Providing New Fire Fighting Facilities Suitable To The Upgrading Capacities Of Berths Or-I N Or-Ii To Accommodate 50 , 000 To 1 , 00 , 000 Dwt Vessels ( Panamax Vessels ) As Per Oisd 156 Guidelines In A Phased Manner Phase-Ii ., VPT-Andhra Pradesh

Visakhapatnam Port Trust has published Providing New Fire Fighting Facilities Suitable To The Upgrading Capacities Of Berths Or-I N Or-Ii To Accommodate 50 , 000 To 1 , 00 , 000 Dwt Vessels ( Panamax Vessels ) As Per Oisd 156 Guidelines In A Phased Manner Phase-Ii .. Submission Date for this Tender is 01-02-2021. Fire Fighting Service Tenders in VPT Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

26397515
Corrigendum : Providing New Fire Fighting Facilities Suitable To The Upgrading Capacities Of Berths Or-I N Or-Ii To Accommodate 50 , 000 To 1 , 00 , 000 Dwt Vessels ( Panamax Vessels ) As Per Oisd 156 Guidelines In A Phased Manner Phase-Ii .
Open Tender
Indian
Andhra Pradesh
VPT
01-02-2021

Tender Details

Providing New Fire Fighting Facilities Suitable To The Upgrading Capacities Of Berths Or-I N Or-Ii To Accommodate 50 , 000 To 1 , 00 , 000 Dwt Vessels ( Panamax Vessels ) As Per Oisd 156 Guidelines In A Phased Manner Phase-Ii .

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Jan-2021 BOQ-Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelines in a p BOQ 16-01-2021
2 06-Jan-2021 DRAWINGS- Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelines Other 16-01-2021
3 11-Jan-2021 CORRIGENDUM Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelin Date 25-01-2021
4 12-Jan-2021 PRE BID REPLIES - CORRIGENDUM-Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per Other 25-01-2021
5 16-Jan-2021 CORRIGENDUM Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelin Other 25-01-2021
6 22-Jan-2021 Corrigendum for Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guide Other 25-01-2021
7 24-Jan-2021 Modified BoQ- Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidel Other 25-01-2021
8 25-Jan-2021 DATE Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelines in a Date 01-02-2021

Key Value

Document Fees
INR 1770 /-
EMD
INR 2839077.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I & OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelines in a phased manner–Phase-II.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Fire Hydrant, Jumbo curtain Nozzles and Water/ Foam Monitors\nSupply, Erection, Testing and Commissioning of Water Cum Foam Tower Monitors in SS316 construction
2 1.01 UL Listed Tower Mounted Long Range Water Cum foam Monitor with fixtures, clamps, SS Fasteners, supporting for riser pipe and monitor suitable to discharge 5678 LPM of water at horizontal range of 80-100 m and vertical range 30-40 m or 5678 LPM foam & water mixture with a horizontal throw range of 70-90 m and vertical range 30-40m with electrical /electro hydraulic equipment's for horizontal and vertical rotation, with base operation control. The operation of tower monitor shall be remote controlled, electrically operated from control tower and from Local flame proof Control panel . \nMOC of Nozzle, Body, Elbow, Bend, Flange, shall be SS316. The Monitor shall be suitable to install on structural platform at height of 20 mtr. All electrical component of shall be flameproof type suitable for gas group IIA/IIB. \nMake: HD Fire/ SBJ / Newage/Fire Tech\n 4 Nos
3 2 Supply, Erection, Testing and Commissioning of Water Cum Foam Ground Monitors in SS316 construction \nUL listed Water Cum foam monitors shall includes all fixtures, clamps, SS Fasteners and flanged connection as per ANSI B16.5 150# . Monitor suitable to discharge 2820 LPM of water at horizontal range of 60 m and vertical range 30 m or 2820 LPM foam & water mixture with a horizontal throw range of 55 m and vertical range 25 m with hadweel for horizontal and vertical rotation, with Manual operation control. \nMOC of Nozzle, Body, Elbow, Bend, Flange, shall be SS316\nMake: HD Fire/ SBJ / Newage/Fire Tech\n 7 Nos
4 3 Supply, Erection, Testing and Commissioning of Jumbo curtain nozzles in SS 316\nJumbo Water curtain nozzles in SS 316 construction, capacity 5000 lpm flanged connection as per ANSI B16.5 150# Complete with all required accessories as per OISD 156-2017 . JC nozzle are required on the central loading platform in front of the loading/ unloading arms . JC Nozzzle shall be capable of operating from the local control panel for each Oil Jetty and operational from Remote Control Panel \nThe MOC of Body, flange shall be SS316. Coverage of nozzle shall be min 40 Mtr horizontally & 20mtrs vertical height.\nMake: SBJ / Newage / HD Fire\n 4 Nos
5 4 Supply, erection, testing and commissioning of Double Headed Standard Fire Hydrants (SS-316 size 63mm)\nMake: SBJ / Sukan / Newage\nHydrant valve Confirming to IS : 5290 Type - A, ISI marked (S.S 316) with two separate landing valve including 80mm dia flanged inlet & 63mm dia female outlet complete with cap and other accessories.
6 4.1 Double headed hydrant valves 11 Nos
7 4.2 Supply , erection , Testing and commissioning 80 mm dia SS 316 with 3mm thk Orifice plates for Hydrant Valve 22 Nos
8 5 Supply, erection, testing and commissioning of External FRP hose cabinet stand/wall mounted type\nFabricated out of FRP Body, 5mm thick & Door with 3mm thk. Front Glass, (3 mm thick glass with rubber beading) door and size of cabinet shall be 900 mm x 750mm x 250mm , quoted rate shall includes suitable stand for mounting, fasteners, Lock, Key, hammer etc. Hose Box shall be suitably marked on the outside with the letters "FIRE HOSE" including necessary locking arrangement\nMake: SBJ / Sukan / Newage 11 Nos
9 6 Supplying , installing, testing and commissioning of 63 mm dia RRL Fire Hose of Type B (as per IS : 636) with SS316 coupling\nMake: SBJ / Newage /Rapiddrop\nof 63 mm dia and length as described below including SS 316 male and female instantaneous type coupling, suitable for burst pressure of min 35.7 kg/sq.cm. Hose shall be permaline hose and coupling to I.S.903-1975 with ISI certification, rivetted to hose pipe with copper rivets & 1.5 mm copper wire\n 22 Nos
10 7 Supplying , installing, testing and commissioning of standard size SS316 Branch pipe with Tripple purpose nozzle standard instantaneous type 63 mm dia coupling as per IS 2871\nMake: SBJ / Newage /Rapiddrop\n 11 Nos
11 8 Hydrant valve Confirming to IS : 5290 Type - A, ISI marked (S.S 316) with single landing valve including 80mm dia flanged inlet & 63mm dia female outlet complete with cap and other accessories.\nMake: SBJ / Sukan / Newage\n
12 8.1 SINGLE headed hydrant valves 3 Nos
13 8.2 Supply , erection , Testing and commissioning 80 mm dia SS 316 with 3mm thk Orifice plates for Hydrant Valve 3 Nos
14 8.3 Supply, erection, testing and commissioning of External FRP hose cabinet stand/wall mounted type\nMake: SBJ / Sukan / Newage\n Fabricated out of FRP Body, 5mm thick & Door with 3mm thk. Front Glass, (3 mm thick glass with rubber beading) door and size of cabinet shall be 900 mm x 750mm x 250mm , quoted rate shall includes suitable stand for mounting, fasteners, Lock, Key, hammer etc. Hose Box shall be suitably marked on the outside with the letters "FIRE HOSE" including necessary locking arrangement\n 3 Nos
15 9 Supplying , installing, testing and commissioning of 63 mm dia RRL Fire Hose of Type B (as per IS : 636) with SS316 coupling\nMake: SBJ / Newage /Rapiddrop\nof 63 mm dia and length as described below including SS 316 male and female instantaneous type coupling, suitable for burst pressure of min 35.7 kg/sq.cm. Hose shall be permaline hose and coupling to I.S.903-1975 with ISI certification, rivetted to hose pipe with copper rivets & 1.5 mm copper wire\n 3 Nos
16 10 Supplying , installing, testing and commissioning of standard size SS316 Branch pipe with Tripple purpose nozzle standard instantaneous type 63 mm dia coupling as per IS 2871\nMake: SBJ / Newage /Rapiddrop\n 3 Nos
17 10.1 Supplying , installing, testing and commissioning of M.S. Swing type of Hose Reel, Wall Mounting type with 19 mm bore with 36 M long Nylon braided high pressure rubber Hose as per IS 884, 6mm bronze shut off nozzle and valve confirming to IS 884. along the SS Isolation valve at tapping point.\nMake: SBJ / Newage /Rapiddrop\n 3 Nos
