Military Engineer Services-MES has published Repair / Maint / Servicing Of Central Gas Plant , Modular Operation Theatre Including Repair/ Maint Of Various Types Of Fans , Stabilizers , Misc B/R Work In The Area Of Age Em ( Hosp ) Under Ge E/M Lucknow .. Submission Date for this Tender is 09-01-2021. Medical Gas System Tenders in Lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 02-Jan-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 09-01-2021 |
Name of Work : REPAIR / MAINT / SERVICING OF CENTRAL GAS PLANT, MODULAR OPERATION THEATRE INCLUDING REPAIR/ MAINT OF VARIOUS TYPES OF FANS, STABILIZERS, MISC B/R WORK IN THE AREA OF AGE EM (HOSP) UNDER GE E/M LUCKNOW. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Comprehensive servicing and maintenance of central gas pipe line system comprising of Oxygen, Nitrous and compressed air system of desired pressure required to operation theatre-05 Nos at Command Hospital (CC) including regular & periodical maintenace/overhauling,replacement of air filters,tail pipe, NRV, pressure control switch, machine belts and shut off valves,including all connected equipments installed for the said purpose having following components of various make/capacity:- Note :- Register signed by Contractor, AGE E/M and USer same time whenever work carried out \n(a) Oil free comprssor of capacity 7.5 HP of make Multitech with pressure control switch-02 Nos\n(b) Heatless air drier of capacity 30cfm of make Multitech-02 Nos\n(c) Automatic control panel for oxygen with alarm system-01 No. \n(d) Automatic control panel for Nitrous oxide with alarm system-01 No. \n(e) 6+6 cylinder Oxygen manifold with NRV & 12 Nos flexible tail pipe-01 No\n(f) 2+2 cylinder Nitrous oxide manifold with NRV & 04 Nos flexible tail pipe-01 No\n(g) Electrical control panel for above compressor \n(h) Digital area alarm system of four gases-01 No\n(j) Parkodex outlet points confirming to HTM-2022/NFPA-99 for oxygen vaccum compressed air & nitrous oxide-44 Nos. \n(k) Isolation valve of 28mm,22mm,15mm & 12mm-20 Nos.\n(l) Backpressure compensated flow meter with humidifier bottles -10 Nos.\n(m) Copper pipe line complete of dia 28mm,22mm,15mm & 12mm installed in the OT complex-600 RM\n(n) Ward vaccum unit with 2000ml polycarbonate jar-08 Nos.\n(o) Joint weekly visit shall be arranged by the contractor and all the OT lights shall be made functional in all respect and necessary report duly signed by the OT incharge of CH(CC) and Base Hospital and JE Concern shall be submitted to AGE Hosp on Same Day . Inspection note shall be endorsed by technician related of repair works to be carriedout.\n(p) Urgent spares shall be readly made available at site during all days by the contractor. | BI01010001010000000000000515BI0100001114 | 12 | Each Job (Every fortnightly) |
2 | 2 | Supplying, and fixing Isolation valve with brass connectors of size 12 mm including testing and commissioning complete all as specified and as directed by Engineer -in-Charge. | 20 | Each | |
3 | 3 | Supplying, and fixing Isolation valve with brass connectors of size 15 mm including testing and commissioning complete all as specified and as directed by Engineer -in-Charge. | 20 | Each | |
4 | 4 | Supplying, and fixing Isolation valve with brass connectors of size 22 mm including testing and commissioning complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
5 | 5 | Supplying, and fixing Isolation valve with brass connectors of size 28 mm including testing and commissioning complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
6 | 6 | Supplying, fixing, testing and commissioning hook loose type outlet point dia cast zinc alloy, for oxygen, compressed air, vacuum and nitrous oxide with stainless steel box complete all as specified and as directed by Engineer -in-Charge | 15 | Each | |
7 | 7 | S&F probe for oxygen outlet unit, compressed air, vacuum and nitrous oxide complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
8 | 8 | Supplying, errecting, testing and commissioning mobile floor suction unit for operation theatre made out of stainliess steel having one vacuum regulator and two suction jar of 2000 ml capacity complete all as specified and as directed by Engineer -in-Charge | 4 | Each | |
9 | 9 | Supply, fixing, laying, testing and commissioning wall mounted ward vacuum unit with collection bottle (200 ml) and regulator including adopter/ commecting clear plastic/ rubber tubes and connecting up complete all as specified and as directed by Engineer -in-Charge | 4 | Each | |
10 | 10 | Supply, fixing, laying, testing and commissioning of back pressure compensated oxygen flow meter (BPC) and humidifier including adopter and connecting up complete all as specified and as directed by Engineer -in-Charge | 18 | Each | |
