Military Engineer Services-MES has published Repair Or Replacement Of Submain Wiring , Mccbs Building Security Lamps , Industrial Sockets , Flame Proof Fittings , Energy Meters And Fixtures Including Repairs To Summer And Winter Appliances And Connected Works At Af Stn Panagarh. Submission Date for this Tender is 25-01-2021. Electrification Work Tenders in AF Station Panagarh West Bengal. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 04-Jan-2021 | BOQ Amendment | BOQ | 18-01-2021 |
2 | 18-Jan-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 25-01-2021 |
REPAIR OR REPLACEMENT OF SUBMAIN WIRING, MCCBs BUILDING SECURITY LAMPS, INDUSTRIAL SOCKETS, FLAME PROOF FITTINGS, ENERGY METERS AND FIXTURES INCLUDING REPAIRS TO SUMMER AND WINTER APPLIANCES AND CONNECTED WORKS AT AF STN PANAGARH | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down carefully aluminium/copper point wiring (light,fan,socket or power) of any type complete, including fittings such as switches,ceiling roses,pendants,regulators sockets etc.,removing from site and making good disturbed surfaces of walls,floors,ceiling etc.,all as directed | 250 | Point | |
2 | 2 | Material and labour for point wiring with 1.50 Sqmm PVC insulated un sheatned multi stranded copper conductor cable (FRLSH) 1100 volts grade two single core conforming to IS-694-1990 and one run of continious earth wire with 1.50 Sqmm PVC insulated unsheatned stranded copper conductor cable (FRLSH) draw in and including heavy duty 20 mm dia PVC conduit (ISI marked) in concealed with all necessary fittings and fixures with GI sunken boxes with earth dolly and 3 mm laminated cover sheet suitable for fixing switch, socket, regulator, fan point, exhaust fan point etc. including making good disturbed surface with CM (1:4) to match with the existing surface complete all as specified for the following :- \nNote:- (a) Red coloured cable shall be used for live connection, black coloured cable shall be used for neutral connection and green coloured cable shall be used for earthing. Separate cable for earthing and neutral to be used for each individual circuit from the distribution board.\n(b) Quoted rates shall be deemed for conduit, cover plate and box of suitable module, cutting chases of wall, making good disturbed wall.\n(c) The Payment shall only be allowed after production of original GST defaced purchase vouchers by Engr- In- Charge\nMake: Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked) | 60 | Point | |
3 | 3 | All as per Item No 02 One 5 pin 6 Amps switch socket outlet point controlled by one switch on independent board. | 20 | Point | |
4 | 4 | All as per Item No 02 One 5 pin 6 Amps switch socket outlet point controlled by one switch on same board. | 15 | Point | |
5 | 5 | All as per Item No 02 but for one 15 Amps socket outlet using by 2.50 sqmm copper conductor cable with 2.50 sqmm PVC insulated single core copper cable for earth continuity conductor. | 40 | Point | |
6 | 6 | Material and labour for point wiring (surface type) with 4.0 Sqmm PVC insulated (FRLSH) unsheathed copper cable multistranded conductor 1100 volts grade controlled by one way switch including 2.5 sqmm PVC (FRLSH) insulated unsheathed copper cable multistrand conductor 1100 volts grade for continuity earth wire connected to common earth dolly drawn through and including PVC casing caping with all accessories and sunk cast pressed steel terminal box made out of MS sheet of 1.6 mm thick for mounting of fittings like switch, socket and fan regulator with3mm thick hylum laminated/bakalite sheet cover complete all as specified for one light point.\nNote:- (a) Red coloured cable shall be used for live connection, black coloured cable shall be used for neutral connection and green coloured cable shall be used for earthing. Separate cable for earthing and neutral to be used for each individual circuit from the distribution board. \n(b) Quoted rates shall be deemed for 'N' capping and box of suitable module.\n(c) The Payment shall only be allowed after production of original GST defaced purchase vouchers by Engr- In- Charge\nMake: Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked) | 95 | Point | |