18 11 Supplying , installing, testing and commissioning of SS 316 Air Release valve with isolation valve of 25 mm. dia.\nMake: Leader / Zoloto / Flowchem\n 1 Nos
19 11.1 Supply , Installation , Testing and commissioning of 25NB Gunmatal (Globe Valve ) Valve for above pressure gauges.\nMake: L&T(Audco), Flowcehm, Advance valves,Venus,Zolato,KBL\n 4 Nos
20 11.2 Supplying , installing, testing and commissioning of M.S. Swing type of Hose Reel, Wall Mounting type with 19 mm bore with 36 M long Nylon braided high pressure rubber Hose as per IS 884, 6mm bronze shut off nozzle and valve confirming to IS 884. along the SS Isolation valve at tapping point.\nMake: SBJ / Newage /Rapiddrop\n 2 Nos
21 12 Supply, erection, testing & commissioning of the following ERW steel pipe as per IS 1239 /3589\nMake: Jindal / Surya Roshni / TATA /Apollo/Lloyds\nSITC of Above ground M S ERW Heavy (Class C) Pipe as per IS:1239 Part-1 for 150mm dia and below & IS:3589 Gr. Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickens of fittings shall be matched with parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB. All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H\nAll ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. \nExternal painting of pipe shall be as per Annexure-1 painting specification. The pipes has to be provided with corrosion and RF pads. Hume pipes, wrapping and coating to be provided where ever pipes are laying under grond.\n
22 12.1 400 NB 450 mtrs
23 12.2 300 NB 1 RO mtrs
24 12.3 250 NB 1 RO mtrs
25 12.4 200 NB 420 mtrs
26 12.5 150 NB 840 mtrs
27 12.6 100 NB 10 mtrs
28 13 Supplying, installing, testing and commissioning of M.S Raised Face flange as per IS 2062 Gr. B , Flange dimensional standard as per ANSI B 16.5 Class 150 and above . All flange shall be provided with internally Poly galss coating 1000 micron\nMake: Fittech/Amforce/ Pipefit/ Montex\n
29 13.1 400 NB 150 Nos
30 13.2 300 NB 1 Nos
31 13.3 250 NB 1 Nos
32 13.4 200 NB 145 Nos
33 13.5 150 NB 290 Nos
34 13.6 100 NB 30 Nos
35 13.7 80 NB 1 Nos
36 14 Supplying , installing, testing and commissioning of SS Super duplex Gate Valve With Rising Spindle ,as per API 603 with flange end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404\nMake: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL\n\n
37 14.1 400 NB 4 Nos
38 14.2 300 NB 1 RO Nos
39 14.3 250 NB 1 RO Nos
40 14.4 200 NB 10 Nos
41 14.5 150 NB 3 Nos
42 14.6 100 NB 25 Nos
43 14.7 50 NB 1 RO Nos
44 15 Supply, Erection, Testing and Commissioning of Motorised SS Super duplex Gate Valve with Actuator.(For Jumbo Curtain & Tower monitor )- 200 NB dia\nMake: L&T(Audco), Flowcehm, Advance valves/CMRI approved : Brans Auma / Rotork / Emerson / Siemens / Danfoss Venus,Zolato,KBL\n\nSS Super duplex Gate Valve with Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and Nut and Bolt as per ASTM A 193 Gr.B8M .The valve shall be tested as per AP I598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404 with open/close limit switches for Position sensing. Torque limit switches for instant torque releasing and control.\na) MOV With Operating Voltage of 415 V AC 50 HZ and flameproof Enclosure with zone IIA/ II B application and 3-phase squirrel cage motor TEFC class F insulated (temperature rise limited to class B) both for motor and its terminal box, for outdoor duty, the motor shall be provided with anti-condensation heater.\nb) Actuator shall be provided with motor over-riding feature like hand wheel for emergency manual operation and a limit switch shall be provided whose contacts shall be used in the motor control circuit to forbid the motorized operation during manual operation by hand wheel. Internal wiring shall be tropical grade PVC insulated, stranded copper conductor cable of 10A rating for control circuits and required rating for motor.\n\n 10 Nos
45 16 Providing & Fixing of Structural steel like Angle, Channels with fabrication, MC200 or MC150 GI coated 200 microns, welding, fasteners etc. complete with corrosion protection as per tender Specifications. \nMake: SAIL /TATA/Essar/Jindal\n 20000 Kgs
46 17 International Shore Fire Connection (IFSC) through which water could be supplied to a tanker fire main if required for shipboard fire fighting. With required accessories.\nMake:SBJ / Sukan / Newage\nOutside Dia : 178 mm\nBolt Circle Dia. : 132 mm\nInside dia : 64 mm\nPipe connection 150NB\nSlots in flange : 4 Holes 19 mm in dia spaced equidistantly on a bolt circle of above dia, slotted to flange periphery flange thickness 14.5 mm minimum.\nBolts and Nuts : 4 Nos. each of 16 mm diameter, 50 mm in length.\n 2 Nos
47 18 Supplying , Installing, Testing and Commissioning of pressure gauges with siphon tube and cock, Glycerine filled, 150mm dial, range - 0 to 25 kg/cm2 as per ,with isolation valve/cock including required all fixing accessories. MOC - SS316 for inlet of Tower Monitor , Water monitor and Water Curtain Nozzle.\nMake: H Guru /General Instruments / Wika\n 15 Nos
48 19 Butterfly Valves of Body Cast Carbon steel ASTM A216 Gr. WCB conforming to BS: 5155 , disc AISI 316, Spindles and retainer ring SSAISI 410, having Nitrile rubber disc seal and body seat, Bronze bearing Bush, Nuts and Bolts SS 316 (For Tower Monitors and Hydrant Valves isolation)\nMake: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL \n100 NB\n 1 Nos
49 20 Supply, Installation, Testing & Commissioning of Modular type ceiling mounted Clean agent type fire extinguisher, ISI Marked IS 15683:2006, having sprinkler with glass bulb rated at 68 deg.C, suitable for Class A,B and C type of fires, Capacity - 15 Kg. (required for Control room).\nMake: Supremex/FireFite/Safex\n 1 Nos
50 21 Fire Water Pump room\n\n
51 21.1 Supply, Erection, Testing and Commissioning of Diesel Engine driven Vertical Turbine pump suitable for rating mentioned below : Pump as per FM/UL listed.\nMake: Pump : Amstrong /Grundfos/KBL/Flowmore/Pentair\nDiesel Engine : Caterpilar / Cummins / MWM, RUSTON /KOEL\n 3 Nos
52 22 SITC of Diesel Engine driven Vertical turbine type pump set (for Hydrant / Water Monitor / Water curtain / Tower Monitor) ,Capacity : 900 cu.mtrs/hr @140 MWC at discharge flange complete with suitable diesel engine, fuel tank, base frame, coupling, coupling guard and all other accessories as required. Pump shall be able to deliver 150% of discharge with minimum 65% rated head with shut off not exceeding 140%. The pump , engine and accessories manufacturing and installation shall comply to OISD codes. Cost include First Fill of Fuel \n(Main Pump set). The pump set and its water contact parts shall be suitable for sea water application (1) MOC of Pump - (a) Casing diffuser: Super Duplex SS, (b) Suction bell mouth: Super Duplex SS, (c) Impeller and allied wear rings: Super Duplex SS, (d) Shaft & Shaft Sleeve: Super Duplex (e) Bearing bush: Thordon (f) Rising (Column) Pipe: Super duplex, (g) Discharge bend: Super Duplex (h) Muff Coupling with collar etc: Super duplex, (i) Suction strainer: Super duplex, (j) Stuffing box: Super duplex, (k) Sleeve, gland: Super Duplex, (l)Fasteners: SS316L, (m) Sole plate, Motor stool: M.S with epoxy coating, (n) Foundation bolts: SS316L, (o) Auto release valve: SS316L, \n (1) The Diesel Engine shall be complete with battery charger panel complete with boost and trickle charging facility, auto-manual selector switch, two sets of maintenance free Lead Acid Batteries, (Batteries to be of sufficient Ampere Hour to be adequate for 10 consecutive starts without recharging with a cold engine under compression) & battery with stand.\n2)Pump shall be Gland packing and companion flanges (SS316L) shall be supplied with pump.\n3) Gear Box: Ambrilo make. AGMA (American Gear Manufacture Association) UL listed\n4) Engine: FM/UL listed. Heat Exchanger Coiled (Sea Water application) with NFPA cooling arrangement. Make: Cummins / KEOL / Cater pillar/MWM/ RUSTON.\n5) Pump shall be with self lubrication.\n6) Column length shall be 16.3 Meter \n7) Pump shall be supplied with suction strainer cleaning arrangement including 25 NB SS316L piping up to pumps, spray nozzles etc.\n8) Pump unit rate shall include all the consumables, lubricants, first filling of diesel, coolant etc.\n9) Residential grade exhaust with suitable thermal insulated. \n10) Fuel Oil storage tank with level indicator and level switch and suitable of 6 hr continuous Operation \n11) Gear Box shall be FM approved \n12) Fuel tank fabricated with min 10 mm plate has to be erected beside each pump separately for running for 6 hours uninterrupted all tanks to be inter connected\n\n\n