11 | 11 | Supplying, fixing, laying, testing and commissioning Oxygen H.P. antistatic rubber tube color coded 'white' of suitable length & size including required fittings and connecting up complete all as specified and as directed by Engineer -in-Charge | 30 | RM | |
12 | 12 | Supplying, fixing, laying, testing and commissioning Oxygen L.P. antistatic rubber tube color coded 'white' of suitable length & size including required fittings and connecting up complete all as specified and as directed by Engineer -in-Charge | 30 | RM | |
13 | 13 | Supplying, fixing, laying, testing and commissioning of oxygen gas outlet (as per HTM-2022 / NFPA-99) with and including matching adopter and connecting up complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
14 | 14 | Supplying, fixing, laying, testing and commissioning of compressed air (4 Bar) outlets (as per HTM-2022 / NFPA-99) with and including matching adopter and connecting up complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
15 | 15 | Supplying, fixing, laying, testing and commissioning of Nitrous gas outlets (as per HTM-2022 / NFPA-99) with and including matching adopter and connecting up complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
16 | 16 | Supplying, fixing, laying, testing and commissioning of Vacuum gas outlets (as per HTM-2022 / NFPA-99) with and including matching adopter and connecting up complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
17 | 17 | Supplying, laying, testing and commissioning medical gases distribution piping system comprising of copper pipes of 12 mm outer dia, having wall thickness 0.90 mm including Tees, Bends, Sockets, Specials, Fittings and fixtures etc. and applying two coats of suitable paint of required colour complete all as specified and as directed by Engineer -in-Charge | 60 | RM | |
18 | 18 | Supplying, laying, testing and commissioning medical gases distribution piping system comprising of copper pipes of 22 mm outer dia, having wall thickness 0.90 mm including Tees, Bends, Sockets, Specials, Fittings and fixtures etc. and applying two coats of suitable paint of required colour complete all as specified and as directed by Engineer -in-Charge | 50 | RM | |
19 | 19 | Supplying, laying, testing and commissioning medical gases distribution piping system comprising of copper pipes of 15 mm outer dia, having wall thickness 0.90 mm including Tees, Bends, Sockets, Specials, Fittings and fixtures etc. and applying two coats of suitable paint of required colour complete all as specified and as directed by Engineer -in-Charge | 50 | RM | |
20 | 20 | Supplying, laying, testing and commissioning medical gases distribution piping system comprising of copper pipes of 28 mm outer dia, having wall thickness 0.90 mm including Tees, Bends, Sockets, Specials, Fittings and fixtures etc. and applying two coats of suitable paint of required colour complete all as specified and as directed by Engineer -in-Charge | 50 | RM | |
21 | 21 | Servicing/overhauling of Oxygen / Nitrous gas control panel including overhauling of regulators,cleaning of filters, replacement of unsv control switches,valves,gauges etc and making panel fully functional in all respect and testing of output pressure of gases upto desired parameters as required inside the operation theatre in CH (CC) all as required at site. | 12 | Each job (every fortnightly) | |
22 | 22 | Servicing/overhauling of medical dry compressed air system, non lubricated, air cooled, 30 CFM capacity with electric motor of suitable capacity not less than 7.5 HP 3 phase comprising air drier, after cooler & pressure control valve with necessary interconnection piping with necessary pressure regulating and control unit with valves, DOL starter,fittings, gauges including connecting the system to distribution piping of the system complete all as specified. | 2 | Each job | |
23 | 23 | S & F HP cylinder complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
24 | 24 | S & F HP ring complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
25 | 25 | S & F HP piston complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
26 | 26 | S & F LP cylinder complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
27 | 27 | S & F LP ring complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
28 | 28 | S & F LP piston complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
29 | 29 | S& F HP / LP valve set and valve guide complete all as specified and as directed by Engineer -in-Charge | 4 | Each \nSet | |
30 | 30 | S& F Main ball bearing set complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
31 | 31 | S & F basin ball bearing complete all as specified and as directed by Engineer -in-Charge | 6 | Each | |
32 | 32 | S & F cage bearing complete all as specified and as directed by Engineer -in-Charge | 6 | Each | |
33 | 33 | S & F HP / LP valve plate complete all as specified and as directed by Engineer -in-Charge | 6 | Each | |