7 | 7 | All as per Item No 06 One 5 pin 6 Amps switch socket outlet point controlled by one switch on independent board. | 15 | Point | |
8 | 8 | All as per Item No 06 One 5 pin 6 Amps switch socket outlet point controlled by one switch on same board. | 10 | Point | |
9 | 9 | All as per Item No 06 but for one 15 Amps socket outlet using by 2.50 sqmm copper conductor cable with 2.50 sqmm PVC insulated single core copper cable for earth continuity conductor. | 35 | Point | |
10 | 10 | Supply and fix as in repairs Switch piano, flush type single pole one way 6 Amps 240V. \nMake: Anchor (Penta)/Havells/ Cona/Plaza | 200 | Each | |
11 | 11 | S & F Switch socket combination, 2 in 1, 5 pin 6 Amps and 16 Amps 240 V ,flush type. \nMake: Anchor (Penta)/Havells/ Cona/Plaza | 70 | Each | |
12 | 12 | Supply and fix switch socket outlet , 3 pin 6 Amps 240 V flush type . \nMake: Anchor (Penta) / Havells/ Cona/Plaza | 60 | Each | |
13 | 13 | Supply and fix switch socket outlet , 5 pin 16 Amps 240 V flush type . \nMake: Anchor (Penta) / Havells/ Cona/Plaza | 15 | Each | |
14 | 14 | Supply and fix Switch piano, flush type single pole one way 16 Amps 240V. \nMake: Anchor (Penta) /Havells/ Cona/Plaza | 15 | Each | |
15 | 15 | Supply and fix ceiling rose surface baklite with three terminals 240 V.\nMake: Anchor (Penta)/Havells/ Cona/Plaza | 55 | Each | |
16 | 16 | Supply and fix ceiling fan regulator socketed, step type heavy duty suitable to work on 230 volts AC supply complete with cover plate all as specified. \nMake: Anchor ( Penta) /Havells/ Cona/Plaza | 50 | Each | |
17 | 17 | Supply and fix bell push flush type 6 Amps.\nMake: Anchor (Penta)/Havells/ Cona/Plaza | 20 | Each | |
18 | 18 | Supply and fix call bell ding dong type SP 230V.\nMake: Anchor (Penta)/Havells/ Cona/Plaza | 40 | Each | |
19 | 19 | Supply and fix lamp Angular holder insulated body with back plate suitable for batten fittings all as specified.\nMake: Anchor (Penta)/Havells/ Cona/Plaza | 30 | Each | |
20 | 20 | Supply and fixing sub-main wiring with PVC insulated & unsheathed four run of 4 Sqmm single core multistrand copper conductor cable (FRLSH), 1100 Volt grade alongwith two run of 2.50 Sqmm PVC insulated & unsheathed copper conductor cable (FRLSH) 1100 Volt grade, connected to common earth dolly as earth continuity conductor, drawn through minimum 25 mm PVC conduit complete all as specified.\nNote:- (a) PVC conduit including accessories shall be measured and paid including the item.\n(b) 2 Run of line conductor and 1 Run of earth continuity conductor shall be measured as one unit length.\n(c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate.\n(d) Rate shall be included for cutting, pinning in, making good to facings where required for pointing in cement mortar 1:3 and cutting chases for concealed conduit wiring and making good, and cutting not exceeding 10 cm girth.\n(d) The Payment shall only be allowed after production of original GST defaced purchase vouchers by Engr- In- Charge.\nMake:Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked) | 90 | Rm | |
21 | 21 | Material and labour for Sub main wiring with PVC insulated unsheathed two run of 4.00 Sq. mm single core multistand copper conductor cable (FRLSH), 1100 volt grade alongwith one run of 2.50 sqmm PVC insulated and unsheathed copper conductor cable (FRLSH) 1100 volt grade, connected to common earth dolly as earth continuity conductor, drawn through 25 mm x 16 mm PVC casing caping complete all as specified.\nNote: (a) PVC casing 'N' caping including accessories shall be measured measured and paid including the item.\n(b) 2 Run of line conductor and 1 Run of earth continuity conductor shall be measured as one unit length.\n(c) Cable requireds for connection to MCBs/DBs shall be deemed to be included in the unit rate.\n(d) The Payment shall only be allowed after production of original GST defaced purchase vouchers by Engr- In- Charge\nMake: Havells(ISI Marked)/ Plaza(ISI Marked)/ KEI(ISI Marked)\n | 80 | Rm | |
22 | 22 | All as per Item No 21 here in before but for 2 runs 2.50 sqmm and 1 run 1.50 sqmm. | 150 | Rm | |
23 | 23 | All as per Item No 21 here in before but for 2 runs 1.50 sqmm and 1 run 1.50 sqmm. | 60 | Rm | |
24 | 24 | All as per Item No 21 here in before but for 2 runs 6.0 sqmm and 1 run 4.0 sqmm. | 40 | Rm | |
25 | 25 | Supply and fix as repairs security light bracket made of 40 mm bore 1.5 mtr long GI tubing medium grade (ISI Marked) with all fittings (ISI marked) including bending, welding as required and making holes including provision of flat iron clamps 50 mm x 6 mm size and fixed to poles or any where as directed by Engineer-In-Charge.\nMake:- Jindal/ TATA/ Prakash\n | 15 | Each | |
26 | 26 | Supply and fix 24-25 W LED street light made up of pressure die cast aluminium housing with high efficient LED with driver IP 65 luminiares comprising of high brightness LEDs and all accessores complete all as specifed and directed. \nMake:- Bajaj Cat No- ENXT P 24L WH SY PC SD/ Havells LED Item Description ENDURAPEARLSL25WLED757SASYTOPCMP/ Crompton Cat No LSTS-25-CDL-M\nNote:- (a) LM-79 and LM-80 certificate from NABL accredited Lab shall be submitted for LED light fittings.\n(b) Warranty certificate shall be submitted for LED light fitting as per standered format for minium 50000 Hrs.\n(c) LED light fitting and drivers shall be of same make.\n | 15 | Each | |
27 | 27 | Supply and fix 18 W LED street light made up of pressure die cast aluminium housing with high efficient LED with driver IP 65 luminiares comprising of high brightness LEDs and all accessores complete all as specifed and directed. \nMake:- Bajaj Cat No- ENXT P 24L WH SY PC SD/ Havells LED Item Description ENDURAPEARLSL25WLED757SASYTOPCMP/ Crompton Cat No LSTS-25-CDL-M\nNote:- (a) LM-79 and LM-80 certificate from NABL accredited Lab shall be submitted for LED light fittings.\n(b) Warranty certificate shall be submitted for LED light fitting as per standered format for minium 50000 Hrs.\n(c) LED light fitting and drivers shall be of same make.\n | 150 | Each | |
28 | 28 | Supply and fix 18-20 W LED T8 tube with extruded Al body, PC diffuser and inbuilt driver Double sided connection and all accessores complete all as specifed and directed. \nMake:- Bajaj Cat No- BLRB 18W LED/ Havells LED Item Description LUMILINEPLUSBS20WLED865SPCSS/ Crompton Cat No LTT8-20\nNote:- (a) LM-79 and LM-80 certificate from NABL accredited Lab shall be submitted for LED light fittings.\n(b) Warranty certificate shall be submitted for LED light fitting as per standered format for minium 50000 Hrs.\n(c) LED light fitting and drivers shall be of same make.\n | 12 | Each | |
29 | 29 | Supply and fix 15W LED surface mounted downlighter with white powder coated aluminum housing with integrated electronic driver and all accessores complete all as specifed and directed. \nMake:- Bajaj Cat No- BPSLR 15W WH/ Havells LED Item Description INTEGRAGRANDDLR15WLED840MOD/ Crompton Cat No LSCSM-15W-NW\nNote:- (a) LM-79 and LM-80 certificate from NABL accredited Lab shall be submitted for LED light fittings.\n(b) Warranty certificate shall be submitted for LED light fitting as per standered format for minium 50000 Hrs.\n(c) LED light fitting and drivers shall be of same make.\n | 8 | Each | |
30 | 30 | Supply and fix Single pole and neutral enclosure with 2 pin and earth plug and socket complete with one single pole MCB of 20 Amps 240 V.\nMake:SIEMENS Cat No 8GB32100RC02 /SCHNEIDER Cat No A9HMES02 ?/ ABB Cat No 1SYI121502C0001 | 8 | Each | |
31 | 31 | Supply and fix sheet metal enclosure MCB DB SPN with 200 Amp rated bus bar 4 way 415 V (double door type) with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonry etc. and making good of disturbed surface to match with existing colour of wall complete all as specified.\nMake: ABB/ Siemens/ Schneider\nNote: (a) Quoted rates shall be deemed for brick wall / concrete wall cutting and making good as per existing surfaces.\n | 16 | Each | |
32 | 32 | All as per Item No 30 but 08 ways DB | 8 | Each | |
33 | 33 | All as per Item No 30 but TPN DB 04 ways DB | 2 | Each | |
34 | 34 | Supply and fix vertical DB TPN with 200 Amp rated bus bar 12 way 415 V (double door type) with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonry etc. and making good of disturbed surface to match with existing colour of wall complete all as specified.\nMake: ABB/ Siemens/ Schneider\nNote: (a) Quoted rates shall be deemed for brick wall / concrete wall cutting and making good as per existing surfaces.\n | 1 | Each | |
35 | 35 | Supply and fix as in repairs MCCB 415V, 3 phases, 50 Hz, 4 pole of capacity 63 Amps 10 KA.\nMake: ABB/ Siemens/ Schneider\nNote: (a) Quoted rates shall be deemed for brick wall / concrete wall cutting and making good as per existing surfaces.\n | 1 | Each | |
36 | 36 | Supply and fix MCB SP 240 volts, 50 Hz capacity 6-32 Amps 'C' curve all as specified.\nMake: ABB/ Siemens/ Schneider\n | 90 | Each | |
37 | 37 | Supply and fix MCB SP 240 volts, 50 Hz capacity 40 Amps 'C' curve all as specified.\nMake: ABB/ Siemens/ Schneider\n | 20 | Each | |
38 | 38 | Supply and fix MCB SPN 240 volts, 50 Hz capacity 6-32 Amps 'C' curve all as specified.\nMake: ABB/ Siemens/ Schneider\n | 15 | Each | |
39 | 39 | Supply and fix MCB SPN 240 volts, 50 Hz capacity 40 Amps 'C' curve all as specified.\nMake: ABB/ Siemens/ Schneider\n | 12 | Each | |
40 | 40 | Supply and fix MCB TPN 415 volts, 50 Hz capacity 63 Amps 'C' curve all as specified.\nMake: ABB/ Siemens/ Schneider\n | 2 | Each | |
41 | 41 | Supply and fix as in repairs 16A-25A MCB Protected Power Unit\nMake ABB/ Havells/L&T\n | 15 | Each | |
42 | 42 | Material and labour for earthing with galvanised steel earth plate electrode 60 cm X 60 cm X 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below ground level connected to 25 mm x 4 mm thick GI strip protected by 40 mm bore light grade galvanised iron pipe and other end connected to test point as directed including funnel with wire mesh and watering pipe 20 mm bore medium grade galvanised iron pipe with charcoal and common salt in alternaterlayers of 15 cm thickness all around the GI plate electrode with concrete pit in PCC 1:3:6 type C-1 with cast iron frame including cast iron cover10mm thick hinged to CI frame and 8mm MS rod for handle, necessary excavation and earth wok in hard/dense soil and disposal of spoil to a distance n exc 50 m and necessary testing complete all as shown in electrical plate No 3 of SSR part-I all as specified. | 2 | Each | |
43 | 43 | Supply and fix as in repairs earth continuity conductor or main earthing lead fixed to wall or battens or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other situation using 4 mm dia GI wire complete. | 30 | Rm | |
44 | 44 | Taking down Ceiling Fan of any Sweep and Make by disconnecting Electric Connection, dismantling Blades, Down Rod and removing Ceiling Fan to MES STORE YARD OF AGE E/M (AF) PANAGARH for Check-ing, complete including Hanging of Ceiling Fan in same position after repair and assemble of parts, connecting up with and including of Flexible Copper 3 Core Wire of 1.5 Sqmm, from Ceiling Rose/Connector to Fan, complete all as specified and as directed. | 165 | Each Job | |
45 | 45 | Taking down Exhaust Fan/wall mounted fan of any Sweep and Make by disconnecting Electric Connection, dismantling Blades, Down Rod and removing Exhaust Fan to MES STORE YARD OF AGE E/M (AF) PANAGARH for Check-ing, complete complete including fixing of exhaust Fan in same position/hole after repair and assemble of parts, connecting up with and including of Flexible Copper 3 Core Wire of 1.5 Sqmm, from Ceiling Rose/Connector to exhaust Fan, complete all as specified and as directed. all as specified and as directed. | 45 | Each Job | |
46 | 46 | M&L for Opening Stator of Ceiling Fan 1200mm Sweep Cleaning of Parts, replacement of Unserviceable Parts as ordered, Greasing of Moveable Parts, Taking out burnt Coil, Cleaning the Segments complete and Re-winding the Same with Supper Enameled Copper Wire of same Gauge and same Weight with Insulation Paper, Varnishing and Heating, Re-assemble the same after repaired and Testing, complete all as specified and as directed .\n | 135 | Each Job | |
47 | 47 | All as per item No 45 above but 1400 mm sweep | 20 | Each Job | |
48 | 48 | Material and labour for preparing Surfaces of Ceiling Fan of any Sweep and Make, complete Body, Blade, Down Rod, Cleaning Dust, Dirts, etc. filling Cavities with Filler and applying One Coat DUCO Paint with Spray Machine including Writing MES No. in Black Paint, complete all as specified and as directed. | 115 | Each Job | |
49 | 49 | Material and labour for preparing Surfaces of Exhaust Fan of any Sweep and Make, complete Body, Blade, , Cleaning Dust, Dirts, etc. filling Cavities with Filler and applying One Coat DUCO Paint with Spray Machine including Writing MES No. in Black Paint, complete all as specified and as directed. | 40 | Each Job | |
50 | 50 | Supply and fix as in repairs PVC insulated and sheathed work shop cable 3 core 0.5 sq mm copper conductor 1100 volt grade. \nMake: Plaza(ISI Marked)/ Polycab(ISI Marked)/ Finolex (ISI Marked) | 40 | Rm | |
51 | 51 | Supply and fix in repairs MS clamp of required size made out of flat iron, nuts, bolts, washer, S hook etc as per required size and shape in any location all as directed | 4 | Kg | |
52 | 52 | Supply and fixing ceiling fan down rod made out of 12 mm dia steel rod heavy duty upto 1 mtr length including taking down unserviceable rod complete all as directed | 12 | Each | |
53 | 53 | Material and labour for replacement of fan capacitor 2.5 Mfd capacity including taking out old burnt capacitor. \nMake: Universal/usha/Bajaj/Havells | 60 | Each | |
54 | 54 | Material and labour for replacement of fan capacitor 3.5 Mfd capacity including taking out old burnt capacitor. \nMake: Universal/usha/Bajaj/Havells | 30 | Each | |
55 | 55 | Taking down, opening and dismantling storage type water heaters (geysers) of capacity 25/35/50 ltrs vertical/horizontal type cleaning, descaling,leak arresting if any, re-assembling and re-installation in the existing place including hydraulic pressure testing of HPRV and container by hand operated hydraulic pump complete after necessary repair/replacement of unserviceable items all as directed . \nNote : Spare as required shall be measured and paid under relevant items | 60 | Each Job | |
56 | 56 | Supply and fix safety valve/high pressure air release valve/vaccum release valve ISI marked. | 22 | Each | |
57 | 57 | Supply and fixing new copper apparatur plate match to the existing one with rubber gasket suitable for 50 ltrs geyser, complete all as specified and as directed. | 5 | Each | |
58 | 58 | All as per item No 56 above but for 25/35 ltrs capacity. | 11 | Each | |
59 | 59 | Supply and fix as in repair glass wool/PUF suitable for geyser, complete all as specified and as directed. | 10 | Kg | |
60 | 60 | Supply and fix heating element of rating 1500 W circular/triangular shape push/thread type with rubber washers of \nMake Theeta/Elcon/Johnson/Racold | 32 | Each | |
61 | 61 | Supply and fix heating element of rating 2000 W circular/triangular shape push/thread type with rubber washers of \nMake Theeta/Elcon/Johnson/Racold | 22 | Each | |
62 | 62 | Supply and fix thermostat for geyser of capacities 25/35 Ltrs of duly ISI Marked. | 50 | Each | |
63 | 63 | Supply and fix thermostat for the geyser of capacities 50 Ltrs duly ISI Marked. | 10 | Each | |
64 | 64 | Supply and fixing in repairs plug top 3 pin 15 Amps of \nMake Anchor/Leader/Cona | 15 | Each | |
65 | 65 | Supply and fixing bottom cover with plate matching to exist one for 50 ltrs capacity, complete all as specified and as directed. | 12 | Each | |
66 | 66 | Supply and fix inner copper tank suitable for geyser of capacities 25 Ltrs | 3 | Each | |
67 | 67 | Supply and fix inner copper tank suitable for geyser of capacities 35 Ltrs | 3 | Each | |
68 | 68 | Supply and fix inner copper tank suitable for geyser of capacities 50 Ltrs | 2 | Each | |
69 | 69 | Supply and fix hot/cold water Flexible corrugated stainless steel connectors (EPDM with SS Braiding) for water heaters of length 600 mm including taking down old/damage connection pipe all as directed | 30 | Each | |
70 | 70 | Supply and fix LED light fitting 18 watt recess mounted round slim and elegant down/panel with high aesthetic appeal, pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size including taking down the existing light fittings. \nMake:- Philips/Crompton/Bajaj | 12 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy