVC insulated copper conductor | | | |
|---|
| 72 | 20.1 | 1 x 1.5 sq. mm | | 20 | Each |
|---|
| 73 | 20.2 | 1 x 2.5 sq. mm | | 200 | Each |
|---|
| 74 | 20.3 | 1 x 4 sq. mm | | 120 | Each |
|---|
| 75 | 20.4 | 1 x 6 sq. mm | | 120 | Each |
|---|
| 76 | 20.5 | 1 x 16 sq. mm | | 80 | Each |
|---|
| 77 | 20.6 | 1 x 35 sq. mm | | 60 | Each |
|---|
| 78 | 20.7 | 1 x 70 sq. mm | | 36 | Each |
|---|
| 79 | 21 | Supply and fixing of 25A modular type A.C Starter on existing box and cover plate | | 1 | Each |
|---|
| 80 | 22 | Earthing with maintenance free chemical compound base by 17mm dia x 3Mtr. Long pre-welded copper bonded rod of 250 micron copper coating including 2 bagsof 25Kg back fill compound conforming IEC 62561-7 to maintain overall earth pit resistance less than 1.0 ohm. The job will be completed with earth pit cover | | 8 | Each |
|---|
| 81 | 23 | Supply & fixing of of following indoor type LED Light fittings with extra high efficiency 120-150 lumens/watt LEDs. The fixture must have of CRI > 80, Colour temperature 6000K/6500K and weather & dust proof with 5 years warranty. | | | |
|---|
| 82 | 23.1 | 36 Watt 595 mm x 595 mm recess mounted | | 10 | Each |
|---|
| 83 | 23.2 | 20 watt 1195mm batton light Aluminium body | | 10 | Each |
|---|
| 84 | 24 | Supplying, Erection, testing and commissioning of floor mounted cubical type factory assembled dust and vermin proof fully segregated and compartmentalized following L.T. Panels suitable for 440V, 50 Hz, AC, having protection of IP 42 degree and CPRI approved. All dimentions and technical specifications are mentioned in Annexure I. GA and schematic drawing (General notes and legends, SLD, BOM, Control Circuit etc.) to be submitted before fabrication. | | | |
|---|
| 85 | 24.1 | Sub. Distribution L.T. Panel (overall dimension in mm W x H x D = 2800 x 2350 x 450) | | 1 | Job |
|---|
| 86 | 24.2 | UPS Panel ( overall dimension in mm. W x H x D = 1400 x 1500 x 400) | | 1 | Job |
|---|
| 87 | 25 | Supply, Installtion, Testing and Commissioning of following components for CCTV system complete with all respect:- | | | |
|---|
| 88 | 25.01 | 2MP IR Dome Camera (Make - Infinova (VH221-A20B-A022) /Bosch /Mobotix) | | 5 | Set |
|---|
| 89 | 25.02 | 8 Ch NVR2 SATA up to 8 TB Supported (Make - Infinova (V3073-08J02)/ Bosch / Mobotix) | | 1 | Nos |
|---|
| 90 | 25.03 | 24 Port L2 Network Switch with PoE (Make - Digisol (DG-GS1528HP/C) / cisco / Avaya) | | 1 | Nos |
|---|
| 91 | 25.04 | 4 TB Hard Disk (Make - Toshiba/Seagate /WD) | | 2 | Nos |
|---|
| 92 | 25.05 | Cat-6 cable (Make - Digisol/ Molex / AMP) | | 305 | Mtr. |
|---|
| 93 | 25.06 | 9 U steel Rack with accessories (Make - VAL / Dlink / Net Rack) | | 2 | Nos |
|---|
| 94 | 25.07 | 20 mm PVC Conduit with accessories (Make- AKG/Presto/Precission) | | 300 | Mtr |
|---|
| 95 | 25.08 | 24 Port Patch Panel (Make - Digisol/ Molex / Avaya) | | 1 | Nos |
|---|
| 96 | 25.09 | Patch cord 1 mtr (Make - Digisol / Molex / Avaya) | | 6 | Nos |
|---|
| 97 | 25.1 | RJ - 45 Connector (Make - Digisol / D-link / AMP) | | 7 | Nos |
|---|
| 98 | 25.11 | 4 x 6 PVC Box (Make - Precission / Presto / AKG) | | 5 | Nos |
|---|
| 99 | 25.12 | 43 inch Industrial type LED display with duty cycle 24 X 7 (Model - LG(43SE3KE) / Samsung / Sony) | | 1 | Nos |
|---|
| 100 | 25.13 | CPU i3 7th Generation with 4GB RAM, 1TB HDD, additional 4GB graphics card (Make - Lenovo/ HP/ Dell) | | 1 | Nos |
|---|
| 101 | 25.14 | Armoured Optical Fiber Cable (Make - Digisol/ Molex /Avaya) | | 300 | Mtr. |
|---|
| 102 | 25.15 | 6 port LIU (Make - Digisol/ Molex / Avaya) | | 2 | Nos. |
|---|
| 103 | 25.16 | SC - SC OFC Patch Cord (Make- Digisol/ Molex / Avaya) | | 2 | Nos. |
|---|
| 104 | 25.17 | Media Converter SC Duplex (Make :- Digisol / Molex / Avaya) | | 2 | Nos. |
|---|
| 105 | 26 | Supply, Installtion, Testing and Commissioning of following components for Air Ventilation / Exhaust system complete with all respect:- | | | |
|---|