34 | 34 | S & F Air filter complete all as specified and as directed by Engineer -in-Charge | 4 | Each | |
35 | 35 | S & F racking Kit complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
36 | 36 | S & F Oil seal complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
37 | 37 | S & F connecting rod seal complete all as specified and as directed by Engineer -in-Charge | 6 | Each \n | |
38 | 38 | M & L for copper winding 0f capicity 7.5 HP with existing gauge same wire complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
39 | 39 | Supply and fixing in repairs nylon 'V' belts of the B - 82 sizes complete all as specified and as directed by Engineer -in-Charge | 2 | Each \n | |
40 | 40 | Supply and fixing in repairs nylon 'V' belts of the B - 32 sizes complete all as specified and as directed by Engineer -in-Charge | 4 | Each | |
41 | 41 | Supply and fixing in repairs nylon 'V' belts of the B - 51 sizes complete all as specified and as directed by Engineer -in-Charge | 4 | Each | |
42 | 42 | Supply and fixing in repairs nylon 'V' belts of the B - 51 sizes complete all as specified and as directed by Engineer -in-Charge | 2 | Each | |
43 | 43 | Supply and fixing in replacement power contactor MNX 18, 3 phase in existing LT panel all as specified and directed. complete all as specified and as directed by Engineer -in-Charge | 8 | Each | |
44 | 44 | Taking out carefully defective / burnt power contactor type ML-1.5 from the LT panel board and supply & fixing new in position in replacement power contractor ML-1.5 complete all as specified and as directed by Engineer -in-Charge | 8 | Each | |
45 | 45 | Attending complaints on priroty basis for maintenance of 04 Nos modular and 05 Nos of conventional operation theatre at Command hospital & Base Hospital Lucknow comprising of anesthesia pendent fixed type-02 Nos and sweivel type-02 (Make: MDD), shadowless light fittings ) having major and satelite dooms of technical specification mentioned hereinafter,shadowless lights for non-conventional OTs-05 Nos (Make:Philips) speripheral lights 2x55 watts (Make:Philips) , scrub sink-04 Nos (Make:MDD), hermatically sealed sliding doors-04 Nos (Make:Metaflux), complete all as specified and as directed by Engineer -in-Charge ( a ) Contractor shall bound to attend the complaint with in one hour after receiving it from JE and AGE. ( b ) Jointly visit shall be arranged by the contractor during changing any spare parts and all the OT lights shall be made functional in all respect and necessary report duly signed by the OT incharge of CH(CC) and Base Hospital and JE Concern shall be submitted to AGE Hosp on Same Day . Inspection note shall be endorsed by technician related of repair works to be carriedout. \n( c ) Urgent spares parts shall be readly made available at site during all days by the contractor. (d) Whenever Coplaint attend by technitian also included servicing of same items. | 90 | Each Job | |
46 | 46 | S&F Halogen bulbs , 12 volts50 watts having input voltage 230±230 Votls and out put voltage 10.5 to 12.5 volts on load in 4 steps of 50 Hz, supply suitable for Trilux OT lights haivng light out put of 120000 Lux for major and 70000 Lux for satellite doom complete all as specified and as directed by Engineer -in-Charge | 160 | Each | |
47 | 47 | S&F Halogen medical reflector 24V 150 watts suitable for shadoless light fitting of make Philips having major and standard doom all as required at site complete all as specified and as directed by Engineer -in-Charge. | 25 | Each | |
48 | 48 | S&F in repair thermostatic mixing valve provided for constant water termpreature withdefined setting of adjustable timing of 1, 3, 5, 10 minute complete all as specified and as directed by Engineer -in-Charge | 15 | Each | |
49 | 49 | S&F in repair electrc photo sensor suitable for two bay surgical surb sink for hads free operation with built in range of adjustment complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
50 | 50 | S&F in repair solenoid valve 24 volt suitable for two bay surgical scurb sink for hands free operation with built in range of adjustment complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
51 | 51 | Supplying and fixing espagnolet electromagnetic lock mounted on track and on both side key switch suitable for hermatically sealed door having width 3500 mm complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
52 | 52 | Supplying and fixing microprocessor controlled sensor suitable for electromechanical sliding door having width 3500 mm and total weight 250 Kgs and slow speed 20-120 mm/sec,starting speed 20-220 mm/sec,opening speed 800mm/sec and closing speed 500 mm/sec operated on 3 phase 415 volts 50 Hz AC supply complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
53 | 53 | S&F in repair foot switch suitable for hermatically sealed door of modular OT of make Metaflux complete all as specified and as directed by Engineer -in-Charge | 5 | Each | |