53 22.1 Supply, Installation, Testing & Commissioning of Electric driven Vertical Turbine Jockey pump suitable for rating mentioned below capable of starting automatically and also manually.\nMake: Pump : KBL/Flowmore/Pentair \nMotor : ABB/CGL/Seimens/WEG\nSITC of Electrical driven Vertical turbine Jockey pump set Capacity : 900 LPM (54 m3/hr)@150 MWC at discharge flange complete with suitable LT Motor , base frame, coupling, coupling guard and all other accessories as required. The pump , Motor and accessories manfacturing and installation shall comply to OISD codes.\nThe pump set and its water contact parts shall be suitable for sea water application \n (1) MOC of Pump - (a) Casing diffuser: Super Duplex SS, (b) Suction bell mouth: Super Duplex SS, (c) Impeller and allied wear rings: Super Duplex SS, (d) Shaft & Shaft Sleeve: Super Duplex (e) Bearing bush: Thordon (f) Rising (Column) Pipe: Super duplex, (g) Discharge bend: Super Duplex (h) Muff Coupling with collar etc: Super duplex, (i) Suction strainer: Super duplex, (j) Stuffing box: Super duplex, (k) Sleeve, gland: Super Duplex, (l)Fasteners: SS316L, (m) Sole plate, Motor stool: M.S with epoxy coating, (n) Foundation bolts: SS316L, (o) Auto release valve: SS316L, \n1)Motor Shall be Non Flameproof having Suitable KW Rating @ 1500 Rpm \n2)Type : 3-phase squirrel cage motor TEFC class F insulated and IE2\n3) Motor Protection : IP 55 \n4) min 18HP / 13.2KW ( bidder shall validate the same during the contruction stage)\n4) Operting Voltage : 415 V AC Supply @ 50 Hz \n5) Column Length - 16.3 Meter\n\n 2 Nos
54 23 SITC of Cassion pipe cover for vertical turbine pump shaft, MOC, SS316L with all required fixing accessories including painting as per Tender specification. (Length shall be as per postiive suction requirement). The unit rate of pipe shall include cost of fittings and painting.\nMake: Fabricated\n\n\n
55 23.1 800 mm dia - 8 mm Thickness 80 Nos
56 23.2 400 mm dia - 8 mm thickness 40 Nos
57 24 Supply, erection, testing & commissioning of the following ERW steel pipe as per IS 1239 /3589.\nMake: Pipes: Jindal / Surya Roshni / TATA / \nFittings: Fittech/ Pipefit/ Montex\nSITC of Above ground M S ERW Heavy ( Class C ) Pipe as per IS:1239 Part-1 for 150mm dia and below & IS:3589 Gr.Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickens of fittings shall be matched with parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB-W.All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193 \n\nAll ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. External painting of pipe shall be as per Tender (Annexure-1 ) painting specification\n\n\n\n
58 24.1 400 NB 42 mtrs
59 24.2 300 NB 102 mtrs
60 24.3 200 NB 1 mtrs
61 24.4 150 NB 1 mtrs
62 24.5 100 NB 42 mtrs
63 24.6 25 NB 36 mtrs
64 25 MCC Panel- Supply , installation, testing & commissioning of Non Flameproof Modular compartmentalized Motor Control Centre fabricated main body from 14 SWG CRCA sheet. The panel shall be dust and vermin proof, 415V 3Ph, 50 Hz as per IP 42 construction. The panel shall be powder coated with FIRE RED with 7 tank process for clearing and phosphating before powder coating. The panel should be with Suitable incomer & outgoing to meet the above mentioned pumps puls with required starter and MCCBs CT, Voltmeter, Phase indicators, indication lamps, Aluminium bus bars with colour coded heat shrinkable insulating sleeves, All MCCB shall be suitable for motor duty application. Main components shall be of Siemens/Merlin Gerin / L&T / Schneider/ ABB. Cost including for required fabricated angle support, earthing & required also. ( as per site conditions it should be placed inside the pump room-indoor) - Vendor shall submit the GA/SLD drawing for review. Note :( STARTER FOR BOTH JOCKEY PUMPS TO BE INSTALLED IN THIS PANEL ONLY )\nMake: SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ\nA.Outgoing Feeder \na) 415 V Soft Starter for 37 KW motor rating for Jockey Pump - 2 Nos\nb) Out going feeders to diesel pumps-3 No's\nB.Incoming Feeder-250A MCCB, 25KA with required RYB Al. Bus bars.\n 1 Nos
65 25.1 SITC of Diesel engine Non Flameproof Control panel with 2 set of battery charger , on/off push buttons , Hooter for all Diesel engine Fire Pumps with required control cables.\nMake:SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ\n\n 3 Nos
66 26 SITC of Annunciation cum Remote Control panel (at Control Room) with on/off push buttons for all Fire Pumps with required control cables from Main panels. \nMake: Baliga / FCG / CEAG / Sudheer\n 1 Set
67 27 Supplying , Installing, Testing and Commissioning of SS Super duplex valve as per A890GR.F5A with double flanged connection as per ANSI B 16.5 Class 150 , Swing type Non-return valve including SS 316 nuts, bolts, as per ASTM A 193 Gr.88 M & 15mm thick compressed asbestos gasket including matching flanges complete as per requirement.\nMake: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL\n\n\n
68 27.1 400 mm nominal dia 2 Nos
69 27.2 300 mm nominal dia 3 Nos
70 27.3 100 mm nominal dia 2 Nos
71 28 Supplying , installing, testing and commissioning of SS Super Duplex Gate Valve With Rising Spindle ,as per API 603 with flange end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404.\nMake: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL\n\n\n
72 28.1 400 mm nominal dia 4 Nos
73 28.2 300 mm nominal dia 7 Nos
74 28.3 100 mm nominal dia 2 Nos
75 29 Supply , Installation , Testing and commissioning of Gunmatal (Globe Valve ) Valve.\nMake:L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL\n\n
76 29.1 50 NB 2 Nos
77 29.2 40 NB 1 Nos
78 29.3 25 NB 6 Nos
79 29.4 20 NB 6 Nos
80 29.5 15 NB 6 Nos
81 30 Supplying , Installing, Testing and Commissioning of pressure gauges with siphon tube and cock, Glycerine filled, 150mm dial, range - 0 to 16 kg/cm2 as per ,with isolation valve/cock including required all fixing accessories. MOC - SS316.\nMake: H Guru /General Instruments / Wika\n 6 Nos
82 31 Supplying , Installing, Testing and Commissioning of pressure switches with tubing, isolation valves. complete as per requirement steel plated with IP 33 protection.(Inside the Pump room) MOC - SS 316 , DPST Contacts.\nMake: Indfos / Switzer / Wika / Emerson\n 5 Nos
83 32 Supplying , Fixing, commissioning of Electromagnetic Type Flow Meter complete with all accessories Flowmeter of size 300 NB having flow handling capacity of 150% of single pump discharge for test line Body - WCB , Flange 300# - with required accessories matching flanges, nuts, bolts gaskets etc.\nMake: E&H/ Emerson/ Yokogawa/ ABB/ Krohne Marshal\n 2 Nos
84 33 Providing & Fixing of 300NB Pressure Releif Valve . Flange end connection as per ASTM A 16.5 150#. with matching flanges, nuts, bolts, gaskets etc. which ever required as per site conditions.\nMake: Darling muesco / Rapidrop / Viking/Tyco\n 2 Nos
85 34 Supplying , installing, testing and commissioning of Precharged air vessel (size 250 mm dia & 1200 mm height) complete with adequate pressure gauge (as per design / requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, required inlet with isolating valve duly painted from inside and outside complete as required. (The vessel should be suitable of working pressure of 16 Kg/Sqcm including synthetic enamel paint over a coat of primer).\nMake: FABRICATED\n 2 Nos
86 35 LT CABLES
87 35.1 Supplying, laying, testing and commissioning of 1100 Volt grade XLPE insulated PVC type aluminium conductor FRLS armoured cables with required accessories. For Jockey Pump. \nMake: Finolex / Universal /RR Cables / Havells /Polycab\n3 C x35 Sq.mm Al Arm cable for main electrical Jokey and Foam pumps\n 200 Rmt
88 35.2 12 C x 2.5 sqmm Cu Conductor, FRLS armoured as Control Cabling for diesel engine complete with all accessories like double compression cable glands 200 Rmt
89 35.3 24C x 1.5 sqmm Cu Control Armoured Cable for FWPH to Control Room complete with all accessories like double compression cable glands 750 Rmt
90 35.4 4C x 1.5 Sq.mm Cu.conductor armoured cable for Flow meter complete with all accessories like double compression cable glands 100 Rmt
91 35.5 2 C x 1.5 sqmm Cu. Conductor, FRLS armoured cable for Instrumentation complete with all accessories like double compression cable glands 200 Rmt
92 36 G.I. Earthing strips of suitable size shall be run on floor / ceiling / walls, from the equipment to the nearest earth pit with necessary accessories as required. (50 X 10 mm).\nMake: ISI Approved\n 150 Rmt
93 37 Design , construction of Earth Pit for pump house including required earth mat, sand, charcoal, GI pipe ,water civil works and other related works . Size of the eath pit and depth as per site conditions and ensure all selected materials must meet the marine applications. The work as per engineer in charge. of VPT.\nMake: Local\n 1 Lot
94 38 CABLE TRAY\nFRP Ladder / Perforated type cable tray with necessary bands, tees and clamps for fixing. All material shall be FRP. Cable Trays shall be considered with Double Coupler Plates. All Bolts shall be SS 316 .Thickness of the cable tray material shall be 6 mm for 300 mm & above & 4 mm for below 300 mm size.\nMake: EPP/ Sumip/ Ercon\n
95 38.1 300 mm 1 Rmt
96 38.2 150 mm 250 Rmt
97 38.3 100 mm 60 Rmt
98 38.4 50 mm 150 Rmt
99 39 Providing & Fixing of Structural steel like Angle, Channels with fabrication, GI coated 100 microns, welding, fasteners etc. complete with corrosion protection as per tender Specifications.\nMake: SAIL /TATA/Essar/Jindal\n 3500 Kgs
100 40 Foam system\n
101 41 Relocating, Erection and testing of Existing Foam Tanks made of 6mm thick SS-316 plate of 15,000 Litres capacity with inlet, outlet connections, drain, venting, ladder, staging, manhole, level indicator, low and high level alarms, with transparent graduated scale & supports / saddles etc.,( Valves & Piping are of SS). Suitable dyke wall to be constructed to house the tank.\nThe cost shall include the temporary storing arrangement for storage of Foam during relocation of foam tank. and shall attend any repairs required \n 2 Nos
102 42 Supply, testing & commissioning of Motor Driven Gear Operated Foam Supply Pump Set with Non Flameproof motor of capacity 350 LPM at 17 kg/cm2 with all accessories for transfer of AR-AFFF foam. The contractor should provide foundation arrangements to suit grouting and install the same as per clients requirement. MOC of PUMP casing, Rotor/Stator Gear, Rotor/Stator Shaft, Relief Valve shall be SS316. . Motor type shall be TEFC , IP 55 and Power Supply suitable for 415 V AC @ 50 Hz ,45kw motor rating.\nMake: Rotadel/Delta / Delpd / ABB/SIEMENS / BBL / CG)\n 1 Nos
103 43 Supply, testing & commissioning of Diesel Engine Driven Gear Operated Foam Supply Pump Set with engine of capacity 375 LPM at 17 kg/cm2 with all accessories for transfer of AFFF foam. The contractor should provide foundation arrangements to suit grouting and install the same as per clients requirement. MOC of PUMP casing, Rotor/Stator Gear, Rotor/Stator Shaft, Relief Valve shall be SS316. \nMake: Rotadel/Delta / Delpd\n 1 Nos
104 44 Supply & testing of Portable Hand Operated Rotary Pump capacity 50 LPM for filling of foam tank complete with all accessories. The material of construction of rotary pump shall be suitable for foam handling.\nMake: Rotadel/Delta / Delpd\n 1 Nos
105 45 MCC Panel- Supply , installation, testing & commissioning of Modular compartmentalized Motor Control Centre fabricated main body from 14 SWG CRCA sheet. The panel shall be dust and vermin proof, 415V 3Ph, 50 Hz as per IP 42 construction. The panel shall be powder coated with FIRE RED with 7 tank process for clearing and phosphating before powder coating. The panel should be with Suitable incomer & outgoing to meet the above mentioned pumps puls with required Star Soft starter and MCCBs CT, Voltmeter, Phase indicators, indication lamps, Aluminium bus bars with colour coded heat shrinkable insulating sleeves, All MCCB shall be suitable for motor duty application. Main components shall be of Siemens/Merlin Gerin / L&T / Schneider. Cost including for required fabricated angle support, earthing & required also. ( as per site conditions it should be placed inside the pump room-indoor) - Vendor shall submit the GA/SLD drawing for review. \n(STARTER to be installed in control panel).\nMake: SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ\na.Outgoing Feeder \na) 415 V Soft Starter for 45 KW motor rating for main Pump - 1 Nos\nb) Out going feeders to diesel pumps-1 No's\nB) Incoming Feeder-250A MCCB, 25KA with required RYB Al. Bus bars.\n\n 1 Nos
106 46 SITC of Diesel engine Control panel with 2 set of battery charger , on/off push buttons , Hooter for all Diesel engine Fire Pumps with required control cables.\nMake:SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ\n 1 Nos
107 47 SITC of UL listed AR- AFFF 3% foam as IS: 4986:2006 / UL-162.\nMake: Integrated / KV fire / Newage\n 2500 Litrs
108 48 Design, supply, erection and testing of SS-316L Inline Balance Pressure Foam Proportionating System consisting of proportioner, spool valves, foam concentrate valve, drain cock valves, duplex gauge, pressure gauge, check valves at foam concentrate inlet, water & foam sensing line, automatic concentrate control valve with flush connection complete in all respect and suitable for out door installation.(Capable for Flow Max - 12000 LPM with 0.5 max. bar pressure drop).\nMake:Fire Tech /HD Fire\n 1 Nos
109 49 SITC of Above ground Seamless SS316L pipe as per ASTM-A-312, TP-316L, Schedule-20 including cutting, screwing, welding etc. and providing all fittings like elbow, tee, reducer, companion flanges, SS316 nut-bolt, SS washer, EPDM gasket etc as per ASTM-A-403, WP-316L, Schedule-20 / ASTM-A-182, F-316, Class 3000# and including structure supports like clamps, ISMC, ISA, Base plate, hanger, U-Bolt etc. and including cutting holes and chases in brick/RCC wall / slabs complete with External painting with SS pipes painting as per tender specification. The unit rate of pipe shall include the cost of fittings and painting.\nMake: Jindal / Surya Roshni / TATA\n\n
110 49.1 150 NB 1 Mtrs
111 49.2 100 NB foam Pump Suction 12 Mtrs
112 49.3 80 NB- Foam Pump Delivery and up to Propotioner assembly 150 Mtrs
113 49.4 65 NB 1 Mtrs
114 49.5 50 NB - foam fill line 1 Mtrs
115 49.6 40 NB -Foam Pump Return Line 120 Mtrs
116 50 Instruments
117 50.1 SITC of Pressure Switch in SS316 enclosure with SS316 internals, range 0-25kg/cm2 with three way valve manifold of SS construction and all other accessories & SS pipe tubing.\nMake: Indfos / Switzer / Wika / Emerson\n 3 Nos
118 50.2 SITC of Pressure Gauge, Bourdon type, Case- Die cast aluminium with polyethylene paint, movement - Ph bronze, wetted parts - brass, 150mm dial, Range 0 - 30 Kg/cm2, accuracy - +/- 1%.\nMake: H Guru /General Instruments / Wika /\n 6 Nos
119 50.3 SITC Level Switch (For Foam tank)Capacitance type, Enclosure - Die cast aluminium with polyethylene paint Electrode - SS316, Insulation on electrode - PVDF, Process connection - SS304.\nMake: Sigma / Levcon\n 2 Nos
120 50.4 SITC of Local Push Button Stations with start, stop PB, local/remote switch, auto/manual switch & ammeter 2 Nos
121 51 SITC of A351GR.CF8M (SS316) Gate valve, Rising Spindle type with indication of close / open positions, class 300,as per API 600 including SS companion flanges, gasket, SS 316 nut-bolt & washer as per specification.\nMake: L&T(Audco) / GM Engineering /Advance valves Venus,Zolato,KBL\n
122 51.1 80 NB 4 Nos
123 51.2 65 NB 3 Nos
124 51.3 50 NB 1 Nos
125 51.4 40 NB 5 Nos
126 51.5 40 NB SS quick coupling with rubber hose 1 Nos
127 51.6 25 NB ball valve 2 Nos
128 52 SITC of A351GR.CF8M (SS316) Non Return valve (bolted cover) Swing check type, as per API594, class 300 including SS companion flanges, gasket, nut-bolt & washer as per specification.\nMake: L&T(Audco) / GM Engineering /Advance valves Venus,Zolato,KBL\n
