Indian Oil Corporation Limited-IOCL has published Supply , Installation , Testing And Commissioning Of 8 . 5 Tr And 11 Tr Ductable Ac As Per Tender Specification At Digboi Refinery. Submission Date for this Tender is 26-12-2020. Coats and Jackets Tenders in IOCL (AOD) DIGBOI Assam. Bidders can get complete Tender details and download the document.
Name of Work: SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 8.5 TR AND 11 TR DUCTABLE AC AS PER TENDER SPECIFICATION AT DIGBOI REFINERY | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | List of item(s) / work(s) as per tender documents | |||
2 | 10 | Design, Engineering, Manufacturing And Procurement Of Materials And Bought Out Components, Assembly, Supply, Erection, Testing, Commissioning, Performance Guarantee Testing at Site of 8.5 TR, 01 No. Air Cooled Ductable Package Air Conditioners For gymnasium hall of TT cum Gym building near Digboi Club As per Technical Specifications & Scope Of Work. | Item10 | 1 | EA |
3 | 20 | Design, Engineering, Manufacturing And Procurement Of Materials And Bought Out Components, Assembly, Supply, Erection, Testing, Commissioning, Performance Guarantee Testing at Site of 11 TR, 01 No. Air Cooled Ductable Package Air Conditioners For TT hall of new TT cum gym building near Digboi club As per Technical Specifications & Scope Of Work | Item20 | 1 | EA |
4 | 30 | Installation testing and commissioning of ductable split AC complete with all material and labour to ensure completion of the job in totality as per directions of EIC. The AC operation must be through a small wall mounted control panel completely flushed inside wall with concealed wiring. A wireless remote control to be provided with each system for remote operation | Item30 | 2 | EA |
5 | 40 | DUCT FABRICATION\ni) 22 Gauge | Item40 | 20 | M2 |
6 | 50 | DUCT FABRICATION\nii) 24 Gauge | Item50 | 70 | M2 |
7 | 60 | ACOUSTIC INSULATION\nSupplying and fixing acoustic insulation on the surface of supply air duct, laminated with 12 mm thick fibre glass of density 48 kg/cum and covered with 30 SWG aluminium perforated sheet. | Item60 | 20 | M2 |
8 | 70 | THERMAL INSULATION\nSupplying and fixing thermal insulation on the outer surface of supply air duct with 25 mm thick fibre glass of density 24 kg/cum with cold bituminous adhesive and fibre glass should be Aluminium foil pasted, secured by PVC strap and anchor clip. | Item70 | 70 | M2 |
9 | 80 | REFRIGERANT PIPING\ni) For split AC\nSupply and installation of refrigerant piping suitable for Above split A.C. Units including Nitryle Rubber Insullation | Item80 | 10 | M |
10 | 90 | REFRIGERANT PIPING\nii) For Ductable AC\nSupplying and installation of Copper Refrigerant pipe as suitable size (for set of suction and liquid line) with Armaflex insulation for Ductable Split Air Conditioner. | Item90 | 15 | M |
11 | 100 | Grills\nSupply and installation Aluminium Powder coated Grills for supply / Return air including all accessories complete | Item100 | 4 | M2 |
12 | 110 | DRAIN PIPING\ni) 25 mm | Item110 | 25 | M |
13 | 120 | DRAIN PIPING\nii) 32 mm | Item120 | 100 | M |
14 | 130 | Canvass connection | Item130 | 10 | EA |
15 | 140 | ODU Structure Wall split AC\nSupplying and installation of M.S. fabricated ODU Structure installation with all accessories for Wall split AC | Item140 | 1 | EA |
16 | 150 | ODU Structure Ductable AC\nSupplying and installation of M.S. fabricated ODU Structure installation with all accessories for Ductable AC | Item150 | 4 | EA |
17 | 160 | Power/ control cabling 3c x 2.5 sq. mm.\nSupply and installation of electrical Power/ control cabling of suitable size between indoor units and indoor units | Item160 | 550 | M |
18 | 170 | DISMANTLING ALUM. / GYPSUM CEILINGS ETC.\nDismantling aluminum/Gypsum partitions, doors, windows, fixed\nglazing and false ceiling including disposal of unserviceable surplus\nmaterials and stacking of serviceable material with in 50 meters\nlead as directed by Engineer-in-charge | Item170 | 50 | M2 |
19 | 180 | 12.5 mm thick tapered edge gypsum moisture resistant board | Item180 | 70 | M2 |
20 | 190 | Two or more coats applied on walls @ 1.25 ltr/10 sqm. over and including one coat of Special primer applied @ 0.75 ltr / 10 sqm. | Item190 | 70 | M2 |
21 | 200 | Providing and applying plaster of paris putty of 2mm thickness over\nplastered surfaces to prepare the surface even and smooth complete | Item200 | 70 | M2 |
22 | 210 | HAND RAILS\nProviding and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony\nrailing & stair case railing & stair case railing including applying a priming coat of approved steel primer.\nM.S. TUBE | Item210 | 30 | KG |
23 | 220 | With cement issued at issue rates from Owner's Stores, including transportation from Stores to work site and returning all excess/ unused cement to Owner' Storeage point after completion of work- Washed stone aggregate 20 mm nominal size | Item220 | 2 | M3 |
24 | 230 | Area indexation @ 26.73% | Item230 | 1 | LS |