54 | 54 | S&F in repair runner wheel MF5 suitable for hermatically sealed door of modular OT of make Metaflux complete all as specified and as directed by Engineer -in-Charge | 5 | Each | |
55 | 55 | S&F in repair guide roller set MF5 suitable for hermatically sealed door of modular OT of make Metaflux complete all as specified and as directed by Engineer -in-Charge | 5 | Each | |
56 | 56 | S&F in repair side sealing gasket suitable for hermatically sealed door of modular OT of make Metaflux complete all as specified and as directed by Engineer -in-Charge | 10 | Each job | |
57 | 57 | S&F in repair teath belt suitable for hermatically sealed door of modular OT complete all as specified and as directed by Engineer -in-Charge | 10 | Each job | |
58 | 58 | S&F in repair photo cell suitable for hermatically sealed door of modular OT complete all as specified and as directed by Engineer -in-Charge | 10 | Each job | |
59 | 59 | S&F in repair motor 370 watts suitable for hermatically sealed door of modular OT complete all as specified and as directed by Engineer -in-Charge | 9 | Each job | |
60 | 60 | S&F in repair SDA 04 controller suitable for hermatically sealed door of modular OT complete all as specified and as directed by Engineer -in-Charge | 9 | Each job | |
61 | 61 | Supply and fix in repair 1.5 sqmm single core, copper wire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and as directed by Engineer -in-Charge | 200 | RM | |
62 | 62 | Supply and fix in repair 2.5 sqmm single core, copper wire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and as directed by Engineer -in-Charge | 200 | RM | |
63 | 63 | Supply and fix in repair 4.0 sqmm single core, copper wire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and as directed by Engineer -in-Charge | 100 | RM | |
64 | 64 | Supply and fix in repair 6.0 sqmm single core, copper wire , multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and as directed by Engineer -in-Charge | 100 | RM | |
65 | 65 | Supply and fix in repair 10.0 sqmm single core, copper wire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and as directed by Engineer -in-Charge | 200 | RM | |
66 | 66 | M & L for check and rectify the all kind of leakages in central gas system meant for operation theatre,MI room CH CC including oxygen,nitrous and compressed air system and receiver tank including control and central alarm panel of respective gases with minor repair carried out . All as specified and directed Note:- (i) any spare parts will be measured and paid in appropreate items. (ii) Contractor shall bound to attend the complaint with in one hour after receiving it from JE and AGE . | 110 | Each Job | |
67 | 67 | Supply and install testing and commissining of air purfier of capicity 85 W Air Purifier with Remote Coverage Area 58 m² (958 square feet) ( especially suitable for\nClean Air Delivery Rate (CADR) 500 m³/h (958 square feet) CADR indicates the volume of purified air (in cubic metre) emoves 99.18% allergens & Filtration upto 0.3 microns, 80 times smaller than PM 2.5 which an air purifier produces every hour with 9 Stages of Filtration: Pre-Filter, Cold-Catalyst, Activated Carbon, Antibacterial, HEPA, UV and Anion + Humidifier, Anti Bacterial Balls & 4-Color indications for PPM level at which light changes from 1-50 Green, 51-100 Blue, 101-200 Yellow, 201-500 & above Red, Maximum PM count 500 , with 02 years warrnty complete all as specified and as directed by Engineer -in-Charge | 3 | Each | |
68 | 68 | Supply and install testing and commissining of Supply and install testing and commissining of 40 W Air Purifier with Remote Air Purifier Type Room Coverage Area 20 m² (485 square feet) ( especially suitable for bedrooms ) Clean Air Delivery Rate (CADR)180 m³/h (485 square feet) CADR indicates the volume of purified air (in cubic metre) which an air purifier produces every hour removes 99.18% allergens & Filtration upto 0.3 microns, 80 times smaller than PM 2.5 which an air purifier produces every hour with 9 Stages of Filtration: Pre-Filter, Cold-Catalyst, Activated Carbon, Antibacterial, HEPA, UV and Anion + Humidifier, Anti Bacterial Balls & 4-Color indications for PPM level at which light changes from 1-50 Green, 51-100 Blue, 101-200 Yellow, 201-500 & above Red, Maximum PM count 500 , with 02 years warrnty complete all as specified and as directed by Engineer -in-Charge | 4 | Each | |
69 | 69 | Disconnecting of ceiling fans of 1200 mm sweep from ceiling rose/connector for cleaning, servicing /oiling and greasing of fan by using appropriate grade of oil / grease and replacing defective parts such as bush bearing , split pin rubber bush, capacitor etc and rehanging the same after proper cleaning and making connection with ceiling fan/connector with flexible wire of size 23/0076 copper conductor multi stranded complete all as specified and as directed by Engineer -in-Charge \n(NOTE :- Parts/component will measuared and paid separtely under respective item of the schedules). | 1380 | Each | |
70 | 70 | Rewinding of ceiling fan 1200 mm sweep AC 230 volts single phase with super enamelled copper winding wire of appropriate/existing gauge/size including packing, insulating material soldering varnishing, assembling and testing including transportation charges to and fro from contractor's workshop complete all as specified and as directed by Engineer -in-Charge | 425 | Each | |
71 | 71 | All as per item No 70 above but 1400 sweep. | 155 | Each | |
72 | 72 | S&F bearing of ceiling fans for ceiling fans of 1200/1400mm sweep to suit for different makes of fans of approved quality including necessary greasing complete all as specified and as directed by Engineer -in-Charge | 60 | Each | |
73 | 73 | S&F bushes gun metal suitable for ceiling fans 1200 / 1400 mm sweep complete all as specified and as directed by Engineer -in-Charge at site. | 60 | Each | |
74 | 74 | S & F condenser / capacitor suitable for 230 volts single phase ceiling fan 1200mm / 1400 sweep of any make and quality of capacity 2.5 MFD complete all as specified and as directed by Engineer -in-Charge | 400 | Each | |
75 | 75 | All as per item No 74 above but 3.15 MFD. | 90 | Each | |
76 | 76 | Painting of ceiling fan 1200/1400mm sweep AC 230 volts single phase complete in situ or at contractor workshop with synthetic enamelled white/matching paint by spraying one cost including filling of cavities after cleaning all dust and marking SM/MES NO with black enamelled paint complete all as specified and as directed by Engineer -in-Charge | 400 | Each | |
77 | 77 | Supply & fixing ceiling fan 1200 mm sweep AC 230 volts single phase including making connection with three core PVC insulated 1100 volts grade multi stranded copper wire of appropriate size including testing complete all as specified and as directed by Engineer -in-Charge | 30 | Each | |
78 | 78 | Rewinding of exhaust fan 300mm to 450mm sweep AC 230 volts single phase with super enamelled copper wire of appropriate size including packing insulating material, soldering, varnishing, assembling and testing including transportation charges to and fro from contractor's workshop complete all as specified and as directed by Engineer -in-Charge | 120 | Each | |
79 | 79 | S&F condenser / capacitor suitable for 230 volts single phase exhaust fan 300mm to 450 sweep of any make and quality of capacity 4 MFD complete all as specified and as directed by Engineer -in-Charge | 90 | Each | |
80 | 80 | S&F exhaust fan frame made out of MS sheet for any make and size of exhaust fan with suitable size of nuts, bolts lugs and washers complete all as specified and as directed by Engineer -in-Charge | 10 | Each | |
81 | 81 | Painting of exhaust fan 300 to 450 mm sweep AC 230 volts single phase complete with synthetic enamelled white / grey / matching paint by spraying one coat including filling of cavities after cleaning all dust and marking SM/MES NO with black enamelled paint complete all as specified and as directed by Engineer -in-Charge | 300 | Each | |
82 | 82 | Supply & fixing exhaust fan 300 mm sweep AC 230 volts single phase with louvers including making connection with three core PVC insulated 1100 volts grade multi stranded copper wire of appropriate size including testing complete all as specified and as directed by Engineer -in-Charge | 12 | Each | |
83 | 83 | Supply & fixing exhaust fan 380 mm sweep AC 230 volts single phase with louvers including making connection with three core PVC insulated 1100 volts grade multi stranded copper wire of appropriate size including testing complete all as specified and as directed by Engineer -in-Charge | 12 | Each | |
84 | 84 | Supply & fixing exhaust fan 450 mm sweep AC 230 volts single phase with louvers including making connection with three core PVC insulated 1100 volts grade multi stranded copper wire of appropriate size including testing complete all as specified and as directed by Engineer -in-Charge | 12 | Each | |
85 | 85 | Supply & fixing exhaust fan fresh air 250 mm sweep AC 230 volts single phase with louvers including making connection with three core PVC insulated 1100 volts grade multi stranded copper wire of appropriate size including testing complete all as specified and as directed by Engineer -in-Charge | 12 | Each | |
86 | 86 | Rewinding of wall fan 450mm sweep AC 230 volts single phase with super enamelled copper wire of appropriate size including packing insulating material, soldering, varnishing, assembling and testing including transportation charges to and fro from contractor's workshop complete all as specified and as directed by Engineer -in-Charge | 60 | Each | |