129 52.1 65 NB 3 Nos
130 53 SITC of Casting Strainer of SS 316L, including SS companion flanges, gasket, SS 316 nut-bolt & washer as per specification. End connection as per ANSI B 16,.5 Class 150.\nMake: Gujarat Autofit / C thru / Multitex / Grand Prix /\nOtoklin/Nilon\n
131 53.1 80NB 2 Nos
132 54 SITC of Stainles steel SS 316L Pressure regulating valve including companion flanges, gasket, SS 316 nut-bolt & washer as per specification.\nMake: Darling Muesco/ Nirmal/ Sanmar\n
133 54.1 40NB 1 Nos
134 55 SITC of Rectangular type Pressure relief valve of SS 316L (Range 16-20 kg/cm2) of size 40 NB including all fixing accessories.\nMake: Darling Muesco/ Nirmal/ Sanmar\n 1 Nos
135 56 SS 316 drain valve -40 NB/25 NB for foam storage tank , Suction and delivery manifold.\nMake: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL\n 4 Nos
136 57 SITC of Foam barrel for 3% AR- AFFF foam storage of solution (Each Cap 200 litre) - with foam concentrate for Ground water Monitor.\n Make:Integrated / KV fire / Firetech\n 4400 Ltrs
137 58 SITC of Foam barrel for 3% AR- AFFF foam storage of solution (Each Cap 200 litre) - with foam concentrate for testing Purpose.\nMake: Integrated / KV fire / Firetech\n 5400 Ltrs
138 59 Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray inside pump house complete with corrosion protection as per tender Specifications.(Annuxure-1).\nMake: SAIL /TATA/Essar/Jindal 500 Kgs
139 60 SITC of Trolley mounted Foam concentrate tank (for Monitor capacity 2580lpm) of CS Construction (corrosion allowance for plate shall be considered minimum 2mm) with internal 4mm thick FRP lining of effective capacity:500 litre including drain valve etc. with Foam concentrate.\nMake: Fire Tech / HD Fire / New Age\n 3 Nos
140 61 MVWS FOR LOADING /UNLOADING MANIFOLD\nSS Super duplex Gate Valve SS with Rising Spindle ,as per API 603 with flange end connection as per ANSI B 16.5 150 # and Nut and Bolt as per ASTM A 193 Gr.B8M .The valve shall be tested as per AP I598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404.\na)MOV With Operating Voltage of 415 V AC 50 HZ and flameproof Enclosure with zone IIA/ II B application and 3-phase squirrel cage motor TEFC class F insulated (temperature rise limited to class B) both for motor and its terminal box, for outdoor duty, the motor shall be provided with anti-condensation heater.\nb)Actuator shall be provided with motor over-riding feature like hand wheel for emergency manual operation and a limit switch shall be provided whose contacts shall be used in the motor control circuit to forbid the motorized operation during manual operation by hand wheel. Internal wiring shall be tropical grade PVC insulated, stranded copper conductor cable of 10A rating for control circuits and required rating for motor. \nMake: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL\n
141 61.1 \n100 NB 6 Nos
142 61.2 25 NB BALL VALVE 2 Nos
143 62 SITC of Pressure Gauge, Bourdon type, Case- Die cast aluminium with polyethylene paint, movement - Ph bronze, wetted parts - brass, 150mm dial, Range 0 - 30 Kg/cm2, accuracy - +/- 1%. The instrument shall be suitable for zone IIA / IIB area classification.\nMake: H Guru /General Instruments / Wika\n 5 Nos
144 63 Providing and fixing a set of UL Listed SS316 MOC Medium Velocity spray nozzle (housing as per A351-CF8M) as per technical specification of Size 1/2" NPT, SS with required Spray angle. Each Nozzle body permanently marked with model number, batch number, spray angle, K-factor & UL mark.\nMake: HD fire /Tyco/ Viking\n 120 Nos
145 64 SITC of Above ground Seamless SS316L pipe as per ASTM-A-312, TP-316L, Schedule-20 including cutting, screwing, welding etc. and providing all fittings like elbow, tee, reducer, companion flanges, SS316 nut-bolt, washer(80-100micron galvanised)), EPDM gasket etc as per ASTM-A-403, WP-316L, Schedule-20 / ASTM-A-182, F-316, Class 3000# and including structure supports like clamps, ISMC, ISA, Base plate, hanger, U-Bolt etc. and including cutting holes and chases in brick/RCC wall / slabs complete with External painting with SS pipes painting as per tender specification. The unit rate of pipe shall include the cost of fittings and painting.\nMake: Jindal/ TATA/ Surya Roshni\n\n
146 64.1 150 NB 1 Mtrs
147 64.2 100NB 220 Mtrs
148 64.3 80NB 230 Mtrs
149 64.4 65NB 1 Mtrs
150 64.5 50NB 110 Mtrs
151 64.6 40NB 53 Mtrs
152 64.7 25NB 100 Mtrs
153 65 Supplying, laying, testing and commissioning of 1100 Volt grade XLPE insulated PVC type aluminium conductor FRLS armoured cables with required accessories.\nMake: Universal / Havells / RR Cables / Gloster Polycab/KEI\n
154 65.1 2C x 1.5 mm2 Copper Armoured FRLS Cable for pressure switch connection 180 Mtr
155 66 Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray inside pump house complete with corrosion protection SUCH AS zinc coated 200 MICRONS.\nMake: SAIL /TATA/Essar/Jindal\n 5000 Kg
156 67 CONTROL SYSTEM FOR TOWER MONITOR
157 68 Supply, erection and testing of Flameproof Electrical System for remote Operation of tower monitor.\nMake:Honeywell/ Siemens / Rockwell/ ABB/ Yokogawa\na) Common Modular PLC Based remote control panel With Redundant CPU and Dual redundant Power supply Module for Powering field devices for operation of Tower monitor , Water Curtain Nozzle . Control panel shall be CRCA Construction with tender painting scheme including Control Desk with required joy-sticks, Push-buttons, emergency stop switch, indicator lamps including inside wiring, earthing etc. up to terminals, System mimic diagram for displaying and overall view of configuration of tower monitors at Jetty (Status of tower monitors function to be indicated by LED indicators) including all required accessories. .PLC should have sufficient I/O with Several sensor/actuator Bus networks with Ethernet TCP/IP, Multi-task application software, Extended application-specific functions :Counting/position control, Analog/PID, Math functions, Fuzzy logic, etc, Compact pocket-size modules, Open network-Profibus-DP, Device Net, Fast Ethernet. compliant to IEC 61131.\nb) PLC panel have provision of connecting Redundant FO cable to connect Local Control Panel . \nC) Remote panel have provision of fire Pump and foam pump operation and status signal \nD) Control Wiring shall be - 0.75 sq.mm Copper Flexible wires & all wiring enclosed in PVC channels . \nE) Separate Grounding bus will be Provided at bottom of the Panel . \nF) All PLC function shall be tested at Factory before dispatched to site \ng)Third party interface over MODBUS TCP/IP\nh)Gas detection\ni)Communication \nj) MVW Spray System \n\n 1 Nos
158 69 Flame Proof Local control panel of Die-Cast Aluminium construction with sufficient I/O Module , Interface module for Control & Operation of ROM & MOV for ROM & Water Curtain system consisting of ,FORWARD, REVERSE, LEFT, Right, Jet & Fog Push Buttons, SS316 , Explosion proof with double compression flameproof glands, suitable for installation in zone IIA/IIB classified area. wire with 25 % spare TB inside. Local control panel connected to PLC panel through Redundant FO cable \nLocal control panel inclusive of:\na) Input/Output Cards\nb) Analogue Input cards for interfacing of gas detector/flame detectors\nc) Push Buttons\nd) Indicating Lamps\ne) MCB's 6TM AND 6 JC\nMake: Honeywell/ Siemens / Rockwell/ ABB/ Yokogawa\n 12 Nos
159 70 Explosion proof Junction box of Die-cast Aluminium construction complete with all required fixing accessories as per E&I Specification. (JB shall be suitable for installation in zone IIA / IIB classified area).\nMake: FCG / CEAG/Sudheer / FEPL/ Baliga /Flexpro\n 12 Nos
160 71 Supply , Installation , Testing and commissioning of 6C single mode Fibre optic FRLS armoured Cable, PVC jacket, Armoured for Interconnection.\nMake: Molex/ Lapp/ Finolex/ Reliance\n 3000 Mtr
161 72 Supplying, laying, testing and commissioning of 1100 Volt grade armoured Fire Survival cables with required accessories.\nMake: Eloster / Havells / RPG/Finolex Polycab/KEI\n
162 72.1 24C x 1.5sq.mm, Cu. Armoured Cable - Control Cable - (RCP to MCC) 120 Mtr
163 72.2 4C x 4sq.mm, Cu. Armoured Cable - Power Cable - (MCC to LCP) 3850 Mtr
164 72.3 12C x 2.5sq.mm Cu. Armoured Cable - Power Cable - (LCP to JB 510 Mtr
165 72.4 6P x 1.5sq.mm Cu. Armouted Cable - Control Cable - (LCP to JB) 510 Mtr
166 72.5 4C x 2.5sq.mm Cu. Armoured Cable - Power Cable - (LCP to MOV) 600 Mtr
167 72.6 5P x 1.5sq.mm Cu. Armouted Cable - Control Cable - (LCP to MOV) 600 Mtr
168 73 CABLETRAY\nFRP Ladder / Perforated type cable tray with necessary bands, tees and clamps for fixing. All material shall be FRP. Cable Trays shall be considered with Double Coupler Plates. All Bolts shall be SS 316 .Thickness of the cable tray material shall be 6 mm for 300 mm & above & 4 mm for below 300 mm size.\nMake: EPP/ Sumip/ Ercon\n
169 73.1 300mm 800 Mtrs
170 73.2 150mm 3600 Mtrs
171 73.3 50mm 1200 Mtrs
172 74 Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray complete with corrosion protection LIKE ZINC COATING OF 200 MICRONS 6000 Kgs
173 75 VHF- Radio System\nMake: Motoroloa\n\n
174 76 Supply, Installation, Testing & configuration of Hand heel units with 1850 mAh li ion, 16 programmable Channels 12.5 kHz / 25 kHz Channel Spacing, 1-5 Watts Power Output, User manual, 2.5" rugged belt clip, Heliflex Antenna, Rapid Charger etc.. 6 Nos
175 77 Supply, Installation, Testing & configuration of VHF Synthesized Transceiver – REPEATER STATION\nFrequency range 136Mhz to 174Mhz,12.5/25 KHz Channel Spacing,50 Watts Power Output , Compact Microphone & cable Installation Kit (Trunnion), Power Cable, Front facing internal 4WSpeaker, Meets MIL STD 810. RG 213 U CO-AXIAL CABLE WITH CONNECTORS With GP Antenna 0db.\n 1 U/R Nos
176 78 Supply, Installation, Testing & configuration of VHF Base station with required accociated accessories to full fill the requirement. 2 Nos
177 79 Liasioning charge for getting the license for Two Way radios systems Govt. Of India under VPT scope.\n ( renewable every year for the Two way radio also under VPT scope )\n\n\n
178 80 Portable Fire Extinguishers\nMake: Kanex / Safex / ANSUL / SBJ/ Zenith Fire\n\n\n
179 81 Supply, erection, testing & commissioning of Portable fire extinguisher\n9 kg Capacity DCP (Dry chemical powder) Extinguishers , MS seamless body, as per IS:15683 18 Nos
180 82 75 kg capacity wheel mounted dry chemical powder fire extinguisher , as per IS : 10658/1999 12 Nos
181 83 50Lit capacity wheel mounted AFFF foam fire extinguishers as per IS: 13386 3 Nos
182 84 4.5 Kg CO2 fire extinguishers 4 Nos
183 85 Dismantling of Existing under ground / above ground pipes, Fire awater Pumps and associated accessories, Valves (Gate Valves, Butterfly Valves, etc).\n\n\n
184 86 Dismantling includes :\nCutting of Pipes and dismattling of Valves\nHanding over the pipes and Valves to VPT designated location.\nDismantling of Electric Pumps and Motor and its associated accessories\nReplacing of Suction, Delivery, Priming Lines, By Pass Lines Pertaining to proposed New Fire Fighting Pumpsets at New Pump House as per drawings enclosed.\nDismantling of old MS works in joists, angles, plates, bracings, pipes of different sizes etc. including cutting rusty bolts and nuts etc. from damaged / corroded structures of jetty and stacking the materials at shore within 150 mtr. lead. Include for loading the dismantled steel materials into truck at Oil Jetty area, carriage of the materials over pucca road lead upto 2-4 Kms. and unload at the VPT Store Division after weighment, stack properly in stack yard etc. as directed including carriage by head load upto a lead of about 30 m of each of the two points.\nExisting Pipe \n450 NB \nExisting Tower monitor - Structral Steel , height 15 meter \nFoam Pump and accessories \nExisting valves Size from 400 NB to 100 NB \nExiting Hydrant Valve and Water monitor with Accessories \n 1 LOT
185 87 Civil work \n\n
186 88 Construction of 20 meter Height RCC civil structure for remote operated monitor with fire proof coating. The top platform of the tower structure shall be 2.5m x 2.5m dimension. The design of RCC structure shall be suitable for wind, sway & siesmic load calculation and calcuation shall be performed on approved licensed software.\nThe tower shall be applied with fire paint UL listed for 2hr fire rating, Min. 7mm thick. The cost shall also include Pile/Open/Raft Foundation as suitable for the given soil load barring capacity.\nPrice for Civil including the following work . Excavation and bacfilling , Civil foundation and operating platform and strair case with hand rail ( concrete ) Design and drawing to be approved by NIT/IIT/Any ICAS member \n 4 Nos
187 89 Tower for Monitor with platform on top of the tower and necessary safety guards, ladder, & mid landing, etc. The tower shall design a taper lattice type steel structure of height 20 m and operating plateform shall be 2.5 m x 2.5 m & the base shall be as per the suitable wind, sway & siesmic load calculation. The calculation shall be performed on approved licensed software. The lattice structure/round pipe structure made from Structural supports including ISA/ISMC/M.S Pipe/M.S Plates/stiffener plate /u bolts/clamps etc. \nThe entire steel structure shall be applied with vermiculite based lightweight fireproof cementitious of thickness corresponding to 2 hours fire rating as per respective UL design number under UL-1709 (XR category) subject to a minimum of 30mm. Vermiculite based lightweight cementitiuos fireproofing system\n 1 UR NO
188 90 RCC Pedestal for above ground pipe .( 400 NB ) Price for civil including Excavation and backfilling and PCC footting etc \n\n
189 90.1 For 400 NB Pipe Double Pipe Support( RCC civil foundation height 300/400 mm from above FFL ) min 1.5Mtrs width. The scope of work including all related civil works like digging, refilling , making flat PCC all in scope of work. 80 Nos
190 90.2 For 400 NB Pipe Single Pipe Support ( RCC civil foundation height 300/400 mm from above FFL ) min. 900mm width. The scope of work including all related civil works like digging, refilling , making flat PCC all in scope of work. 75 Nos
191 90.3 For 200 NB/150NB/100NB Pipe Single Pipe Support ( RCC civil foundation height 300/400 mm from above FFL ) min. 700mm width. The scope of work including all related civil works like digging, refilling , making flat PCC all in scope of work. 270 Nos
192 91 RCC foundation for Fire Water pumps , includes reinforment for founadation Foam pumps and Foam Storage tank 30 Cu.meter
193 92 RCC/PCC Foundation for Water monitor Operating Plat form and Hose Box foundation 30 Cu.meter
194 93 Excavation and backfilling of Soft Soil for under ground piping 40 Cu.meter
195 94 RCC Civil foundation for MS. Platform 15 Cu.meter
196 94.1 Design, Supply, Installation, Testing , loading and unloading of Construction of Control Tower with ( 5Mtrs x 5Mtrs x 22Mtrs with landing outside for stair case with Ground Floor +TOP Floor with 4 feet walk way out side the room ) Design and claculation to be approved by IIT/NIT/Any IACS member below specification to be followed : \nBoring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). 600 mm dia Note: Truck Mounted rotary/TMR/Tubewell boring machine shall not be used .\nVertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge. Single pile upto 50 tonne Safe capacity Initial test (Test Load 2.5 times the Safe\ncapacity)\nVertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Routine test ( Test load 1.5 times safe load)\nEarth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.\nCEMENT CONCRETE (CAST IN SITU) Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone\naggregate 40 mm nominal size)\nDESIGN MIX CONCRETE Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).All works upto plinth level\n 1 Lot