| 106 | 26.1 | Heavy duty Axial flow fan capacity 7000CMH (motor - 1450 RPM, 2 HP, 415Volt AC) with static pressure 25mmWG for exhaust hot air (Make - Crompton / ABB / Havells). The motor must be fitted on a base frame with wall hanging hoock. The job is including inlet & outlet bird screen and a control panel incorporating with input MCB, contactor, overload rely with cable remote. | | 1 | Set |
|---|
| 107 | 26.2 | Heavy duty Axial flow fan capacity 5600 CMH (motor - 1450 RPM, 1.5 HP, 415Volt AC) with static pressure 25mmWG for supply fresh ambient air (Make - Crompton / ABB / Havells). The motor must be fitted on a base frame with wall hanging hoock. The job is including inlet filter with canopy, inlet & outlet bird screen and a control panel incorporating with input MCB, contactor, overload rely with cable remote. | | 1 | Set |
|---|
| 108 | 26.3 | Ducting for exhaust / Supply Air (air velocity inside the duct to be maintain 11 to 12 M/Sec.) with GI sheet (22 SWG for main duct line and 24SWG for branch duct line), MS support, hanging rod & fastner and also with line damper for every branch. | | 740 | Sq. ft. |
|---|
| 109 | 26.4 | Air grill with volume control damper 190mm X 190mm made from powder coated GI Sheet | | 12 | Nos |
|---|
| 110 | 26.5 | Air grill with volume control damper 160mm X 160mm made from powder coated GI Sheet | | 13 | Nos |
|---|
| 111 | 26.6 | Control Panel incorporating with input 10A FP MCB, 10A Four pole contactor, 3-6 A overload relay, On-OFF LED indicator, Multifunctional Meter complete with all accessories | | 2 | Set |
|---|
| 112 | 27 | Supply, Installtion, Testing and Commissioning of following components to be commissioned in the existing Edward make addressable fire alarm sysytem for expansion of the coverage area. The job to be executed strictly by authorised sales and service provider of the manufacturer and complete with all respect:- | | | |
|---|
| 113 | 27.01 | Fire Alarm Control panel including CPU, Loopcard, Battery, charger , power supply etc. as per Annex-II. | | 1 | No. |
|---|
| 114 | 27.02 | Intelligent Addressable microprocessor based Multi-Criteria smoke cum Heat detector , optical type having 20 pre alarm senstivity settings and 5 alarm senstivity settings with blinking LED and being capable of being addressed electronically.The microprocessor’s non-volatile memory shall permanently store the detector’s serial number, device type and system address. (Make - EDWARD, Smodel - SIGA-PHD + SIGA-SB) | | 20 | Nos |
|---|
| 115 | 27.03 | Respones Indicator (Make- Agni / Ravel ) | | 10 | Nos |
|---|
| 116 | 27.04 | Addressable control module complete as required for switching ON of Hooter cum strobe, Telephone Jack and Speaker circuit capable of being addressed electronically. (Make- EDWARDS, Model - SIGA-CC1) | | 2 | Nos |
|---|
| 117 | 27.05 | Intelligent Addressable Single action manual pull station, capable of being addressed electronically. (Make- EDWARDS, Model - SIGA-278) | | 2 | Nos |
|---|
| 118 | 27.06 | Fire Alarm Hooter cum Strobe (sound output of minimum 85 dB ), made Addressable with the help of Intelligent Addressable Signal Module, capable of being addressed electronically including seperate power supply arrangement complete as required and suitable for wall/ceiling mounting (Make- EDWARDS, Model - G1RF-HDVM) | | 2 | Nos |
|---|
| 119 | 27.07 | Addressable control relay module complete as required for switching ON of smoke extraction fans / Pressurisation Fans etc. and switching off AHU' s, capable of being addressed electronically. (Make- EDWARDS, Model - SIGA-CR) | | 1 | Nos |
|---|
| 120 | 27.08 | Addressable Monitor module complete as required for monitoring flow switches/ interface with any third party equipment capable of being addressed electronically. (Make- EDWARDS, Model - SIGA-CT1) | | 1 | Nos |
|---|
| 121 | 27.09 | Addressable Fault Isolator module complete as required for determining the short in a circuit and separating the segment having the short capable of being addressed electronically. (Make- EDWARDS, Model - SIGA-IM) | | 1 | Nos |
|---|
| 122 | 27.1 | 2 x 1.5 sq mm shielded PVC sheathed copper conductor 1100 volts grade Armoured FRLS cable of approved make in concealed or surface fixing, supporting, saddling etc complete in all respect. (Make- Pollycab/ Nicco/ CCI) | | 300 | Mtr. |
|---|