87 | 87 | Replacement of selector switch including pulling cord of wall fan 450mm sweep AC 230 volts single phase with super enamelled copper wire of appropriate size including packing insulating material, soldering, varnishing, assembling and testing complete all as specified and as directed by Engineer -in-Charge | 15 | Each | |
88 | 88 | S & F air circulator fans 230 volts single phase oscillating 450 mm sweep suitable for wall mounting including making necessary electrical connection with ceiling rose complete all as specified and as directed by Engineer -in-Charge | 12 | Each | |
89 | 89 | Overhauling, repairing, reassembling, refixing, re-installation of water heaters / geysers to their original position, making all necessary water & electric connections and testing complete all as specified and as directed by Engineer -in-Charge\nNote (i) Labour for assembling of all old/ serviceable and new parts to make the geyser in serviceable conditionshall include in this items.\n(ii) Parts renewed shall be measured and paid separately. | 160 | Each Job | |
90 | 90 | Supply & Fixing heating element 1.5 KW (ISI marked) suitable for geyser of 25 litres capacity, horizontal or vertical type any make complete all as specified and as directed by Engineer -in-Charge. Make Dasspass | 160 | Each | |
91 | 91 | Supply & Fixing heating element 2 KW (ISI marked) suitable for geyser of 50 litres capacity, horizontal or vertical type any make complete all as specified and as directed by Engineer -in-Charge. Make Dasspass | 120 | Each | |
92 | 92 | Supply & Fixing thermostat, minimum 300 mm long, suitable for any make & type of geyser 25 / 50 litres capacity horizontal or vertical type complete all as specified and as directed by Engineer -in-Charge | 120 | Each | |
93 | 93 | Supply & Fixing indicating lamp for geysers of any type make & capacity complete all as specified and as directed by Engineer -in-Charge | 55 | Each | |
94 | 94 | M&L for painting old surfaces of geysers of 25 litres capacity of any make with one coat of paint of approved shade or tint after necessary preparation to surfaces and writing of MES Nos as approved size of letter complete all as specified and as directed by Engineer -in-Charge | 15 | Each | |
95 | 95 | S&F of PVC connection 15 mm dia with 2 Nos brass coupling, nuts from geyser inlet / outlet, 40 cm length suitable for 15 mm bore GI pipe complete all as specified and as directed by Engineer -in-Charge | 45 | Each | |
96 | 96 | Supply, installation testing and commissioning of storage type water heater 25 ltrs capacity vertical mounting type complete made out of CRCA outer body, copper storage tank, heating element,thermostat,thermal cut out, glass wool etc. complete including making necessary electrical connections with suitable size copper multistranded cable complete all as specified and as directed by Engineer -in-Charge | 12 | Each | |
97 | 97 | S&F PVC insulated and PVC sheathed 3 core copper conductor flexible round cable size 23 / 0.0076 complete all as specified and as directed by Engineer -in-Charge | 200 | RM | |
98 | 98 | S&F of chromium plated stop cock with brass spindle & with crutch or butterfly handle screwed down high pressure suitable for 15 mm bore GI tubing complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
99 | 99 | S&F Bib taps, cast copper alloy with crutch handle, screwed for 15 mm bore dia. Iron pipe or for brass ferrule and fixed complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
100 | 100 | S&F non-return valve, gun metal, suitable for 15 mm bore GI tubing complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
101 | 101 | S&F pressure releasing valve ISI marked complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
102 | 102 | Supply and fixing of plug top polycarbonate 3 pin, 16 Amps complete all as specified and as directed by Engineer -in-Charge | 50 | Each | |
103 | 103 | Supply & fixing in repair SPN sheet metal enclosure with socket plug top and MCBs with 2 pin and earth plug and socket rated 20 Amps capacity including single pole MCB of 20 Amps complete all as specified and as directed by Engineer -in-Charge | 20 | Each | |
104 | 104 | S & F MCB SP, 6 to 32 Amps, B Series, 240 Volts complete all as specified and as directed by Engineer -in-Charge | 15 | Each | |
105 | 105 | S&F GI nipple, 15 mm bore, medium grade upto 150 mm length complete all as specified and as directed by Engineer -in-Charge | 30 | Each | |
106 | 106 | S&F GI pipe, 15 mm bore, medium grade mm length complete all as specified and as directed by Engineer -in-Charge | 90 | RM | |
107 | 107 | S & F nipple, bend, tee, etc clamp as per site requirement complete all as specified and as directed by Engineer -in-Charge | 10 | KG | |
108 | 108 | S & F Voltage stabilizer for automatic operation single phase intelligent Time Delay System, Compatible with Regular & Inverter ACs, Wall Mounting Cabinet Design, Energy efficient design, smart Digital Display, Built In Thermal Overload Protection Low & High Voltage Cut-off Protection, Latest IC Technology of capicit 05kVA . make -V Gaurd Cat part MOP suitable for 2.0 TR inverter AC or equivalent | 15 | Each | |
109 | 109 | Point wiring for one light/fan point controlled by one, one way switch by using 1.5 Sq mm nominal cross sectional area multistranded copper conductor, PVC insulated unsheathed FRLS cables in and including PVC concealed conduits and conduit accessories/fittings, pressed steel terminal switch boxes, 3 mm thick Bakelite sheet top cover (ISI Marked) fitted with Chromium plate brass screws washers and 1.5 Sq mm nominal cross sectional area multistranded copper conductor green PVC insulated unsheathed earth wire and connecting to earth dolly and make wall surface as existing same colour complete all as specified and as directed by Engineer-in- Charge. \n | 120 | Per Point | |
110 | 110 | Switch piano flush type of of polycarbonate, SP, 5/6 Amps, one way, complete all as specified and as directed by Engineer-in- Charge. \n | 120 | Each | |
111 | 111 | Socket out let 2 in 1 socket 5 pin of polycarbonate , (6 Amps) flush type controlled by one switch complete all as specified and directed. | 120 | Each | |
112 | 112 | Ceiling fan regulator electronic type deluxe 240 Volts 5 step ISI Marked as in replacement ,complete all as specified and as directed by Engineer-in- Charge. | 250 | Each | |
113 | 113 | Preparation of old decorated plastered or unplastered surfaces of walls by brooming down or steel wire brushing scraping down smoke soot, moulds moss and efflorescent salts, trading oil and greasy spots and applying one coat of white wash complete all as specified and directed by the Engineer in Charge. | 5000 | Sqm | |
114 | 114 | All as per item No. 113 above but on ceiling. | 500 | Sqm | |
115 | 115 | Preparation of old plastered or unplastered surfaces of walls by washing, rubbing down & stopping etc, and applying one coat of cement base paint of any tint/shade complete all as specified and directed by the Engineer in Charge. | 3500 | Sqm | |
116 | 116 | Preparation of old plastered or unplastered surfaces of walls by washing, rubbing down & stopping etc, and applying one coat of distemper oil emulsion of any tint/shade complete all as specified and directed by the Engineer in Charge. | 3000 | Sqm | |
117 | 117 | All as per item No 116 above but on ceiling. | 250 | Sqm | |
118 | 118 | Preparation of old painted wood and wood based surfaces of any description, not otherwise described over 10 cm width or girth, including knotting and stopping and applying one coat of synthetic enamel paint , complete all as specified and directed by the Engineer in Charge. | 1000 | Sqm | |
119 | 119 | Preparation of old painted surfaces of steel of any description, not otherwise described over 10 cm width or girth, including knotting and stopping and applying one coat of synthetic enamel paint , complete all as specified and directed by the Engineer in Charge. | 100 | Sqm | |
120 | 120 | Complete removal of existing treatment of walls and applying two coats of distemper oil emulsion over a coat of primer and a thin layer of Birla or JK white wall putty on old plastered surfaces including prepration, complete all as specified and directed by the Engineer in Charge. | 1050 | Sqm | |
121 | 121 | Applying one coat of Apex ( Asian Paint) / Weather coat (Berger) over old painted surface including preparation of wall surface , complete all as specified and directed by the Engineer in Charge. | 1000 | Sqm | |
122 | 122 | Rendering 10mm thick on fair faces of brick wall or concrete surface in cement mortar 1:6 finished even and fair without using extra cement, including taking down old cement plaster on brick wall, racking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed by Engineer-in-Charge. | 200 | Sqm | |
123 | 123 | Rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 finished even and fair with and including WPC compound (2% of cement weight) as per manufacturer's instructions , including taking down old cement plaster on brick wall, racking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed by Engineer-in-Charge. | 356 | Sqm | |
124 | 124 | Rendering 5mm thick on concrete surfaces in ceiling in cement mortar 1:3 finished even and fair without using extra cement using including taking down cement plaster on brick or stone wall etc. including racking out joints, hacking for key and scrubbing down with water etc. ,complete all as specified and directed by Engineer-in- Charge. | 25 | Sqm | |
125 | 125 | Prepartion of newly plastered or unplastered surfaces of ceiling and applying three coat of white wash ,complete all as specified and directed by Engineer-in- Charge. | 25 | Sqm | |
126 | 126 | Preparation of newly plastered surfaces and applying two coats of oil bound disemper over one coat of oil base primer on walls surface over and including a thin layer of wall care putty ,complete all as specified and directed by Engineer-in- Charge. | 200 | Sqm | |
127 | 127 | Applying one coats of plastic emulsion paint interior quality any shade over old painted surface including preparation of wall surface complete all as specified and directed by the Engineer in Charge. | 100 | Sqm | |
128 | 128 | Preparation of newly plastered or unplastered surfaces of walls by brooming down and priming plastered and other surfaces with and applying two coats of cement base paint over a coat of cement paint primer (before application of cement base paint) ,complete all as specified and directed by Engineer-in- Charge.\n | 300 | Sqm | |
129 | 129 | Brickwork with Fly ash bricks (bricks shall be burnt clay flyash building bricks as per IS- 13757), straight or curved on plan exceeding 6.0 m mean radius built in cement sand mortar 1:6 including demolition of brickwork or stone boulder masonry built in cement mortar including all quoins, arches, pillars etc but excluding ashlar facings, dressed stone work and precast concrete articles, complete all as specified and as directed by Engineer -in-Charge. | 6 | Cubic Metre | |
130 | 130 | Pre painted galvatume aluminium zinc coating GI based plain steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering / cladding to wall, fixed with self tapping screws, including taking down old asbestos cement (corrugated, semi corrugated etc) sheet in roof covering etc complete all as specified and directed by Engineer-in-Charge.\n | 50 | Sqm | |
131 | 131 | Dismantling wrought iron or mild steel work of any description not otherwise provided for ,complete all as specified and directed by Engineer-in- Charge. \n | 3 | Qtl | |
132 | 132 | Steel work in tubular trusses including special shape washer etc. complete using ERW or induction butt welded tubes conforming to IS 1161-1979 grade St.240 ,with one shop coat of zink chromote primer paint, complete all as specified and directed by Engineer-in-Charge. | 300 | Kg | |
133 | 133 | Demolition of unreinforced cement concrete in ground floors and paving n.exc 15cm thickness (below or above ground level) , complete all as specified and directed by the Engineer in Charge. | 7.5 | Cum | |
134 | 134 | Plain cement concrete 1:5:10, type E-2, using 40 mm graded mechanically crushed stone aggregates as in sub base to floor complete all as specified and directed by the Engineer in Charge. | 50 | Sqm | |
135 | 135 | Factory made Machine pressed PCC intelocking tiles 60mm thick M-35 Grade of shape and size confirming to IS 15658-2006 as approved, laid dry over and including sand not less than 40 mm thick, interstices filled in floors / pathway , laid bedded and pointed in cement mortar complete all as specified and directed by the Engineer in Charge. | 50 | Sqm | |
136 | 136 | Plain cement concrete (1:2:4) type B-1 using 20mm graded stone aggregate as in coping, padding and bed block, wall through and the like including weathering slightly rounded or chamfered angles and throating including necessary form work complete all as specified and directed by the Engineer in Charge. | 1 | Cum | |
137 | 137 | Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) rubbish off the premises ,complete all as specified and directed by Engineer-in- Charge. | 30 | Sqm | |
138 | 138 | Vitrified ceramic tiles 10mm thick (square /rectangular) coloured ( Dark Shade ) polished tiles, area of each tile not exceeding 0.38 Sq.m, laid in floors with neat cement slurry @ 3.00 kg/Square Metre over and including 15 mm thick screed bed of cement mortar (1:6) including pointing in coloured cement to match the shade of tiles, complete all as specified and directed by Engineer-in- Charge. | 35 | Sqm | |
139 | 139 | Preparation of new steel surfaces of any description, not otherwise described, over 10 cm width or girth and applying two coat of synthetic enamel paint (Ordinary tint) over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge. | 48.6 | Sqm | |
140 | 140 | Taking up or down steel water tubing and connections of 15 mm bore complete all as specified and directed by Engineer-in- Charge. | 30 | RM | |
141 | 141 | Taking up or down steel water tubing and connections of 20 mm bore complete all as specified and directed by Engineer-in- Charge. | 10 | RM | |
142 | 142 | Steel water tubing, 15 mm bore medium grade, galvanized with all fittings and fixed complete to walls, ceiling or laid in floors, complete all as specified and directed by Engineer-in- Charge. | 30 | RM | |
143 | 143 | Steel water tubing, 20 mm bore medium grade, galvanized with all fittings and fixed complete to walls, ceiling or laid in floors, complete all as specified and directed by Engineer-in- Charge. | 10 | RM |