197 94.2 DESIGN MIX CONCRETE Providing and laying in position machine batched and machine mixed design mix M 30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).All works above plinth level upto floor V level\nFORM WORK Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete s\nFORM WORK 5.9 Centering and shuttering including strutting, propping etc. and removal of form for : Suspended slabs, beams, columns etc\nSTEEL REINFORCEMENT 5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more\nTop Floor slab min 2m away from main wall that is (7x7 meter area ) with 3 feet sun shed sloped with concrete work only Designed approved by NIT/IIT/Any IACS Member \nBrick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand)\n18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge\nCEMENT PLASTER (IN FINE SAND) 12 mm cement plaster of mix : 1:6 (1 cement: 6 fine sand)\nDistempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water thinnable priming coat with cement primer sqm 153.45 13.42 Distempering with 1st quality acrylic distemper inside finishing\nEXTERIOR FINISHING: Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm)\n\n\n
198 95 Providing and fixing water closet squatting pan (Western pan ) with S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: 17.1.1 White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests wash room to be furnished by tiles at six feet level 1 Nos
199 96 Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :Range of two urinal basins with 5 litre white P.V.C. automatic flushing cistern 2 Nos
200 97 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar tap \nProviding and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:\n(a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC. slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.\n(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.\n(c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge.\n(d) Finishing the surface with 20 mm thick joint less cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep.\n(e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. “All above operations to be done in order and as directed and specified by the Engineer-in-Charge :\n
201 98 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates\nand similar works \nS & F Door suitable to marine environment \nS & F Window/ aluminium frame with glasses \nProviding and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size 600 X 600 mm\nProviding and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete.\nDesign & built, providing & fixing of industrial grade capsule lift including all fittings, accessories complete as directed by EIC, Lift liesence certificate from the government body under vendor scope. The vendor have responsible till the complete the all works up to VPT satisfactory and hand cover the lift.\nMake: RK Elevators / Sunrise Lifts /Schiender\nTop floor 3 wall mount fans, and one two ton split AC , necessary lighting and socket points.\nMake: LG/VOLTAS/ for split AC and USHA /CROMPTON for fans\n
202 99 Electrical Audit of the entire berth by a competent person under Petroleum rule 114. and OISD guidelines related to Electrical Installations submit to VPT Project In charge \n1. Supply of any material must be as per site conditions and with prior approvals from VPT 2)Transportation for contractor’s staff, tools and tackles and consumables to the site is in the scope of contractor. 3) At present there is no power supply at berth. The power supply is in the scope of contractor.\n5) . For fabrication of materials at fabrication yard (on shore )supply shall be provided on chargeable basis 6) . The Vendor must visit the site and understand the site conditions and VPT requirement and accordingly Remote control PLC based panel shall be considered. 7) All line items are billable against actual ITEMS ARE FABRICATED AND ERECTED AT SITE\n 1 Lot
203 99.1 Supply , Installation , Testing and Commissioning of Fire alarm and Control Panel having the Following features:\na) Redundant Central Processing Unit ( CPU)\nb)16 lines 40 character backlit alphanumeric liquid crystal display (LCD)\nc) Loop ( signalling line circuit) Control Module with loop capacity of max. 250 devices. ( No. of loops : 3 nos.)\nd) Redundant Power Supply Unit\ne) Modbus gateway ( Redundant) \nf) Network Communication Interface for repeter panel.\ng) 24 hours backup battery and battery charger\nj) Stand alone enclosure\nk) Autodialer ( 5nos. dialing)\nl) Loop expandable to 5 loops \nApprovals : UL listed / FM / VDS approved.\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 1 Nos
204 99.2 Supply , Installation , Testing and Commissioning of Repeater panel having the same display size and keypads as the Main Fire alarm Panel with required network communication interface unit.\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 1 Nos
205 100 FIELD DEVICES
206 100.1 Supplying, Installation, Testing and Commissioning of Addressable Multi-criteria Detector (Smoke & Heat).The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Device shall be with standard base. UL Listed.\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 20 Nos
207 100.2 Supply, Installation, Testing & Commissioning of Flame proof Conventional Manual Call Point for outdoor marine application with Stainless Steel(SS-304) hardware, Material, 2Wire : Aluminium Lm6, IP 65, Anti corrosive epoxy powder coated Finish, Cable Entry : 2 x M25, Neoprene Gasket, 24V DC operating Voltage. The line item should include 1 meter length MS channel painted with Fire red colour to mount the MCP along with canopy and Flame proof double compression cable glands & Flame proof MS platted stoppers to shield against rainy conditions and FLP JB with foundation works and related flexible hard conduits till the Hooter.\nMake: Flamepack / Baliga /\nFlexpro / Neptune / Airlight/ FEPL/ EX-Protecta\n 23 Nos
208 100.3 Addressable Monitor Module for monitoring of FLP Manual call point \nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 23 Nos
209 100.4 Supply, Installation, Testing & Commissioning of Flame proof Conventional Hooters For outdoor marine application Hooter, FLP, Type: Conventional \nArea classification: ZONE 1- Gr. IIA/IIB\nMOC : Aluminium diecast (LM6)\nIP rating -IP66 -\nInput Supply :24V DC; \nSound level:106dB at 1 meter distance; \nTone type: Single tone;\nCable Entries: 2Nos 0.75ET;\nFinish: Epoxy Light grey shade 631/IS-5. With FLP double compression glants and Plugs. \nMake: Flamepack / Baliga /\nFlexpro / Neptune / Airlight/ FEPL/ EX-Protecta\n 10 Nos
210 100.5 Supply, Installation, Testing & Commissioning of Addressable Safe Area Manual Call point.\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 2 Nos
211 100.6 Addressable Control Relay Module for driving of FLP hooters .\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 10 Nos
212 100.7 Addressable Relay Module for AHU tripping & closing of Fire Dampers.\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 2 Nos
213 100.8 Supplying, Installation, Testing and Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. FLP JB shall be considered. ( if required by system)\nMake: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK\n 6 Nos
214 100.9 Supply installation, Testing & Commissioning of Flame Proof Electrical Siren with Horizontal Single Mounting single Phase 220/250V, 2800 RPM 50Hz, AC RPM 50 C/s 1 km range, 1/2 HP, with required accessories like Flame proof double compression cable glands & Flame proof MS platted stoppers to shield against rainy conditions with required junction box. with required starter control panel to start / stop manually from control room or specified locations.\nMake: Kheraj / Perfect\n 2 Nos
215 101 FLAME AND GAS LEAK DETECTION SYSTEM
216 102 HYDROCARBON GAS DETECTORS ( ZONE -1 - EEx'd)\nType : Infrared Point type\nAccessories to be supplied : Calibration cup, Splash guard/dust guard ( SS material), rain guard , flashback arrestor , collecting cone \nDetector output: 4-20ma\nRange : 0-100% LEL\nWith display unit \nPoison resistant\nResponse time : T90</+ 10 seconds\nRepeatability : +/- 2% FSD\nIP rating : IP-65 Detector\nHousing material : SS 316\nZero drift : 2% FSD per year maximum \nCertification : FM approved/ UL listed\nHazardous certification Approval : PESO/CMIFR \nAmbient Temperature : 0-50degree C\n( Detector will be connected to nearest LCP)\nMake: Drager / Oldham / Crowcon / Gas sensor/ Det- Tronics\n 24 Nos
217 103 FLAME DETECTOR\nType: UV/IR \nSpectral Response: UV: 0.185-0.260 µm; IR: 2.5-3 µm \nDetection Range: For Methane 16 Feet \nResponse Time: 5 seconds; High Speed 150 msec response to saturated signal Adjustable time delay up to 30 seconds Sensitivity Range: up to 15 meters \nField of view: Horizontal: 100 degrees, Vertical: 95 degrees Should have Automatic and Manual in-built test to ensure continued reliable operation Detector output: 4-20ma Should have Heated window for operation in harsh weather conditions \nOperating temperature: -40 OC to +70 OC \nPower supply: 18 to 30 V DC \nCable Entry: 2 entries \nShould be EMI/ RFI protected as per EN61326-3 and EN61000-6-3 \nOutputs: i) Relays for alarm ii) fault indication iii) 4-20 mA iv) HART protocol v) RS-485 output \nShould have a special logic circuit to help prevent false alarms caused by solar radiation. \n Enclosure: Explosion proof \nIngress Protection: IP 66\nCertification : FM approved/ UL listed\nHazardous certification Approval : PESO/CMIFR \n( Detector will be connected to nearest LCP)\nMake: Tyco / Agni Controls/ Spectrex/ Rezontech / Gas sensor\n 6 Nos
218 104 FLAME AND GAS LEAK DETECTION SYSTEM
219 105 Supply, Installation, Testing & Commissioning of Flame Proof-Exf T6 IP 65 Speaker with 30W rated and 15W/20W/25W line matching transformer with Cast Aluminium LM 6, ZoneI & II, Gas groups Class-I & IIA, IIB, IIC, Neoprane Gasket, SS, 100V / 70V Line transformer, Sound output 115db, earthing terminals, input terminal blocks, Pilfer proof, FLP JBs with Mounting MS stand corrosion resistance for Hooter and JB with foundation works and related flexible hard conduits till the Hooters. Approval CCE & BIS, IS 2148.\nMake: Baliga\n 12 Nos
220 106 Supply, Installation, Testing & Commissioning of 6W wall Mount Speaker with line matching transformer and mounting accessories for indoor application.(For office area etc).\nMake: Honeywell/ Bosch/Aties\n 5 Nos
221 107 Supply, Installation, Testing & Commissioning of 6 Zone PA controller built in amplifier . And shall have pre-recorder massage facility to evacuate in case of emergency conditions, and as per technical specification.\nMake: Honeywell/ Bosch/Aties\n 1 Nos
222 108 Supply, Installation, Testing & Commissioning of 240 / 480W Power Amplifier.\nMake: Honeywell/ Bosch/Aties\n 1 Nos
223 109 Supply, Installation, Testing & Commissioning of 6 Zone Call Station with Goose neck Mic. with interconnecting cable. \nMake: Honeywell/ Bosch/Aties\n\n 1 Nos
224 110 Supply & Fixing of PA Rack .( Height as per site conditions) with interconnecting cable and cable power manager.\nMake: Honeywell/ Bosch/Aties\n 1 Nos
225 111 Supply, Installation, Testing & Commissioning of Music DVD Player with interconnecting cable.\nMake: panasonic / Philips\n 1 UR Nos
226 112 CLOSED CIRCUIT TELEVISION
227 113 CCTV Cameras: Cameras shall be True Day/night and shall have Motion detection, tamper detection, WDR, Electronic shutter, White balance, BLC,DC IRIS, Anti-flicker, Vandal proof Housing(IEEE802.3 CLASS 3). Cost shall be inclusive of fixing accessories such as mounting stand etc. Camera should be POE Enabled & should be FCC & UL listed/Approved & also ONVIF compliant. Other requirement shall be as per technical specification. Note: The contractor shall propose the best suitable CCTV camera which shall cater to the operational requirement asked for. The contractor shall select the lens, resolution, view angle, type and other parameters of the camera and propose this best technology camera to cater the requirement as per the indicative location of the CCTV cameras are shown in the layouts. The contractor shall furnish the breakup sheet for total number of CCTV camera selected along with his quote.\nEnclosure : Flameproof , PTZ\nMake: Axis/ Bosch/Interlogix/ Pelco\n 6 Nos
228 114 Network Video Recorder ( NVR)
229 115 The storage solution shall be NVR based with Hot swappable of hard drive and hot spare redundancy (N+1). The actual estimated storage requirement shall be worked out as per the number of cameras at 10 fps, 4CIF resolution for 45 days storage. The contractor shall propose the best cost effective solution for storage with reference to the parameters mentioned in the technical specification. The contractor shall furnish the backup calculation sheet for storage while quoting.\nMake: Axis/ Bosch/Interlogix/ Pelco\n 1 Nos
230 116 Video Management Software:
231 117 The Video Management System shall be a software based solution running on SMS server and communicating over Ethernet network using the TCP/IP network protocol. The proposed solution shall be based on the latest compatible Windows Server Operating System. The NVMS shall sustain full operation using CIF, 2CIF, VGA, 4CIF, 800 x 600 (0.5 m pixel) and Megapixel video\nresolutions (upto 5 MP ). It shall support all types of cameras and latest compression technology and Onvif compliant. The contractor shall propose his best solution to meet the requirement. The cost shall include the required licenses to meet the requirement.\nMake: Axis/ Bosch/Interlogix/ Pelco\n 1 Nos
232 118 IP Based Joystick Controller for PTZ Cameras. The same should be FCC & UL listed.\nMake: Axis/ Bosch/Interlogix/ Pelco\n 1 Nos
233 119 MS poles for outdoor cameras, made out of 5mm thick, 80mm dia pipe with zinc chromite primer & powder coating of suitable shade along with Outdoor IP 65 rated Flameproof Junction box for termination, Power supply & module fixing. Total Pole height including pedestal = 5Mts.\nMake: Local\n 6 Nos
234 120 F) NETWORKING ACCESSORIES \n\n
235 121 Supply, Installation , Testing and Commissioning of 24 ports , 10/100/1000Base-T ports + 4 SFP ports Metro Ethernet Switch and shall be rack mountable with SMPS power supply & other termination. The switch shall have 1 Gigabit port to communicate with other switches. Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann 1 Nos
236 121.1 Supply, Installation , Testing and Commissioning of 8 ports , 10/100/1000Base-T ports + 2 SFP ports Metro Ethernet Switch and shall be rack mountable with SMPS power supply & other termination. The switch shall have 1 Gigabit port to communicate with other switches.\nMake: Moxa / Dlink/ Net gear / Cisco/ Hearschmann\n 6 Nos
237 122 Supply, Installation , Testing and Commissioning of Wall Mount enclosure (9U x 550 W x 500 D) ,\nFront Glass Door (tinted, Toughened) with Lock & Key, 2 pairs of 19" Mounting Rails with U-Marking Welded Side Walls \nStandard Accessories: 1U Cable Manager (1), Hardware Packet (1 Pkt) 6 Socket 5 Amp. Power Distribution Unit (1 No) Roof Mounted Fan Unit / 90 CFM /230V AC (1 No).\nMake: Moxa / Dlink/ Net gear / Cisco/ Hearschmann\n 6 Nos
238 123 Supply, Installation , Testing and Commissioning of LIU 24 PORT Rack Mount - Loaded (SC) SM.\nMake: Local\n 1 Nos
239 124 Supply, Installation , Testing and Commissioning of Work station: 70 inch Monitor\nOS comprising Intel Xeon Processor, Quad Core 3.2 GHz. 8 GB\nddR3 Ram, 500GB SATA Hdd, USB Ports, Keyboard & Mouse.\nMake: HP/ DELL\n 1 Nos
240 125 CABLES AND ACCESSORIES\n\n
241 126 Supply, Installation , Testing and Commissioning of the following size of Armoured Cables and type \n\n
242 126.1 1P X 1.5 Sq.mm Fire Survival cable for Manual call point Loop connections.\nMake: Polycab/Technoflex/KEI\n 4500 Mtrs
243 126.2 2C X 2.5 Sq.mm FS cable for Hooter Loop connections.\nMake: Polycab/Technoflex/KEI\n 1250 Mtrs
244 126.3 1P X 1.5 Sq.mm Fire Survival cable for FLP Speakers connections.\nMake: Polycab/Technoflex/KEI\n 3000 Mtrs
245 126.4 Supply, Installation, Testing, and commissioning of GI Conduit applicable for marine applications with required foundation works and fittings.\nMake: ISI mrked\n 1000 Mtrs
246 126.5 Cat - E Ar. cable for Camera integration.\nMake: Dlink / Belden / Radiant\n 600 Mtrs
247 126.6 3C X 2.5 Sq.mm FS Power cable for Network Switches.\nMake: Polycab / Bonton /Deepanja/ Polycab / Radiant\n 2000 Mtrs
248 126.7 Supply , Installation , Testing and commissioning of 6C single mode Fibre optic FRLS armoured Cable, PVC jacket, Armoured for Interconnection for CCTV & Repeater Panel.\nMake: Molex/ Lapp/ Finolex/ Reliance\n 2400 Mtrs
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail