Tidel Park Ltd-TPL has published Supply, Installation, Testing And Commissioning Of Air Condition And Mechanical Ventilation System (Acmv), Electrical (Ht&Lt) Installation, Fire Protection System (Fps), Integrated Building Management System (Ibms) And Lift Installation Works. Submission Date for this Tender is 05-01-2021. Passenger Lift Tenders in Tidel Park Pattabiram Tamil Nadu. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 28-Dec-2020 | PAYMENT TERMS | Technical Bid | 05-01-2021 |
Name of Work: Supply, Installation, Testing and Commissioning of Air Condition and Mechanical Ventilation System (ACMV), Electrical (HT<) Installation, Fire Protection System (FPS), Integrated Building Management System (IBMS) and Lift Installation works | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | AIR CONDITIONING WORKS | |||
2 | 1.1 | Plant room - High side works\nSupply, installation, testing and commissioning of Air cooled chillers with following particulars | |||
3 | 1.2 | Actual capacity of 401 TR(+/-1.5%) Air Cooled screw chillers (Imported), 1.32 (+/-1 ) KW/TR temp: 6 deg C leaving and 13 deg C entering condition, at Chennai ambient condition DB temp. 104deg F and WB temp. 83 Deg F, suitable disconnect switch IP65 local switch, chiller pressure rating shall be 16kg/cm2, required pressure differentail sensor, Black Epoxy coated/E coated /Gold coated fins, Condensor fins covered with 12 guage SS316 mesh for mechanical protection. Compressor sound jacket using Armasound material thickness shall be 50mm thick armosound accoustic insulation with 22G Alu cladding with suitable vibration isolator. For Copper coil with Aluminum fins --- 2 years DLP from the date of commissioning and handing over. for E coated Al-Al condenser coil --- 2 years DLP from the date of commissioning and handing over plus minimum 10 years Warranty for condensor coil with consumables and oil if any rework, 4point chiller testing at chiller factory, cost includes sea fright and local transport, 4point testing at any one selected chiller, travel cost, import duty, local tax, local clarence from port, local trasport, loading and unloading, erection of chillers using telescope suitable capcity crane to shifted from site to respective location, insurance from chiller factory to site, Cost inculde at site perfromance test with OEM Engineer (Note: chiller origin from USA, Eupore only). | 5 | Nos | |
4 | 1.3 | Suitable cable entry adaptor box with isolator and should have weather protection type | 5 | Nos | |
5 | 1.4 | Suitable Differential pressor sensor | 5 | Nos | |
6 | 1.5 | Suitable Vibration isolator for chiller | 5 | Nos | |
7 | 1.6 | 25mm dia Flow switch with suitable required size of cables/wire/flexiable hose with GI conduit between flow switch and chiller | 5 | Nos | |
8 | 1.7 | Compressor sound jocket -50mm thick armosound materials with 24g GI glading | 5 | Nos | |
9 | 1.8 | Plant Manager with required temreature sensors, RH sensors,ambient sensor and if any required sensor to meet the plant manger opeation, required cat5 cable, required screened cables,required FRLS cable, 25mm Gi conduits wherever required, GI flexible hose, suitable required size of cable tray with top cover, cable tray height shall be 50mm and thick on the same 2mm. App cable length shall be 1600 rmt. | 1 | Nos | |
10 | 1.9 | Suitable Flange end connection with insulation | 5 | Nos | |
11 | 2 | Supply, installation, testing and commissioning of End suction long coupled back pull out base mounted primary pumps with bronze impeller,Mechnical seal, capacity of 764 US gpm@15m head, Pump Pressure rating shall be of 16 kg/cm2, Motor shall be IE3 type, Selected motor rating shall be minimum 15% above BKW.Pump base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated type motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided.Cost inculde at site perfromance test with OEM Engineer | 6 | Nos | |
12 | 2.1 | Supply, installation, testing and commissioing of Suitable Inertia frame with Vibration mounting springs for the above selection of pumps-required concrete M30 grade with reinforcement 200 Kg/Cum. | 6 | Nos | |
13 | 2.2 | Supply, installation, testing and commissoing of cubical IP54 indoor type panel for Primary Pump with Suitable IP21 VFD, Main incomig and Individual disconnect switch are MPCP for primary pumps, iliumination lights, MPCP, saftey switch, ammeter, voltmer and energy meter, VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standardand, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation (5nos working + 1 stand by) | 1 | Nos | |
14 | 2.3 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable cable perfrated cable Tray, tray height shall be 100mm and tray sheet thickness shall be 2mm, App cable length shall be 60 to 110 rmt. | 6 | Nos | |
15 | 2.4 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination for both the ends. | 6 | Nos | |
16 | 2.5 | Supply, installation, testing and commissioing of insulation for Pump casing using 30mm thick nitrile rubber insulation with 22G al clading for the above mentioned pumps. | 6 | Unit | |
17 | 2.6 | Supply,instaltion,testing and commissioing of 2runs of 6swq GI wire for earthing, app cable length 25 rmt. | 6 | Unit | |
18 | 2.7 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required support for installation | 6 | Unit | |
19 | 2.8 | Supply, installation, testing and commissioing of Emergency Locakable Push button station cabling for the above 3 core 1.5 square copper armoud fire rated cable length shall be 25rmt to 30rmt between motor to vfd. | 6 | Unit | |
20 | 2.9 | Supply, installation, testing and commissioing of Enamel painting for pump base and required water flow sticker has to be envisized. | 6 | Unit | |
21 | 3 | Supply, installation, testing and commissioning of end suction long coupled back pullout, base mounted Secondary pumps with bronze impeller, Mechanical seal, capacity of 1086 Us Gpm@40m head, Pump Pressure rating shall be of 16 kg/cm2, Motor shall be IE3 type, Selected motor rating shall be minimum 15% above BKW. Pump base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated type motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided.Cost inculde at site perfromance test with OEM Engineer | 5 | Nos | |
22 | 3.1 | Supply, installation, testing and commissioing of Suitable Inertia frame with Vibration mounting spring for the above selection of pumps-required concrete M30 grade with reinforcement 200 Kg/Cum. | 5 | Nos | |
23 | 3.2 | Supply, installation, testing and commissioing of Common cubical IP54 panel for Secondary Pump logic controller with Suitable IP21 VFD with bypass star delta starter, Main incoming and Individual pumps disconnect switch are MPCB for secondary pumps, iliumination lights, ammeter, voltmer and energy meter, VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standardand, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated,Panel shall be as per the IS standard of electrial standard and required BMS compatable for the above operation (4nos working + 1 stand by). | 1 | Nos | |
24 | 3.3 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable cable perfrated cable Tray, tray height shall be 100mm and tray sheet thickness shall be 2mm, App cable length shall be 60 to 110 rmt | 5 | Nos | |
25 | 3.4 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination | 5 | Nos | |
26 | 3.5 | Supply, installation, testing and commissioing of insulation for Pump casing using 30mm thick nitrile rubber insulation with 22G al clading for the above mentioned pumps | 5 | Unit | |
27 | 3.6 | Supply, installation, testing and commissioing for 2 run of 25x1.5 mm GI flat for earthing , App. cable length shall be 25 rmt | 5 | Unit | |
28 | 3.7 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above , Fire rated type with required support | 5 | Unit | |
29 | 3.8 | Supply, installation, testing and commissioing of Emergency Locakable Push button station cabling for the above , 3 core 1.5 square copper armoud fire rated cable length shall be 25rmt to 30rmt between motor to vfd | 5 | Unit | |
30 | 3.9 | Supply, installation, testing and commissioing of Enamel painting for pump base and required water flow sticker has to be enisized | 5 | Unit | |
31 | 4 | Supply, installation, testing and commissioing of 2nos of DP sensor of Secondary pump operation with required amplifier and nessersery support and copper tubing between dp sensor to chilled water line, | 1 | Unit | |
32 | 4.1 | Supply, installation, testing and commissioing for 4 core 1.5 square screened copper armoud fire rated cable including 20mm(2mm thick) GI conduit with aux., length shall be app 1600 rmt between dp sensor to vfd | 1600 | Rmt | |
33 | 4.2 | Supply, installation, testing and commissioning of Swing type Non return Valve suitable for the pipes, pressure rating of PN16, with insulation and 24g Alu cladding | |||
34 | 4.3 | 200 mm dia | 6 | Nos | |
35 | 4.4 | 250 mm dia | 5 | Nos | |
36 | 4.5 | Supply, installation, testing & commissioning of Y Strainers with matching flanges .The Strainer shall be With removable bronze screen and a permanent magnett, drain port with valve and with insulation and 24g AL cladding.The strainer shall be Pressure Rating PN 16 kg/cm2 | |||
37 | 4.6 | 200 mm dia | 2 | Nos | |
38 | 4.7 | 250 mm dia | 2 | Nos | |
39 | 4.8 | 400mm dia | 1 | Nos | |
40 | 4.9 | Supply, installation, testing and commissioning of Metallic SS bellows suitable tie rod and Tabel E flange inculing flange, pressure rating of PN16 | |||
41 | 5 | 200 mm dia | 26 | Nos | |
42 | 5.1 | 250 mm dia | 10 | Nos | |
43 | 5.2 | 500 mm dia | 4 | Nos | |
44 | 5.3 | Supply, installation, testing and commissioning of Suction Guide suitable for pumps, pressure rating of PN16 -with insulation and 24g Alu cladding | |||
45 | 5.4 | 200 mm dia | 6 | Nos | |
46 | 5.5 | 250 mm dia | 5 | Nos | |
47 | 5.6 | Supply, installation, testing and commissioning of two way on/off and modulation type motorised isolation valve suitable for pipes, with actuator 230v power supply, BMS compatible, pressure rating of PN16, suitable for chilled water application-with insulation and 24g Alu cladding | |||
48 | 5.7 | 200 mm dia-on/off valve | 5 | Nos | |
49 | 5.8 | 200 mm dia-modulating type valve | 1 | Nos | |
50 | 5.9 | Supply, installation, testing and commissioning of Manual Balancing valve suitable for pipes,pressure rating of PN16 -with insulation and 24g Alu cladding | |||
51 | 6 | 200 mm dia | 5 | Nos | |
52 | 6.1 | Supply, installation, testing and commissioning of Butterfly valve with extended stem of 100mm length, pressure rating of PN16 | |||
53 | 6.2 | 500 mm dia | 4 | Nos | |
54 | 6.3 | 250 mm dia | 12 | Nos | |
55 | 6.4 | 200 mm dia | 24 | Nos | |
56 | 6.5 | 150 mm dia | 2 | Nos | |
57 | 6.6 | 100 mm dia | 1 | Nos | |
58 | 6.7 | 80 mm dia | 1 | Nos | |
59 | 6.8 | 65 mm dia | 1 | Nos | |
60 | 6.9 | 50 mm dia | 4 | Nos | |
61 | 7 | Supply, installation, testing and commissioning of pressurised closed expansion tank with working and stand by pump motor, required controllor for operation, bms compatible -capacity of 5000 liter for water. 50mm thick rigid puff insulation with 24G GI galding with float valve arrangement | 1 | Nos | |
62 | 7.1 | Supply, installation, testing and commissioing of ms angle iron support with primay and two coat of enamal painting for plant room supports and Trench header line supports. | 7500 | Kg | |
63 | 7.2 | Supply, installation, testing and commissioing of 12mm thick Ms Checkered plate with primary and two coat of painting for shaft closings etc. | 2000 | Kg | |
64 | 7.3 | Supply, installation, testing and commissioing of PVC insulated, copper conductor 1.1kv grade, Armoured copper cable,FRLS XLPE cables | |||
65 | 7.4 | 3.5C x 240 sqmm FRLS xlpe Cable | 200 | Rmt | |
66 | 7.5 | 4C X25 sqmm FRLS xlpe | 125 | Rmt | |
67 | 7.6 | 4C X10 sqmm FRLS xlpe | 240 | Rmt | |
68 | 7.7 | Supply, installation, testing and commissioing of cable end termination with Double brass compression gland and Copper lugs for the following sizes of PVC Insulated XLPE armoured conductor FRLS copper cable of 1.1KV grade complete as required.. | |||
69 | 7.8 | 3.5C x 240 sqmm FRLS xlpe Cable | 16 | Nos | |
70 | 7.9 | 4C X25 sqmm xlpe | 8 | Nos | |
71 | 8 | 4CX10 sqmm xlpe | 16 | Nos | |
72 | 8.1 | Supply, installation, testing and commissioing of Copper earth plate 25 x3 mm x 2 run (route length) | 240 | Rmt | |
73 | 8.2 | Supply, installation, testing and commissioing of Copper earth plate 8SWG Cu Wire | 600 | Rmt | |
74 | 8.3 | Supply, installation, testing and commissioing of GI Perforated 2mm thick Tray with GI angle supports, height of the tray shall be 100mm with top Cover. | |||
75 | 8.4 | 600mm width | 200 | Rmt | |
76 | 8.5 | 450mm width | 180 | Rmt | |
77 | 8.6 | 300mm width | 140 | Rmt | |
78 | 8.7 | 200mm width | 64 | Rmt | |
79 | 8.8 | 150mm width | 30 | Rmt | |
80 | 8.9 | Supply, installation, testing and commissioing of Pressure gauge with SS 314 syphons,ball Valves pressure rating 25kg/cm2 ,100mm dia range -0 to 15 kg/cmsq with mercury filled. | 38 | Nos | |
81 | 9 | Supply, installation, testing and commissioing of Temp. gauge with SS 314 syphons, ball Valves pressure rating 25kg/cm2, mercury filled thermowell,100mm dia, -10 to 20 deg C | 14 | Nos | |
82 | 9.1 | Supply, installation, testing and commissioing of 25mm Ball valves with screw end, pressure rating PN 25 with insulation and 24g Alu cladding | 38 | Nos | |
83 | 9.2 | Supply, installation, testing and commissioing of Auto air vent size 25mm dia, pressure rating shall be PN16 | 12 | Nos | |
84 | 9.3 | Supply, installation, testing and commissioning of Electromagnetic Descaler for Chilled water flow capacity-6000usgpm and pipe size 500 mm dia | 1 | Nos | |
85 | 9.4 | Supply, installation, testing and commissioning of trible duty valves for pumps, pressure rating of PN16 -with insulation and 24g Alu cladding | |||
86 | 9.5 | 250 mm dia | 5 | Nos | |
87 | 9.6 | 200 mm dia | 6 | Nos | |
88 | 9.7 | Supply, installation, testing and commissioning of MS C class pipe,Fe 410 steel grade-welded(ERW) with Rigid Polyurthane foam(Puff section), density 48 Kg/m3 of 75mm thick for 600 mm to 150mm(+/-5mm) and below pipe 50mm(+/-5mm) thick, warping sheet of 500gram/sqmt polythene , 24G Al.cladding , providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil scope including, excavation, dewatering, brickworks, pedestals, covers, etc., | |||
89 | 9.8 | 500mm dia (clear 11mm thick) | 280 | Rmt | |
90 | 9.9 | 250mm dia( clear 11mm thick) | 240 | Rmt | |
91 | 10 | 200mm dia(clear 11mm thick) | 145 | Rmt | |
92 | 10.1 | 50mmdia (C class -4.5mm thick ) | 50 | Rmt | |
93 | 10.2 | Supply, installation of air and water flow singage/Equipemnt tag/valve tag for all HVAC Items | 1 | Unit | |
94 | 10.3 | Carrying out hydronic water balancing by two time for chilled water circuit as per the design flow, commissioing stage one time and 100% operational stage to meet the design parameter . | 1 | Unit | |
95 | 10.4 | Supply , installation , testing and commissioning of Centrifugal type, Side Stream Filter for Chilled water, 500mm dia-6000 gpm. | 1 | Nos | |
96 | 10.5 | Supply, installation, testing and commissioning of 500mm Dia Air and Dirt separator with strainer and auto airvent. Vessel shell diameter is to be three times the nominal inlet/ outlet pipe diameter, with a minimum vessel volume for sufficient velocity reduction.The air separator must be designed, constructed and stamped for 232 psig @ 350°F (1599 kPa @ 177°C) in accordance with Section VIII, Division I of the ASME Boiler and Pressure Vessel Code (Only for ASME Stamping). The Air separator shall be PN-16 rated. Insulation as per the connected chilled water piping and as per the specification. The quoted price shall be inclusive of structural support for the tank,Pressure Rating PN 16. | 1 | Nos | |
97 | 10.6 | Low side works (Piping and air distribution): | |||
98 | 10.7 | Supply, installation, testing and commissioning of MS C class pipe,Fe 410 steel grade-welded(ERW) with Rigif Polyurthane foam(puff section), density 48 Kg/m3 of 75mm thick for 600 mm to 150mm(+/-5mm) and below pipe 50mm(+/-5mm) thick, warping sheet of 500gram/sqmt polythene , 24G Al.cladding , providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.- under ground piping civil scope including, excavation, dewatering, brickworks, pedestals, covers, etc., During commissioning stage contractor to do cleaning of inside pipe line by the way of water flushing wth pressure recirculation pump of normal drinking water to achive the good qulaity of water level to witnessed by engineer incharge/Clint. | |||
99 | 10.8 | 500 mm dia(clear 11mm thick) | 550 | Rmt | |
100 | 10.9 | Supply, installation, testing and commissioning of MS C class pipe,Fe 410 steel grade-welded(ERW) with Rigid Polyurathane foam( puff section), density 48 Kg/m3 of 100mm thick for 600 mm to 150mm(+/-5mm) and below pipe 50mm(+/-5mm) thick warping sheet of 500gram/cm polytheneand 24G Al.cladding, providing and fixing in position necessary fittings like bends, elbows, tees, reducers, mating flanges, nipples for mounting sensor (if any) & sockets for BAS (if any), fabricated to size and shape in workshop or brought out ready made where available of acceptable quality. The quoted price shall inclusive of necessary supports, hangers, welding, smooth finishing, anchors, saddles, sleeves, brackets, adequate number of expansion joints, clamps, bolts, nuts and all accessories as required to complete the installation. Test points to be provided in the pipeline wherever required.During commissioning stage contractor to do cleaning of inside pipe line by the way of water flushing wth pressure recirculation pump of normal drinking water to achive the good qulaity of water level to witnessed by engineer incharge/Clint. | |||
101 | 11 | 300 mm dia(clear 11mm thick) | 60 | Rmt | |
102 | 11.1 | 250 mm dia( clear 11mm thick) | 340 | Rmt | |
103 | 11.2 | 200 mm dia ( clear 11mm thick) | 310 | Rmt | |
104 | 11.3 | 150 mm dia (clear 9mm thick) | 130 | Rmt | |
105 | 11.4 | 125 mm dia (C class -6mm thick) | 90 | Rmt | |
106 | 11.5 | 100 mm dia (C class -6mm thick) | 85 | Rmt | |
107 | 11.6 | 80 mm dia (C class -6mm thick) | 1277 | Rmt | |
108 | 11.7 | 65 mm dia (C class-6mm thick) | 502 | Rmt | |
109 | 11.8 | 50 mm dia (C class-4.5mm thick) | 1942 | Rmt | |
110 | 11.9 | 40 mm dia (C class - 4mm thick) | 10 | Rmt | |
111 | 12 | 32 mm dia (C class-4mm thick) | 2548 | Rmt | |
112 | 12.1 | 25 mm dia (C class-4mm thick) | 20 | Rmt | |
113 | 12.2 | 20 mm dia (C class -3.2mm thick) | 10 | Rmt | |
114 | 12.3 | Supply, installation, testing and commissioing of C class CPVC pipe (SDR 13.5) with Insulated Condensate Drain/process cooling piping-25mm thick TF quality Thermocole density 32 Kg/m3, 24G AL. cladding | |||
115 | 12.4 | 100 mm dia (C class) | 240 | Rmt | |
116 | 12.5 | 80 mm dia (C class) | 405 | Rmt | |
117 | 12.6 | 50 mm dia (C class) | 980 | Rmt | |
118 | 12.7 | 32 mm dia (C class) | 405 | Rmt | |
119 | 12.8 | Supply, installation, testing and commissioning of Manual Balancing valve pressure rating of PN16 -with insulation, suitable for 230v supply | |||
120 | 12.9 | 400 mm dia | 1 | Nos | |
121 | 13 | 250 mm dia | 2 | Nos | |
122 | 13.1 | 200 mm dia | 1 | Nos | |
123 | 13.2 | 150 mm dia | 2 | Nos | |
124 | 13.3 | Supply, installation, testing and commissioning of Butterfly Valve with extended stem of 100mm length, pressure rating of PN16 , Suitable for chilled water application -SS wafer/stem for chilled water application -with insulation and 24g Alu cladding | |||
125 | 13.4 | 500 mm dia | 2 | Nos | |
126 | 13.5 | 400 mm dia | 2 | Nos | |
127 | 13.6 | 250 mm dia | 6 | Nos | |
128 | 13.7 | 150 mm dia | 4 | Nos | |
129 | 13.8 | 100 mm dia | 6 | Nos | |
130 | 13.9 | 80 mm dia | 84 | Nos | |
131 | 14 | 65 mm dia | 88 | Nos | |
132 | 14.1 | 50 mm dia | 112 | Nos | |
133 | 14.2 | Supply, installation, testing & commissioning of Y Strainers with matching flanges .The Strainer shall be With removable bronze screen and a permanent magnett, drain port with valve. The strainer shall be suitable for the following pipe connection. Pressure Rating PN 16 | |||
134 | 14.3 | 80 mm dia | 22 | Nos | |
135 | 14.4 | 65 mm dia | 22 | Nos | |
136 | 14.5 | 50 mm dia | 3 | Nos | |
137 | 14.6 | 32 mm dia | 32 | Nos | |
138 | 14.7 | Supply, installation, testing and commissioning of automatic Pressure Independent Balancing control valve . The valves shall be threaded ends for DN 15 to DN 32, non ferrous a metal brass copper alloy body . EPDM O ring seals. Valve shall have 4 turn digital readout hand wheel.The larger size valve shall be Cast iron body with flanged connection . The spindle shall be stainless steel and EDPM O ring seals.8,12 or 16 turn digital readout Duly mounted with Modulating actuator IP42/54 Accordingly type suitable for 24V AC As per technical specifications and drawings etc,. ( Maximum Pressure drop across valve is 0.3 WC).Cost inculde at site perfromance test with OEM Engineer. | |||
139 | 14.8 | 80 mm dia | 22 | Nos | |
140 | 14.9 | 65 mm dia | 25 | Nos | |
141 | 15 | 50 mm dia | 3 | Nos | |
142 | 15.1 | 32 mm dia | 34 | Nos | |
143 | 15.2 | 25mm dia | 47 | Nos | |
144 | 15.3 | Supply, installation, testing and commissioning of Ball valve with strainer flange end, pressure rating of PN25-with insulation and 24G Alu cladding | |||
145 | 15.4 | 32 mm dia | 12 | Nos | |
146 | 15.5 | 25 mm dia | 49 | Nos | |
147 | 15.6 | Supply, installation, testing and commissioing of Pressure gauge with SS 314 syphons,ball Valves pressure rating 25kg/cm2 ,100mm dia range -0 to 15 kg/cmsq with mercury filled | 264 | Nos | |
148 | 15.7 | Supply, installation, testing and commissioing of Temp. gauge with SS 314 syphons, ball Valves pressure rating 25kg/cm2, mercury filled thermowell,100mm dia, -10 to 20 deg C | 264 | Nos | |
149 | 15.8 | Supply, installation, testing and commissioing of Ball valves with flange end, pressure rating PN 25 with insulation and 24g Alu cladding. | |||
150 | 15.9 | 32 mm dia | 164 | Nos | |
151 | 16 | 25 mm dia | 197 | Nos | |
152 | 16.1 | Supply, installation, testing and commissioing of Auto air vent size 25mm dia , pressure rating shall be PN16 | 180 | Nos | |
153 | 16.2 | Supply, installation, testing and commissioing of SMACNA standard, factory fabricated box type, flanged GI ducting ,120GSM, 250pa, using food grade sealant for leakage arresting, wall to wall duct crossing area to be sealed with fire retardant sealent.and neccessary supports. | |||
154 | 16.3 | 18G | 110 | Sq.M | |
155 | 16.4 | 20G | 1742.5 | Sq.M | |
156 | 16.5 | 22G | 5610 | Sq.M | |
157 | 16.6 | 24G | 4972.5 | Sq.M | |
158 | 16.7 | Supply, installation, testing and commissioing of MS duct -3mm thick, factory fabricated box type,Angle flanged formevery 1.2m lenght of duct, out side duct shall be having fire rated paints, duct shall be pressure rating 250pa, using food grade sealant for leakage arresting, wall to wall duct crossing area to be sealed with fire retardant sealentand and neccessary supports. | 382.5 | Sq.M | |
159 | 16.8 | Supply and installation of Heavy duty Aluminium extruded powdered coated grilles with Collar damper | 285 | Sq.M | |
160 | 16.9 | Supply, installation, testing and commissioing of Motorised Fire damper,suitable acutators(24v/230v) (Standeard UL555/AMCA 550D) with control panel for maual and auto operation. outer frames shall be of 16G GSS construction, All fire dampers shall be complete with factory fabricated and fitted duct sleeve, Fire damper rating shall comply with leakage Class-1 (8 CFM@ 4 Inch WG static), closure temperature of 74 C and damper shall be 90 Minutes fire rated. Extended sleeve of 400mm length & thickness of 20G with complete boxing. | 230 | Sq.M | |
161 | 17 | Supply, installation, testing and commissioing of required input power from electrical panel to fire control control panel and power/control wring/gi conduits/flexible conduits between fire damper and control panel, | 65 | Rmt | |
162 | 17.1 | Supply, installation, testing and commissioing of Butterfly dampers dia 300 mm, suitable dia insulated flexable duct , GI 24G plenum box with 6mm thick thermal insulation , size of plenum box 600 x600 x 450 | 20 | Nos | |
163 | 17.2 | Supply, installation, testing and commissioing of Butterfly dampers dia 250 mm,suitable dia insulated flexable duct , GI 24G plenum box with 6mm thick thermal insulation , size of plenum box 600 x600 x 450 | 220 | Nos | |
164 | 17.3 | Supply, installation, testing and commissioing of Butterfly dampers dia 200 mm,suitable dia insulated flexable duct , GI 24G plenum box with 6mm thick thermal insulation , size of plenum box 600 x600 x 450 | 20 | Nos | |
165 | 17.4 | Supply, installation, testing and commissioing of toilet exhast Aluminium disc valves (size 100 to 200mm(+/-5mm)) with control damper | 770 | Nos | |
166 | 17.5 | Supply, installation, testing and commissioing of Duct Thermal Insulation materials constructed by laminating a closed cell cross linked polyethylene foam or nitrile rubber insulation with tough re inforced aluminum foil facing of 19 mm thick insulation for SA duct passing through the Conditioned space, Class O standards, thermal conductivity 0.032 w/m k(20 deg c ,50-70% R.H) | 5695 | Sq.M | |
167 | 17.6 | Supply, installation, testing and commissioing of Duct Thermal Insulation materials constructed by laminating a closed cell cross linked polyethylene foam or nitrile rubber insulation with tough re inforced aluminum foil facing of 13 mm thick insulation for RA duct passing through the Conditioned space, Class O standards, thermal conductivity 0.032 w/m k(20 deg c ,50-70% R.H). | 180 | Sq.M | |
168 | 17.7 | Supply, installation, testing and commissioning of Duct Accoustic (Nitrile rubber base, Open cell material 25mm thick, Thermal conductivity 0.047w/m.k@20deg C, excellent absorption, 99.9% reduction of bacterial growth, class1 fire performance, with a density of 140-180Kg/cubicmeter). | 1028.5 | Sq.M | |
169 | 17.8 | Supply, installation, testing and commissioing of non return air dampers for low leakage type with spring loaded. | 75 | Sq.M | |
170 | 17.9 | Supply, installation of gripple hanger system for ducts installation -length shall be 10m and hanging weight 60 -120kg. (To consider 1Lot) | 120 | Nos | |
171 | 18 | Supply, installation, testing and commissioning of SS 316 pipe of 50mm(+/-5mm) dia for pressure difference (To quote in Rmt) | 800 | Rmt | |
172 | 18.1 | Supply, installation, testing and commissioning of External Extruded Aluminum heavy duty type louvers | 35 | Sq.M | |
173 | 18.2 | Supply, installation, testing and commissioning of Double skin low leakage VAVs, selection of VAV 5 to 6 m/sec, dba level less than 30db,A in built thermostart and controller, suitable size of cabling, conduiting, cat 5 cable for between thermostart to VAV, and VAV to isolater, required 5A isolator, fast activating type of VAV that is 3 to 5 seconds, interlocking arrangement between AHU to VAV for on/off operation VAVs, required modulation actuvator , 230 volts type and inclusive of digital theromstart type with required suitable cable and conduits between thermostart to VAV | |||
174 | 18.3 | 4500 to 3000cfm | 4 | Nos | |
175 | 18.4 | 3000 to 2500cfm | 4 | Nos | |
176 | 18.5 | 2600 to 2000cfm | 1 | Nos | |
177 | 18.6 | 2000 to 1800cfm | 2 | Nos | |
178 | 18.7 | 1800 to 1500cfm | 2 | Nos | |
179 | 18.8 | 1500 to 1200cfm | 1 | Nos | |
180 | 18.9 | 500 to 900cfm | 20 | Nos | |
181 | 19 | Supply, installation, testing and commissioing of cat5 scrennedcables with 25mm GI conduits with aux. | 450 | Rmt | |
182 | 19.1 | Supply, installation, testing and commissioing of Static pressure sensor 200pascal and required cable/conduits between sensor and VFDs,app mimium length shall be 40rmt | 59 | Nos | |
183 | 19.2 | Supply, installation, testing and commissioing of Heavry extruded Alumium Round/square diffuser - S/R neck size 450-600mm/ 200 to 300mm dia | 190 | Nos | |
184 | 19.3 | Supply, installation, testing and commissioing of (S/R) Al. Swrile type/tegular type diffusers neck size 450 to 600mm size | 120 | Nos | |
185 | 19.4 | Towards Duct Pressure testing for all installed ducts as per the SMACNA standard | 12435 | Sq.M | |
186 | 19.5 | Towards Concrete/brick wall opening and closing of the same after duct/pipe work with smooth finsih for wherever crossing ducts/pipes by using fire rated foam/civil morters | 2 | Imp | |
187 | 19.6 | Supply, installation, testing and commissioing of Sprial/Oval ducts with bends,120GSM, required reducer,bend, tee and dummy, ducts inner shall be 9mm thick thermal insulation with al.foil faced with necessary support. | |||
188 | 19.7 | 1200 to 1000mm - sheet thick ness 1.2mm | 20 | Rmt | |
189 | 19.8 | 950 to 800mm - sheet thickness 1.2mm | 10 | Rmt | |
190 | 19.9 | 750 to 600 mm - sheet thick ness 0.8mm | 20 | Rmt | |
191 | 20 | 550 to 400 mm - sheet thick ness 0.64 | 20 | Rmt | |
192 | 20.1 | Supply, installation, testing and commissioing of 25mm thick rigid puff panel ,densisty of 48kg/cm3 plennum box having inner and outer skin thickness of 0.64mm with inside plenum all sides shall be 25mm thick Armosund accouctic materilas to be fixed/lined for accoustic clss o type materils, proper Aluminum support for accoustic insulation inside the plennum box,Thermal conductivity 0.047w/m.k@20deg C, excellent absorption, 99.9% reduction of bacterial growth, class o fire performance, with a density of 140-180Kg/cubicmeter. | 1000 | Sq.M | |
193 | 20.2 | Supply, installation, testing and commissioing of AHU Room wall accoustic using of 50mm thick Fiber glass with density of 48 kg/cm3, 50 mm air gap tob maintained between wall and Aluminum C channel(24G), insider wall shall to be two caot primer and two coat enamel block painted , C channel 24G GI (space 600 x600), Rp tissue to fixed inside and outside fiber glass with 24G Aluminum proprated sheet , Accoustic insulation shall be provided all side inside of AHU room inculding ceiling area. | 4950 | Sq.M | |
194 | 20.3 | Supply, installation, testing and commissioing of 18G Aluminum Volume Control Dampers with operating handle aero foil blade with rubber beeding for Supply/Return/Exhaust air duct branches in accordance with the approved shop drawings.The dampers shall be supplied with matching flanges on both sides. | 225 | Sq.M | |
195 | 20.4 | Supply and instaltion of Underdeck insulation thickness of 24mm thick Nitrile rubber insulation using adashive stick on ceiling, further 12 GI wire nuting between 1m x 1m(12GGI wire), materials shall be class O type | 340 | Sq.M | |
196 | 20.5 | SUB METERING | |||
197 | 20.6 | Supply of ULTRASONIC BTU: BTU meter shall include the following Cold Meter Integators & Ultrasonic Flow meters. Cold Meter Integators: Shall include matched pair temperature sensor [Pocket for insertion to be included]. Shall have the features of working on Battery power supporting up to 16 Years, Data logging for up to 5 years, no external power supply, 8 Diigit LCD display, Protection category of IP65, M-BUS O/P card and vendor to furnish the country of origin of these meters. Flow meters: The flow meter shall include screwed / Flanged meters incorporate with ultrasonic flow sensing technology with totalising register. The meter shall be complying with EN 1434 and MID in class2 standards. The flow sensor shall have a Dynamic flow range of at least 1:250 [i.e Minimum flow: Nominal flow].Cost inculde at site perfromance test with OEM Engineer \nBtu Transmitters as per the specification for tenant billing. Btu Meters shall consist of following items of following sizes:-\nInline Flow Meter\nMatch Pair Sensors\nHeat Integrator\nMinimum 4 Data / Meter to Master Contoroller - T1 / T2 / Flow / KWH - with 2 mtr 2C shielded communication cable | |||
198 | 20.7 | 100mm dia | 2 | Nos | |
199 | 20.8 | 80mm dia | 20 | Nos | |
200 | 20.9 | 65mm dia | 21 | Nos | |
201 | 21 | 50mm dia | 3 | Nos | |
202 | 21.1 | 32mm dia | 27 | Nos | |
203 | 21.2 | 25mm dia | 3 | Nos | |
204 | 21.3 | Ventilation works | |||
205 | 21.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 1 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thickness, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Capacity of 30000 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW. STAIRCASE AND FIRE LIFT WELL PRESSURIZATION. Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
206 | 21.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch, saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 3 | Nos | |
207 | 21.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt . | 3 | Unit | |
208 | 21.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination. | 3 | Unit | |
209 | 21.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt. | 3 | Unit | |
210 | 21.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support. | 3 | Unit | |
211 | 22 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button. | 3 | Unit | |
212 | 22.1 | Charges for Air balancing works for the above units. | 3 | Unit | |
213 | 22.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
214 | 22.3 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the fan Supports. | 3 | Nos | |
215 | 22.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 1 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Capacity of 26000 cfm exhaust air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW.DG room exhaust system. Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
216 | 22.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 3 | Nos | |
217 | 22.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
218 | 22.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 3 | Unit | |
219 | 22.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 3 | Unit | |
220 | 22.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 3 | Unit | |
221 | 23 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
222 | 23.1 | Charges for Air balancing works for the above units | 3 | Unit | |
223 | 23.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
224 | 23.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 3 | Nos | |
225 | 23.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 1 mm thick pre-coated and pre plasticized sheets, Puff panel of25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%,unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Capacity of 22000 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW.Application - Plant Room Fresh Air.Cost inculde at site perfromance test with OEM Engineer. | 1 | Nos | |
226 | 23.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
227 | 23.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
228 | 23.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
229 | 23.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
230 | 23.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
231 | 24 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
232 | 24.1 | Charges for Air balancing works for the above units | 1 | Unit | |
233 | 24.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
234 | 24.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
235 | 24.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 1 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm (+/-1mm)thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Capacity of 22000 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW,Application - DG Room Fresh Air. once confirm machine capacity with DG vendor.Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
236 | 24.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 3 | Nos | |
237 | 24.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
238 | 24.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 3 | Unit | |
239 | 24.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 3 | Unit | |
240 | 24.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 3 | Unit | |
241 | 25 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
242 | 25.1 | Charges for Air balancing works for the above units | 3 | Unit | |
243 | 25.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
244 | 25.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 3 | Nos | |
245 | 25.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Capacity of 15500 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW,Application - STP fresh air unit.Cost inculde at site perfromance test with OEM Engineer. | 1 | Nos | |
246 | 25.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
247 | 25.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
248 | 25.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
249 | 25.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
250 | 25.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
251 | 26 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
252 | 26.1 | Charges for Air balancing works for the above units | 1 | Unit | |
253 | 26.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
254 | 26.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
255 | 26.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Capacity of 15500 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW, Application - Kitchen Fresh air.Cost inculde at site perfromance test with OEM Engineer. | 1 | Nos | |
256 | 26.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
257 | 26.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
258 | 26.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
259 | 26.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
260 | 26.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
261 | 27 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
262 | 27.1 | Charges for Air balancing works for the above units | 1 | Unit | |
263 | 27.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
264 | 27.3 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the fan Supports. | 1 | Nos | |
265 | 27.4 | Supply, Installation, Testing and Commissioning of Double skin inline fan, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Forward curved impeller with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, etc, Fan total efficiency shall be minimum 65%, - Capacity of 2900 CFM - TSP 30mm. Selected Motor rating shall be minimum 15% above BKW,unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements Application - Toilet Exhaust.Cost inculde at site perfromance test with OEM Engineer | 24 | Nos | |
266 | 27.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 24 | Nos | |
267 | 27.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 24 | Unit | |
268 | 27.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 24 | Unit | |
269 | 27.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 24 | Unit | |
270 | 27.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 24 | Unit | |
271 | 28 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 24 | Unit | |
272 | 28.1 | Charges for Air balancing works for the above units | 24 | Unit | |
273 | 28.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 24 | Nos | |
274 | 28.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 24 | Nos | |
275 | 28.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm (+/-1mm)thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 70%,unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements , Capacity of 5300 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW,Application - Transformer Room Exhaust. Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
276 | 28.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch, saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 3 | Nos | |
277 | 28.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
278 | 28.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 3 | Unit | |
279 | 28.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 3 | Unit | |
280 | 28.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 3 | Unit | |
281 | 29 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
282 | 29.1 | Charges for Air balancing works for the above units | 3 | Unit | |
283 | 29.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
284 | 29.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 3 | Nos | |
285 | 29.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 70%,unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Capacity of 4400 cfm - TSP 50mm, Selected Motor rating shall be minimum 15% above BKW,Application - Transformer Room Fresh air.Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
286 | 29.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 3 | Nos | |
287 | 29.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
288 | 29.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 3 | Unit | |
289 | 29.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 3 | Unit | |
290 | 29.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 3 | Unit | |
291 | 30 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
292 | 30.1 | Charges for Air balancing works for the above units | 3 | Unit | |
293 | 30.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
294 | 30.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard. | 3 | Nos | |
295 | 30.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 1 mm thick pre-coated and pre plasticized sheets, Puff insulation of 25 mm(+/-1mm) thickness between the panels, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%,unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements cabinet shall have Polyester Powder coating suitabe for outdoor type - Capacity of 22000 cfm fresh air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW-LIFTWELL PRESSURIZATION.Cost inculde at site perfromance test with OEM Engineer | 10 | Nos | |
296 | 30.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch, saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 10 | Nos | |
297 | 30.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cable Tray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 10 | Unit | |
298 | 30.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 10 | Unit | |
299 | 30.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 10 | Unit | |
300 | 30.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 10 | Unit | |
301 | 31 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 10 | Unit | |
302 | 31.1 | Charges for Air balancing works for the above units | 10 | Unit | |
303 | 31.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 10 | Nos | |
304 | 31.3 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the fan Supports. | 10 | Nos | |
305 | 31.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 1 mm thick pre-coated and pre plasticized sheets, Puff panel 25 mm(+/-1mm) thickness, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements cabinet shall have Polyester Powder coating suitabe for outdoor type - Capacity of 22000 cfm exhaust air unit- TSP 50mm. Selected Motor rating shall be minimum 15% above BKW. Plant room fresh air. Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
306 | 31.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch, saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
307 | 31.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
308 | 31.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
309 | 31.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
310 | 31.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
311 | 32 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
312 | 32.1 | Charges for Air balancing works for the above units | 1 | Unit | |
313 | 32.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
314 | 32.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
315 | 32.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%, unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirementscabinet shall have Polyester Powder coating suitabe for outdoor type - Capacity of 16500 cfm exhaust air unit- TSP 50mm.Selected Motor rating shall be minimum 15% above BKW , Application - WTP/FIRE PUMP Exhaust air.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
316 | 32.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
317 | 32.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
318 | 32.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
319 | 32.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
320 | 32.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
321 | 33 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
322 | 33.1 | Charges for Air balancing works for the above units | 1 | Unit | |
323 | 33.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
324 | 33.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
325 | 33.4 | Supply, installation, testing and commissioning of SISW fan, Aerofoil backward curved impeller with motor of IE 3 type VFD Compatible, Suitable base frame, belt guard, outlet damper needs to be provoided, fan should be with polyester powder coating suitable for outdoor type, Capacity of 18000 cfm - TSP 100mm. Fan total efficiency shall be minimum 75%, Suitable Spring vibration isolators to be fitted with Fans,unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements contractor should provide suitable motor canopy. Selected Motor rating shall be minimum 15% above BKW, Application - STP Exhaust. Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
326 | 33.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch, saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
327 | 33.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
328 | 33.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
329 | 33.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
330 | 33.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
331 | 34 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
332 | 34.1 | Charges for Air balancing works for the above units | 1 | Unit | |
333 | 34.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Unit | |
334 | 34.3 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the fan Supports. | 1 | Nos | |
335 | 34.4 | Supplying, installing, testing and commissioning of SISW fan, backward curved impeller with motor of IE 3 type VFD Compatible, outlet damper needs to be provoided, fan should be with polyester powder coating suitable for outdoor type, Fan shall be provided with Suitable base frame, belt guard, Drain plug and service door. Capacity of 15500 cfm - TSP 125mm. Fan total efficiency shall be minimum 75%, Suitable Spring vibration isolators to be fitted with Fans, contractor should provide suitable motor canopy, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements Selected Motor rating shall be minimum 15% above BKW Application - Kitchen exhaust | 1 | Nos | |
336 | 34.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
337 | 34.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
338 | 34.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
339 | 34.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
340 | 34.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
341 | 35 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
342 | 35.1 | Charges for Air balancing works for the above units | 1 | Unit | |
343 | 35.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
344 | 35.3 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the fan Supports. | 1 | Nos | |
345 | 35.4 | Supply, Installation, Testing and Commissioning of Double skin cabinet type, inner skin and outer skin shall be minimum 0.8mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm (+/-1mm)thick, density of insulation shall be 48 Kg/sq.m, DIDW Airfoil backward curve fan with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, inlet side having 900mm wide plenum section with 10micron filter, Spring Vibration Isolators, etc, Fan total efficiency shall be minimum 75%,unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements Capacity of 15500 cfm exhaust air unit- TSP 50mm.Selected Motor rating shall be minimum 15% above BKW , Application - WTP/FIRE PUMP Fresh air.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
346 | 35.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
347 | 35.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
348 | 35.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
349 | 35.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
350 | 35.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
351 | 36 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
352 | 36.1 | Charges for Air balancing works for the above units | 1 | Unit | |
353 | 36.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Unit | |
354 | 36.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
355 | 36.4 | Supply, Installation, Testing and Commissioning of Double skin inline fan, inner skin and outer skin shall be minimum 0.8 mm thick pre-coated and pre plasticized sheets, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Forward curved impeller with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, 10micron filter, etc, Fan total efficiency shall be minimum 65%, - Capacity of 2900cfm - TSP 30mm.Selected Motor rating shall be minimum 15% above BKW ,unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Application - Toilet Fresh Air.Cost inculde at site perfromance test with OEM Engineer | 24 | Nos | |
356 | 36.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 24 | Nos | |
357 | 36.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 24 | Unit | |
358 | 36.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 24 | Unit | |
359 | 36.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 24 | Unit | |
360 | 36.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 24 | Unit | |
361 | 37 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 24 | Unit | |
362 | 37.1 | Charges for Air balancing works for the above units | 24 | Unit | |
363 | 37.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 24 | Nos | |
364 | 37.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 24 | Nos | |
365 | 37.4 | Supply, Installation, Testing and Commissioning of Single skin type inline fan with acouostic lining, 1 mm thick casing DIDW Forward curved fan with Single phase motor, Direct Driven, outlet damper need to be provoided, inlet side with 10micron filter - Capacity of 600 cfm - TSP 25mm. Selected Motor rating shall be minimum 15% above BKW,Application - Utility block maintenance room fresh air.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
366 | 37.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
367 | 37.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
368 | 37.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
369 | 37.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
370 | 37.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
371 | 38 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
372 | 38.1 | Charges for Air balancing works for the above units | 1 | Unit | |
373 | 38.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
374 | 38.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
375 | 38.4 | Supply, Installation, Testing and Commissioning of Single skin inline fan with acouostic lining, 1 mm thick casing , DIDW Forward curved fan with Single phase motor, Direct Driven, outlet damper need to be provoided, - Capacity of 600 cfm - TSP 25mm. Selected Motor rating shall be minimum 15% above BKW,Application - Utility block maintenance room, Electrical Room, Garbage Room Exhaust.Cost inculde at site perfromance test with OEM Engineer | 4 | Nos | |
376 | 38.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 4 | Nos | |
377 | 38.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 4 | Unit | |
378 | 38.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 4 | Unit | |
379 | 38.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 4 | Unit | |
380 | 38.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 4 | Unit | |
381 | 39 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 4 | Unit | |
382 | 39.1 | Charges for Air balancing works for the above units | 4 | Unit | |
383 | 39.2 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 4 | Nos | |
384 | 39.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 4 | Nos | |
385 | 39.4 | Supply, Installation, Testing and Commissioning of Double skin inline fan, inner skin and outer skin shall be minimum 0.8 mm thick, Puff panel of 25 mm(+/-1mm) thick, density of insulation shall be 48 Kg/sq.m, DIDW Forward curved impeller with motor shall be IE 3 type VFD compatible, outlet damper need to be provoided, etc, Fan total efficiency shall be minimum 65%, - Capacity of 1000 CFM - TSP 30mm. Selected Motor rating shall be minimum 15% above BKW, Application - pantry Exhaust.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
386 | 39.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass dol star starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
387 | 39.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
388 | 39.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
389 | 39.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
390 | 39.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
391 | 40 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button. | 1 | Unit | |
392 | 40.1 | Charges for Air balancing works for the above units | 1 | Unit | |
393 | 40.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
394 | 40.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
395 | 40.4 | Supply, Installation, Testing and Commissioning of Circular Inline fan, outlet damper need to be provoided - Capacity of 100 cfm - TSP 20mm,Selected Motor rating shall be minimum 15% above BKW, Application - Utility block toilet exhaust | 2 | Nos | |
396 | 40.5 | Supply, installation, testing and commissioing of suitable Isolater switch | 2 | Nos | |
397 | 40.6 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 2 | Unit | |
398 | 40.7 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 2 | Unit | |
399 | 40.8 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 2 | Unit | |
400 | 40.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 2 | Unit | |
401 | 41 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 2 | Unit | |
402 | 41.1 | Charges for Air balancing works for the above units | 2 | Unit | |
403 | 41.2 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 2 | Nos | |
404 | 41.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 2 | Nos | |
405 | 41.4 | Supply, installation, testing and commissioing of Smokespill Vane axial fan 11500CFM @ 25 mm wg Static Pressure, Fan with Single Speed Motor, Speed shall be 960 RPM, DB level shall be less than 70 dB(A) at 1m distance with both side sound attenuator having round diameter as per the suitable selection of fan diameter and outer casing thickness shall be 0.8 mm 220GSM Gi Sheet, 50mm thick fiber glass with the density of 48kg/m2, required RP tissue and 0.8 mm Gl Perforated sheet for the above suitable size fan dia, Silencer length shall be minimum of 1.5 times dia of impeller. Rigid Mounting frame for ceiling/floor and required terminal box with suitable rating and suitable for cable termination, motor and fan shall be suitable for high tempreature of 250degC 2hrs rating, Selected Motor rating shall be minimum 15% above BKW, fan base with suitable size of coushy foot/spring mounting, Unit oulet shall be fire rated canvas 200dge 2hrs rating with TDF flange end,The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, Application - Basement Exhaust.Cost inculde at site perfromance test with OEM Engineer | 2 | Nos | |
406 | 41.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 2 | Nos | |
407 | 41.6 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 2 | Unit | |
408 | 41.7 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE fire rated cable for the above unit with suitable perfrated cableTray with 50thick, sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 90 to 110 rmt | 2 | Unit | |
409 | 41.8 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 2 | Unit | |
410 | 41.9 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 2 | Unit | |
411 | 42 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 2 | Unit | |
412 | 42.1 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 2 | Unit | |
413 | 42.2 | Charges for Air balancing works for the above units | 2 | Unit | |
414 | 42.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 2 | Nos | |
415 | 42.4 | Supply, installation, testing and commissioing of Vane axial fan 11500CFM @ 25 mm wg Static Pressure, Fan with Single Speed Motor, Speed shall be 960 RPM, DB level shall be less than 70 dB(A) at 1m distance with both side sound attenuator having round diameter as per the suitable selection of fan diameter and outer casing thickness shall be 0.8 mm 220GSM Gi Sheet, 50 mm thick fiber glass with the density of 48kg/m2, required RP tissue and 0.8 mm Gl Perforated sheet for the above suitable size fan dia , Silencer length shall be minimum of 1.5 times dia of impeller, Rigid Mounting frame for ceiling/floor and required terminal box with suitable rating and suitable for cable termination, fan base with suitable size of coushy foot/spring mounting , Unit outlet shall be fire rated canvas 300dge 2hrs rating with TDF flange end,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Selected Motor rating shall be minimum 15% above BKW,Application - Basement Fresh Air.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
416 | 42.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
417 | 42.6 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Unit | |
418 | 42.7 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE fire rated cable for the above unit with suitable perfrated cableTray with 50thick, sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 90 to 110 rmt | 1 | Unit | |
419 | 42.8 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
420 | 42.9 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
421 | 43 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 1 | Unit | |
422 | 43.1 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
423 | 43.2 | Charges for Air balancing works for the above units | 1 | Unit | |
424 | 43.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
425 | 43.4 | Jet fans axial type dia 315 mm dia for Basements/floor. Fans shall be operate with dual speed motor suitable for 250 Deg C for 2 hours fire rating, mounting legs, bell mouth shape at inlet, 2 bird screen with impeller dia not exceeding 315 mm. Silencer having round diameter as per the suitable selection of fan diameter and outer casing thickness shall be 0.8 mm thick 220GSM Gi Sheet, 50 mm thick fiber glass with the density of 48kg/m2, required RP tissue and 0.8 mm Gl Perforated sheet for the above suitable size fan dia , Silencer length shall be minimum of 2 times dia of impeller . fan base with suitable size of coushy foot/spring mounting , Unit oulet shall be fire rated canvas 200dge 2hrs rating with TDF flange end,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements.Cost inculde at site perfromance test with OEM Engineer | 4 | Nos | |
426 | 43.5 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 90 to 110 rmt | 4 | Unit | |
427 | 43.6 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 4 | Unit | |
428 | 43.7 | Supply, installation, testing and commissioing for 2 run of 6 G GI wire for earthing, App. route length shall be 30 rmt | 4 | Unit | |
429 | 43.8 | Supply, installation, testing and commissioing of Emergency Lockable Push button station for the above, Fire rated type with required GI angle iron support | 4 | Unit | |
430 | 43.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square XLPE copper armoud fire rated cable length shall be 20rmt between motor to Push button | 4 | Unit | |
431 | 44 | Charges for Air balancing works for the above units | 4 | Unit | |
432 | 44.1 | Supply, installation, testing and commissioing of Limit switch cabling from limit switch to Vfd, app length shall be 30rmt of 2 core 1.5sqmm XLPE copper armoured cable with end termination | 4 | Unit | |
433 | 44.2 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 4 | Nos | |
434 | 44.3 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 4 | Nos | |
435 | 44.4 | CO/CO2 detector head (Analog sensor-Should match the specifications),0- 250 ppm, with necessary arrangement of suitable fixing | 4 | Nos | |
436 | 44.5 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPEscrenned cable for the above unit with suitable 20mm GI conduits, inclusive of bend and reducers, App cable length 90 to 110 rmt | 4 | Nos | |
437 | 44.6 | Supply, installation, testing and commissioing car park control panel of logic control operation normal mode and fire mode - 4jet fans. 1 no fres air fans. I no normal exhast fans and 1 nor fir exhast fans | 1 | Nos | |
438 | 44.7 | Supply, installation, testing and commissioning of Double skin Dry Scruber unit for Kitchen exhast, panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, Capacity of 15500 CFM,ESP 20mm.In a single pass through the separator, given solids with a specific gravity of 2.6 and water at 1.0, performance is expected to be 98% of 74 microns and larger. In Re-circulating Systems -- 98% performance is predictable to as fine as 40 microns (given solids with a specific gravity of 2.6), Separator -- Centrifugal-action design, incorporating a true tangential inlet and mutually tangential Swirlex internal accelerating slots.Solids Collection Vessel -- Housing shall be 304 stainless steel with stainless steel basket and coated carbon steel lid with air pressure relief valve.inclusive of idicator package,automatice purge valve,piping and control valve and electrical panel,fan base with suitable size of coushy foot/spring mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
439 | 44.8 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
440 | 44.9 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
441 | 45 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination | 1 | Unit | |
442 | 45.1 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. Route length shall be 90 rmt | 1 | Unit | |
443 | 45.2 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 1 | Unit | |
444 | 45.3 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square mm XLPE copper armoured fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
445 | 45.4 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 1 | Nos | |
446 | 45.5 | Charges for Air balancing works for the above with low side | 1 | Unit | |
447 | 45.6 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm copper armoud cable with end termination | 1 | Unit | |
448 | 45.7 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
449 | 45.8 | Supply, installation, testing and commissioning of Double skin Dry Scruber unit for STP exhast, panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, Capacity of 15500 CFM, ESP 20mm. In a single pass through the separator, given solids with a specific gravity of 2.6 and water at 1.0, performance is expected to be 98% of 74 microns and larger. In Re-circulating Systems -- 98% performance is predictable to as fine as 40 microns (given solids with a specific gravity of 2.6), Separator -- Centrifugal-action design, incorporating a true tangential inlet and mutually tangential Swirlex internal accelerating slots. Solids Collection Vessel -- Housing shall be 304 stainless steel with stainless steel basket and coated carbon steel lid with air pressure relief valve.inclusive of idicator package, automatice purge valve, piping and control valve and electrical panel, fan base with suitable size of coushy foot/spring mounting, The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements. Cost inculde at site perfromance test with OEM Engineer. | 1 | Nos | |
450 | 45.9 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. | 1 | Nos | |
451 | 46 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
452 | 46.1 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination | 1 | Unit | |
453 | 46.2 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. Route length shall be 90 rmt | 1 | Unit | |
454 | 46.3 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 1 | Unit | |
455 | 46.4 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square mm XLPE copper armoured fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
456 | 46.5 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 1 | Nos | |
457 | 46.6 | Charges for Air balancing works for the above with low side | 1 | Unit | |
458 | 46.7 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm copper armoud cable with end termination | 1 | Unit | |
459 | 46.8 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
460 | 46.9 | Main building - Air Handling Units | |||
461 | 47 | Supply, installation, testing and commissioning of Double skin air handling unit, panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM, Aerofoil Backward curve fans with required high efficiency IE3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet side aluminium damper, SS 304- 18G drain pan with 19mm thick nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for fans, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 33 TR- 20000 CFM/ESP not less than 25 mm,Selected Motor rating shall be minimum 15% above BKW.Cost inculde at site perfromance test with OEM Engineer | 16 | Nos | |
462 | 47.1 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 16 | Nos | |
463 | 47.2 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps, Aluminium reflector, electronic ballast and all other components. The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment. The lamps should be CE certified. The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years. "The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable, wire, end termination, isolator, conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 16 | Nos | |
464 | 47.3 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 16 | Unit | |
465 | 47.4 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 16 | Unit | |
466 | 47.5 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 16 | Unit | |
467 | 47.6 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 16 | Unit | |
468 | 47.7 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 16 | Unit | |
469 | 47.8 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 16 | Nos | |
470 | 47.9 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 16 | Unit | |
471 | 48 | Charges for Air balancing works for the above units | 16 | Unit | |
472 | 48.1 | Charges for Water balancing for the above | 16 | Unit | |
473 | 48.2 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 16 | Unit | |
474 | 48.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 16 | Nos | |
475 | 48.4 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 16 | Unit | |
476 | 48.5 | Supply, installation, testing and commissioning of Double skin air handling unit, panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil faced backward curve fans with required high efficiency IE3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 18 TR- 10200CFM ESP not less than 25MM.Selected Motor rating shall be minimum 15% above BKW.Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
477 | 48.6 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 1 | Nos | |
478 | 48.7 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps, Aluminium reflector, electronic ballast and all other components. The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified. The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable, wire, end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 1 | Nos | |
479 | 48.8 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
480 | 48.9 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
481 | 49 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
482 | 49.1 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 1 | Unit | |
483 | 49.2 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
484 | 49.3 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 1 | Nos | |
485 | 49.4 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 1 | Unit | |
486 | 49.5 | Charges for Air balancing works for the above units | 1 | Unit | |
487 | 49.6 | Charges for Water balancing for the above | 1 | Unit | |
488 | 49.7 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 1 | Unit | |
489 | 49.8 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
490 | 49.9 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 1 | Unit | |
491 | 50 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 05TR- 3020CFM, ESP not less than 15mm.Selected Motor rating shall be minimum 15% above BKW, Ceiling suspended type.Cost inculde at site perfromance test with OEM Engineer | 2 | Nos | |
492 | 50.1 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 2 | Nos | |
493 | 50.2 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps, Aluminium reflector, electronic ballast and all other components. The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years. "The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable, wire, end termination, isolator, conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 2 | Nos | |
494 | 50.3 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 2 | Unit | |
495 | 50.4 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 2 | Unit | |
496 | 50.5 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 2 | Unit | |
497 | 50.6 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 2 | Unit | |
498 | 50.7 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 2 | Unit | |
499 | 50.8 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 2 | Unit | |
500 | 50.9 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 2 | Unit | |
501 | 51 | Charges for Air balancing works for the above units | 2 | Unit | |
502 | 51.1 | Charges for Water balancing for the above | 2 | Unit | |
503 | 51.2 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 2 | Unit | |
504 | 51.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. | 2 | Nos | |
505 | 51.4 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 2 | Unit | |
506 | 51.5 | Supply, installation, testing and commissioning of Double skin air handling unit, panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 8 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM, Aerofoil Backward curvefans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator.- Capacity Minimum of 18 TR- 10200CFM ESP not less than 25mm.Selected Motor rating shall be minimum 15% above BKW, Ceiling suspended unit. Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
507 | 51.6 | Supply and installation of inline centrifugal circulator coil pump 20gpm @ 8m head IE3 motor with inbulid VFD with controller connected to operate the above AHU and suitable control panel necessary cabling between motor to VFD. Required temperature/Pressure sensor to be included interconnect to pump motor. | 1 | Nos | |
508 | 51.7 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 1 | Nos | |
509 | 51.8 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 1 | Unit | |
510 | 51.9 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
511 | 52 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
512 | 52.1 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
513 | 52.2 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 1 | Unit | |
514 | 52.3 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
515 | 52.4 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 1 | Unit | |
516 | 52.5 | Charges for Air balancing works for the above units | 1 | Unit | |
517 | 52.6 | Charges for Water balancing for the above | 1 | Unit | |
518 | 52.7 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 1 | Unit | |
519 | 52.8 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
520 | 52.9 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 1 | Nos | |
521 | 53 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 1 | Unit | |
522 | 53.1 | Supply, installation, testing and commissioning of Double skin air handling unit, panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM, Aerofoil Backward curvefans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator.- Capacity Minimum of 13 TR- 6100CFM/ESP not less than 25mm.Selected Motor rating shall be minimum 15% above BKW,Ceiling suspended unit.Cost inculde at site perfromance test with OEM Engineer | 5 | Nos | |
523 | 53.2 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 5 | Nos | |
524 | 53.3 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 5 | Nos | |
525 | 53.4 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 5 | Unit | |
526 | 53.5 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 5 | Unit | |
527 | 53.6 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 5 | Unit | |
528 | 53.7 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 5 | Unit | |
529 | 53.8 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 5 | Unit | |
530 | 53.9 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 5 | Unit | |
531 | 54 | Charges for Air balancing works for the above units | 5 | Unit | |
532 | 54.1 | Charges for Water balancing for the above | 5 | Unit | |
533 | 54.2 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 5 | Unit | |
534 | 54.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 5 | Nos | |
535 | 54.4 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard. | 5 | Nos | |
536 | 54.5 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 5 | Unit | |
537 | 54.6 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 21 TR- 12500 CFM/ESP not less than 25mm.Selected Motor rating shall be minimum 15% above BKW.Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
538 | 54.7 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 3 | Nos | |
539 | 54.8 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 3 | Unit | |
540 | 54.9 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
541 | 55 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 3 | Unit | |
542 | 55.1 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 3 | Unit | |
543 | 55.2 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 3 | Unit | |
544 | 55.3 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
545 | 55.4 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 3 | Nos | |
546 | 55.5 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 3 | Unit | |
547 | 55.6 | Charges for Air balancing works for the above units | 3 | Unit | |
548 | 55.7 | Charges for Water balancing for the above | 3 | Unit | |
549 | 55.8 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 3 | Unit | |
550 | 55.9 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
551 | 56 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 3 | Unit | |
552 | 56.1 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator.- Capacity Minimum of 39 TR- 24000 CFM/ESP not less than 25mm,Selected Motor rating shall be minimum 15% above BKW.Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
553 | 56.2 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 3 | Nos | |
554 | 56.3 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 3 | Nos | |
555 | 56.4 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
556 | 56.5 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 3 | Unit | |
557 | 56.6 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 3 | Unit | |
558 | 56.7 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 3 | Unit | |
559 | 56.8 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
560 | 56.9 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 3 | Nos | |
561 | 57 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 3 | Unit | |
562 | 57.1 | Charges for Air balancing works for the above units | 3 | Unit | |
563 | 57.2 | Charges for Water balancing for the above | 3 | Unit | |
564 | 57.3 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 3 | Unit | |
565 | 57.4 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
566 | 57.5 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 3 | Unit | |
567 | 57.6 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 8 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 39 TR- 17000 CFM/ESP not less than 25mm, Selected Motor rating shall be minimum 15% above BKW, GYM AREA. Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
568 | 57.7 | Supply and installation of inline centrifugal circulator coil pump 104gpm @ 8m head IE3 motor with inbulid VFD with controller connected to operate the above AHU and suitable control panel necessary cabling between motor to VFD. Required temperature/Pressure sensor to be included interconnect to pump motor. | 1 | Nos | |
569 | 57.8 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 1 | Nos | |
570 | 57.9 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 1 | Nos | |
571 | 58 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
572 | 58.1 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 1 | Unit | |
573 | 58.2 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 1 | Unit | |
574 | 58.3 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 1 | Unit | |
575 | 58.4 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 1 | Nos | |
576 | 58.5 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 1 | Unit | |
577 | 58.6 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 1 | Unit | |
578 | 58.7 | Charges for Air balancing works for the above units | 1 | Unit | |
579 | 58.8 | Charges for Water balancing for the above | 1 | Unit | |
580 | 58.9 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 1 | Unit | |
581 | 59 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
582 | 59.1 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 1 | Unit | |
583 | 59.2 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the abovefor fans, unit base with suitable size of coushy foot mounting , the motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 27TR- 15000 CFM/ESP not less than 25mm.Selected Motor rating shall be minimum 15% above BKW.Cost inculde at site perfromance test with OEM Engineer | 14 | Nos | |
584 | 59.3 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 14 | Nos | |
585 | 59.4 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 14 | Nos | |
586 | 59.5 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 14 | Unit | |
587 | 59.6 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 14 | Unit | |
588 | 59.7 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 14 | Unit | |
589 | 59.8 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 14 | Unit | |
590 | 59.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 14 | Unit | |
591 | 60 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 14 | Nos | |
592 | 60.1 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 14 | Unit | |
593 | 60.2 | Charges for Air balancing works for the above units | 14 | Unit | |
594 | 60.3 | Charges for Water balancing for the above | 14 | Unit | |
595 | 60.4 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 14 | Unit | |
596 | 60.5 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 14 | Nos | |
597 | 60.6 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 14 | Unit | |
598 | 60.7 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 6 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM,Aerofoil Backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the above fans, unit base with suitable size of coushy foot mounting ,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. Capacity Minimum of 4 TR- 1600CFM/ESP not less than 25mm. Selected Motor rating shall be minimum 15% above BKW,Ceiling suspended type.Cost inculde at site perfromance test with OEM Engineer | 31 | Nos | |
599 | 60.8 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 31 | Nos | |
600 | 60.9 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 22 | Nos | |
601 | 61 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 31 | Unit | |
602 | 61.1 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 31 | Unit | |
603 | 61.2 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 31 | Unit | |
604 | 61.3 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 31 | Unit | |
605 | 61.4 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 31 | Unit | |
606 | 61.5 | Supply, installation, testing and commissioing of MS channel support with two coat of enamal painting for Unit supports, Support shall be with cushy foot mounting or spring mounting as per the manufacter standard | 31 | Nos | |
607 | 61.6 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 31 | Unit | |
608 | 61.7 | Charges for Air balancing works for the above units | 31 | Unit | |
609 | 61.8 | Charges for Water balancing for the above | 31 | Unit | |
610 | 61.9 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 31 | Unit | |
611 | 62 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 31 | Nos | |
612 | 62.1 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 31 | Unit | |
613 | 62.2 | Supply and instaltion of Skin Fan Coil unit with 4Row deep coil,high static fan minimum of 9mm external static,extended valve box GI 12G tray with insulation 19mm thick nitrile rubber, skin thickness shall 0.8mm thick pre-coated and pre plasticized sheets,13FPI,12.5mm dia 0.5mm thick copper coil, three speed regulator and two way modulation valve with 230v type and 2nos suitable ball valve with strianers 1no,modulation valve with actuvators including fire rated canvas conection, 4rmt suiable cableing between unit motor to electrical isolators/control valve/Uv light, Inclusive of required UV lamps capacity with cabling and conduits between UV lamp to electrical panel.with required support. Electrcial isolator panel to bve inculded in scope of work , Panel haveing provison for operate three speed control switch for fcu motor operation, 1no of 24v/230v Provision for control valve power supply and 1 nos isilator switch for UV light power provison.Cost inculde at site perfromance test with OEM Engineer | |||
614 | 62.3 | 3TR-1200 CFM -9mm ext static- 55dba @1m from unit | 22 | Nos | |
615 | 62.4 | 2.5TR-1000CFM -9mm ext static- 55dba @1m from unit | 22 | Nos | |
616 | 62.5 | 2.0TR-800CFM -9mm ext static- 55dba @1m from unit | 2 | Nos | |
617 | 62.6 | Supply, installation, testing and commissioning of Double skin air handling unit , panel having 50mm(+/-2mm) thick puff 48 kg/cum density, inner and outer skin shall be 0.8mm thick pre-coated and pre plasticized sheets, 8 ROW deep coil having 13 FPI with coil face velocity 450 FPM and filter face velocity shall be 350 FPM, Aerofoil backward curve fans with required high efficiency IE 3 Motors -TEFC Squirrel gauge induction motor, commissioning filter, 10micron pre filter and 5micron back filter washable type, 900mm depth Return air plenum section with fresh air and return air aluminium damper and outlet aluminium damper, SS 304- 18G drain pan with 19mm thich nitrille insulation, limit switch and safety guard, view panel, required spring mounted vibration isolator for the abovefor fans, unit base with suitable size of coushy foot mounting , The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator,Capacity Minimum of 75TR- 20000CFM/ESP not less than 25mm. HRW unit fresh air 5000Cfm,wheel shall be 400mm depth ,ESP 25mm for main supply air fans. Fressh air fan ext static 12mm,Selected Motor rating shall be minimum 15% above BKW.Cost inculde at site perfromance test with OEM Engineer | 2 | Nos | |
618 | 62.7 | Supply and installation of inline centrifugal circulator coil pump gpm 200us gpm@ 8m head IE3 motor with inbulid VFD with controller connected to operate the above AHU and suitable control panel necessary cabling between motor to VFD. Required temperature/Pressure sensor to be included interconnect to pump motor. | 2 | Nos | |
619 | 62.8 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter, disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 2 | Nos | |
620 | 62.9 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps, Aluminium reflector, electronic ballast and all other components. The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified. The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years. "The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable, wire, end termination, isolator, conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 2 | Nos | |
621 | 63 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 2 | Unit | |
622 | 63.1 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above both the end termination | 2 | Unit | |
623 | 63.2 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. route length shall be 30 rmt | 2 | Unit | |
624 | 63.3 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 2 | Unit | |
625 | 63.4 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square copper XLPE armoured fire rated cable length shall be 20rmt between motor to Push button | 2 | Unit | |
626 | 63.5 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 2 | Nos | |
627 | 63.6 | Supply, installation, testing and commissioing of Regid MS supports with Enamal painting for valve packages | 2 | Unit | |
628 | 63.7 | Charges for Air balancing works for the above units | 2 | Unit | |
629 | 63.8 | Charges for Water balancing for the above | 2 | Unit | |
630 | 63.9 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm XLPE copper armoured cable with end termination | 2 | Unit | |
631 | 64 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 2 | Unit | |
632 | 64.1 | Supply, installation, testing and commissioing of AHUs/CSUs manifold for the above capcities which include required supply and return line with Puff insulation 24Gi cladding, 2nos of Isolation butterfly valve, suitable size Self dynamic valves, 2 nos pressure gauge, 2 nos temp gauge drain valve, auto air vent with isolation valve | 2 | Unit | |
633 | 64.2 | Supplying, installation, testing and commissioning of HEAT RECOVERY WHEEL UNIT with assembled condition all Sheet metal cabinet type double skin HRU, the inner and outer sheets of the double skin shall be 0.8 mm thick pre-coated and pre plasticized sheets with 50 mm (+/-2mm)thick. Backward curve aero foil fan, fan motor, fan casing insulation for accoustic, 450 mm depth enthalpy recovery, Filter section with Pre Filter, Bag Filter, Hepa filter (Box type 450mm(+/-5mm) length ) & UVGI lamp on both sides, sound level shall be 60dbA from 1 mtr for both sides of air stream. Units shall be complete with opposed blade volume control dampers at both oulets, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, Fresh air temp DB:104F, WB: 82F, Exhaust air temp DB:76F, RH:60-66%, duct static pressure sensor (range 100-150pa). capacity of Supplying air fan 21000cfm@ external static not less than 25mm and exhaust air fan shall be 16800cfm-ESP not less than 15mm, 76% of efficieny for sensibel and latent heat, exhaust/fresh air side consist of EU3,EU9, with Ultra violet germicidal irradiation Lamp on both sides, Energy wheel velocity shall be less as per coil face velocity.unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1. Cost inculde at site perfromance test with OEM Engineer | 2 | Nos | |
634 | 64.3 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply /Return/Wheel air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 2 | Nos | |
635 | 64.4 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt.for fans, unit base with suitable size of coushy foot mounting , Unit oulet damper shall be fire rated canvas 200dge 2hrs rating with TDF flange end,The motor shall comply IEC60034 for construction and IE3 efficiency,Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements,Copper header with Ms Addaptor with suitable flange conection to conect the piping, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1, two pass PVC drift Eliminator. | 2 | Nos | |
636 | 64.5 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 2 | Unit | |
637 | 64.6 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination | 2 | Unit | |
638 | 64.7 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. Route length shall be 90 rmt | 2 | Unit | |
639 | 64.8 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 2 | Unit | |
640 | 64.9 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square mm XLPE copper armoured fire rated cable length shall be 20rmt between motor to Push button | 2 | Unit | |
641 | 65 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 2 | Nos | |
642 | 65.1 | Charges for Air balancing works for the above with low side | 2 | Unit | |
643 | 65.2 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm copper armoud cable with end termination | 2 | Unit | |
644 | 65.3 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 2 | Unit | |
645 | 65.4 | Supplying, installation, testing and commissioning of HEAT RECOVERY WHEEL UNIT with assembled condition all Sheet metal cabinet type double skin HRU, the inner and outer sheets of the double skin shall be 0.8 mm thick pre-coated and pre plasticized sheets with 50 mm(+/-2mm) thick. Backward curve aero foil fan, fan motor,fan casing insulation for accoustic, 450 mm depth enthalpy recovery, Filter section with Pre Filter, Bag Filter, Hepa filter ( Box type 450mm(+/-5mm) length ) & UVGI lamp on both sides, sound level shall be 60dbA from 1 mtr for both sides of air stream. Units shall be complete with opposed blade volume control dampers at both oulets, Duct flexible connector (fire proof) shall be provided at outlets. Limit switches for the doors with necessary cabling works for the proper function. Bulk head fitting including necessary electrical and control cabling for its proper operation, Fresh air temp DB:104F, WB: 82F, Exhaust air temp DB:76F, RH:60-66%, duct static pressure sensor (range 100-150pa). capacity of Supplying air fan 8500cfm@ external static 25mm and exhaust air fan shall be 6800cfm /ESP 15MM, 76% of efficieny for sensibel and latent heat, exhaust/fresh air side consist of EU3,EU9 , with Ultra violet germicidal irradiation Lamp on both sides, Energy wheel velocity shall be less as per coil face velocity.for fans, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1. Cost inculde at site perfromance test with OEM Engineer | 1 | Nos | |
646 | 65.5 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply/Return/Wheel air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 1 | Nos | |
647 | 65.6 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps, Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 1 | Nos | |
648 | 65.7 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 1 | Unit | |
649 | 65.8 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination | 1 | Unit | |
650 | 65.9 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. Route length shall be 90 rmt | 1 | Unit | |
651 | 66 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 1 | Unit | |
652 | 66.1 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square mm XLPE copper armoured fire rated cable length shall be 20rmt between motor to Push button | 1 | Unit | |
653 | 66.2 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 1 | Nos | |
654 | 66.3 | Charges for Air balancing works for the above with low side | 1 | Unit | |
655 | 66.4 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm copper armoud cable with end termination | 1 | Unit | |
656 | 66.5 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 1 | Nos | |
657 | 66.6 | Supplying, installation, testing and commissioning of HEAT RECOVERY WHEEL UNIT with assembled condition all Sheet metal cabinet type double skin HRU, the inner and outer sheets of the double skin shall be 0.8 mm thick pre-coated and pre plasticized sheets with 50 mm(+/-2) thick. Backward curve aero foil fan, fan motor, fan casing insulation for accoustic, 450 mm depth enthalpy recovery, Filter section with Pre Filter, Bag Filter, Hepa filter ( Box type 450mm(+/-5mm) length ) & UVGI lamp on both sides, sound level shall be 60dbA from 1 mtr for both sides of air stream.Units shall be complete with opposed blade volume control dampers at both oulets, Duct flexible connector (fire proof) shall be provided at outlets.Limit switches for the doors with necessary cabling works for the proper function.Bulk head fitting including necessary electrical and control cabling for its proper operation, Fresh air temp DB:104F, WB: 82F, Exhaust air temp DB:76F, RH:60-66%, duct static pressure sensor (range 100-150pa). capacity of Supplying air fan 6000cfm@ external static 25mm and exhast air fan shall be 4800cfm, 76% of efficieny for sensibel and latent heat, exhaust/fresh air side consist of EU3,EU9 , with Ultra violet germicidal irradiation Lamp on both sides, Energy wheel velocity shall be less as per coil face velocity.for fans, unit base with suitable size of coushy foot mounting, The motor shall comply IEC60034 for construction and IE3 efficiency, Motor winding shall be vacuum pressure impregnated for all motors. Insulated bearing on non-drive end for Motor frame of 315 and above shall be provided. fans are rated and tested in accordance with AMCA standard to meet the air and sound performance requirements, EN1886/AHRI1350 standard for Thermal transmittance –T2/CT1, Thermal bridging –TB2/CTB1, Casing air leakage –l2, filter bypass leakage –F9, Casing strength –D1 /CD1.Cost inculde at site perfromance test with OEM Engineer | 3 | Nos | |
658 | 66.7 | Supply, installation, testing and commissioing of Suitable IP55 VFD & PID controller (A0-2.Ai-4, DO-5,DI -5) with by pass star delta starter for operation of Ahus Supply/Return/Wheel air fan, auto/manual switch,saftey switch, ammeter, voltmer and energy meter,disconnet switch VFD/star delta units shall be provided with factory fitted Active Harmonic Filters meeting IEEE 519 standards and THDI not exceeding 5%, panel shall be as per the IS standard of electrial standard and, CRCA-14 G / 2mm thick Sheet steel enclosed, indoor floor mounted free standing cubicle type & CNC fabricated, required BMS compatable for the above operation. Panel having provison for 2no of 12v/24 v/230 volts transformer/isolator switch for two way valves and limit switch input power requirment and 2nos of 230 volts power supply for UV lights and fire damper control panel power requirment. Panel should be designed for fire control operation and BMS compatable type | 3 | Nos | |
659 | 66.8 | Supply and installation of f UVGI systems for the AHU comprising of all the neccesary accessories ie UV Lamps,Aluminium reflector,electronic ballast and all other components.The UV lamps should Comply with UL Standard 1995, 153, 1598 as applicable to usage of UVC Emitters in HVAC Equipment.The lamps should be CE certified.The UV lamp should have a life of 18000 hrs. The Power Supplies and Fixtures shall be warranted for 10-years."The UVC dose at the extreme edges of the coil shall not be less than 1225 µW/cm2 and end of life intensity on the coil face shall exceed 750 µW/cm2 at the end of the 18000 hours of operation period measured in 2.5 m/s airflow at 13 Deg C. cost include Power cable,wire,end termination, isolator,conduit and 18Ggi earth between UV lamp to electrical panel., dsitance between elctical panel t Uv lamp app 50 tp 70 rmt | 3 | Nos | |
660 | 66.9 | Supply, installation, testing and commissioing of fire rated suitable copper armoured XLPE cable for the above unit with suitable perfrated cableTray with 50thick, tray sheet thickness -2mm, GI angle Iron support for tray, inclusive of bend and reducers, App cable length 40 to 110 rmt | 3 | Unit | |
661 | 67 | Supply, installation, testing and commissioing of suitable fire rated Double compression cable gland for the above termination | 3 | Unit | |
662 | 67.1 | Supply, installation, testing and commissioing for 2 run of 12G GI wire for earthing, App. Route length shall be 90 rmt | 3 | Unit | |
663 | 67.2 | Supply, installation, testing and commissioing of Emergency Push button station for the above, Fire rated type with required support | 3 | Unit | |
664 | 67.3 | Supply, installation, testing and commissioing of Emergency Lockable Push button station cabling for the above, 3 core 1.5 square mm XLPE copper armoured fire rated cable length shall be 20rmt between motor to Push button | 3 | Unit | |
665 | 67.4 | Supply, installation, testing and commissioing of PCC pedestal 300X300X200mm H with required M30 Grade concrete with 6 nos of 12mm Thick Rubber pads for the AHU Supports. | 3 | Nos | |
666 | 67.5 | Charges for Air balancing works for the above with low side | 3 | Unit | |
667 | 67.6 | Supply, installation, testing and commissioing of Limit switch/bulk head cabling from ahus to vfd, app length shall be 90rmt of 3core 1.5sqmm copper armoud cable with end termination | 3 | Unit | |
668 | 67.7 | Supply, installation, testing and commissioing charges for fire rated canvas connection for the above. fire rating shall be 300dge 2hrs rating with TDF flange end | 3 | Nos | |
669 | 67.8 | ELECTRICAL WORKS | |||
670 | 67.9 | MAIN BUILDING WORKS\nHT PANEL INSTALLATION & TRANSFORMER | |||
671 | 68 | ESTABLISHMENT OF 33KV RECEIVING STATION \nINDOOR TYPE 33KV RING MAIN GEAR UNIT\nSupply, Erection, Testing and commissioning of 1 set of totally enclosed, floor standing, sheet steel clad cubicle pattern Indoor type RMG Panel 33 KV HT Switch Board, consist 2nos of 33KV 1250A VCB as incomer and 1 no of 33KV 1250A VCB as outgoing panel with one set of 1250 amps coloured PVC sleeved copper bus bars and accessories as per detailed specification , and TANGEDCO latest norms. | 1 | Unit | |
672 | 68.1 | INDOOR TYPE HT 33KV VCB METERING 1 PANEL \nSupply, Erection, Testing and commissioning of 1 set of totally enclosed, Indoor type floor standing, sheet steel clad cubicle pattern 1 Panel 33 KV (Metering Panel) HT Switch Board, 1 no of 33KV 1250A VCB as Incomer and Cable termination chamber for outgoing terminaiton for panel and provide one set of 1250 amps coloured PVC sleeved copper bus bars and accessories as below and as per detailed specification as per volume -III | 1 | Unit | |
673 | 68.2 | ESTABLISMENT OF 33KV SUB STATION \nINDOOR TYPE - 33KV HT 5 PANEL \nSupply, Erection, Testing and commissioning of 1 set of totally enclosed, indoor type floor standing, sheet steel clad cubicle pattern 5 Panel 33 KV HT Switch Board consistsing of 1 no of 33KV 1250A VCB as Incomer and 4Nos of 33KV 630A VCB as outgoing panel and provide one set of 1250 amps coloured PVC sleeved copper bus bars and accessories as per detailed specification . | 1 | Unit | |
674 | 68.3 | IN DOOR TYPE - 2500 KVA TRANSFORMER\nSupply, Erection, Testing & commissioning of Indoor type 2500KVA ,3 phase , 50Hz, 33KV/433 V, DYn 11, DRY type Distribution transfomer with vaccum on load tap changer and complete accessories as specified including freight , packing forwarding uptoTidel site -pattabiram including unloading the unit for the plinth and accessories ,Transport and storage insurance for 90 days at site for the Distribution transfomer. as per detailed specification.\n(Any foundation, plinth or any related civil works for RMU, HT< Panel and transformer is Civil Contractor's scope .the foundation drawings should be submitted by the Electrical contractor .) | 3 | Unit | |
675 | 68.4 | BATTERY CHARGER –BATTERY – DC PANEL SYSTEMS\nSupplying installing testing and commissioning of Power pack panel with 230/415 Volt AC input supply and 110 Volt DC continous output suitable for closing / tripping / indication of 16 Nos HT VCB Panel boards with Battery Bank consisting of 55 Nos 2V batteries of minimum 200AH capacity (VRLA Type) and comprising of Self contained Float cum Boost charger ( minimum 20Amps), complete with Incoming and outgoing MCBs, suitable capacity of AC and DC ammeters and voltmeters including connections, powder coating/painting etc as required . The panel shall be of suitable size fabricated from CRCA sheet steel of minimum 1.6 mm thick and shall be free standing, floor mounting type with louvres for ventilation, backed up by fine wire mesh to make the cabinet vermin and dust proof and suitable size Battery rack with front transparent cover etc as required. | 1 | Unit | |
676 | 68.5 | Dc cable for from DC DB to Respective Ht panel -4C x 2.5 sq.mm armoured copper cable | 500 | Rmt | |
677 | 68.6 | HT CABLE & END TERMINATION\nSupplying of following sizes of 33KV, 3 core, Earthed, XLPE Insulated, Aluminium conductor individual core screened, flat steel strip armoured, PVC sheathed cable conforming to IS 7098 / (PART-II) 2011 | |||
678 | 68.7 | 33 KV 3C 300 sq.mm. XLPE Armoured Cable form 33KV HT RMG panel to to 33KV HT 1 panel and HT 1 Panel to 33KV HT 5 Panel. (5 | 150 | Rmt | |
679 | 68.8 | 33KV 3C 240sq.mm. XLPE Armoured Cable. From 33KV HT 5 panel to 33KV/0.433KV Distribution transformer 1,2 & 3. | 280 | Rmt | |
680 | 68.9 | Laying of one No. 33KV, 3 core, Earthed, XLPE Insulated, Aluminium conductor individual core screened, flat steel strip armoured, PVC sheathed cable of grade exceeding 33KV but not exceeding 33KV of size not exceeding 400 sq.mm in the existing RCC /HUME /STONE WARE/ METAL PIPE | 10 | Rmt | |
681 | 69 | Laying of one No. 33KV, 3 core, Earthed, XLPE Insulated, Aluminium conductor individual core screened, flat steel strip armoured, PVC sheathed cable of grade exceeding 33KV but not exceeding 33KV of size not exceeding 400 sq.mm in the existing Masonary open duct / Cable trays as required. | 350 | Rmt | |
682 | 69.1 | Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 33 KV grade , of size exceeding 120 sq. mm. but not exceeding 400sq.mm. direct in ground including 1.2 mtr. depth excavation, sand cushioning, protective covering and refilling the trench etc. as required. and as specification. | 70 | Rmt | |
683 | 69.2 | Supplying and making indoor end cable termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 33KV XLPE aluminuim conductor of 3 core, 300 sqmm cable. | 6 | Unit | |
684 | 69.3 | Supplying and making indoor end cable termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 33KV XLPE aluminuim conductor of 3 core, 240 sqmm cable. | 6 | Unit | |
685 | 69.4 | Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for 33KV XLPE aluminuim conductor of 3 core,300 sqmm cable. | 1 | Unit | |
686 | 69.5 | Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for 33KV XLPE aluminuim conductor of 3 core,240 sqmm cable. | 1 | Unit | |
687 | 69.6 | Supply,laying,testing and commissioning of control cable size 24 core 2.5 sqmm PVC insulated, PVC sheathed armoured copper conductor cable. From HT Panel to Marshaling Box. | 190 | Rmt | |
688 | 69.7 | Supply, terminations,testing and commissioning of control cable size 24 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 12 | Unit | |
689 | 69.8 | Supply,laying,testing and commissioning of control cable size 19 core 2.5 sqmm PVC insulated, PVC sheathed armoured copper conductor cable. From OLDC to RTCC Panel. | 155 | Rmt | |
690 | 69.9 | Supply, terminations,testing and commissioning of control cable size 19 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 6 | Unit | |
691 | 70 | Supply,laying,testing and commissioning of control cable size 4 core 2.5 sqmm PVC insulated, PVC sheathed armoured copper conductor cable. From LT panel to Marshaling Box. | 60 | Rmt | |
692 | 70.1 | Supply, terminations,testing and commissioning of control cable size 4 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 6 | Unit | |
693 | 70.2 | Supply,laying, testing and commissioning of control cable size 4 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. From RTCC to OLTC. | 160 | Rmt | |
694 | 70.3 | Supply, terminations,testing and commissioning of control cable size 4 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 6 | Unit | |
695 | 70.4 | Supply,laying, testing and commissioning of control cable size 3 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. From LT panel to Marshaling Box. | 60 | Rmt | |
696 | 70.5 | Supply, terminations,testing and commissioning of control cable size 3 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 6 | Unit | |
697 | 70.6 | PART - B\nLT PANELS, DBS, ELECTRICAL CABLES WIRING & LIGHT FIXTURE, EARTHING. ETC. | |||
698 | 70.7 | LT PANEL BOARD\nMAIN MV PANEL -1 (As per IEC 61439 & IAC as per IS 61641)\nSupply, Installation, Testing and Commissioning of Medium Voltage floor mounting Cubicle Type Single bus bar system Panel Board suitable for 415 V, 3 Phase, 50 Hz 65Ka Power Distribution System with the following mounting complete as per specifications attached.\nA) Incomer - 1, 2 For Transformer 1, 2 : \n1Nos 4000 AMPS ACB, 65 KA (Ics) AC Motor operated Draw Out ( EDO ) Type Four Pole Microprocessor based relay having Over current, short circuit earth fault with time setting Earth fault and 6NO + 6 NC, indication for test,service,isolated ON/OFF trip indications, ShutterAssembly,Racking interlock Manual / Electrical closing & tripping Ready to close indication contact, Site changable rear terminal adaptors, Mechanical door interlock, Trip unit shall be Microprocessor based LSING protection with onboard communication port supporting modbus TCP communication protocol as specified in the technicalSpecifications. all busbars RYBN should 100% rated | 1 | Unit | |
699 | 70.8 | Continue above\nEthernet modules provided shall be with two Ethernet ports to minimize the number of Ethernet switches required in the system. as specified in the technicalSpecifications.\nThere shall be one set of Metering Compartment incorporated with the following:- \n1No - Class 1.0, Digital Maximum Demand Meter with controller, Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fuses etc.\n1No - Multi control relay for contorl of Under voltage, Over voltage, Single phase preventor, Phase rotation, with control fuses wiring etc.\n3Nos. - 4000/5A CL-0.2, 15VA current transformer with CT short link terminal block for Maximum demand Meter.\n1 No. - CDG11 Earth Fault relay \n1 Set of Differencial Protection relay\n4 No. 4000/5A 5P10 15VA Current transformer with CT short link terminal block for Earth fault relay.\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse.\nTNC switch for breaker ON, OFF, Trip & Auto Manual Selector switch | |||
700 | 70.9 | Continue above\nfor selection of auto and manual mode.\n1 Set of Surge Protection device Type-I/Class B IS/IEC 62305-4\n3 No. 4000/5A CL-1, 15VA Current transformer with CT short link terminal block for APFCR relay.\nB) DG Incomer 1, 2 : \n4000 AMPS ACB, 65 KA (Ics) AC Motor operated Draw Out ( EDO )Type Four Pole Microprocessor based relay having Over current, short circuit with time setting and 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications,ShutterAssembly,Racking interlock Manual /Electrical closing& tripping Ready to close indication contact, Site changable rear terminal adaptors, Mechanical door interlock, Trip unit shall be Microprocessor based LSIG protection with LSING protection with onboard communication port supporting modbus TCP communication protocol as specified in the technical Specifications | |||
701 | 71 | Continue above\nshall be with two Ethernet ports to minimize the number of Ethernet switches required in the system, as specified in the technicalSpecifications.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.3Nos. - 4000/5A CL-0.2, 15VA current transformer with CT short link terminal block for Multi function Meter.\n1No - Multi control relay for contorl of Under voltage, Over voltage, Single phase preventor, Phase rotation, Reverse Power with control fuses wiring etc.\n4 No. 4000/5A 5P10 15VA Current transformer with CT short link terminal block for Earth fault relay\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse.\nTNC switch for breaker ON, OFF, Trip & Auto Manual Selector switch | |||
702 | 71.1 | Continue above\nfor selection of auto and manual mode.\nC) Bus Coupler - 4Nos. :\n4000 AMPS , 65 KA (Ics) AC Motor operated Draw Out ( EDO )Type Four Pole ACB with out protection 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications, Shutter Assembly, Racking interlock Manual /Electrical closing & tripping as specified in the technical Specifications. 1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. TNC switch for breaker ON, OFF, Trip & Auto Manual Selector switch for selection of auto and manual mode. | |||
703 | 71.2 | Continue above\nD) Outgoing - Part - A \n2 Nos. of 2000 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , 4P Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC, indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 2000/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
704 | 71.3 | Continue above\n1 Nos. of 1600 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN , Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1600/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
705 | 71.4 | Continue above\n2 Nos. of 1250 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN , FP , Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1250/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
706 | 71.5 | Continue above\n3 Nos. of 630 AMPS TPN MCCB with Manual Closing Mechanism of 65 kA Short Circuit Rating with Microprocessor based adjestable.O/L & S/C Protection with variable earth fault protection.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 630/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
707 | 71.6 | Continue above\nE) Outgoing - Bus - B \n2 Nos. of 2000 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , 4P , Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 2000/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
708 | 71.7 | Continue above\n1 Nos. of 1600 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN , Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1600/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
709 | 71.8 | Continue above\n2 Nos. of 1250 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN , Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1250/5A CL-1, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
710 | 71.9 | Continue above\n3 Nos. of 630 AMPS 1Nos 630 Amps TPN MCCB with Manual Closing Mechanism of 65 kA Short Circuit Rating Microprocessor based adjestable O/L relay and fixed S/C Protection.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 630/5A CL-1, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
711 | 72 | Continue above\nF) Busbar :\n4000A TPN 65 KA Copper Busbar with heat shrinkable colour insulated PVC sleeves.Current density - 1.2Amps/Sqmm.\nNote: To be provide 1No+1Nc potential free contact terminal block with wiring for all incoming and outgoing breakers for BMS.Electrical & Mechanical Interlock to be provide for all incomer and buscoupler.PLC Automatic EB and DG changeover system to be provide as per the logic ref.main SLD.\n | |||
712 | 72.1 | LT PANEL BOARD\nMAIN MV PANEL -2 (As per IEC 61439 & IAC as per IS 61641)\nSupply, Installation, Testing and Commissioning of Medium Voltage floor mounting Cubicle Type Single bus bar system Panel Board suitable for 415 V, 3 Phase, 50 Hz Power Distribution System with the following mounting complete as per specifications attached.\nA) Incomer - 3 For Transformer 3 : \n1Nos 4000 AMPS ACB, 65 KA (Ics) AC Motor operated Draw Out ( EDO ) Type Four Pole Microprocessor based relay having Over current, short circuit with time setting Earth fault and 6NO + 6 NC, indication for test,service,isolated ON/OFF trip indications, ShutterAssembly,Racking interlock Manual / Electrical closing & tripping Ready to close indication contact, Site changable rear terminal adaptors, Mechanical door interlock, Trip unit shall be Microprocessor based LSING protection with onboard communication port supporting modbus TCP communication protocol as specified in the technicalSpecifications | 1 | Unit | |
713 | 72.2 | Continue above\nEthernet modules provided shall be with two Ethernet ports to minimize the number of Ethernet switches required in the system. as specified in the technicalSpecifications.\nThere shall be one set of Metering Compartment incorporated with the following:- \n1No - Class 1.0, Digital Maximum Demand Meter with controller, Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fuses etc.\n1No - Multi control relay for contorl of Under voltage, Over voltage, Single phase preventor, Phase rotation, with control fuses wiring etc.\n3Nos. - 4000/5A CL-0.2, 15VA current transformer with CT short link terminal block for Maximum demand Meter.\n1 No. - CDG11 Earth Fault relay \n1 Set of Differencial Protection relay\n4 No. 4000/5A 5P10 15VA Current transformer with CT short link terminal block for Earth fault relay.\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse.\nTNC switch for breaker ON, OFF, Trip & Auto Manual Selector switch | |||
714 | 72.3 | Continue above\n for selection of auto and manual mode.\n1 Set of Surge Protection device Type-I/Class B IS/IEC 62305-4\n3 No. 4000/5A CL-1, 15VA Current transformer with CT short link terminal block for APFCR relay.\nB) DG Incomer 3 : \n4000 AMPS ACB, 65 KA (Ics) AC Motor operated Draw Out ( EDO )Type Four Pole Microprocessor based relay having Over current, short circuit with time setting and 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications,ShutterAssembly,Racking interlock Manual /Electrical closing& tripping Ready to close indication contact, Site changable rear terminal adaptors, Mechanical door interlock, Trip unit shall be Microprocessor based LSIG protection with LSING protection with onboard communication port supporting modbus TCP communication protocol as specified in the technical Specifications | |||
715 | 72.4 | Continue above\nshall be with two Ethernet ports to minimize the number of Ethernet switches required in the system, as specified in the technicalSpecifications.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.3Nos. - 4000/5A CL-0.2, 15VA current transformer with CT short link terminal block for Multi function Meter.\n1No - Multi control relay for contorl of Under voltage, Over voltage, Single phase preventor, Phase rotation, Reverse Power with control fuses wiring etc.\n4 No. 4000/5A 5P10 15VA Current transformer with CT short link terminal block for Earth fault relay\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse.\nTNC switch for breaker ON, OFF, Trip & Auto Manual Selector switch | |||
716 | 72.5 | Continue above\nfor selection of auto and manual mode.\nC) Bus Coupler - 2Nos. :\n4000 AMPS , 65 KA (Ics) AC Motor operated Draw Out ( EDO )Type Four Pole ACB with out protection 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications, Shutter Assembly, Racking interlock Manual /Electrical closing & tripping as specified in the technical Specifications. 1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. TNC switch for breaker ON, OFF, Trip & Auto Manual Selector switch for selection of auto and manual mode. | |||
717 | 72.6 | Continue above\nD) Outgoing - Bus - C \n1 Nos. of 1600 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN, Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1600/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
718 | 72.7 | Continue above\n6 Nos. of 1250 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN, Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technicalSpecifications.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1250/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
719 | 72.8 | Continue above\n1 Nos. of 630 AMPS TPN MCCB with Manual Closing Mechanism of 65 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 630/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse.\n2 Nos. of 400 AMPS TPN MCCB with Manual Closing Mechanism of 65 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 400/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
720 | 72.9 | Continue above\n1 Nos. of 160 AMPS TPN MCCB with Manual Closing Mechanism of 65 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 160/5A CL-0.5, 15VA current transformer with CT short link terminal block for Duel source Multi function Meter.\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | |||
721 | 73 | Continue above\nE) Busbar :\n4000A TPN 65 KA Copper Busbar with heat shrinkable colour insulated PVC sleeves.Current density - 1.2Amps/Sqmm.\nNote: To be provide 1No+1Nc potential free contact terminal block with wiring for all incoming and outgoing breakers for BMS.Electrical & Mechanical Interlock to be provide for all incomer and buscoupler.PLC Automatic EB and DG changeover system to be provide as per the logic ref.main SLD.\nAutomatic Fire flooding arrangement to be provide for all incomer and outgoing feeder compartment as per the CEA & CEIG norms. | |||
722 | 73.1 | 600KVAR CAPACITOR PANEL FOR 2500KVA TRANSFORMER :\nSupply, Installation, Testing and Commissioning of Medium Voltage floor mounting Cubicle Type Distribution Board suitable for 415 V, 3 Phase, 50 Hz Power Distribution System with the following mounting complete as per specifications attached including necessary control wiring for automatic correction of capacitors ( 16 Stage ) and as specification.\nIncomer:\n1600 AMPS ACB, 50 KA (Ics) AC Motor operated Draw Out ( EDO )Type ,TP&N, Microprocessor based relay having Over current, short circuit with time setting and 6NO + 6 NC,indication for test,service,isolated ON/OFF trip indications, ShutterAssembly,Racking interlock Manual /Electrical closing& tripping as specified in the technical Specifications.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1 Set of R Y B LED Type Indicating Lamps with HRC fuses and toggle switches .\n1 No 16 Stage Automatic Power factor correction relay for automatic correction of Power factor.\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese \n | 3 | Unit | |
723 | 73.2 | Continue above\netc.\n3Nos. - 1600/5A CL-1, 15VA current transformer with CT short link terminal block for Multi function Meter\nBusbars\n2000A TPN Copper Busbar with heat shrinkable colour insulated PVC sleeves.\nOutgoing:\n3 sets of 100 KVAR capacitor bank each comprising of:\ni) 1 no. 400 A TP MCCB with manual closing mechnism of 50 kA rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\nii) 1 No 100KVAR 3 Pole Capacitory Duty contactor\niii) 1 No. 100 KVAR MPP-H based capacitor\niv) 1 No. 100 KVAR 7% Detuned Reactor.\nv) 1 Set of ON/ OFF push button and indicating lamps. | |||
724 | 73.3 | 4 sets of 50 KVAR capacitor bank each comprising of: \ni) 1 no. 200 A TP MCCB with manual closing mechnism of 50 kA rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nii) 1 No 50KVAR 3 Pole Capacitory Duty contactor\niii) 1 No. 50 KVAR MPP-H based capacitor\niv) 1 No. 50 KVAR 7% Detuned Reactor.\nv) 1 Set of ON/ OFF push button and indicating lamps. | |||
725 | 73.4 | 3 sets of 25 KVAR capacitor bank each comprising of:\ni) 1 no. 100 A TP MCCB with manual closing mechnism of 50 kA rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nii) 1 No 25KVAR 3 Pole Capacitory Duty contactor \niii) 1 No. 25 KVAR MPP-H based capacitor \niv) 1 No. 25 KVAR 7% Detuned Reactor.\nv) 1 Set of ON/ OFF push button and indicating lamps. | |||
726 | 73.5 | 1 sets of 15 KVAR capacitor bank each comprising of:\ni) 1 no. 63 A TP MCCB with manual closing mechnism of 50 kA rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nii) 1 No 15KVAR 3 Pole Capacitory Duty contactor\niii) 1 No. 15 KVAR MPP-H based capacitor\niv) 1 No. 15 KVAR 7% Detuned Reactor.\nv) 1 Set of ON/ OFF push button and indicating lamps. | |||
727 | 73.6 | 1 sets of 10 KVAR capacitor bank each comprising of:\ni) 1 no. 40 A TP MCCB with manual closing mechnism of 50 kA rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nii) 1 No 10KVAR 3 Pole Capacitory Duty contactor\niii) 1 No. 10 KVAR MPP-H based capacitor\niv) 1 No. 10 KVAR 7% Detuned Reactor.\nv) 1 Set of ON/ OFF push button and indicating lamps.\nBusbar:\n1600A TPN 50KA Copper Busbar with heat shrinkable colour insulated PVC sleeves.Current density - 1.2Amps/Sqmm.\n\nNOTE: (Client shall installed harmonic fileter after commissioning and conducting study based on requirement) \n | |||
728 | 73.7 | ESSENTIAL PANEL | |||
729 | 73.8 | Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1 & 2 :\n1250 AMPS ACB, 50 KA (Ics) Electrical Draw Out ( EDO )Type Four Pole Microprocessor based relay having Over current, short circuit with time setting and 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications,ShutterAssembly,Racking interlock Manual /Electrical closing& tripping as specified in the technicalSpecifications.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 1250/5A CL-1, 15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | 1 | Unit | |
730 | 73.9 | Continue above\nB) Outgoing :\n2Nos. of 800 AMPS ACB, 50KA (Ics) Manual operated Draw Out ( MDO ) Type ,TP&N Microprocessor based relay having Over current, short circuit with time setting and 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications,ShutterAssembly,Racking interlock Manual closing & tripping as specified in the technical Specifications.\n2 Nos 630 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\n1 Nos 400 Amps TP&N MCCB with Manual Closing Mechanism of 50 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\nC) Busbar:\n1250A TPN 50 KA, Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2 Amps/Sqmm. | |||
731 | 74 | UTILITY PANEL\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer : \n400 AMPS TPN MCCB with Manual Closing Mechanism of 50 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 400/5A CL-1, 15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse.\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set.- ON, OFF, Trip indication lamp for breaker status with protection fuse. | 1 | Unit | |
732 | 74.1 | Continue above\nB) Outgoing :\n1 Nos 200 Amps TP&N MCCB with Manual Closing Mechanism of 50 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n3 Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 50 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n4 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 50 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n9 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 50 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n400A TPN 50KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. . | |||
733 | 74.2 | LIFT PANEL:\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 630 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel Source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 630/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
734 | 74.3 | Continue above\nB) Outgoing :\n16 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n630A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. \nELR with CBCT 100mA to be provided for all outgoing feeders. | |||
735 | 74.4 | LIFT WELL PRESARATION PANEL (TERRACE) :\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 400 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with Microprocessor based adjestable O/L relay and fixed S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel Source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 400/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
736 | 74.5 | Continue above\nB) Outgoing :\n16 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n400A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
737 | 74.6 | PUMP PANEL -1 (Rain water storage & Harwesting)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer :\n1Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-1, 15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
738 | 74.7 | Continue above\nB) Outgoing :\n1Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n8Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n100A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. \n | |||
739 | 74.8 | VENTILATION PANEL-1: (STP & WTP ROOM)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel Source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
740 | 74.9 | Continue above\nB) Outgoing :\n2 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n5 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n100A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. \n | |||
741 | 75 | VENTILAITON PANEL-2 : (UTILITY BUILDING )\nA) Incomer:\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \n1Nos 160 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 160/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit.. | 1 | Unit | |
742 | 75.1 | Continue above\nB) Outgoing :\n3 No. 100Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating withadjustable Thermal O/L and fixed Magnetic S/C Protection.\n4No. 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n160A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. | |||
743 | 75.2 | SSB-1(GF):\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 200 Amps Four pole Fixed Type Motorized MCCB with Shunt trip, Autimatic Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 200/5A CL-0.2 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit..\n1Set of ELR 100mA with CBCT to be provided for Incomer feeder. | 1 | Unit | |
744 | 75.3 | Continue above\nB) Outgoing :\n2 Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n3 Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n200A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
745 | 75.4 | SSB-2:\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 100 Amps Four pole Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with, On, Off, Trip Indication lamp protection fuse for potential circuit.\n1Set of ELR 100mA with CBCT to be provided for Incomer feeder. | 1 | Unit | |
746 | 75.5 | Continue above\nB) Outgoing :\n2 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n5 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n100A TPN Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. \n | |||
747 | 75.6 | SSB-3 :(SSB-3 typical for 4 to 13 &15 to 21)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 160 Amps Four pole Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 160/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit.\n1Set of ELR 100mA with CBCT to be provided for incomer feeder.\n | 18 | Unit | |
748 | 75.7 | Continue above\nB) Outgoing :\n2 Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection with Suitable Class 0.2, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, suitable rating of CTs and communication port RS 485 having MODBUS Protocol with control fusese etc.\n1 Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating withadjustable Thermal O/L and fixed Magnetic S/C Protection.\n2 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n1 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n160A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
749 | 75.8 | SSB-14 (13F ) :\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 100 Amps Four Fixed Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit.\n1Set of ELR 100mA with CBCT to be provided for Incomer feeder. | 1 | Unit | |
750 | 75.9 | Continue above\nB) Outgoing :\n3 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n3 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n100 A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
751 | 76 | SSB-22 (21F ) :\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 63 Amps Four pole Fixed Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 63/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit.\n1Set of ELR 100mA with CBCT to be provided for Incomer feeder. | 1 | Unit | |
752 | 76.1 | Continue above\nB) Outgoing :\n2 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n4 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n63 A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. | |||
753 | 76.2 | A/C SB-1 : (GF)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1 :\n1Nos 100 Amps TP&N with Manual Closing Mechanism of 25 kA Short Circuit Rating withadjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
754 | 76.3 | Continue above\nB) Outgoing :\n2 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n3 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n100 A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
755 | 76.4 | A/C SB-2 : (1F)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1 :\n1Nos 63 AmpsTP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. -63/2A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
756 | 76.5 | Continue above\nB) Outgoing :\n6 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n63 A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
757 | 76.6 | A/C SB-3 : (2F) ( TYPICAL A/C SB - 3 TO A/C SB - 21)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 63 Amps Four pole Fixed Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with Thermal O/L and Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual Source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. -63/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 19 | Unit | |
758 | 76.7 | Continue above\nB) Outgoing :\n2 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection. with Suitable Class 0.2, Digital Dual source Multifunction Meter with Inbuilt Selector Switch, suitable rating of CTs and communication port RS 485 having MODBUS Protocol with control fusese etc.\n3 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n63 A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. | |||
759 | 76.8 | A/C SB-22 : ( 21TH Floor )\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer 1& 2 :\n1Nos 160 Amps Four pole Fixed Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with Thermal O/L and Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 2.0, Digital Dual Source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. -160/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
760 | 76.9 | Continue above\nB) Outgoing :\n2 Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n4 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n160 A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
761 | 77 | PSB-1 :(GF)\nA) Incomer:\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \n1Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 125/5A CL-0.5,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit. | 1 | Unit | |
762 | 77.1 | Continue above\nB) Outgoing :\n2 No. 100 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n2 No. 63Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n2 No. 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n125A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. | |||
763 | 77.2 | LSB-1 :(GF)\nA) Incomer:\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \n1Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-0.5,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit..\n | 1 | Unit | |
764 | 77.3 | Continue above\nB) Outgoing :\n4 No. 32Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n2 No. 63Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n63A TPN, 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \nCurrent density - 1.2Amps/Sqmm. | |||
765 | 77.4 | VENTILAITON PANEL : (BLOCK-1 TERRACE)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 125/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit. | 1 | Unit | |
766 | 77.5 | Continue above\nB) Outgoing :\n4 No 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n5 No 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n125A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.\nCurrent density - 1.2Amps/Sqmm. | |||
767 | 77.6 | Isolator, MCB and MCCB with enclosure\nDesign, supply, fixing, testing and commissioning of following switch gear with suitable metal enclosure, adopter box to receive suitable rating of incoming and outgoing cable, fixing angle frame, anchor fastner all accossories etc. | |||
768 | 77.7 | 63Amps 4P MCCB with enclosure for 30KVA & 20KVA UPS. | 6 | Unit | |
769 | 77.8 | 63Amps TPN MCB Isolator with enclosure for Lift 11Nos | 11 | Unit | |
770 | 77.9 | 32Amps TPN MCB Isolator with enclosure for 6KVA Inverter. | 2 | Unit | |
771 | 78 | 32Amps TPN MCB Isolator with Weather proof enclosure for terrece fans . | 14 | Unit | |
772 | 78.1 | 16Amps TPN MCB Isolator with enclosure. For toilet exhaust fan . | 56 | Unit | |
773 | 78.2 | 6 Amps 4Nos. Single Pole MCB with 4P enclosure. | 24 | Unit | |
774 | 78.3 | 25 Amps DP MCB Isolator with enclosure. | 2 | Unit | |
775 | 78.4 | BUS DUCT & RISING MAIN\nBUS DUCT (AIR INSULATED)\nSupply, Erection,Testing and Commissioning of Alumnium enclosur 1600 A 65kA TPN 433v, 50HZ, Air insulated LV BUS duct comprising of 4P Copper Busbar housed in Aluminium enclosure, Including Vertical Bends, Horizontal bends, Spring & Fix Hangers with 2 no of External copper earth (25 mm x 6 mm copper ) . The busduct shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc., for Transformer -1, 2 & 3 APFC panel (technical Specification enclosed.)\nIP 52: INDOOR | 27 | Rmt | |
776 | 78.5 | Supply,Erection,Testing and Commissioning of 1600A Copper Flexible joints , Flange End ( Air insulated) at the MV panel side and APFCR panel side with required Standard Accessories etc., complete as required.( 1 set = R,Y,B & N ). | 6 | Unit | |
777 | 78.6 | Supply,Erection,Testing and Commissioning of 4000 A 65kA 4P 433v, 50HZ, Air insulated LV BUS duct comprising of 4P Copper Busbar housed in Aluminium enclosure, Including Vertical Bends, Horizontal bends, Spring & Fix Hangers with 2 no of External copper earth ( 50 mm x 6 mm copper ) . The busduct shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc., from 2500KVA Transformer secondary side to MV panel and Synchronizing panel to MV panel. (As per the detailed Technical Specification enclosed.)\nIP 52: INDOOR | 100 | Rmt | |
778 | 78.7 | Supply,Erection,Testing and Commissioning of 4000A Copper Flexible joints, Flange End (Air Insulated) at the Transformer secondary side, MV panel side and Synchronizing panel side and additional flexible joints to be provided every 5 mtrs. with required Standard Accessories etc., complete as required.( 1 set = R,Y,B & N ). | 12 | Unit | |
779 | 78.8 | RISING MAIN - 1 & 1A, 2 & 2A | |||
780 | 78.9 | Supply, Installation, Testing and Commissioning of the following indoor Air insulated Sandwich type Rising Main suitable for 2000 A 4P Copper busbar 3 phase, 415V, 4 wire, 65kA, 50Hz, A.C system. Current density of copper as per manufacturers standard. .The Sandwich type Rising Main enclosure complete with supporting frames. The busbar should be also equipped with double earthing (25 mm x 6 mm copper ) continuously for Body and Necessary DMC/SMC Supports for Rising Main Earthing.Every floor crossing may be provided with suitable vapour barrier. | 310 | Rmt | |
781 | 79 | End Feed Unit:\nSupply,erection, testing and commissioning of 1 No 2000 AMPS ACB, 65 KA (Ics) AC Draw Out ( MDO ) Type Four Pole Microprocessor based relay having Over current, short circuit with time setting and 6NO + 6 NC,indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual /Electrical closing & tripping of Raising Main incomer including Metal enclosure, interconnection to the Raising Main with Copper Bus bars and necessary cable end box.\n1 Set of R Y B LED Type Indicating Lamps with HRC fuses and toggle switches \nThere shall be one set of Metering Compartment incorporated with the following:- 1No - Class 1.0, Digital duel source Multi funtion Meter with Inbuilt Selector Switch, with communication port RS 485 having MODBUS Protocol with control fuses etc.\n1No - Multi control relay for contorl of Under voltage, Over voltage, Single phase preventor, Phase rotation, with control fuses wiring etc.\n3Nos. - 2000/5A CL-1, 15VA current transformer with CT short link terminal block for Multi Function Meter.\n1 Set of Surge Protection relay Type I+II / Class B+C | 4 | Unit | |
782 | 79.1 | Supply,Erection,Testing and Commissioning of 2000A Copper Flexible joints, at the rising main side with required Standard Accessories etc., complete as required. ( 1 set = R,Y,B & N ) | 4 | Unit | |
783 | 79.2 | Supply,Erection,Testing and Commissioning of 2000A Copper Flange end (Provision cost) with eqillizer and Adopter Box at the end feed unit side with required Standard Accessories etc., complete as required.( 1 set = R,Y,B & N ) | 4 | Unit | |
784 | 79.3 | Supply,Erection,Testing and Commissioning of 2000A Copper End cover for 2000A rating Sandwich Copper BBT.with required Standard Accessories etc, complete as required. | 4 | Unit | |
785 | 79.4 | Supply,erection, testing and commissioning of Tap off Boxes of the following rating on the Raising Main including interconnection to the Raising Main. | |||
786 | 79.5 | 200 A Plug in box with 200A TPN MCCB with Manual Closing Mechanism of 35 KA Short Circuit Rating with both adjustable Thermal O/L and Magnetic S/C Protection with necessary interconnections with solid Copper Bus of required capacity as per specification & MCCB should have dedicated potential free contacts (ON/OFF) & TRIP status to monitor mentioned status from BMS system | 2 | Unit | |
787 | 79.6 | 160 A Plug in box with 160A TPN MCCB with Manual Closing Mechanism of 35 KA Short Circuit Rating with both adjustable Thermal O/L and Magnetic S/C Protection with necessary interconnections with solid Copper Bus of required capacity as per specification & MCCB should have dedicated potential free contacts (ON/OFF) & TRIP status to monitor mentioned status from BMS system | 80 | Unit | |
788 | 79.7 | 125 A Plug in box with 125A TPN MCCB with Manual Closing Mechanism of 35 KA Short Circuit Rating with both adjustable Thermal O/L and Magnetic S/C Protection with necessary interconnections with solid Copper Bus of required capacity as per specification & MCCB should have dedicated potential free contacts (ON/OFF) & TRIP status to monitor mentioned status from BMS system | 2 | Unit | |
789 | 79.8 | 100A Plug in box with 100 A TPN MCCB with Manual Closing Mechanism of 35 KA Short Circuit Rating with both adjustable Thermal O/L and Magnetic S/C Protection with necessary interconnections with solid Copper Bus of required capacity as per specification & MCCB should have dedicated potential free contacts (ON/OFF) & TRIP status to monitor mentioned status from BMS system | 2 | Unit | |
790 | 79.9 | 63A Plug in box with 63 A TPN MCCB with Manual Closing Mechanism of 35 KA Short Circuit Rating with both adjustable Thermal O/L and Magnetic S/C Protection with necessary interconnections with solid Copper Bus of required capacity as per specification & MCCB should have dedicated potential free contacts (ON/OFF) & TRIP status to monitor mentioned status from BMS system | 40 | Unit | |
791 | 80 | Note:The raising main measurement shall be taken from top of incomer to top of the raising main enclosure. Raising Mains shall be provided with 25 x 6mm double copper earth bar of capacity as per specifications for the entire length and cost of earth bar shall be included. | |||
792 | 80.1 | DISTRIBUTION BOARDS | |||
793 | 80.2 | MAIN BUILDING LDB & ELDB :\n6W TPN MCB LDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer : 3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 18Nos 6 A SP MCB . | 23 | Unit | |
794 | 80.3 | 8W TPN MCB LDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer : 3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 24 Nos 6 A SP MCB . | 6 | Unit | |
795 | 80.4 | 12W TPN MCB LDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 12 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer : 3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 36 Nos 6 A SP MCB . | 1 | Unit | |
796 | 80.5 | 8W TPN MCB ELDB GF : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer :3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 24 Nos 16A SP MCB . | 1 | Unit | |
797 | 80.6 | 8W SPN MCB ELDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY SP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1 Nos 25 A DP MCB\nOutgoing : \n6 Nos 6 A SP MCB | 3 | Unit | |
798 | 80.7 | UTILITY BUILDING LDB & ELDB\n4W TPN MCB LDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 4 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer : 3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 12 Nos 6 A SP MCB . \n | 1 | Unit | |
799 | 80.8 | 8W TPN MCB LDB for GF & FF Utility building\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer :3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 24 Nos 6 A SP MCB. | 2 | Unit | |
800 | 80.9 | 8W SPN MCB LDB RMG ROOM : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY SP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1 Nos 25 A DP MCB\nOutgoing : \n6 Nos 6 A SP MCB | 1 | Unit | |
801 | 81 | 12W SPN MCB ELDB for : UTILITY BUILDING\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 12 WAY SP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1 Nos 25 A DP 30mA RCCB\nOutgoing : \n10 Nos 6 A SP MCB | 1 | Unit | |
802 | 81.1 | 6W TPN MCB LPDB SECURITY ROOM : :\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer :3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 18 Nos 6 A SP MCB. | 1 | Unit | |
803 | 81.2 | POWER DISTRIBUTION BOARD MAIN BUILDING :\n4W TPN MCB PDB for :\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 4 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 12 Nos 16/20 A SP MCB. | 23 | Unit | |
804 | 81.3 | 6W TPN MCB PDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 18 Nos 16/20 A SP MCB . \n | 1 | Unit | |
805 | 81.4 | 12W TPN MCB PDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 12 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 36 Nos 16/20 A SP MCB . \n | 1 | Unit | |
806 | 81.5 | POWER DISTRIBUTION BOARD UTILITY BUILDING :\n4W TPN MCB PDB for :\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 4 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 12 Nos 16/20 A SP MCB. | 1 | Unit | |
807 | 81.6 | 6W TPN MCB PDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 18 Nos 16/20 A SP MCB . \n | 1 | Unit | |
808 | 81.7 | 8W TPN MCB PDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 24 Nos 16/20 A SP MCB . \n | 2 | Unit | |
809 | 81.8 | DISTRIBUTION BOARD - UPS : \n4W TPN MCB UPSDB for :\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 4 WAY TP & N MCB Distribution Board with 'D' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs \nOutgoing : 12 Nos 16/20 A SP MCB. \n | 2 | Unit | |
810 | 81.9 | 8W TPN MCB UPSDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'D' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs \nOutgoing : 24 Nos 16/20 A SP MCB. \n | 5 | Unit | |
811 | 82 | VERTICAL DISTRIBUTION BOARD\n4W VTPN MCB Main UPS DB for :\nFabrication, Supply, Installation, Testing and Commissioning of Vertical type 4 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB \nOutgoing : 4Nos 6/10 A TP MCB. \n | 1 | Unit | |
812 | 82.1 | 8W VTPN MCB VENTILATION DB :\nFabrication, Supply, Installation, Testing and Commissioning of Vertical type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB \nOutgoing : 8Nos 6/10 A TP MCB. \n | 22 | Unit | |
813 | 82.2 | 12W VTPN MCB VENTILATION DB :\nFabrication, Supply, Installation, Testing and Commissioning of Vertical type 12WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB \nOutgoing : 12Nos 6/10 A TP MCB. \n | 1 | Unit | |
814 | 82.3 | 12W VTPN MCB EXTERNAL LIGHTING DB 1,2,&3 :\nFabrication, Supply, Installation, Testing and Commissioning of Vertical type 12 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB \nOutgoing : 12Nos 6/10 A TP MCB. \n | 3 | Unit | |
815 | 82.4 | LIFT DISTRIBUTION BOARD: : \n6W TPN MCB LIFT DB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer :3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 18 Nos 16A SP MCB . | 12 | Unit | |
816 | 82.5 | UPS & INVERTERS | |||
817 | 82.6 | Supply and Erection of 80 KVA Modular UPS Frame with 3 X 20 KVA true Hot-Swappable Modules(Rack mount UPS in customized Panel is not acceptable) with 3-phase input and Three phase output and efficiency up to 96%. Maintanance free batteies suitable for backup system should have Half an hour backup for 30 kVA UPS load at 0.9 output power factor.The scope includes providing 80 KVA External Isolation Transformer at input, neccesary battery stand , inter connecting cables from UPS battery.The scope also includes providing neccesary by-pass arrangement and all other requirements. The capacity of the battery shall be of 12V DC with a minimum of Suitable ampere hour and as per specification. for Ground floor & first floor office. | 2 | Unit | |
818 | 82.7 | Supply and Erection of 20 KVA/18 KW UPS Systems with 3-phase input and Three phase output and 20 KVA Isolation Transformer at input. Maintanance free batteies suitable for backup system should have Half an hour continous rating at 0.9 output Power factor.The scope includes providing neccesary battery stand , inter connecting cables from UPS battery.The scope also includes providing neccesary by-pass arrangement and all other requirements. The capacity of the battery shall be of 12V DC with a minimum of Suitable ampere hour and as per specification. for IBMS | 1 | Unit | |
819 | 82.8 | Supply and Erection of 10 KVA UPS Systems with 3-phase input and Three phase output. Maintanance free batteies suitable for backup system should have Half an hour continous rating for 6 KVA load with 0.9 output Power Factor.The scope includes providing neccesary battery stand , inter connecting cables from UPS battery.The scope also includes providing neccesary by-pass arrangement and all other requirements. The capacity of the battery shall be of 12V DC with a minimum of Suitable ampere hour and as per specification. for Utility \n | 1 | Unit | |
820 | 82.9 | LT CABLING & END TERMINATION : | |||
821 | 83 | Supply and Laying of XLPE insulated and PVC inner sheathed , FRLS outer sheathed , aluminium conductor, 1.1 KV grade armoured, MV cable of the following sizes as required, generally conforming to IS:7098 Part-1 | |||
822 | 83.1 | 3 1/2 X 400 sqmm. | 10113 | Rmt | |
823 | 83.2 | 3 1/2 X 300 sqmm. | 6040 | Rmt | |
824 | 83.3 | 3 1/2 X 240 sqmm. | 15 | Rmt | |
825 | 83.4 | 3 1/2 X 185 sqmm. | 10 | Rmt | |
826 | 83.5 | 3 1/2 X 150 sqmm. | 1241 | Rmt | |
827 | 83.6 | 3 1/2 X 120 sqmm. | 15 | Rmt | |
828 | 83.7 | 3 1/2 X 95 sqmm. | 430 | Rmt | |
829 | 83.8 | 3 1/2 X 70 sqmm. | 14 | Rmt | |
830 | 83.9 | 3 1/2 X 50 sqmm. | 1660 | Rmt | |
831 | 84 | 3 1/2 X 35 sqmm. | 2260 | Rmt | |
832 | 84.1 | 4 x 25 sqmm. | 1465 | Rmt | |
833 | 84.2 | 4 x 16 sqmm . | 7695 | Rmt | |
834 | 84.3 | Supply and Laying of XLPE insulated and PVC inner sheathed , FRLS outer sheathed , Copper conductor, 1.1 KV grade armoured, MV cable of the following sizes as required, generally conforming to IS:7098 Part-1 | |||
835 | 84.4 | 4 x 6 sqmm . | 2410 | Rmt | |
836 | 84.5 | 4 x 4 sqmm . | 1765 | Rmt | |
837 | 84.6 | 4 x 2.5 sqmm . | 3960 | Rmt | |
838 | 84.7 | 2 x 2.5 sqmm . | 1525 | Rmt | |
839 | 84.8 | 5Runs of 16Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 10 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (30 KVA UPS & UPS O/G DBs) | 45 | Rmt | |
840 | 84.9 | 5Runs of 10Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 6 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (20KVA UPS UPS O/G DBs) | 25 | Rmt | |
841 | 85 | 5Runs of 6Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 4 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (6KVA UPS UPS O/G DBs) | 25 | Rmt | |
842 | 85.1 | TERMINATION : | |||
843 | 85.2 | Supplying and making end termination with brass Double compression gland and aluminium lugs for following size of XLPE insulated and PVC inner sheathed , FRLS outer sheathed aluminium conductor cable of 1.1 KV | |||
844 | 85.3 | 3 1/2 X 400 sqmm. | 64 | Unit | |
845 | 85.4 | 3 1/2 X 300 sqmm. | 86 | Unit | |
846 | 85.5 | 3 1/2 X 240 sqmm. | 2 | Unit | |
847 | 85.6 | 3 1/2 X 185 sqmm. | 2 | Unit | |
848 | 85.7 | 3 1/2 X 150 sqmm. | 122 | Unit | |
849 | 85.8 | 3 1/2 X 120 sqmm. | 2 | Unit | |
850 | 85.9 | 3 1/2 X 95 sqmm. | 18 | Unit | |
851 | 86 | 3 1/2 X 70 sqmm. | 2 | Unit | |
852 | 86.1 | 3 1/2 X 50 sqmm. | 16 | Unit | |
853 | 86.2 | 3 1/2 X 35 sqmm. | 28 | Unit | |
854 | 86.3 | 4 x 25 sqmm. | 98 | Unit | |
855 | 86.4 | 4 x 16 sqmm . | 200 | Unit | |
856 | 86.5 | Supplying and making end termination with brass Double compression gland and aluminium lugs for following size of XLPE insulated and PVC inner sheathed , FRLS outer sheathed Copper conductor cable of 1.1 KV | |||
857 | 86.6 | 4 x 6 sqmm . | 122 | Unit | |
858 | 86.7 | 4 x 4 sqmm . | 80 | Unit | |
859 | 86.8 | 4 x 2.5 sqmm . | 230 | Unit | |
860 | 86.9 | 2 x 2.5 sqmm . | 48 | Unit | |
861 | 87 | 5Runs of 16Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 10 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (30 KVA UPS & UPS O/G DBs) | 12 | Unit | |
862 | 87.1 | 5Runs of 10Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 6 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (20KVA UPS UPS O/G DBs) | 6 | Unit | |
863 | 87.2 | 5Runs of 6Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 4 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (6KVA UPS UPS O/G DBs) | 6 | Unit | |
864 | 87.3 | CABLE TRAY & M.S ITEMS: | |||
865 | 87.4 | Supply, erection of following sizes ( Hot dip galvanised iron ) GI ladder type cable rack system made out of sheet steel folded to required shape with adequate number of supports. (Cable tray support price is not required in this Items).\nThe cable tray shall have runners rugs of suitable size, horizontal elbow, vertical elbow 90 Deg. Up vertical elbow 90 Deg. Down, re-deep, coupler plates, materials. The cable tray shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc. The tray shall have suitable cable clamping arrangements etc. | |||
866 | 87.5 | 150 mm Width X 50mm Height X 3mm Thick. | 800 | Rmt | |
867 | 87.6 | 300 mm Width X 50mm Height X 3mm Thick. | 25 | Rmt | |
868 | 87.7 | 450 mm width X 50mm Height X 3mm Thick. | 1840 | Rmt | |
869 | 87.8 | 600 mm.width X 75mm Height X 3mm Thick. | 95 | Rmt | |
870 | 87.9 | 900 mm width X 75mm Height X 3mm Thick. | 10 | Rmt | |
871 | 88 | 1000 mm width X 100mm Height X 3mm Thick. | 310 | Rmt | |
872 | 88.1 | 1250 mm width X 100mm Height X 3mm Thick. | 1535 | Rmt | |
873 | 88.2 | Supply and erection of M.S. Material for ladder type cable trays, panel boards ,chequer plate, cable supports, rising main & bus duct , SB, DB's supports, iron embeded in the wall, steel structure in open Area painted with two coats of primer and two coats of enamel paint. Substation to main panel room , ahu room and lighting conduit trays and suspensions of lighting conduit . | 51600 | Kgs | |
874 | 88.3 | MS chequer plate : \nDesign, cutting, and fixing of 6 mm thick chequered plate with required MS angles for closing around the cable tray shafts and communication shafts. It should be covered with neatly without any gap around the cable tray as per IE Regulation. The gap between cable tray and the chequred plate shall be covered with insulating materials. \n | 201 | Sq.m | |
875 | 88.4 | INTERNAL WIRING FOR BLOCK-1: | |||
876 | 88.5 | Wiring for Dependent 6 A, 3 Pin Socket outlet with 2 x 1.5 sqmm FRLS PVC insulated Stranded Copper conductor Cable and 1 x 1.5 sqmm FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire, in the lighting switch board, 6 Amps modular type Single Way Switch, 6 A 5 pin, modular type shuttered socket outlet including making connections etc., as per specification | 1 | Point | |
877 | 88.6 | Wiring for Lift Well Light Point and socket oulet with 2 x 1.5 sqmm FRLS PVC insulated Stranded Copper Conductor Cable along with 1 x 1.5 sqmm FRLS PVC insulated Stranded copper conductor cable as earth wire in surface MS conduit including providing and fixing Galvanised / Cadmium plated MS switch box, 2 no 6A Single Way Modular Switch for (controlling light point and socket Outlet) , 1 No 6 A 5 Pin shuttered modular socket outlet with modular switch plate and making necessary connections etc., as per specification (5 Meters shall be considered for Wires & conduit per point.) | 253 | Points | |
878 | 88.7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 6 /16 A modular Shuttered socket outlet and 16 A modular switch, connections etc. as required.ahu room ,pantry (Raw Power) | 265 | Points | |
879 | 88.8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular Shuttered socket outlet and 15/16 A modular switch, connections etc. as required .. (Raw Power) | 3 | Points | |
880 | 88.9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular Shuttered socket outlet and 15/16 A modular switch, connections etc. as required for Hand Dryer. (Raw Power) | 50 | Points | |
881 | 89 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular Shuttered socket outlet and 15/16 A modular switch, connections etc. as required for Napkin Vending Machine. (Raw Power) | 22 | Points | |
882 | 89.1 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2/3 pin 5/6 A modular Shuttered socket outlet and 5/6 A modular switch, connections etc. as required. (UPS Power) | 65 | Points | |
883 | 89.2 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and 3 no of fixing 2/3 pin 5/6 A modular Shuttered socket outlet and 1 no of 16 A modular switch, connections etc. as required.(UPS Power) | 145 | Points | |
884 | 89.3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing andf fixing 6 pin 5/16 A modular Shuttered socket outlet and 1 no of 16 A modular switch, connections etc. as required.(UPS Power) | 4 | Points | |
885 | 89.4 | Wiring for power :\nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
886 | 89.5 | 2 x 2.5 sqmm +1 x 1.5 sqmm (E) | 3820 | Rmt | |
887 | 89.6 | 2 x 4 sqmm +1 x 2.5 sqmm (E) | 6050 | Rmt | |
888 | 89.7 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. | |||
889 | 89.8 | 25 mm | 7825 | Rmt | |
890 | 89.9 | Supplying and fixing of following sizes of PVC conduit along with the accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required: | |||
891 | 90 | 25 mm | 500 | Rmt | |
892 | 90.1 | Supplying and fixing of following sizes of aluminium raceways along with the accessories in surface/recess including cutting, fixing on the foor/walll and making good the same.aluminium race ways & JB-BOQ 89.2 to 89.5 (As per the manufacturer's standards(1.5mm) | |||
893 | 90.2 | 100 x 50 mm thickness 1.5mm Aluminium raceways. | 60 | Rmt | |
894 | 90.3 | Supplying and fixing of following sizes of floor junction box along with the accessories in surface/recess including cutting, fixing on the foor and making good the same. | |||
895 | 90.4 | 150 x 150 x 75mm thickness 1.5mm floor junction box. | 12 | Rmt | |
896 | 90.5 | MS conduit wiring (for lighting): \nWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in 25 mm surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. | |||
897 | 90.6 | Group A (One light controlled by one switch - 6mtrs ) | 110 | Points | |
898 | 90.7 | Group B (Two light controlled by one switch - 9mtrs) | 330 | Points | |
899 | 90.8 | Group C (Three light controlled by one switch - 12mtrs) | 245 | Points | |
900 | 90.9 | Run of main wiring for circuit / power / sub main etc :\nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
901 | 91 | 2 x2.5 sqmm + 1 x 1.5 sqmm (E) | 19445 | Rmt | |
902 | 91.1 | Supplying and fixing of following sizes of MS conduit along with the accessories in surface including cutting the wall and making good the same in case of recessed conduit as required: | |||
903 | 91.2 | 25 mm. | 16005 | Rmt | |
904 | 91.3 | INTERNAL WIRING FOR UTILITY BUILDING. | |||
905 | 91.4 | Wiring for dependent 6 A, 3 Pin Socket outlet with 2 x 1.5 sqmm FRLS PVC insulated Stranded Copper conductor Cable and 1 x 1.5 sqmm FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire, in the lighting switch board, 6 Amps modular type Single Way Switch, 6 A 5 pin, modular type shuttered socket outlet including making connections etc., as per specification (for exhaust fan) . | 2 | Points | |
906 | 91.5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 no of 6 pin 5/6 & 15/16 A modular Shuttered socket outlet and 2 nos of 16 A modular switch, connections etc. as required. (Raw Power) | 11 | Points | |
907 | 91.6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and 3 no of fixing 2/3 pin 5/6 A modular Shuttered socket outlet and 1 no of 16 A modular switch, connections etc. as required.(UPS Power) for IBMS, Maintenence room and (system use for security room Raw Power) | 19 | Points | |
908 | 91.7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 6 /16 A modular Shuttered socket outlet and 16 A modular switch, connections etc. as required.security room (Raw Power) | 7 | Points | |
909 | 91.8 | Wiring for power: \nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
910 | 91.9 | 2 x2.5 sqmm + 1 x 1.5 sqmm (E) | 190 | Rmt | |
911 | 92 | 2 x 4 sqmm + 1 x 2.5 sqmm (E) | 400 | Rmt | |
912 | 92.1 | Supplying and fixing of following sizes of MS conduit along with the accessories in surface including cutting the wall and making good the same in case of recessed conduit as required: | |||
913 | 92.2 | 25 mm. | 480 | Rmt | |
914 | 92.3 | MS conduit wiring (for lighting) :\nWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in 25 mm surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. \n | |||
915 | 92.4 | Group A (One light controlled by one switch - 6mtrs ) | 14 | Points | |
916 | 92.5 | Group B (Two light controlled by one switch - 9mtrs) | 16 | Points | |
917 | 92.6 | Group C (Three light controlled by one switch - 12mtrs) | 14 | Points | |
918 | 92.7 | Run of main wiring for circuit /power / sub main etc : \nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
919 | 92.8 | 2 x2.5 sqmm + 1 x 1.5 sqmm (E) | 200 | Rmt | |
920 | 92.9 | Supplying and fixing of following sizes of MS conduit along with the accessories in surface including cutting the wall and making good the same in case of recessed conduit as required: | |||
921 | 93 | 25 mm. | 150 | Rmt | |
922 | 93.1 | (LDB to Group controlled Light &ELDB to Group controlled Light) : \nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
923 | 93.2 | 2 x2.5 sqmm + 1 x 1.5 sqmm (E) | 3260 | Rmt | |
924 | 93.3 | Supplying and fixing of following sizes of MS conduit along with the accessories in surface including cutting the wall and making good the same in case of recessed conduit as required: | |||
925 | 93.4 | 25 mm. | 2745 | Rmt | |
926 | 93.5 | LIGHT FIXTURES FOR BLOCK-1: | |||
927 | 93.6 | Supply, Installation, testing and commissioning of recessed mounting round 18W fittings, of all types complete with all accessories etc. directly on ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For GF Main lobby. \nModel No: Divinity LONGER / Wall washer (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 15 | Nos | |
928 | 93.7 | Supply, Installation, testing and commissioning of recessed mounting flat square 12W LED fittings, of all types complete with all accessories etc. directly on ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Security check area. \nModel No: Divinity FLAT SQUARE DLTOFLSDRD-12 / direct surface (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 70 | Nos | |
929 | 93.8 | Supply, Installation, testing and commissioning of Direct surface 28W LED fittings, of all types complete with all accessories etc. directly on ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Business Lounge, 1st floor Lobby, Work Centre area. \nModel No: Divinity VIRAJ 70 DR / Lense direct surface (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 10 | Nos | |
930 | 93.9 | Supply, Installation, testing and commissioning of Suspended Triangle Down Light fo 35W LED fittings, of all types complete with all accessories etc. directly on ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Business Lounge, 1st floor Lobby, Work Centre area. \nModel No: Divinity CIRA SOFT TRIANGLE DLATCSTDSD-35W (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 30 | Nos | |
931 | 94 | Supply, Installation, testing and commissioning of Suspended Linear Down Light for 60w LED ( Lenth 3600mm ) with integrated LED Driver and Diffuser , of all types complete with all accessories etc. directly on ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Business Lounge, 1st floor Lobby, Work Centre area. \nModel No: Divinity VIRAJ 45 LED (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 81 | Nos | |
932 | 94.1 | Supply, Installation, testing and commissioning of Suspended Linear Down Light for 20w LED ( Lenth 2400mm ) with integrated LED Driver and Diffuser, of all types complete with all accessories etc. directly on ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For security check & co working space\nModel No: Divinity VIRAJ 45 LEDor equivalent (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 94 | Nos | |
933 | 94.2 | Supply, Erection, Testing and commissioning of recessed mounting LED strip light fixture with driver (each 5mtrs / 1 driver) with necessary interconnecting wires & fixing hardwares etc. all complete as required. \nModel no: Divinity-10W PROFESSIONAL LED STRIP IP20 WW (or) Equivalent in Philips make (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 2344 | Rmt | |
934 | 94.3 | Supply, Installation, testing and commissioning of DIVINITY VIRAJ 50 Suspended Light for 35w LED ( Lenth 1200mm ) with integrated LED Driver and Diffuser , 35W LED fittings, of all types complete with all accessories etc. directly fixing false ceiling including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Business centre west side. \nModel No: DIVINITY VIRAJ 50 35W (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 10 | Nos | |
935 | 94.4 | Supply, Installation, testing and commissioning of Recessed mounted down light fixture 25 Watts LED IP65. and with necessary clamps, screws etc. light fixture with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For Business Lounge,main lobby,main enterance IP65. \nModel no: Divinity DV HOBIO (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 116 | Nos | |
936 | 94.5 | Supply, Installation, testing and commissioning of recess mounting 15 W Round light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For 1st floor conference room.\nModel no: Divinity FLAT ROUND 15w (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 17 | Nos | |
937 | 94.6 | Supply, Installation, testing and commissioning of recessed mounting 18 W Round down light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For corridor\nModel no: Divinity ARA 18w (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 904 | Nos | |
938 | 94.7 | Supply, Installation, Testing and commissioning of recessed mounted 2 X 18W doube head light fixture directly mounted on the false ceiling including modifying the falseceiling opening and making good the same including stay wire, anchor fastner,interconnection with 2.5 sq. mm, FRLS PVC insulated copper conductor single core cable etc. complete as required. For 1st floor Work center \nModel no: Divinity ELEMENT / Double Head (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 11 | Nos | |
939 | 94.8 | Supply, Installation, testing and commissioning of 70 W Pendant light fixture with supporting steel rope kit and accessories etc.,fixed on the ceiling and wiring with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. for Cabin \nModel No:Divinity JETTA RING ACOUSTICS / Pendant (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 11 | Nos | |
940 | 94.9 | Supply, Installation, testing and commissioning of 35 W Curve Pendant light fixture with supporting steel rope kit and accessories etc.,fixed on the ceiling and wiring with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. for Business center \nModel No:Divinity CURVE SOFT / Pendant (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 1 | Nos | |
941 | 95 | Supply, Installation, testing and commissioning of prewired, IP65 40W LED batten weather proof fittings, of all types complete with all accessories etc. directly on ceiling / wall, including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor single core cable etc. as required. For AHU room, Electrical Room. \nModel no:Crompton CDR-206-18-57-SL-NWH 40W WH (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 254 | Nos | |
942 | 95.1 | Supply, Installation, testing and commissioning of 50W 900mm Square Pendant light fixture with supporting steel rope kit and accessories etc.,fixed on the ceiling and wiring with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. for 1st Floor Work center\nModel No:Divinity SIGMA SOFT SQUARE / Pendant (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 17 | Nos | |
943 | 95.2 | Supply, Installation, testing and commissioning of Recessed down light for 8w led with remote led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets.\nModel no: Divinity LYNX 8w led (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 220 | Nos | |
944 | 95.3 | Supply, Installation, testing and commissioning of Recessed down light for 14w led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets.\nModel no: Divinity LLF-039A 14W led (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 373 | Nos | |
945 | 95.4 | Supply, Installation, testing and commissioning of surface down light for 18 w led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For staircase.\nModel no: Crompton Pearl II 18w (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 188 | Nos | |
946 | 95.5 | Supply, Installation, testing and commissioning of recessed down light for 20w led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For staircase. Model no: Divinity ROUTAN (DLTOROUDRM-20) 20w (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 3 | Nos | |
947 | 95.6 | Supply, Installation, testing and commissioning of 100W highbay down LED light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For landscape.\nModel no:Crompton LHB11-100-CDL/60-M 100W LED highbay (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 47 | Nos | |
948 | 95.7 | Supply, Installation, testing and commissioning of k-lite 60W Surface LED down light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For landscape.\nModel no: K-Lite ASTON prime 42001x60W LED light (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 17 | Nos | |
949 | 95.8 | Supply, Installation, testing and commissioning of Bulk head Light fittings with 10W LED light and accessories etc.,directly fixed on the wall and wiring with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For Lift Well. \nModel no:Crompton LBHE-10-CDL 10W LED (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 255 | Nos | |
950 | 95.9 | Supply, Installation, testing and commissioning of surface Path light for 12w led with led driver and diffuser all accessories etc.,directly on to the wall including modifying the wall openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For terrace garden.\nModel no: K-LITE SUDO/SUDO MINI-OPEN FRAME 2741 12W LED (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 22 | Nos | |
951 | 96 | Supply, Installation, testing and commissioning of surface down light for 15w led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For terrace garden.\nModel no: K-LITE CYLIN 7345 (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 24 | Nos | |
952 | 96.1 | Supply, Installation, testing and commissioning of surface inground light for 8w led IP65 with led driver and diffuser all accessories etc.,directly on to the garden and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For terrace garden and outer garden.\nModel no: K-LITE 4097 INGROUND 8W (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 6 | Nos | |
953 | 96.2 | Supply, Installation, testing and commissioning of Recessed down light for 3w led and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets.\nModel no: K-lite GEMMA ROUND MICRO 3W LED ID 7662 (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 154 | Nos | |
954 | 96.3 | Supply, Installation, testing and commissioning of Surface wall washer led light for 36w led and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets.\nModel no: Divinity Archishape 36 w LED 20w (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 32 | Nos | |
955 | 96.4 | Aviation lighting systems located in terrace on Pole mounted or tower\nmounted Aviation Warning lighting fixture suitable for2 X 12W LED single and double doom options with IP54 rated.\nModel no: k-light 6649 AVIATOR-2 ( or )Crompton (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 1 | Nos | |
956 | 96.5 | LIGHT FIXTURES FOR UTILITY BUILDING: | |||
957 | 96.6 | Supply, Installation, testing and commissioning of prewired, IP65 40W LED batten weather proof fittings, of all types complete with all accessories etc. directly on ceiling / wall, including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For AHU room, Electrical Room. \nModel no: Crompton CDR-206-18-57-SL-NWH 40W WH (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 240 | Nos | |
958 | 96.7 | Supply, Installation, testing and commissioning of suspended type 150W Highbay LED down light complete with all accessories etc. directly suspended on true ceiling, including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Stairecase areas. \nModel no: Crompton LHB11-150-CDL/60-M (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 31 | Nos | |
959 | 96.8 | Supply, Installation, testing and commissioning of suspended type 35W LED down light complete with all accessories etc. directly suspended on true ceiling, including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For Stairecase areas. \nModel no: Crompton LWV12-35-(CDL) 35W LED (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 83 | Nos | |
960 | 96.9 | Supply, Installation, testing and commissioning of recessed mounting 18 W Round down light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For corridor\nModel no: Divinity ARA 18w (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 51 | Nos | |
961 | 97 | Supply, Installation, testing and commissioning of surface down light for 18 w led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For staircase.\nModel no: Crompton Pearl II 18w (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 19 | Nos | |
962 | 97.1 | Supply, Installation, testing and commissioning of Wall mounted table fan wiring with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. \nModel no: Crompton (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 5 | Nos | |
963 | 97.2 | Supply , fixing, testing and commissioning of 25w LED Street light fixture Outdoor type IP 65 protection.directly fixed on the wall including wall bracket ,1 meter GI pipe and wiring with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. \nModel no: Crompton LSTS-25-CDL-M 25W WH (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 22 | Nos | |
964 | 97.3 | Supply, Installation, testing and commissioning of surface inground light for 8w led IP65 with led driver and diffuser all accessories etc.,directly on to the garden and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For terrace garden and outer garden.\nModel no: K-LITE 4097 INGROUND 8W (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 12 | Nos | |
965 | 97.4 | EARTHING: | |||
966 | 97.5 | Earthing with copper earth plate 600X600X3 mm including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe 3.0 Metre long etc. with charcoal/ coke and salt as required. | 6 | Nos | |
967 | 97.6 | Earthing with Cast Iron earth pipe 3.0 metre long, 100 mm dia including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe etc. with charcoal/ coke and salt as required. for HT Panel Body earth . | 25 | Nos | |
968 | 97.7 | Earthing with Galvanized Iron earth pipe 3.0 metre long, 100 mm dia including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe etc. with charcoal/ coke and salt as required. for Lift Body earth. | 24 | Nos | |
969 | 97.8 | Providing and fixing 75 mm x 10 mm copper strip on surface or in recess for connections etc. as required. | 150 | Rmt | |
970 | 97.9 | Providing and fixing 60 mm x 10 mm copper strip on surface or in recess for connections etc. as required. | 10 | Rmt | |
971 | 98 | Providing and fixing 25 mm x 6 mm copper strip on surface or in recess for connections etc. as required. | 10 | Rmt | |
972 | 98.1 | Providing and fixing 50 mm x 6 mm GI strip on surface or in recess for connections etc. as required. | 4540 | Rmt | |
973 | 98.2 | Providing and fixing 25 mm x 5 mm GI strip on surface or in recess for connections etc. as required. | 4805 | Rmt | |
974 | 98.3 | Providing and fixing 8 Swg cu wire on surface or in recess for connections etc. as required. | 4710 | Rmt | |
975 | 98.4 | Providing and fixing 10 Swg cu wire on surface or in recess for connections etc. as required. | 10 | Rmt | |
976 | 98.5 | Providing and fixing 32 mm x 10 mm copper strip 0.5meter long with 2 nos. of insulator fixing on the wall including screws angor fastner wi all accessories for UPS dedicated earth clamp etc., as required. | 50 | Rmt | |
977 | 98.6 | Coil earth to street light poles with No.8 SWG GI wire of 11.5 metres of length in which 10 metres of totalength compressed in to a coil of one meter length (75mm to 100mm dia) connected suitable with hexagonaearth bolt of size 8mm in to 25mm welded on the pole at one end with a coil position fixed on the earth | 245 | Rmt | |
978 | 98.7 | UPS EARTH PIT | |||
979 | 98.8 | Earthing with copper earth plate 600X600X3 mm including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe 3.0 Metre long etc. with charcoal/ coke and salt as required. | 48 | Nos | |
980 | 98.9 | Supply and Laying of PVC insulated,XLPE, Copper conductor, 1.1 KV grade armoured, MV cable of the following sizes as required, generally conforming to IS:7098 Part-I | |||
981 | 99 | 1C 50sqmm. | 5625 | Rmt | |
982 | 99.1 | 1C 16sqmm. | 730 | Rmt | |
983 | 99.2 | Supplying,Erecting, connecting & commissioning a of 750mm. Long 50x6 mm. Cu flat in open fashion with necessary clamps, screws, etc. as earth link. | 21 | Nos | |
984 | 99.3 | STREET / YARD LIGHTING: | |||
985 | 99.4 | Design, supply, erection and testing steel tubular poles height 6 M with bottom 125 mm dia. & 4.5mm thickness and 100 mm dia.& 3.65mm for middle and 75 mm dia. & 3.25mm thickness along with 1 M long bracket including providing base plate providing concreting in foundation. Construction of pillar accommodating 20A DP MCB housed in weather proof box including wiring to the light fittings with 3 runs of 2.5sqmm PVC insulated copper conductor, supplying and fixing 4 way 30 A rated terminal block loop in loop out cable arrangements coil earthing etc. The pole shall be painted with one coat of primer and two coats of enamel paint as required by the Engineer in charge. \nModel no: K-Lite KP-7293 Cobra Ht.6000 (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 44 | Unit | |
986 | 99.5 | Supply , fixing, testing and commissioning of Street light Outdoor Fixture IP65 of LED street light luminaire \nModel no: K-Lite Waco ID 4291 60W LED light fixture (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 44 | Unit | |
987 | 99.6 | Supply , fixing, testing and commissioning of 3M height Hot dip galvanized poles, with integral control box, MCB and cable termination arrangement with top bracket. \nModel no :K-Lite KP-8105 MONARC LIGHTING POLE -6 meter monarc Ht.6000 ((or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | |||
988 | 99.7 | a) Double bracket type. | 58 | Unit | |
989 | 99.8 | Supply , fixing, testing and commissioning of Outdoor type Street light 60w light Fixture IP65 EDGE Series of LED street light luminaire \nModel no :Crompton LSTP-72-CDL-M (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 116 | Nos | |
990 | 99.9 | Supply , fixing, testing and commissioning of Bollard light luminaire \nModel no:Crompton LBLA3-10-CDL 10W LED (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 5 | Nos | |
991 | 100 | Supply, Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 4Cx16sqmm Aluminium armoured cable direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as requried. | 6555 | Rmt | |
992 | 100.1 | SAFETY EQUIPMENTS : | |||
993 | 100.2 | Supply and installing the following items as per local Electrical Inspectorate's requirement. | |||
994 | 100.3 | 6 mm thick rubber mat. | 50 | Sq.m | |
995 | 100.4 | 12 mm thick rubber mat. | 10 | Sq.m | |
996 | 100.5 | Fire Buckets stand suitable for 4 Nos. fire buckets with Fire Buckets filled with stand. | 2 | Unit | |
997 | 100.6 | First Aid Box with stand. | 2 | Nos | |
998 | 100.7 | Shock Treatment Chart in 2 Language (Local Language and English) | 2 | Nos | |
999 | 100.8 | Supply & Fixing HT cable route marker with 10cm. x 10cm. 5mm thick G.I.plate with inscription thereon, bolted/ welded to 35mm x 35mm x 6mm angle iron, 60 cm. long and fixing the same in ground as required. | 10 | Nos | |
1000 | 100.9 | Supply and fixing of 11 KV Al Danger Boards of size 12" x 8" both in Tamil and English | 3 | Nos | |
1001 | 101 | Supply and fixing of 440V Al Danger Boards of size 6"x 4" both in Tamil and English | 25 | Nos | |
1002 | 101.1 | Supply of 11 KV Tested Gloves with Box filled with chalk powder. | 1 | Nos | |
1003 | 101.2 | Supply, Erection, Testing and commissioning of "EXIT" sign lamp fitted with integral inverter and battery for half an hour back up power with necessary suspension arrangement,connecting wires and all as required as per site requirement. | 30 | Nos | |
1004 | 101.3 | Supply, Erection, Testing and commissioning of "ENTRY" sign lamp fitted with integral inverter and battery for half an hour back up power with necessary suspension arrangement,connecting wires and all as required as per site requirement. | 30 | Nos | |
1005 | 101.4 | Dry chemical powder type fire extinguishers complete with initial charges, carbon dioxide gas cartridge, hose and fixing brackets etc of the following capacities confiriming to IS: 2171 5 KG capacity. | 8 | Unit | |
1006 | 101.5 | TNEB AND CEA APPROVALS : | |||
1007 | 101.6 | 1, ARRANGING LOAD SANCTION : | |||
1008 | 101.7 | Liasion with TNEB including submission of application forms, obtaining load sanction 5000 KVA and other associated works. (Excluding Advice Payments - The necessary statutory fees will be paid by the client against proof of demand)) | |||
1009 | 101.8 | a, Registration | 1 | Unit | |
1010 | 101.9 | b, Development | 1 | Unit | |
1011 | 102 | c, Commissioning | 1 | Unit | |
1012 | 102.1 | 2, ARRANGING SAFETY | |||
1013 | 102.2 | a, Getting drawing approval from Electrical Inspectorate to Govt/Central Electrical Authority of Tamil Nadu. (Excluding Advice Payments - The necessary statutory fees will be paid by the client against proof of demand)) | 1 | Ls | |
1014 | 102.3 | b, Preparation completion Report, Arranging for Inspection Electrical Inspectorate to Govt/Central Electrical Authority of Tamil Nadu. (Excluding Advice Payments - The necessary statutory fees will be paid by the client against proof of demand)) | 1 | Ls | |
1015 | 102.4 | MISCELLANEOUS ITEMS : | |||
1016 | 102.5 | Preparation of AS BUILT Drawings -3 SET | 1 | Unit | |
1017 | 102.6 | RESTAURANT BUILDINGS | |||
1018 | 102.7 | Electrical cables, LT panels ,Wiring & Light fixtures ,Earthing etc. | |||
1019 | 102.8 | FOOD COURT MAIN PANEL-1\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 630 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating Microprocessor based adjestable O/L relay and fixed S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 630/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set. of On, Off, Trip indicating lamps for breaker status with protection fuse for potential circuit.. | 1 | Unit | |
1020 | 102.9 | Continue above\nB) Outgoing :\n3 Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n3 Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n4 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n630A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. | |||
1021 | 103 | LSB-1 (FOOD COURT)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating withadjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 63/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set. of On, Off, Trip indicating lamps for breaker status with protection fuse for potential circuit.. | 1 | Nos | |
1022 | 103.1 | Continue above\nB) Outgoing :\n6 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n63A TPN 25KA Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \n | |||
1023 | 103.2 | PSB-1 (FOOD COURT)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 100 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 100/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set. of On, Off, Trip indicating lamps for breaker status with protection fuse for potential circuit. | 1 | Unit | |
1024 | 103.3 | Continue above\nB) Outgoing :\n6 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n100A TPN Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \n | |||
1025 | 103.4 | VENT & AHU PANEL-1 (FOOD COURT-GF)\nDesign, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed \nA) Incomer:\n1Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nThere shall be one set of Metering Compartment incorporated with the following:-\n1No - Class 1.0, Digital Duel source Multifunction Meter with Inbuilt Selector Switch, communication port RS 485 having MODBUS Protocol with control fusese etc.\n3Nos. - 125/5A CL-1 ,15VA current transformer with CT short link terminal block for Multi function Meter\n1Set. - 3Nos. of R,Y,B phase indicating lamps with protection fuse for potential circuit..\n1Set. of On, Off, Trip indicating lamps for breaker status with protection fuse for potential circuit.. | 1 | Unit | |
1026 | 103.5 | Continue above\nB) Outgoing :\n3 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\n4 Nos 32 Amps TP&N MCCB with Manual Closing Mechanism of 25 kA Short Circuit Rating with adjustable Thermal O/L and fixed Magnetic S/C Protection.\nC) Busbar :\n125A TPN 25KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status. \n | |||
1027 | 103.6 | MCB with enclosure\nDesign, supply, fixing, testing and commissioning of following switch gear with suitable metal enclosure, adopter box to receive suitable rating of incoming and outgoing cable, fixing angle frame, anchor fastner all accossories etc. | |||
1028 | 103.7 | 32AmpsTPN Isolatior with enclosure. For Lift. | 2 | Nos | |
1029 | 103.8 | 25Amps DP MCB with enclosure. For 3kva UPS | 2 | Nos | |
1030 | 103.9 | DISTRIBUTION BOARDS | |||
1031 | 104 | FOOD COURT LDB & ELDB :\n6W TPN MCB LDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer :3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 18 Nos 6 A SP MCB . | 1 | Unit | |
1032 | 104.1 | 8W TPN MCB LDB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB\nSub Incomer :3 Nos 25 A DP MCBs with 30mA ELCB\nOutgoing : 24 Nos 6 A SP MCB . | 3 | Unit | |
1033 | 104.2 | 12 W SPN MCB ELDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 12 WAY SP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1 Nos 25 A DP MCB\nOutgoing : \n10 Nos 6 A SP MCB | 1 | Unit | |
1034 | 104.3 | 8W SPN MCB : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY SP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1 Nos 25 A DP MCB\nOutgoing : \n6 Nos 6 A SP MCB | 9 | Unit | |
1035 | 104.4 | POWER DISTRIBUTION BOARD MAIN BUILDING :\n4W TPN MCB PDB for :\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 4 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 12 Nos 16/20 A SP MCB. | 2 | Unit | |
1036 | 104.5 | 6W TPN MCB PDB for : \nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 6 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs with 30mA ELCB\nOutgoing : 18 Nos 16/20 A SP MCB . \n | 1 | Unit | |
1037 | 104.6 | DISTRIBUTION BOARD - UPS : \n8W TPN MCB UPSDB for :\nFabrication, Supply, Installation, Testing and Commissioning of Phase Segregated Type 8 WAY TP & N MCB Distribution Board with 'D' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 63 A, 4P MCB\nSub Incomer :3 Nos 63 A DP MCBs \nOutgoing : 24 Nos 16/20 A SP MCB. \n | 1 | Unit | |
1038 | 104.7 | VERTICAL DISTRIBUTION BOARD\n8W VTPN MCB MELDB for :\nFabrication, Supply, Installation, Testing and Commissioning of Vertical type 8 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB \nOutgoing : 8Nos 6/10 A TP MCB. \n | 1 | Unit | |
1039 | 104.8 | 12W VTPN MCB VENTILATION DB for :\nFabrication, Supply, Installation, Testing and Commissioning of Vertical type 12 WAY TP & N MCB Distribution Board with 'C' curve MCB's and double door, dust & vermin proof and copper bus bar comprising of the following : \nIncoming : 1No 32 A, 4P MCB \nOutgoing : 12Nos 6/10 A TP MCB. \n | 1 | Unit | |
1040 | 104.9 | 4W VTPN distribution boards : \nLIFT DB : Supplying and fixing of sheet steel, MCB distribution board, 415V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. for LIFT DB for Main Hall, MLCP, Restaurant.comprising of the following : \nIncoming : 1No 63 A, 4P MCB \nOutgoing :1 Nos 40 A TP MCB \nOutgoing : 2Nos 16 A TP MCB. | 2 | Unit | |
1041 | 105 | UPS & INVERTERS | |||
1042 | 105.1 | Supply and Erection of 3 KVA UPS Systems with 1-phase input and Single phase output. Maintanance free batteies suitable for backup system should have Half an hour continous rating at 0.8 output Power factor.The scope includes providing neccesary battery stand , inter connecting cables from UPS battery.The scope also includes providing neccesary by-pass arrangement and all other requirements. The capacity of the battery shall be of 12V DC with a minimum of Suitable ampere hour and as per specification. | 1 | Unit | |
1043 | 105.2 | LT CABLING & END TERMINATION : | |||
1044 | 105.3 | Supply and Laying of XLPE insulated and PVC inner sheathed , FRLS outer sheathed , aluminium conductor, 1.1 KV grade armoured, MV cable of the following sizes as required, generally conforming to IS:7098 Part-1 | |||
1045 | 105.4 | 3 1/2 X 300 sqmm. | 1025 | Rmt | |
1046 | 105.5 | 3 1/2 X 95 sqmm. | 25 | Rmt | |
1047 | 105.6 | 3 1/2 X 50 sqmm. | 100 | Rmt | |
1048 | 105.7 | 3 1/2 X 35 sqmm. | 85 | Rmt | |
1049 | 105.8 | 4 x 25 sqmm. | 25 | Rmt | |
1050 | 105.9 | 4 x 16 sqmm . | 210 | Rmt | |
1051 | 106 | Supply and Laying of XLPE insulated and PVC inner sheathed , FRLS outer sheathed , copper conductor, 1.1 KV grade armoured, MV cable of the following sizes as required, generally conforming to IS:7098 Part-1 | |||
1052 | 106.1 | 4 x 6 sqmm . | 10 | Rmt | |
1053 | 106.2 | 4 x 4 sqmm . | 15 | Rmt | |
1054 | 106.3 | 4 x 2.5 sqmm . | 430 | Rmt | |
1055 | 106.4 | 5Runs of 6Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 4 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm. thick MS Conduits laid in surface conduits (3KVA UPS UPS O/G DBs) | 10 | Rmt | |
1056 | 106.5 | TERMINATION : | |||
1057 | 106.6 | Supplying and making end termination with brass Double compression gland and aluminium lugs for following size of XLPE insulated and PVC inner sheathed , FRLS outer sheathed aluminium conductor cable of 1.1 KV | |||
1058 | 106.7 | 3 1/2 X 300 sqmm. | 6 | Unit | |
1059 | 106.8 | 3 1/2 X 95 sqmm. | 2 | Unit | |
1060 | 106.9 | 3 1/2 X 50 sqmm. | 4 | Unit | |
1061 | 107 | 3 1/2 X 35 sqmm. | 2 | Unit | |
1062 | 107.1 | 4 x 25 sqmm. | 6 | Unit | |
1063 | 107.2 | 4 x 16 sqmm. | 18 | Unit | |
1064 | 107.3 | Supplying and making end termination with brass Double compression gland and aluminium lugs for following size of XLPE insulated and PVC inner sheathed , FRLS outer sheathed Copper conductor cable of 1.1 KV | |||
1065 | 107.4 | 4 x 6 sqmm. | 2 | Unit | |
1066 | 107.5 | 4 x 4 sqmm. | 4 | Unit | |
1067 | 107.6 | 4 x 2.5 sqmm. | 22 | Unit | |
1068 | 107.7 | 5Runs of 6Sq.mm. PVC Insulated stranded copper conductor wires ( One each for Phase, 2 Neutral ) with 1Run of 4 Sq.mm. PVC Insulated multi stranded copper conductor wires for continuous earthing in 2.0 mm thick MS Conduits laid in surface conduits (3KVA UPS UPS O/G DBs) | 6 | Unit | |
1069 | 107.8 | CABLE TRAY & M.S ITEMS: | |||
1070 | 107.9 | Supply, erection of following sizes ( Hot dip galvanised iron ) GI ladder type cable rack system made out of sheet steel folded to required shape with adequate number of supports. (Cable tray support price is not required in this Items).\nThe cable tray shall have runners rugs of suitable size, horizontal elbow, vertical elbow 90 Deg. Up vertical elbow 90 Deg. Down, re-deep, coupler plates, materials. The cable tray shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc. The tray shall have suitable cable clamping arrangements etc. | |||
1071 | 108 | 150 mm Width X 50mm Height X 3mm Thick. | 60 | Rmt | |
1072 | 108.1 | 300 mm Width X 50mm Height X 3mm Thick. | 325 | Rmt | |
1073 | 108.2 | 450 mm width X 50mm Height X 3mm Thick. | 30 | Rmt | |
1074 | 108.3 | 600 mm.width X 75mm Height X 3mm Thick. | 85 | Rmt | |
1075 | 108.4 | Supply and erection of M.S. Material for ladder type cable trays, cable supports, SB, DB's supports, iron embeded in the wall, steel structure in open Area painted with two coats of primer and two coats of enamel paint. Substation to main panel room , ahu room and lighting conduit trays and suspensions of lighting conduit . | 400 | Kgs | |
1076 | 108.5 | MS chequer plate : \nDesign, cutting, and fixing of 6 mm thick chequered plate with required MS angles for closing around the cable tray shafts and communication shafts. It should be covered with neatly without any gap around the cable tray as per IE Regulation. The gap between cable tray and the chequred plate shall be covered with insulating materials. \n | 1.5 | Sq.m | |
1077 | 108.6 | INTERNAL WIRING FOR FOOD COURT: | |||
1078 | 108.7 | Wiring for Lift Well Light Point and socket oulet with 2 x 1.5 sqmm FRLS PVC insulated Stranded Copper Conductor Cable along with 1 x 1.5 sqmm FRLS PVC insulated Stranded copper conductor cable as earth wire in surface MS conduit including providing and fixing Galvanised / Cadmium plated MS switch box, 2 no 6A Single Way Modular Switch for (controlling light point and socket Outlet) , 1 No 6 A 5 Pin shuttered modular socket outlet with modular switch plate and making necessary connections etc., as per specification (5 Meters shall be considered for Wires & conduit per point.) | 4 | Nos | |
1079 | 108.8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos 6 pin 6 /16 A modular Shuttered socket outlet and one 16 A modular switch, connections etc. as required.ahu room , pantry (Raw Power) | 2 | Nos | |
1080 | 108.9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular Shuttered socket outlet and 15/16 A modular switch, connections etc. as required .. (Raw Power) | 17 | Nos | |
1081 | 109 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular Shuttered socket outlet and 15/16 A modular switch, connections etc. as required for Hand Dryer. (Raw Power) | 4 | Nos | |
1082 | 109.1 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular Shuttered socket outlet and 15/16 A modular switch, connections etc. as required for Napkin Vending Machine. (Raw Power) | 2 | Nos | |
1083 | 109.2 | Wiring for power :\nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
1084 | 109.3 | 2 x 4 sqmm +1 x 2.5 sqmm (E) | 525 | Rmt | |
1085 | 109.4 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. | |||
1086 | 109.5 | 25 mm | 355 | Rmt | |
1087 | 109.6 | MS conduit wiring (for lighting): \nWiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in 25 mm surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. | |||
1088 | 109.7 | Group A (One light controlled by one switch - 6mtrs ) | 6 | Nos | |
1089 | 109.8 | Group B (Two light controlled by one switch - 9mtrs) | 30 | Nos | |
1090 | 109.9 | Group C (Three light controlled by one switch - 12mtrs) | 7 | Nos | |
1091 | 110 | Run of main wiring for circuit / power / sub main etc :\nWiring with following sizes of FRLS PVC insulated Stranded Copper Conductor Cable along with FRLS PVC insulated Stranded Cu. Conductor Cable as earth wire in Existing MS Conduit in recess/surface including making connection etc., as per specification. | |||
1092 | 110.1 | 2 x2.5 sqmm + 1 x 1.5 sqmm (E) | 2862 | Rmt | |
1093 | 110.2 | Supplying and fixing of following sizes of MS conduit along with the accessories in surface including cutting the wall and making good the same in case of recessed conduit as required: | |||
1094 | 110.3 | 25 mm. | 2085 | Rmt | |
1095 | 110.4 | LIGHT FIXTURES FOR FOOD COURT: | |||
1096 | 110.5 | Supply, Installation, testing and commissioning of prewired, IP65 40W LED batten weather proof fittings, of all types complete with all accessories etc. directly on ceiling / wall, including connections with 2.5 sq.mm. FRLS PVC insulated, copper conductor, single core cable etc. as required. For AHU room, Electrical Room. \nModel no: Crompton CDR-206-18-57-SL-NWH 40W WH (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 31 | Nos | |
1097 | 110.6 | Supply, Installation, testing and commissioning of recess mounting 18W ARA Round light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For corridors.\nModel no: Divinity ARA Round light (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 58 | Nos | |
1098 | 110.7 | Supply, Installation, testing and commissioning of Recessed down light for 5w led with remote led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets. Model no: Divinity Atom 5w led (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 7 | Nos | |
1099 | 110.8 | Supply, Installation, testing and commissioning of Recessed down light for 18 w led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets.\nModel no: Crompton CDR-206-18-57-SL-NWH (or) Philips make (or) k-light make (or) Havells make (or) Divinity make | 8 | Nos | |
1100 | 110.9 | Supply, Installation, testing and commissioning of Recessed squre down light for 24W led with led driver and diffuser all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For toilets.\nModel no: K-LITE- ISHA SQUARE - 3361-24W LED (or) Philips make (or) Divinity make (or) Havells make (or) Crompton make | 140 | Nos | |
1101 | 111 | Supply, Erection, Testing and commissioning of recessed mounting 25 w LED strip light with accorlic cover in linear column (customised) light fixture with driver fixing on to column as per site requirement with necessary interconnecting wires & fixing hardwares etc. all complete as required. Divinity (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 207 | Rmt | |
1102 | 111.1 | Supply, Installation, testing and commissioning of recess mounting 32W Round light with all accessories etc.,directly on to the false ceiling including modifying the false ceiling openings and making good the same and wiring and connections with 2.5 sq.mm. FRLS PVC insulated, Copper conductor, single core cable as required. For corridors.\nModel no: Divinity ARA Round light (or) Philips make (or) k-light make (or) Havells make (or) Crompton make | 6 | Nos | |
1103 | 111.2 | EARTHING: | |||
1104 | 111.3 | Earthing with copper earth plate 600X600X3 mm including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe 3.0 Metre long etc. with charcoal/ coke and salt as required. | 2 | Nos | |
1105 | 111.4 | Earthing with C.I. earth pipe 3.0 metre long, 100 mm dia including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe etc. with charcoal/ coke and salt as required. Body earth . | 2 | Nos | |
1106 | 111.5 | Earthing with G.I. earth pipe 3.0 metre long, 100 mm dia including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe etc. with charcoal/ coke and salt as required. for Lift Body earth. | 3 | Nos | |
1107 | 111.6 | Providing and fixing 50 mm x 6 mm GI strip on surface or in recess for connections etc. as required. | 585 | Rmt | |
1108 | 111.7 | Providing and fixing 25 mm x 5 mm GI strip on surface or in recess for connections etc. as required. | 230 | Rmt | |
1109 | 111.8 | Providing and fixing 8 Swg cu wire on surface or in recess for connections etc. as required. | 280 | Rmt | |
1110 | 111.9 | Providing and fixing 10 Swg cu wire on surface or in recess for connections etc. as required. | 10 | Rmt | |
1111 | 112 | Providing and fixing 25 mm x 6 mm copper strip 0.5meter surface or in recess for connections with insulator bold nut etc. as required. | 1 | Nos | |
1112 | 112.1 | DG Set With Exhaust pipe, Stack, Under ground HSD tank and connected works\nDG SET & ACOUSTIC ENCLOSURE-2250KVA | |||
1113 | 112.2 | Supply, installation, testing and commissioning of Prime rated Diesel Generator set with Diesel Engine developing suitable BHP at 1500 RPM considering de-rating factor if any water / coolant cooled, microprocessor based power command control module, floor mounted with acoustic enclosure coupled to 2250 KVA (minimum) brushless type 415V+/-5%V, 3 phase, 1500 RPM, O.8 PF, exciting alternator conforming to latest environment protection regulations for emission and noise level complete with all accessories including supply and installation of isolator panel with capacity of 4000A TPN MDO ACB, engine control panel with meter, CTs and transducers for all metering and protection, Antivibration mountings, silencer, electric starter, batteries & battery charger, base tank of 990 ltrs with level indicator, 1 no. daily fuel tank of 990 ltrs., capacity with, radiator, first fill of lubricating oil and diesel for testing and commissioning and all spares and accessories as required complete with necessary civil foundation works including transportation of DG set insurance etc. The work should be as per Central Inspectorate / Pollution Control Board Standards. Civil foundation shall be under the scope of owner. | 3 | Nos | |
1114 | 112.3 | EXHAUST CHIMNEY & STACK | |||
1115 | 112.4 | Exhaust System | |||
1116 | 112.5 | Design, manufacture, supply, installation, testing and commissioning of following MS exhaust pipe as per IS 3589 and it shall be insulated with 50 mm thick wool insulation wrapped in chicken mesh and clad with 26 gauge aluminium sheet including all MS epoxy painted support structural as required suitable for 2250 kVA exhaust line, as per manufacturer's recommendation upto silencer. The rate shall be inclusive of necessary, bends, flanges, gaskets, 'Y' transformation piece, fixing of residential silencer supplied along with the engine, inspection point, welding arrangements as specified to suit the site conditions. The exhaust pipe should be painted with 2 coats of high temp alumninum paint before the insulation. The tenderer shall submit calculation along with the size offered for the DG set, as detailed below, individually: | |||
1117 | 112.6 | Supply, installation, testing and commissioning of Providing 350mm/400mm dia, not less than 4.5mm thk MS exhaust pipe factory rolled pipe as per IS 3589 (the pipe dia should be indicated in mm as per the manufacturers recommendation for satisfactory operation. | 45 | Rmt | |
1118 | 112.7 | Supply, installation, testing and commissioning of Providing 50 mm thick wool insulation and 26gauge aluminum clading for the above said 350mm/400mm dia. MS exhaust pipe with all other necessary accessories. | 45 | Rmt | |
1119 | 112.8 | Supply, installation, testing and commissioning of Providing 450mm/500mm dia, not less than 4.5mm thk MS exhaust pipe factory rolled pipe as per IS 3589 (the pipe dia should be indicated in mm as per the manufacturers recommendation for satisfactory operation. | 140 | Rmt | |
1120 | 112.9 | Supply, installation, testing and commissioning of Providing 50 mm thick wool insulation and 26gauge aluminum clading for the above said 450mm/500mm dia. MS exhaust pipe with all other necessary accessories. | 140 | Rmt | |
1121 | 113 | Supply & fixing of 50mm thick wool insulation and 26gauge aluminum clading for 2250KVA engine residential silencer including cutting, fixing of mineral wool, polythene covering,chicken mesh and aluminium cladding complete as per the specifications etc. as required. | 6 | Nos | |
1122 | 113.1 | Supply and installation of discharge end 45deg bend with bird mesh in 6mm dia SS material and rain water protection arrangement at the end. | 3 | Nos | |
1123 | 113.2 | Supply and installation of expansion bellows in SS construction with flanged end for 2250 KVA DG exhaust pipe . | 6 | Nos | |
1124 | 113.3 | Supply and Installation of Drain plugs /flages for ehaust pipe. | 3 | Nos | |
1125 | 113.4 | Supply and installation of inspection nozzle with flange, cap for ehaust pipe at approach level 150dia | 3 | Nos | |
1126 | 113.5 | Supply and Installation of DG gas test nozzle at approach level | 3 | Nos | |
1127 | 113.6 | Design, supply and fixing of copper lightning spike at the top of the stack with suitable supports. | 1 | Unit | |
1128 | 113.7 | Supply, fixing of LED integral type aviation lamp at top of the Chimney with Auto ON / OFF connecting cables upto aviation lamp, control switch etc | 1 | Nos | |
1129 | 113.8 | STACK FOR EXHAUST PIPE | |||
1130 | 113.9 | Supply and Installation of MS prefabricated steel structure in typical bolt nut arrangement for 35 M Hight chimney stack for taking total 3 x 2250kVA DG exhaust pipe from ground level to top level in the utility building column / beam as per design to be free issued to civil contractor for embedding in RCC. | 25 | MT | |
1131 | 114 | SECTION-D: FUEL TANKS & PIPE LINES | |||
1132 | 114.1 | Supplying and Installation Testing and commissioning of 990Lts Fuel Tank fabricated by 2mm Sheet, suitable stiffners, Man Hole (400x400) , Breath went, Drain,Delivery, Fuel level indicator,Float valve arrangement, Level switch,Lifting Hook,etc as required.( One Intermediate tank one overflow tank) | 2 | Nos | |
1133 | 114.2 | Supply and laying of 50mm dia C class MS pipe in the exposed surface the pipe line shall be painted with one coat of primer and two coats of synthetic enamel paint i/c. with necessary supports complete as required. (FROM DAY TANK TO DG SET AND RETURN TO DAY TANK and FROM INTERMEDIATE TANK TO DAY TANK). | 150 | Rmt | |
1134 | 114.3 | 25 mm dia float valve for day tank | 5 | Nos | |
1135 | 114.4 | 50 mm dia ball valve | 16 | Nos | |
1136 | 114.5 | SECTION-E: ELECTRICAL PANEL SYSTEMS | |||
1137 | 114.6 | AUTO START & AUTO SYNC. PANEL | |||
1138 | 114.7 | Design, supply, testing and commissioning of Auto start and Auto syn panel with auto load sharing arrangement of Indoor, cubicle type floor mounting panel made out of MS sheet enclosure with Copper busbars, single busbar system, cable chamber, interconnection, painting, earthing, protection relays etc. comprising of the following : (DG AMF with auto Synchronising control Panel) | 1 | Unit | |
1139 | 114.8 | INCOMING | |||
1140 | 114.9 | From DG Set 2250 KVA - 3 Nos. | |||
1141 | 115 | 3 Nos 4000 AMPS ACB, 65 KA (Ics) AC Motor operated Draw Out ( EDO ) Type Four Pole Microprocessor based relay having Over current, short circuit with time setting, Earth fault and 6NO + 6 NC, indication for test,service,isolated ON/OFF trip indications, ShutterAssembly,Racking interlock Manual / Electrical closing & tripping Ready to close indication contact, Site changable rear terminal adaptors, Mechanical door interlock, Trip unit shall be Microprocessor based LSING protection with RS 485 communication port supporting modbus RTU communication protocol as specified in the technical Specifications with 800A 4P Motorized MCCB for neutral contact with all other necessary accessories. | |||
1142 | 115.1 | Each Instrumental compartment shall be comprising of following | |||
1143 | 115.2 | Synchronizing relay showing power factor, KW, KVA, RPM, Temprature indicator, and 'Multi load manager, Energy meter, Voltmeter, Instantaneous over current, earthfault relay (3 O/C+ 1 E/F), Restricted earth fault relay, Standby earth fault relay, Under voltage relay, Over voltage relay, Reverse directional power relay, Differential protective relay, Under frequency relay, Over frequency relay and Master trip relay, necessary CTs, PTs, control MPCB/MCB/ ELCB/RCBOs, RYB Indication lamps and “ON/OFF/Trip/Rest" indicating lamp, and emergency lockable push buttons, GCU, Battery charger and also as per the specification and SLD. | |||
1144 | 115.3 | BUSCOUPLER | |||
1145 | 115.4 | 2Nos 6300 AMPS ACB, 65 KA (Ics) AC Motor operated Draw Out ( EDO ) Type Four Pole without release and 6NO + 6 NC, indication for test,service,isolated ON/OFF trip indications, ShutterAssembly,Racking interlock Manual / Electrical closing & tripping Ready to close indication contact, Site changable rear terminal adaptors, Mechanical door interlock, with all other necessary accessories. | |||
1146 | 115.5 | The buscoupler shall be provided with mechanical & electrical Inetrlocking arrangements. and also should have on/off/trip indication lamps and control MPCB/MCB/ ELCB/RCBOs with all other necessary accessories and also refer the SLD. | |||
1147 | 115.6 | OUTGOINGS | |||
1148 | 115.7 | BUS A | |||
1149 | 115.8 | 1 Nos. of 4000 AMPS ACB, 65 KA (Ics) Draw Out ( EDO )Type , TPN Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC, indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual / Electrical closing& tripping as specified in the technicalSpecifications. | |||
1150 | 115.9 | 1 Nos. of 1250 AMPS ACB, 65 KA (Ics) Draw Out ( EDO )Type , TPN Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC, indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual / Electrical closing& tripping as specified in the technicalSpecifications. | |||
1151 | 116 | BUS B\n1 Nos. of 4000 AMPS ACB, 65 KA (Ics) Draw Out ( EDO )Type , TPN Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC, indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual / Electrical closing& tripping as specified in the technicalSpecifications. | |||
1152 | 116.1 | BUS C\n1 Nos. of 4000 AMPS ACB, 65 KA (Ics) Draw Out ( MDO )Type , TPN Microprocessor based relay having Over current, short circuit with time setting and 4NO + 4 NC, indication for test,service,isolated ON/OFF tripindications, ShutterAssembly,Racking interlock Manual / Electrical closing& tripping as specified in the technicalSpecifications.4000A TPN MDO ACB 65kA – 1 Nos | |||
1153 | 116.2 | All the Outgoing feeder shall be ON/OFF/Trip indication lamps, all ACBs should have two nos (spare) potential free contactor, Multi function meter with RS 485 port. The rate shall inclusive of necessary CTs, PTs and control switches, Front operating handles etc., All switch boards shall be fabricated as per the detailed specification enclosed. Suitable size outgoing cable chamber and extra busbars should be provided for connecting the number of outgoing cables as per the schematic drawing.The board shall be fabricated for future extension of the panel board. | |||
1154 | 116.3 | The panel should have suitable arrangements for engine start, synching & load sharing by auto & manual option with all required meters, relays like dual voltmeter, dual frequency meter, synchronoscope, sychronization relay & control, auto load sharing relay, voltage and current balane relay, auto / manual selector switch etc. | |||
1155 | 116.4 | The necessary electrical interlocking arrangement between incomers by hardware control wiring along with PLC (Programmable Logic Control). The hardware control wiring and other necessary control wiring and PLC operation shall be feasible to extend for the panel as per the detailed specification and drawings enclosed. - Each incoming feeders should have inbuilt battery charger for DG sets and the battery charger shall be of 24Volts, 40Amps,SCR controlled with all accessories having automatic boost and trickle charging arrangements with volt and current limiting circuits, voltmeter for AC/DC supply, ammeter for charging circuit (DC), automatic cut off facility when the Engine alternator is in working condition, MCB for protection, suitable for 230V,50Hz, AC supply, interconnections, body earthing etc. complete as per technical specification and drawings. | |||
1156 | 116.5 | 6300A TPN 65KA Copper Busbar with heat shrinkable colour insulated PVC sleeves.Current density - 1.2Amps/Sqmm. | |||
1157 | 116.6 | BUS DUCT | |||
1158 | 116.7 | Supply,Erection,Testing and Commissioning of 4000 A 65kA 4P 433v, 50HZ, Air insulated LV BUS duct comprising of 4P Copper Busbar housed in Aluminium enclosure, Including Vertical Bends, Horizontal bends, Spring & Fix Hangers with 2 no of External copper earth ( 50 mm x 6 mm copper ) . The busduct shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc., from DG set side to Synchronizing panel.(As per the detailed Technical Specification enclosed.) | 60 | Rmt | |
1159 | 116.8 | FLEXIBLE JOINIT | |||
1160 | 116.9 | Supply,Erection,Testing and Commissioning of 4000A Copper Flexible joint ,Flange End at the DG set side and Synchronizing panel side and additonal flexible joint to be provided every 5 mtrs with required Standard Accessories etc., complete as required.( 1 set = R,Y,B & N ) | 6 | Set | |
1161 | 117 | Supply and Installation flexible bellow to receive 4000A 4P copper. Busduct at alternator end. | 3 | Rmt | |
1162 | 117.1 | CONTROL CABLE & END TERMINATION | |||
1163 | 117.2 | Supply,laying,testing and commissioning of control cable size 24 core 1 sqmm PVC insulated, PVC sheathed armoured screened copper conductor cable. From Synchronizing panel to DG set. | 50 | Rmt | |
1164 | 117.3 | Supply, terminations,testing and commissioning of control cable size 24 core 1 sqmm PVC insulated, PVC sheathed screened copper conductor cable. | 6 | Unit | |
1165 | 117.4 | Supply,laying,testing and commissioning of control cable size 12 core 2.5 sqmm PVC insulated, PVC sheathed armoured copper conductor cable. From Synchronizing panel to DG set. | 800 | Rmt | |
1166 | 117.5 | Supply, terminations,testing and commissioning of control cable size 12 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 25 | Unit | |
1167 | 117.6 | Supply,laying, testing and commissioning of control cable size 4 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. From MV panel to Synchronizing panel. | 600 | Rmt | |
1168 | 117.7 | Supply, terminations,testing and commissioning of control cable size 4 core 2.5 sqmm PVC insulated, PVC sheathed copper conductor cable. | 25 | Unit | |
1169 | 117.8 | Supply,laying,testing and commissioning of control cable size 4 core 1 sqmm PVC insulated, PVC sheathed armoured screened copper conductor cable. From Synchronizing panel to DG set. | 50 | Rmt | |
1170 | 117.9 | Supply, terminations,testing and commissioning of control cable size 4 core 1 sqmm PVC insulated, PVC sheathed screened copper conductor cable. | 6 | Unit | |
1171 | 118 | CABLE TRAY & M.S ITEMS: | |||
1172 | 118.1 | Supply, erection of following sizes GI ladder type cable rack system made out of sheet steel folded to required shape with adequate number of supports. (Cable tray support price is not required in this Items).\nThe cable tray shall have runners rugs of suitable size, horizontal elbow, vertical elbow 90 Deg. Up vertical elbow 90 Deg. Down, re-deep, coupler plates, materials. The cable tray shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc. The tray shall have suitable cable clamping arrangements etc. | |||
1173 | 118.2 | 150 mm Width X 50mm Height X 3mm Thick. | 50 | Rmt | |
1174 | 118.3 | 300 mm Width X 50mm Height X 3mm Thick. | 50 | Rmt | |
1175 | 118.4 | EARTHING: | |||
1176 | 118.5 | Earthing with copper earth plate 600X600X3 mm including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe 3.0 Metre long etc. with charcoal/ coke and salt as required. | 6 | Nos | |
1177 | 118.6 | Earthing with Cast Iron earth pipeearth pipe 3.0 metre long, 100 mm dia including accessories, and providing masonry enclosure (Chamber size of 1050X1050X700) with fabricated MS Chequre plate of 600X600X6 cover with frame & keel arangement, and watering pipe etc. with charcoal/ coke and salt as required. for Body earth | 7 | Nos | |
1178 | 118.7 | Providing and fixing 75 mm x 10 mm copper strip on surface or in recess for connections etc. as required. | 145 | Rmt | |
1179 | 118.8 | Providing and fixing 60 mm x 10 mm GI strip on surface or in recess for connections etc. as required. | 160 | Rmt | |
1180 | 118.9 | SECTION-G: SAFETY AND MISCELLANIOUS ITEMS | |||
1181 | 119 | Supply and Fixing of Safety items consists of 5KG CO2 type fire extinguisher,Foam type fire extinguisher,GI Fire bucket with round bottom,Shock treatement chart in three launguage like Tamil,English,Hindhi,Rubber mat,First Aid kid, Display board for display the DG set details. | 5 | Unit | |
1182 | 119.1 | STATUTORY APPROVAL | |||
1183 | 119.2 | Preparation of the drawing and submission to the statutory authorities Chief Electrical inspectorate to Govt. of Tamil Nadu for commissioning the system including arranging inspection and also necessary approval / safety certificate from authorities etc. for the Electrical / DG Installation. (Excluding PCB) | 1 | Unit | |
1184 | 119.3 | UNDER GROUND DIESEL TANK AND CONNECTED WORKS | |||
1185 | 119.4 | DIESEL STORAGE &TRANSFER | |||
1186 | 119.5 | Designing, Supply of storage tank, piping and pipe fittings, valves, Gaskets and supports structural, Installation, pre commissioning, painting as per code and commissioning and getting approval of storage &pumping system for Diesel unloading and transfer from diesel storage yard to plant use as per technical specification and codes and Indian standards and also as per rules and regulation stipulated by chief Controller of explosive dept and The petroleum Rules 2002 amended by 2005. | |||
1187 | 119.6 | Diesel Tank | |||
1188 | 119.7 | Diesel tank of following capacity horizontal cylindrical type to with stand maximum pressure of 0.5kg/sq cm in IS-10987. MOC mild steel plates with safety accessories with complete supporting structure, roof Hand rail, ladder, walkway platform , flanged nozzles, manhole Vent valve with Box trap over flow valve, isolation valves and drain Valve shall be provided and IS10987-1992:Code of practice for design, fabrication, testing & installation of underground horizontal cylindrical steel storage tanks double skin shell for petroleum products and as per rules and regulation of Chief controller of Explosive Dept . Fabrication, Transportation, insurance,Unloading at site, Installation, Testing & Comissioning of HSD tank suitably designed forUnder ground installation as per enclosed drawing and as per rules and regulation stipulated by chief control of explosive dept and The petroleum Rules 2002 amended by 2005.. | |||
1189 | 119.8 | Tank to be suitably fabricated out of M.S. plate shell minimum 6mm& end plate minimum 8mm ) with stiffeners double wall leak proof , necessary accessories such as outlet, inlet, manhole, Aluminium dipstick, bolts, nuts and necessary brackets on the tank for holding turn buckle etc.complete all as per approved design/drawing Tank dia is inner vesssel dia2.65mtrsLength is 6.00m &outer dia 2.75m & Length is 6.40m Duly treated with necessary anti corrosive compound externally and stiffener angle for endplate ,bottom pad plate and tumbuckles with support arrangement, The tanks to be tested for leaks under water fill test .Rate quoted shall include for necessary transportation, loading, unloading at site as directed, including necessary anticorrosive treatment to tank etc.complete. Propervent pipe with end with ss mesh(mesh size 10-25mesh) flanged end to avoid insects entry. | |||
1190 | 119.9 | Painting :2 coats of Epoxy primer and 2 coats of bitumen paint. | |||
1191 | 120 | Test Certificates :Hydraulic test, and radiographic test as per standards and as per rules and regulation of Chief controller of Explosive Dept To be Furnished. | |||
1192 | 120.1 | Diesel transfer Pumping control system having Solenoid valve control & instrumentation with level sensor, indicating and control instrument, valve and accessories | |||
1193 | 120.2 | Capacity :30 KL | 1 | Unit | |
1194 | 120.3 | TRANSFER PUMP: | |||
1195 | 120.4 | Supply, Transportation, Insurance, Unloading at site, decanting, installation & commissioning of HSD Unloading pump of approved type and make of centrifugal pump capacity of 6 cum/hr. against head of 20 Mtrs approx. to work on 3 Phase 415 V 50 cycles with necessary suction and discharge piping with valve cum strainer, non return valve flame proof motor, flame proof starter suitable for outdoor installation, suction and delivery outlets, companion flange nuts, bolts, gaskets etc. complete. Rate quoted shall include for foundation bolts, motor guard, flame proof glands, terminations for starters and motors, adequate size cable from starter to motors. and earthing inside the yard MS supports as necessary for pump installation. Pumps are as per DIN 24255/ ISO 2858 /API 610 | |||
1196 | 120.5 | Type Centrifugal pumps/positive suction (screwed type) | |||
1197 | 120.6 | Capacity flow :4CMH | |||
1198 | 120.7 | Total Head : 20MWC | |||
1199 | 120.8 | Speed RPM :2990 | |||
1200 | 120.9 | Shaft EN9/SS304 | |||
1201 | 121 | Casing :CI | |||
1202 | 121.1 | Impeller :CS /CI | |||
1203 | 121.2 | Coupling :DIRECT | |||
1204 | 121.3 | Gland : MECHANICAL SEAL | |||
1205 | 121.4 | Base Frame with FRP coating To be provided | |||
1206 | 121.5 | Qty 1W+ 1 Stand by-1 SET | |||
1207 | 121.6 | Make :Rotomech pump with Kirloskar / cromptron/ABB | 1 | Unit | |
1208 | 121.7 | In the Inlet Y strainer Filter (500 microns) is to be provided | |||
1209 | 121.8 | ELECTRICAL CONTROL PANEL | |||
1210 | 121.9 | Supplying, installing, testing and commissioning of flame proof starter panel for HSD unloading and transfer pumps. | 1 | Unit | |
1211 | 122 | PIPING | |||
1212 | 122.1 | DIESEL piping carried out of out of MS class 'C' pipes as per IS 1239 of latest version for sizes wall thickness for pipes 150-mm and as per IS 3589 with 6.25-mm for above 200-mm size with seamless fittings as per technical specifications and standard The works shall include the standard pipe fitting like equal tee, unequal tee, reducer, elbow, bend etc,all inclusive all necessary SECONDARY supports, painting & banding as per specifications. ALL JOINTS ARE TO BE WELDED For both indoor and outdoor Over head and under ground pipes Make: TATA/JINDAL/Equivalent | |||
1213 | 122.2 | 40 mm NB | 150 | Rmt | |
1214 | 122.3 | 25mm NB | 20 | Rmt | |
1215 | 122.4 | 50 mm NB | 20 | Rmt | |
1216 | 122.5 | 80 mmNB | 10 | Rmt | |
1217 | 122.6 | Cast Steel BALL valves with flanged fasteners, support arrangement as per specifications of sizes and quantities as detailed below: The rate quoted shall include for providing flange with necessary gaskets, nuts, bolts, washers, etc | |||
1218 | 122.7 | 40 mm NB AUDCO /ANIL/FLOCON /ADVANCE MAKE | 14 | Nos | |
1219 | 122.8 | 40 mm NB Cast STEEL Non Return VALVE | 2 | Nos | |
1220 | 122.9 | 50 mm NB AUDCO /ANIL/FLOCON /ADVANCE MAKE | 2 | Nos | |
1221 | 123 | 80 mm NB AUDCO /ANIL/FLOCON /ADVANCE MAKE | 1 | Nos | |
1222 | 123.1 | Flanged end size 40 NB BUCKET TYPE strainer stain less steel mesh of size 300Micron strainer body made out of hot tipped Galvanized /CI Flanged connection Cl 150 ANSI | 2 | Nos | |
1223 | 123.2 | Flanged end size 80 NB BUCKET TYPE strainer stain less steel mesh of size 300Micron strainer body made out of hot tipped Galvanized /CI Flanged connection Cl 150 ANSI | 1 | Nos | |
1224 | 123.3 | FLEXIBLE UNLOADING HOSE :Supply of Neoprene hose as per BS 1435/1968 suitable for diesel oil including fitting of one end flanged and other end with suitable coupler. (Decanting Hose) a) 80 mm dia. X3 Mtrs long | 1 | Nos | |
1225 | 123.4 | FIRE EXTINGUISHERS | |||
1226 | 123.5 | Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity. MECHANICAL FOAM TYPE - 9 LTRS Mechanical foam type fire extinguisher of 9 Ltrs. Capacity, with initial filling in brand new cylinder with powder coated finish fitted with Gun metal union, discharge hose, complete, confirming to IS code. | 3 | Nos | |
1227 | 123.6 | SAND FILLED GI BUCKETS -4nos With Holding Stand Made in MS Painted two coates of anticorosive enamel paint over a coat of Red Oxide Primer, with painted safty letter as instructed. | 1 | Unit | |
1228 | 123.7 | Supply, fabrication & fixing pipe supports in M.S angle iron/plates, pipes, etc., as per dwg., instruction at site Rate quotedshall include for supply & providing necessary welding, cutting,U clamps, bolts, nuts, washers as per specification. | 500 | Kg | |
1229 | 123.8 | Supply, fabrication &installation of M.S FENCING using chainlink 10cm x 10cm using M.S angle /channel/Wire Mesh for hieght of 2.50 mtrs hieght. Quoted rate shall include for supply & providing necessary welding, cutting,clamps, bolts, nuts, washers , civil works with concrete for fundation support for fencing post members inculding painting the fence & angle with two coats of anti corosive paint over one coat of Red oxide primer and necesarry gate opening arrangment as instructed and as per specification to meet the norms as per CCOE and other statutory rules and regulations. | 78 | Rmt | |
1230 | 123.9 | Supply, installation, testing & Commissioning of 100mm dia 13mm thick 2500mm long earth electrode as per IS 3043 complete with all works like excavation, refilling with soil treating media like charcoal, salt, Bentanite powder, watering the system etc. equipped with heavy duty top cover madeout of Cast iron or RCC slab meant for Heavy duty 75 ton truck loads. Rate shall be inclusive of testing of earth electrode to acheive combined earth resistance less than 2 Ohms. | 2 | Unit | |
1231 | 124 | Flow Meter to suit oil flow measurement with internal contact, parts made out of stainless steel and compatable system | |||
1232 | 124.1 | 50 mm NB | 1 | Nos | |
1233 | 124.2 | TRANSFER & LEVEL CONTROL SYSTEM DIESEL TRANSFER PUMPING CONTROL SYSTEM -SOLENOID VALVE Control For the below said control, instrumentation with level sensor, indicating and control instrument, valve and accessories are to installed with necessary electrical cabling work upto HSD storage pump house to start/stop the supply pump. 1) When the tank level reaches high , feed incoming valve gets closed & LAH starts. 2) When tank level reaches low, LAL starts & discharge pump stops. 3) When level reaches high -high >80% of volume of tank -LAHH starts. | 1 | Nos | |
1234 | 124.3 | Supply and fixing of the Digitial level indiciator with RS485 Port for the under ground stroage lank with necessary matching flanges. | 1 | Nos | |
1235 | 124.4 | MISCELLANEOUS ITEMS : | |||
1236 | 124.5 | Construction of HSD Tank for the size of (7.5m x 4.5m x 4m) including of excavation, filling, pcc, rcc, formwork, reinforcement and all the necessary civil works | 1 | Unit | |
1237 | 124.6 | Construction of DG set Exhaust Stack foundation for the size of (3m x 3m x 2m) including of excavation, filling, pcc, rcc, formwork, reinforcement and all the necessary civil works | 1 | Unit | |
1238 | 124.7 | LIGHTNING ARRESTOR FOR MAIN BUILDING, UTILITY BUILDING, AND FOOD COURT: | |||
1239 | 124.8 | MAIN BUILDING LIGHTNING ARRESTER : | |||
1240 | 124.9 | Air Terminal :\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU I (5450 08 6) | 420 | Mtr | |
1241 | 125 | Supply & Installation off Roof conductor holder for parapet- Polyamide Conductor holder:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance OBO Type No. 177 30 M8(5207 46 0 ) | 330 | Nos | |
1242 | 125.1 | Supply & Installation of Polyamide roof cable holder for flat roof:DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance. OBO Type No. 165 MBG 8-10 ( 5218 70 0) | 90 | Nos | |
1243 | 125.2 | Supply & Installation of cross universal connector: For T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . OBO Type No.251 8-10 ( 5312 03 5 ) | 50 | Nos | |
1244 | 125.3 | Supply & Installation of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. OBO Type No. 172 AR ( 5218 92 6 ) | 15 | Nos | |
1245 | 125.4 | Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ). OBO Type No. 249 8-10 ST ( 5311 50 0 ) | 30 | Nos | |
1246 | 125.5 | Supply & Installation of vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod :\nMeets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202).\nMeets the requirement of VDE0185/305(IS/IEC 62305) \n4Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. OBO Type No. 101 VL 4000 (5401 99 5). | 13 | Nos | |
1247 | 125.6 | Supply & Installation of Accessories : System consist of Fang Fix with base and clamp, on the top air terminal is erected. OBO Type No. F-FIX 16 ( 5403 20 0 ). | 13 | Nos | |
1248 | 125.7 | Supply & Installation of Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform.16 KG stone of 365 mm diameter, high level of stability.Quick and easy mounting of interception rod using anchors.Concrete, frost-resistant, can be stacked.OBO Type No. F-FIX S16 I (5450 08 0) | 26 | Nos | |
1249 | 125.8 | Periphery Ring :\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU I (5450 08 6) | 1000 | Mtr | |
1250 | 125.9 | Supply & Installation of conductor holder for concrte slab- Polyamide Conductor holder:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance OBO Type No. 177 30 M8(5207 46 0 ) | 1000 | Nos | |
1251 | 126 | Supply & Installation of cross universal connector: \nFor T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . OBO Type No.251 8-10 ( 5312 03 5 ) | 120 | Nos | |
1252 | 126.1 | Down Conductor:\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU (5021 28 6 ) | 2100 | Mtr | |
1253 | 126.2 | Supply & Installation of conductor holder inside façade as specified in drawing . Bottom section stainless steel(V2A) with 8.5 mm slot made of conductor holder of stainless steel (V2A with @ 1 meter distance OBO Type No. 159 K VA | 2100 | Nos | |
1254 | 126.3 | Supply & Installation of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer OBO Type No. 271 8-10 ( 5317 40 1 ) | 20 | Nos | |
1255 | 126.4 | Supply & Installation of Enclosure for Test joint: RoHS Complied, IP66, 6mm², 500V, IK08, UV resistant, Halogen free Thermoplastic junction box ,installation of cables either directly through the 7 x M25 seals, polypropylene,Light grey.\nOverall Dimensions: 114mm X 114mm X57mm, Internal Dimensions: 100mm X 100mm X 48mm OBO TYPE : T 60 (2007 061) | 20 | Nos | |
1256 | 126.5 | Supply & Installation of Lightnig counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. OBO Type No. LSC I+II ( 5091 72 2 ) | 1 | Nos | |
1257 | 126.6 | Earthing :\nSupply & Installation of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm square\nAccording to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx:70 micron coating) Should be tested and used exclusively for lightning protection earthing system and ring equipotential bonding. OBO Type No. 5052 DIN 30X3 ( 5019 34 4 ) | 280 | Mtr | |
1258 | 126.7 | Supply & Installation of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. OBO Type No. 255 FL30 FT (5314 53 4 ) | 45 | Nos | |
1259 | 126.8 | Supply & Installation of flat conductor holder suitable for FL 30. Installed with 2 hexagonal bolts.OBO Type No. 166 LS 70 (5226570) | 20 | Nos | |
1260 | 126.9 | Supply & Installation of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabricOBO Type No.356 50 ( 2360 05 5 ) | 2 | Nos | |
1261 | 127 | Supply & Installation of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER) | 20 | Nos | |
1262 | 127.1 | Supply & Installation of universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . | 20 | Nos | |
1263 | 127.2 | Supply & Installation of Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . | 20 | Nos | |
1264 | 127.3 | Supply & Installation of The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system (OBO Type No.UFE) . | 20 | Nos | |
1265 | 127.4 | UTILITY BUILDING BUILDING LIGHTNING ARRESTER : | |||
1266 | 127.5 | Air Terminal :\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU I (5450 08 6) | 425 | Mtr | |
1267 | 127.6 | Supply & Installation off Roof conductor holder for parapet- Polyamide Conductor holder:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance OBO Type No. 177 30 M8(5207 46 0 ) | 200 | Nos | |
1268 | 127.7 | Supply & Installation of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance.OBO Type No. 165 MBG 8-10 ( 5218 70 0) | 225 | Nos | |
1269 | 127.8 | Supply & Installation of cross universal connector: For T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts. OBO Type No.251 8-10 ( 5312 03 5 ) | 55 | Nos | |
1270 | 127.9 | Supply & Installation of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. OBO Type No. 172 AR ( 5218 92 6 ) | 13 | Nos | |
1271 | 128 | Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ). OBO Type No. 249 8-10 ST ( 5311 50 0 ) | 26 | Nos | |
1272 | 128.1 | VSupply & Installation of ertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod :\nMeets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202).\nMeets the requirement of VDE0185/305(IS/IEC 62305) 4Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. OBO Type No. 101 VL 4000 ( 5401 99 5 ). | 6 | Nos | |
1273 | 128.2 | Supply & Installation of Vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod :\nMeets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202).\nMeets the requirement of VDE0185/305(IS/IEC 62305) \n4Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. OBO Type No. 101 VL 2000 ( 5401 98 3 ). | 2 | Nos | |
1274 | 128.3 | Supply & Installation of Accessories : System consist of Fang Fix with base and clamp, on the top air terminal is erected. OBO Type No. F-FIX 16 ( 5403 20 0 ). | 8 | Nos | |
1275 | 128.4 | Supply & Installation of Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform.16 KG stone of 365 mm diameter, high level of stability.Quick and easy mounting of interception rod using anchors.Concrete, frost-resistant, can be stacked.OBO Type No. F-FIX S16 I ( 5450 08 0 ) | 16 | Nos | |
1276 | 128.5 | Down Conductor:\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU (5021 28 6 ) | 260 | Mtr | |
1277 | 128.6 | Supply & Installation of conductor holder for Sidewall- Polyamide Conductor holder:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance OBO Type No. 177 30 M8(5207 46 0 ) | 260 | Nos | |
1278 | 128.7 | Supply & Installation of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer OBO Type No. 271 8-10 ( 5317 40 1 ) | 14 | Nos | |
1279 | 128.8 | Supply & Installation of Enclosure for Test joint: RoHS Complied, IP66, 6mm², 500V, IK08, UV resistant, Halogen free Thermoplastic junction box ,installation of cables either directly through the 7 x M25 seals, polypropylene,Light grey.\nOverall Dimensions: 114mm X 114mm X57mm, Internal Dimensions: 100mm X 100mm X 48mm OBO TYPE : T 60 (2007 061) | 14 | Nos | |
1280 | 128.9 | Supply & Installation of Lightnig counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. OBO Type No. LSC I+II ( 5091 72 2 ) | 1 | Nos | |
1281 | 129 | Earthing :\nSupply & Installation of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm square\nAccording to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx:70 micron coating) Should be tested and used exclusively for lightning protection earthing system and ring equipotential bonding. OBO Type No. 5052 DIN 30X3 ( 5019 34 4 ) | 225 | Mtr | |
1282 | 129.1 | Supply & Installation of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. OBO Type No. 255 FL30 FT (5314 53 4 ) | 30 | Nos | |
1283 | 129.2 | Supply & Installation of flat conductor holder suitable for FL 30. Installed with 2 hexagonal bolts.OBO Type No. 166 LS 70 (5226570) | 14 | Nos | |
1284 | 129.3 | Supply & Installation of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric.OBO Type No.356 50 ( 2360 05 5) | 2 | Nos | |
1285 | 129.4 | Supply & Installation of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER) | 14 | Nos | |
1286 | 129.5 | Supply & Installation of universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . | 14 | Nos | |
1287 | 129.6 | Supply & Installation of Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . | 14 | Nos | |
1288 | 129.7 | Supply & Installation of The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system (OBO Type No.UFE) . | 14 | Nos | |
1289 | 129.8 | FOOD COURT BUILDING LIGHTNING ARRESTER : | |||
1290 | 129.9 | Air Terminal :\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU I (5450 08 6) | 435 | Mtr | |
1291 | 130 | Supply & Installation off Roof conductor holder for parapet- Polyamide Conductor holder:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance OBO Type No. 177 30 M8(5207 46 0 ) | 290 | Nos | |
1292 | 130.1 | Supply & Installation of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance. OBO Type No. 165 MBG 8-10 ( 5218 70 0) | 145 | Nos | |
1293 | 130.2 | Supply & Installation of cross universal connector: For T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . OBO Type No.251 8-10 ( 5312 03 5 ) | 55 | Nos | |
1294 | 130.3 | Supply & Installation of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. OBO Type No. 172 AR ( 5218 92 6 ) | 11 | Nos | |
1295 | 130.4 | Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ). OBO Type No. 249 8-10 ST ( 5311 50 0 ) | 22 | Nos | |
1296 | 130.5 | VSupply & Installation of ertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod :\nMeets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202).\nMeets the requirement of VDE0185/305(IS/IEC 62305) 4Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. OBO Type No. 101 VL 4000 ( 5401 99 5 ). | 2 | Nos | |
1297 | 130.6 | Supply & Installation of Vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod :\nMeets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202).\nMeets the requirement of VDE0185/305(IS/IEC 62305) 4Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. OBO Type No. 101 VL 2000 ( 5401 98 3 ). | 2 | Nos | |
1298 | 130.7 | Supply & Installation of Accessories : System consist of Fang Fix with base and clamp, on the top air terminal is erected. OBO Type No. F-FIX 16 ( 5403 20 0 ). | 4 | Nos | |
1299 | 130.8 | Supply & Installation of Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform.16 KG stone of 365 mm diameter, high level of stability.Quick and easy mounting of interception rod using anchors.Concrete, frost-resistant, can be stacked.OBO Type No. F-FIX S16 I ( 5450 08 0 ) | 8 | Nos | |
1300 | 130.9 | Down Conductor:\nSupply & Installation of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No. RD 8/ALU (5021 28 6 ) | 200 | Mtr | |
1301 | 131 | Supply & Installation of conductor holder for Sidewall- Polyamide Conductor holder:\nWith M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.\nWeather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance OBO Type No. 177 30 M8(5207 46 0 ) | 200 | Nos | |
1302 | 131.1 | Supply & Installation of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer OBO Type No. 271 8-10 ( 5317 40 1 ) | 12 | Nos | |
1303 | 131.2 | Supply & Installation of Enclosure for Test joint: RoHS Complied, IP66, 6mm², 500V, IK08, UV resistant, Halogen free Thermoplastic junction box ,installation of cables either directly through the 7 x M25 seals, polypropylene,Light grey.\nOverall Dimensions: 114mm X 114mm X57mm, Internal Dimensions: 100mm X 100mm X 48mm OBO TYPE : T 60 (2007 061) | 12 | Nos | |
1304 | 131.3 | Supply & Installation of Lightnig counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. OBO Type No. LSC I+II ( 5091 72 2 ) | 1 | Nos | |
1305 | 131.4 | Earthing :\nSupply & Installation of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm square\nAccording to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx:70 micron coating) Should be tested and used exclusively for lightning protection earthing system and ring equipotential bonding. OBO Type No. 5052 DIN 30X3 ( 5019 34 4 ) | 230 | Mtr | |
1306 | 131.5 | Supply & Installation of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. OBO Type No. 255 FL30 FT (5314 53 4 ) | 25 | Nos | |
1307 | 131.6 | Supply & Installation of flat conductor holder suitable for FL 30. Installed with 2 hexagonal bolts.OBO Type No. 166 LS 70 (5226570) | 12 | Nos | |
1308 | 131.7 | Supply & Installation of Plastic Corrosion Protection strip: Approx 1.1mm thick. Width 50mm. Made of petrolatum-coated chemical fibre fabric.OBO Type No.356 50 ( 2360 05 5 ) | 2 | Nos | |
1309 | 131.8 | Supply & Installation of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER) | 12 | Nos | |
1310 | 131.9 | Supply & Installation of universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . | 12 | Nos | |
1311 | 132 | Supply & Installation of Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . | 12 | Nos | |
1312 | 132.1 | Supply & Installation of The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system (OBO Type No.UFE) . | 12 | Nos | |
1313 | 132.2 | Fire Protection System (FPS) Works | |||
1314 | 132.3 | FPS - MAIN BUILDING\nPUMP HOUSE EQUIPMENTS | |||
1315 | 132.4 | Supply, installation, testing and commissioning of Diesel Engine driven fire pump suitable for automatic operation. Horizontal, high pressure multistage, multi outlet, centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and SS (304) shaft with mechanical seal, capable for delivering 2850LP Matlowzone outlet head of 145.0mts medium zone outlet head of 185.0 m to ensure a minimum pressure of 3.5 Kg/Sq cm at the farthest or topmost hydrant / sprinkler. Along with control panel and interlocking facility with main fire panel and fire alarm panel. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side (The pump should be tested for bench mark at factory and shall be gotten approved by the Local fire Authority). Heat exchanger cooled (secondary cooling) diesel engine of speed 1500 RPM suitable for the above pump with automatic starting mechanism and other accessories including fuel tank (fabricated from 3mm MS sheet, painted with two coats of synthetic enamel paint over a coat of primer) of capacity adequate to sustain pump operation for 8 hours continuous working. The tank shall be fitted with Magnetic oil level indicator, MH with cover, drain valve, air vent including structural supports (painted with approved shade), 2 Nos. x 12 volt battery, heat exchanger with necessary piping connections & fittings, flexible coupling, coupling guard & exhaust pipe connection complete as required.Common bed plate for mounting Pump and Motor fabricated of Motor fabricated of suitable M.S. Channel as per manufacturer's recommendations.Suitable Pump-Foundations as per manufacturer's design and 4 nos. Dunlop (cushy foot) heavy duty Anti vibration mounting pads. | 1 | Unit | |
1316 | 132.5 | Supply, installation, testing and commissioning of electrically driven high pressure multistage, multioutlet, centrifugal fire hydrant / sprinkler pump, suitable for automatic operation consisting of the following:\nHorizontal, / vertical high pressure multistage, multioutlet, centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and S.S. (304) Shaft with mechanical seal, capable for delivering 2850 LPM at low zone outlet head of 145.0 mts, medium zone outlet head of 185.0 m to ensure a minimum pressure of 3.5 Kg/Sqcm at the farthest or topmost hydrant / sprinkler. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side. (The pump should be tested for bench mark at factory and shall be get approved by the Local fire Authority). Squirrel cage induction motor totally enclosed fan cooled type suitable for 415 Volts ± 15%, 3 phase, 50 HZ A.C. supply of suitable for the above pump with synchronous speed of 2900 RPM conforming to IP55 protection and class insulation with flexible coupling and coupling guard including earthling as per relevant Indian Standard &specifications. conforming to IS: 325 Common bed plate for mounting Pump and Motor fabricated of Motor fabricated of suitable M.S. Channel as per manufacturer's recommendations. Suitable Pump-Foundations as per manufacturer's design and 4 nos. Dunlop (cushy foot) heavy duty Anti vibration mounting pads. | 2 | Unit | |
1317 | 132.6 | Supply, Installations, Testing & Commissioning of Electrical Motor Driven Automatic pressurisation (Jockey) pumping set consisting of the following as per specifications. Horizontally /Vertical mounted centrifugal type multi-stage multi outlet fire pump for building pressure loss due to any leakage in the system and capable to deliver approx 180 LPM against a total head of 185 M confirming to IS:1520., having cast iron body, bronze impeller, stainless steel shaft and complete with Pressure Gauge with G.M. stop valve etc. on the delivery side including bypass arrangement (with25mmdia.G.M.StopValve and upto5 M.G.I. medium pipe) for periodical testing of the working of the pumping set. Squirrel cage induction motor totally enclosed fan cooled type suitable for 415 Volts ± 15% 3 phase. 50 hz A.C. supply of suitable for the above pump with synchronous speed of 1500/3000 RPM confirming to IS: 325 & duly coupled with above pump coupled with flexible coupling including earthling as per relevant Indian Standardand specifications. Common bed plate for mounting pump and motor fabricated of suitable M.S. channel as per manufacturer's recommendations. Pump foundations as per manufacturer ' s design and required numbers of Dunlop Anti-vibration (cushy foot) heavy duty mounting pads. | 2 | Unit | |
1318 | 132.7 | Supply, Installation, Testing and Commissioning of C.I. body, EPDM seat, SGI disc, Gate valve OS&Y PN 25, | |||
1319 | 132.8 | 300 mm NB. | 2 | Nos | |
1320 | 132.9 | 250 mm NB. | 4 | Nos | |
1321 | 133 | 200 mm NB. | 6 | Nos | |
1322 | 133.1 | 150 mm NB. | 6 | Nos | |
1323 | 133.2 | 65 mm NB. | 14 | Nos | |
1324 | 133.3 | Supply, Installation, Testing and Commissioning of Swing type check valve flanged end PN25 CS boby conforming to ANSI B 16.5 Vertical installation. | |||
1325 | 133.4 | 250 mm NB | 2 | Nos | |
1326 | 133.5 | 200 mm NB | 2 | Nos | |
1327 | 133.6 | 150 mm NB. | 5 | Nos | |
1328 | 133.7 | 100 mm NB. | 5 | Nos | |
1329 | 133.8 | Supply, Installation, Testing and Commissioning of gunmetal gate valve having screwed ends as per specification with necessary flanges, nut, bolts & washers, etc. complete as required conforming to IS 778. | |||
1330 | 133.9 | 32 mm NB Gate valve | 12 | Nos | |
1331 | 134 | 25 mm NB Gate valve | 26 | Nos | |
1332 | 134.1 | Supply, Installation, Testing and Commissioning of C.I body & cover, SS304 strainer & carbon steel bolts & nuts. - Pot type Strainer. | |||
1333 | 134.2 | 300 mm NB. | 2 | Nos | |
1334 | 134.3 | Supply, installation, testing & commissioning of approved make Flexible connections (SS) at Pump Inlet & pump Outlet side with flange PN 25 | |||
1335 | 134.4 | 250 mmNB | 3 | Nos | |
1336 | 134.5 | 200 mm NB | 6 | Nos | |
1337 | 134.6 | 100 mm NB | 4 | Nos | |
1338 | 134.7 | Supply, Installation, Testing and Commissioning of above ground piping carried out of MS class C Heavy Duty pipe as per IS: 1239 for pipes up to 150mm NB and as per IS : 3589 with a wall thickness of 6.35mm for pipes 200mm NB and above together with fittings, valves and accessories as under: | |||
1339 | 134.8 | Work will include painting for the above ground piping with one coat of primer and two coat of enamel paint of approved colour. Work will include cleaning of pipe, degreasing, etc. | |||
1340 | 134.9 | 300 mm NB Pipes. | 15 | Rmt | |
1341 | 135 | 250 mm NB Pipes. | 20 | Rmt | |
1342 | 135.1 | 200 mm NB Pipes. | 63 | Rmt | |
1343 | 135.2 | 80 mm NB Pipes. | 55 | Rmt | |
1344 | 135.3 | 25 mm NB Pipes. | 57 | Rmt | |
1345 | 135.4 | Supply, Installation, Testing and Commissioning of Dial type pressure guage with 150mm dial and a range of 0-10 Kg./sq.cm. together with siphon and pet cock. | 61 | Nos | |
1346 | 135.5 | Supply, Installation, Testing and Commissioning of pressure switches together with accessories. | 10 | Nos | |
1347 | 135.6 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. | 2 | Unit | |
1348 | 135.7 | Supply, Installation, Testing and Commissioning of Autostart IP55 panel for the Diesel engine complete auto/ manual switch, indication lamps protective fuses Battery charger with transformer with rectifier resistance DC ammeter, DC voltmeter, Trickle / booster / off selector switch - 2 Nos., suitable of working on 230 V, AC, single phase, enclosure being vermin & dust proof. | 1 | Unit | |
1349 | 135.8 | a) 20Amps DPMCB - 2 Nos. | |||
1350 | 135.9 | b) Battery charger with transformer with rectifier resistance DC ammeter, DC voltmeter, Trickle / booster / off selector switch - 2 Nos. | |||
1351 | 136 | c) 1 set of indicating lamps for the following : | |||
1352 | 136.1 | 1. phase indication | |||
1353 | 136.2 | 2. battery charger on | |||
1354 | 136.3 | 3. over load relay | |||
1355 | 136.4 | 4. DC supply on | |||
1356 | 136.5 | 5. control switch on | |||
1357 | 136.6 | 6. Engine fails to start | |||
1358 | 136.7 | 7. Pump on | |||
1359 | 136.8 | 8. Low oil pressure | |||
1360 | 136.9 | 9. High water temperature | |||
1361 | 137 | 10. Auto manual selector switch | |||
1362 | 137.1 | d) 1 sets of push button stations for the following : | |||
1363 | 137.2 | 1. Engine Start | |||
1364 | 137.3 | 2. Engine Stop | |||
1365 | 137.4 | 3. Engine - hooter ACK | |||
1366 | 137.5 | 4. Engine - fault reset | |||
1367 | 137.6 | e) Selector switches (Engine control, mode selector)-1 No. | |||
1368 | 137.7 | f) Auxilary relays / contactors / timer for sequence operating for starting and stopping of the engine - 1 set. | |||
1369 | 137.8 | g) Hooter for audio alarm (Industrial type) - 1 No. | |||
1370 | 137.9 | Supply, Installation, Testing and Commissioning of Sheet steel fabricated cubicle type, MCC with Star-Delta starter IP55 panel for the electrical motor driven pumpset, DOL starter for Jockey pumpset complete with isolator switch, voltmeter, ammeter manual / auto mode switch, indicating lamps etc., Potential free contacts pumps, for third party integeration for Fire alarm system, BMS, etc., for identifying the on/off status, trip status for all pumps and lube oil level status for diesel driven pump. | 1 | Unit | |
1371 | 138 | INCOMING: 2Nos, 800ATP&N 25KA MCCB, 800A TP&N copper Busbars with colour coded heat shrinkable PVC sleeves. 1 Set of RYB indicating lamps with individual HRC control fuses. 1 Nos. 96 sq.mm, 0-630 Amps, Ammeter with selector switch and suitable rated current transformers. 1 Nos. 0-800A 96sq.mm, Voltmeter with selector switch | |||
1372 | 138.1 | Incomer shall be with mechanical interlock with 2 lock & 1 Key | |||
1373 | 138.2 | OUTGOING: Feeder for main pumps - 2nos. 400 A TP&N 25KA MCCB and Soft starter with overload relay, single phase preventor and indicating lamps with ON/OFF push buttons. | |||
1374 | 138.3 | Feeder for Jokey Pump - 2nos 63A 25 KA TP&N MCCB without releases Soft starter with over load relay, single phase preventor and indicating lamps with ON/OFF push buttons, 1 No . Automanual selector switch. | |||
1375 | 138.4 | 1no Dummy provision. | |||
1376 | 138.5 | 2no 16A TP MCCB for battery charger and control panel. | |||
1377 | 138.6 | Supply, Installation, Testing and Commissioning of PVC insulated, XLPE, aluminium conductor, 1.1 KV grade armoured, MV cable of the following sizes as required, generally conforming to IS:1554/Part-I/1970 | |||
1378 | 138.7 | 2R 3 1/2 X 150 sqmm | 90 | Rmt | |
1379 | 138.8 | 1R 4C X 25 sqmm | 24 | Rmt | |
1380 | 138.9 | 12 C X 2.5 sqmm copper aromoured cable for Diesel engines. | 43 | Rmt | |
1381 | 139 | 2 C X 2.5 sqmm copper aromoured cable for instrumentation | 85 | Rmt | |
1382 | 139.1 | Supply, Installation, Testing and Commissioning of cable end termination with brass compression gland and Aluminium lugs for the following sizes of PVC Insulated XLPE Aluminium armoured conductor cable of 1.1KV grade complete as required.. | |||
1383 | 139.2 | 2R 3 1/2 X 150 sqmm | 8 | Unit | |
1384 | 139.3 | 1R 4C X 25 sqmm | 1 | Unit | |
1385 | 139.4 | 12 C X 2.5 sqmm copper aromoured cable for Diesel engines. | 1 | Unit | |
1386 | 139.5 | 2 C X 2.5 sqmm copper aromoured cable for instrumentation | 19 | Unit | |
1387 | 139.6 | Providing and fixing 25 mm x 3 mm copper strip on surface or in recess for connections etc. as required. | 35 | Rmt | |
1388 | 139.7 | Providing and fixing following sizes of copper wire on surface or in recess for connections etc. as required. | |||
1389 | 139.8 | 8 SWG Copper | 40 | Rmt | |
1390 | 139.9 | Supply, Installation, Testing and Commissioning of perforated G.I.sheet cable tray with neccessory angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500 mm.Size of the tray shall be as mentioned below for laying the above mentioned cables. | |||
1391 | 140 | 300mm | 30 | Rmt | |
1392 | 140.1 | 150mm | 25 | Rmt | |
1393 | 140.2 | Supply, Installation, Testing and Commissioning of diesel pump exhaust, 100mm Dia MS pipe with residential type silencer, mineral wool thermal insulation and 24G aluminium cladding, with necessary supports, clamps, bolts, nuts, etc., | 25 | Rmt | |
1394 | 140.3 | Supply and Erection Structural Supports like MS Angle / Channel / 'U' clamps, etc., for pump room | 1300 | Kgs | |
1395 | 140.4 | Supply, Installation, Testing and Commissioning of 16 Zone sprinkler anunciator panel with Touch key pad, 20 X 4 Charater LCD Display, Inbuild RS-485 Communiction card can connect Max. 16 panels in a single network communication, Peer to Peer network through RS-485 communication.with 12V, 7AH Battery- 2nos. | 4 | Nos | |
1396 | 140.5 | HYDRANT | |||
1397 | 140.6 | Supply, Installation, Testing and Commissioning of MS class C Heavy duty pipe as per IS : 1239 for pipes up to 150mm NB and as per IS : 3589 for above 150mm with a wall thickness of 6 mm for pipes 200mm NB and above together with fittings, valves and accessories as under: | |||
1398 | 140.7 | Work will include painting for the external below ground piping with all necessary fittings including weather proof protection with bitumatic paint and tape(4mm) before adhering the tape to the pipe, it is advisable to gently heat the synthetic primer coated pipe by a run of LPG torch until the wrapper gets blend with the pipe, tape is wrapped by spiral method over the pipe, the thickness of overlapped wrapping must be not less than 10mm thick in pipes and in joints wrapiing thickness must be not less than 40mm Work will include cleaning of pipe, degreasing, excavatio of soil 1.5mtr below the ground or as shown in the dwg and to backfill with river sand the excavated soil. etc. | |||
1399 | 140.8 | 150 mm NB | 870 | Rmt | |
1400 | 140.9 | 100 mm NB | 306 | Rmt | |
1401 | 141 | 80 mm NB | 45 | Rmt | |
1402 | 141.1 | Work will include painting for the above ground piping with one coat of primer and two coat of enamel paint of approved colour. Work will include cleaning of pipe, degreasing, necessary supports, clamps, bolts, nuts,etc. Headers shall be worded indicating the direction of the pipe and its purpose. | |||
1403 | 141.2 | 150 mm NB | 592 | Rmt | |
1404 | 141.3 | 80 mm NB | 45 | Rmt | |
1405 | 141.4 | 25 mm NB | 60 | Rmt | |
1406 | 141.5 | Supply, Installation, Testing and Commissioning of C.I. body, EPDM seat, SGI disc, Butterfly valve PN 25, SGI Hand lever operated, wafer ends conforming to BS:5155. | |||
1407 | 141.6 | 150 mm NB. | 3 | Nos | |
1408 | 141.7 | 100 mm NB. | 6 | Nos | |
1409 | 141.8 | Supply, Installation, Testing and Commissioning of gunmetal gate valve having screwed ends as per specification with necessary flanges, nut, bolts & washers, etc. complete as required conforming to IS 778. | |||
1410 | 141.9 | 25 mm NB Gate valve | 46 | Nos | |
1411 | 142 | Supply and installation of RCC Hume pipes of 300 mm dia with collars for road / below floor crossing of Fire water pipes as per IS 458. The rate shall includes excavation, soil levelling for bed and ends shall be closed with Brick masonry work as directed by site engineer. | 200 | Rmt | |
1412 | 142.1 | Supply, Installation, Testing and Commissioning of Air Release Valve with Ball Valve - 25 mm dia to all wet risers all complete. | 16 | Nos | |
1413 | 142.2 | Supply, Installation, Testing and Commissioning of Internal hydrants including landing valve stations hose reels, etc., comprising of the following. | |||
1414 | 142.3 | 63mm dia Twin outlet landing valve as per IS : 5290 together with cap and chain. | 44 | Nos | |
1415 | 142.4 | Hose reel drum assembly with swinging and rolling arrangement together with 19mm dia x 45.0 mtrs. long hose, cnc machined Single rod IS standard Bright Material with Special “O” rings & Grooved Nozzle. and 6.25mm nozzle durable Nylon material, Jet spray & shut by hand revolving., 19mm NB ball valve at tap-off etc., as per IS : 884. | 46 | Nos | |
1416 | 142.5 | 2 nos - 65 mm dia R.R.L Hose of 15 Mtrs. Length, together with heavy GM couplings combined with 2 nos nozzle & branch pipe as per IS2871. | 44 | Nos | |
1417 | 142.6 | Supply, Erection, Testing and Commissioning of MS hose cabinet stand mounted type, fabricated out of M.S sheet of 16 swg, with glass fronted (4mm thick glass with rubber beeding) door and size of the cabinet shall be 900mm x1200 mm x 250 mm, Qouted rate shall be includes suitable stand for mounting as fastners etc., and cabinet shall be powder coated of approved colour both inside and outside. | 46 | Nos | |
1418 | 142.7 | Supply, Installation, Testing and Commissioning of External standpost type Yard hydrants comprising of the following. | |||
1419 | 142.8 | 63mm dia Single hydrant valve as per IS : 5290 together with cap and chain. | 25 | Nos | |
1420 | 142.9 | 2 nos - 65 mm dia R.R.L Hose of 15 Mtrs. Length, together with heavy GM couplings combined with 1 nos nozzle & branch pipe. | 25 | Nos | |
1421 | 143 | Supply, Installation, Testing and Commissioning of MS hose cabinet stand mounted type, fabricated out of M.S sheet of 16 swg, with glass fronted (4mm thick glass with rubber beeding) door and size of the cabinet shall be 600mm x750 mm x 250 mm, Qouted rate shall be includes suitable stand for mounting as fastners etc., and cabinet shall be powder coated of approved colour both inside and outside. | 25 | Nos | |
1422 | 143.1 | Supply, Installation, Testing and Commissioning of Fire brigade inlet siamese connection (4way) manifold in including valves and check valve of size 150mm size along with 4 nos. 63mm dia instantaneous inlet arrangements to the main header with cap and chain etc., for external hydrants.including Buterfly valve with NRV. | 1 | Nos | |
1423 | 143.2 | Supply, Installation, Testing and Commissioning of Fire brigade inlet siamese connection (4way) manifold in including valves and check valve of size 150mm size along with 4 nos. 63mm dia instantaneous inlet arrangements to the main header with cap and chain etc., for fire sump.including Buterfly valve. | 1 | Nos | |
1424 | 143.3 | Supply, Installation, Testing and Commissioning of Fire brigade inlet siamese connection (1way) manifold in including valves of size 100mm size along with 1 no. 63mm dia instantaneous inlet arrangements to the main header with cap and chain etc., for fire sump draw out.including Buterfly valve. | 1 | Nos | |
1425 | 143.4 | Construction of Valve Pits Size of 1000 x 1000 mm outer dimension and to be required. internal dimension as under, upto 1.5 Mtr depth with brick masonry in cement mortor 1:5, with thickness of masonry 225mm, 1:3:6 cement concrete foundation 150mm thick over 150mm sand bed, channelling in 1:2:4 cement concrete, plastering in 1:3 cement mortor for internal and external surface & finished with floating coat of neat cement. Fixing of 600*600 including precasting D.I. manhole heavy duty grade C-250,weight of cover must be 90kg theft proof cover and frame including painting of the frame & cover .The work shall include all necessary excavation and back filling. | 6 | Nos | |
1426 | 143.5 | Supply and Erection Structural Supports like MS Angle / Channels, etc., for Hydrant. | 1500 | Kgs | |
1427 | 143.6 | SPRINKLER SYSTEM | |||
1428 | 143.7 | Supply, Installation, Testing and Commissioning of FM approved & UL listed Control Valve consisting of - 1 no. Alarm valve(Clapper check type, Vertical mount), 1 no. Main stop valve, 1 no. water motor with alarm gong (light weight non metallic material), with strainer, Pressure guage drain valve and proper drain piping etc., as per specification. | |||
1429 | 143.8 | i) 200 mm dia. | 2 | Unit | |
1430 | 143.9 | ii) 150 mm dia. | 2 | Unit | |
1431 | 144 | ii) 100 mm dia. | 1 | Unit | |
1432 | 144.1 | Supply, Installation, Testing and Commissioning of above ground piping carried out of MS class C Heavy duty piping as per IS : 1239 for pipes up to 150mm NB & IS 3589 for above 150mm together with fittings, valves and accessories as under : | |||
1433 | 144.2 | Work will include painting for the above ground piping with one coat of primer and two coat of enamel paint of approved colour. Work will include cleaning of pipe, degreasing, necessary angle supports, clamps, bolts, nuts,etc. | |||
1434 | 144.3 | 200 mm NB | 1063 | Rmt | |
1435 | 144.4 | 150 mm NB | 752 | Rmt | |
1436 | 144.5 | 100 mm NB | 450 | Rmt | |
1437 | 144.6 | 80 mm NB | 78 | Rmt | |
1438 | 144.7 | 65 mm NB | 197 | Rmt | |
1439 | 144.8 | 50 mm NB | 902 | Rmt | |
1440 | 144.9 | 40 mm NB | 599 | Rmt | |
1441 | 145 | 32 mm NB | 60 | Rmt | |
1442 | 145.1 | 25 mm NB | 1075 | Rmt | |
1443 | 145.2 | Supply, Installation, Testing and Commissioning of C.I. Butterfly valve PN 25 Hand lever operated, wafer ends conforming to BS:5155. | |||
1444 | 145.3 | 200 mm NB | 4 | Nos | |
1445 | 145.4 | 150 mm NB | 46 | Nos | |
1446 | 145.5 | 100 mm NB. | 54 | Nos | |
1447 | 145.6 | Supply, installation, testing and commissioning of FM approved make vane type flow switches (flow sensors) suitable to be fixed directly on line of the following diameters, with 1 NO & 1 NC potential free contacts (suitable provision for IBMS system) | |||
1448 | 145.7 | 150mm dia | 44 | Nos | |
1449 | 145.8 | 100mm dia | 1 | Nos | |
1450 | 145.9 | Supply, Installation, Testing and Commissioning of chromium finish, 15mm size Upright / Pendent type sprinkler suitable to operate at 68/79 deg.C temperature(K=80). | 1650 | Nos | |
1451 | 146 | Supply, Installation, Testing and Commissioning of braided SS 304 flexi hose dropper 1.2mtr length with standard support accessories, neat finish, withstand system test and working pressure. | 798 | Nos | |
1452 | 146.1 | Supply, Installation, Testing and Commissioning of Rosette plates for sprinklers at False ceiling level. | 798 | Nos | |
1453 | 146.2 | Supply and Erection Structural Supports like MS Angle / Channels, etc., for sprinkler. | 3800 | Kgs | |
1454 | 146.3 | Supply and installation of hot dip GI puddle flanges, as per IS-1239, fabricated out of 6mm MS Plate, fixed at the RCC walls of the fire tanks & Over head tanks, work includes paiting with 2 coats of primer complete as required, refer tender dwgs for details. | |||
1455 | 146.4 | 300mm Dia GI flange | 2 | Nos | |
1456 | 146.5 | 150mm Dia GI flange | 2 | Nos | |
1457 | 146.6 | 100mm Dia GI flange | 2 | Nos | |
1458 | 146.7 | 50mm Dia GI flange | 4 | Nos | |
1459 | 146.8 | Liasoning work for Obtaining Local Fire Authority NOC/Approvals for complete systyem & miscellaneous work etc. | 1 | Unit | |
1460 | 146.9 | EXTINGUISHER | |||
1461 | 147 | Supply and fixing of Minimax or approved equivalent make ABC 6kg, IS 15683 Gas cartridge type with fire rating 4A 34B. Design, construction and testing as per IS 15683, Body hydro tested at 35bar, operating temperature -30°C to +55°C, external epoxy powder coating with PO shade No 538 of IS 5, supplied with standard accessories. Cylinder must be subjected to Anti-corrosive treatment of 7 tank process. | 140 | Nos | |
1462 | 147.1 | Supply and fixing of Minimax or approved equivalent make 4.5kg CO2 Type Fire Extinguisher with fire rating 21B. Design, construction and testing as per IS 15683, supplied with Body bearing IS 7285 mark, operating temperature -30°C to +55°C, external double PU paint coating with PO shade No 538 of IS 5, Packing 7ply thick corrugated, co2 purity IS 15222, Valve IS 3224, supplied with standard accessories. | 100 | Nos | |
1463 | 147.2 | Supply and Fixing of 50L Mechanical Foam trolly wheeled type 300g gas catridge fitted Fire Extinguisher, design, construction, testing as per IS13386, external expoxy powder coating with red shade no 538 of IS 5 and with standard accessories. | 6 | Nos | |
1464 | 147.3 | SIGNAGES | |||
1465 | 147.4 | Providing and installing in position the following type of sign boards made out of 3mm thick "Opaque" PVC foam board with computer cut, PVC reflective self adhesive vinyle painted foam board, complete with mirror fasteners. | |||
1466 | 147.5 | NOTE: CONTRACTOR BRANDING IS NOT ALLOWED IN THE SIGNAGES. | |||
1467 | 147.6 | Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back ground.The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor near Manual call points. | 164 | Nos | |
1468 | 147.7 | Floor indentification signage ( ie, GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with contrasting colour from back ground.Size shall be 15cm x 60cm. | 44 | Nos | |
1469 | 147.8 | FPS - RETAURANT BUILDING\nHYDRANT | |||
1470 | 147.9 | Work will include painting for the above ground piping with one coat of primer and two coat of enamel paint of approved colour. Work will include cleaning of pipe, degreasing, necessary supports, clamps, bolts, nuts,etc. Headers shall be worded indicating the direction of the pipe and its purpose. | |||
1471 | 148 | 100 mm NB | 270 | Rmt | |
1472 | 148.1 | 25 mm NB | 10 | Rmt | |
1473 | 148.2 | Supply, Installation, Testing and Commissioning of C.I. body, EPDM seat, SGI disc, Butterfly valve PN 25, SGI Hand lever operated, wafer ends conforming to BS:5155. | |||
1474 | 148.3 | 100 mm NB. | 2 | Nos | |
1475 | 148.4 | Supply, Installation, Testing and Commissioning of gunmetal gate valve having screwed ends as per specification with necessary flanges, nut, bolts & washers, etc. complete as required conforming to IS 778. | |||
1476 | 148.5 | 25 mm NB Gate valve | 4 | Nos | |
1477 | 148.6 | Supply and installation of RCC Hume pipes of 300 mm dia with collars for road / below floor crossing of Fire water pipes as per IS 458. The rate shall includes excavation, soil levelling for bed and ends shall be closed with Brick masonry work as directed by site engineer. | 30 | Rmt | |
1478 | 148.7 | Supply, Installation, Testing and Commissioning of Air Release Valve with Ball Valve - 25 mm dia to all wet risers all complete. | 4 | Nos | |
1479 | 148.8 | Supply, Installation, Testing and Commissioning of Internal hydrants including landing valve stations hose reels, etc., comprising of the following. | |||
1480 | 148.9 | 63mm dia Single hydrant valve as per IS : 5290 together with cap and chain. | 4 | Nos | |
1481 | 149 | Hose reel drum assembly with swinging and rolling arrangement together with 19mm dia x 45.0 mtrs. long hose, cnc machined Single rod IS standard Bright Material with Special “O” rings & Grooved Nozzle. and 6.25mm nozzle durable Nylon material, Jet spray & shut by hand revolving., 19mm NB ball valve at tap-off etc., as per IS : 884. | 4 | Nos | |
1482 | 149.1 | 2 nos - 65 mm dia R.R.L Hose of 15 Mtrs. Length, together with heavy GM couplings combined with 2 nos nozzle & branch pipe as per IS2871. | 4 | Nos | |
1483 | 149.2 | Supply, Erection, Testing and Commissioning of MS hose cabinet stand mounted type, fabricated out of M.S sheet of 16 swg, with glass fronted (4mm thick glass with rubber beeding) door and size of the cabinet shall be 900mm x1200 mm x 250 mm, Qouted rate shall be includes suitable stand for mounting as fastners etc., and cabinet shall be powder coated of approved colour both inside and outside. | 4 | Nos | |
1484 | 149.3 | Pressure reducing valve | |||
1485 | 149.4 | Supply, Installation, Testing and Commissioning of Pressure reducing valve for Yard Hydrant and Restaurant Pressure Rating 14kg/cm2 to 7kg/cm2 150 NB | 3 | Nos | |
1486 | 149.5 | Supply and Erection Structural Supports like MS Angle / Channels, etc., for Hydrant. | 300 | Kgs | |
1487 | 149.6 | SPRINKLER SYSTEM | |||
1488 | 149.7 | Supply, Installation, Testing and Commissioning of FM approved & UL listed Control Valve consisting of - 1 no. Alarm valve(Clapper check type, Vertical mount), 1 no. Main stop valve, 1 no. water motor with alarm gong (light weight non metallic material), with strainer, Pressure guage drain valve and proper drain piping etc., as per specification. | |||
1489 | 149.8 | i) 100 mm dia. | 2 | Nos | |
1490 | 149.9 | Supply, Installation, Testing and Commissioning of above ground piping carried out of MS class C Heavy duty piping as per IS : 1239 for pipes up to 150mm NB & IS 3589 for above 150mm together with fittings, valves and accessories as under : | |||
1491 | 150 | Work will include painting for the above ground piping with one coat of primer and two coat of enamel paint of approved colour. Work will include cleaning of pipe, degreasing, necessary angle supports, clamps, bolts, nuts,etc. | |||
1492 | 150.1 | 100 mm NB | 165 | Rmt | |
1493 | 150.2 | 80 mm NB | 39 | Rmt | |
1494 | 150.3 | 65 mm NB | 48 | Rmt | |
1495 | 150.4 | 50 mm NB | 16 | Rmt | |
1496 | 150.5 | 40 mm NB | 10 | Rmt | |
1497 | 150.6 | 32 mm NB | 12 | Rmt | |
1498 | 150.7 | 25 mm NB | 145 | Rmt | |
1499 | 150.8 | Supply, Installation, Testing and Commissioning of C.I. Butterfly valve PN 25 Hand lever operated, wafer ends conforming to BS:5155. | |||
1500 | 150.9 | 100 mm NB. | 8 | Nos | |
1501 | 151 | 80 mm NB. | 3 | Nos | |
1502 | 151.1 | Supply, installation, testing and commissioning of FM approved make vane type flow switches (flow sensors) suitable to be fixed directly on line of the following diameters, with 1 NO & 1 NC potential free contacts (suitable provision for IBMS system) | |||
1503 | 151.2 | 100mm dia | 5 | Nos | |
1504 | 151.3 | Supply, Installation, Testing and Commissioning of chromium finish, 15mm size Upright / Pendent type sprinkler suitable to operate at 68/79 deg.C temperature(K=80). | 98 | Nos | |
1505 | 151.4 | Supply, Installation, Testing and Commissioning of braided SS 304 flexi hose dropper 1.2mtr length with standard support accessories, neat finish, withstand system test and working pressure. | 49 | Nos | |
1506 | 151.5 | Supply, Installation, Testing and Commissioning of Rosette plates for sprinklers at False ceiling level. | 49 | Nos | |
1507 | 151.6 | Supply and Erection Structural Supports like MS Angle / Channels, etc., for sprinkler. | 300 | Kgs | |
1508 | 151.7 | Supply and installation of hot dip GI puddle flanges, as per IS-1239, fabricated out of 6mm MS Plate, fixed at the RCC walls of the fire tanks & Over head tanks, work includes paiting with 2 coats of primer complete as required, refer tender dwgs for details. | |||
1509 | 151.8 | 100mm Dia GI flange | 1 | Nos | |
1510 | 151.9 | 50mm Dia GI flange | 4 | Nos | |
1511 | 152 | EXTINGUISHER | |||
1512 | 152.1 | Supply and fixing of Minimax or approved equivalent make ABC 6kg, IS 15683 Gas cartridge type with fire rating 4A 34B. Design, construction and testing as per IS 15683, Body hydro tested at 35bar, operating temperature -30°C to +55°C, external epoxy powder coating with PO shade No 538 of IS 5, supplied with standard accessories. Cylinder must be subjected to Anti-corrosive treatment of 7 tank process. | 8 | Nos | |
1513 | 152.2 | Supply and fixing of Minimax or approved equivalent make 4.5kg CO2 Type Fire Extinguisher with fire rating 21B. Design, construction and testing as per IS 15683, supplied with Body bearing IS 7285 mark, operating temperature -30°C to +55°C, external double PU paint coating with PO shade No 538 of IS 5, Packing 7ply thick corrugated, co2 purity IS 15222, Valve IS 3224, supplied with standard accessories. | 8 | Nos | |
1514 | 152.3 | SIGNAGES | |||
1515 | 152.4 | Providing and installing in position the following type of sign boards made out of 3mm thick "Opaque" PVC foam board with computer cut, PVC reflective self adhesive vinyle painted foam board, complete with mirror fasteners. | |||
1516 | 152.5 | NOTE: CONTRACTOR BRANDING IS NOT ALLOWED IN THE SIGNAGES. | |||
1517 | 152.6 | Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back ground.The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor near Manual call points. | 6 | Nos | |
1518 | 152.7 | Floor indentification signage ( ie, GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with contrasting colour from back ground.Size shall be 15cm x 60cm. | 8 | Nos | |
1519 | 152.8 | INTEGRATED BUILDING MANAGEMENT SYSTEM (IBMS) Work | |||
1520 | 152.9 | Fire Alarm System - Main Building\nFire Alarm Control Panel | |||
1521 | 153 | Supply, Installation, Testing & Commissioning of Microprocessor based Intelligent Analog Addressable Type 10 Loops Fire Alarm Control Panel with with auto dailer with 240 character LCD display, seven access level. 2500 event historic logging, flash EPROM sufficient numbers of programmable relay control, 240V DC standby & Battery backup/battery charger minimum of 24 hrs (please provide battery calculations), auto dialer, The FACP shall have provision of Minimun 2 loop expansion, FA panel should have a provision for Tenant FACP Panel integration.The FACP shall be networkable type over IP/OFC. The FACP loops is designed considering 250 devices per loop and each loop is loaded 80%. FA Panel should have Network Card for BMS integration over Modbus / BacnetIP. Panel should have minimum redundancy or 100% spare capacity so that multiple fails can be taken care with compromise on the functionality of the system. (Location: Main Building ). | 1 | Nos | |
1522 | 153.1 | Supply, Installation,Testing & Commissioning of Active Repeater Panel | 1 | Nos | |
1523 | 153.2 | Supply, installation, testing & commissioning of Master panel for 2 way voice system, 20 zones. Should support Master to remote and remote to master calling facility, Group Calls, Conference Calls, It should be supplied with necessary battery backup. | 1 | Set | |
1524 | 153.3 | DETECTORS | |||
1525 | 153.4 | Photo Detectors: Supply, Installation, Testing and Commissioning of Intelligent Addressable Photo Electric Type Smoke Detectors Above False Ceiling with indicating lamp, mounting base and all other mounting accessories complete as required. | 389 | Nos | |
1526 | 153.5 | Multi Sensor Detector: Supply, Installation, Testing and Commissioning of Intelligent Addressable Multi Sensor Detectors with indicating lamp, mounting base and all other mounting accessories complete as required. | 576 | Nos | |
1527 | 153.6 | Response Indicator: Supply, Installation, testing and commissioning of Response Indicator with all mounting accessories complete as required. | 389 | Nos | |
1528 | 153.7 | DEVICES | |||
1529 | 153.8 | Addressable Manual Call Points: Supply, Installation, testing and commissioning of Intelligent Addressable Manual Call Points single action indicating lamp, mounting base and all other mounting accessories complete as required. | 53 | Nos | |
1530 | 153.9 | Control Relay Module For AHU's: Supply, Installation, testing and commissioning of Addressable Control Modules with indicating lamp, mounting base and all other mounting accessories complete as required.with all the mounting accessories complete as required. | 44 | Nos | |
1531 | 154 | Control Relay Module For Hooters: Supply, Installation, testing and commissioning of Addressable Control Modules with indicating lamp, mounting base and all other mounting accessories complete as required.with all the mounting accessories complete as required. | 92 | Nos | |
1532 | 154.1 | Monitor Module: Supply, Installation, testing and commissioning of Addressable Monitor Modules (2Inputs/1 Output) with indicating lamp, mounting base and all other mounting accessories complete as required. | 88 | Nos | |
1533 | 154.2 | Remote Phone Jack: Supply, Installation, testing and commissioning of 2 way communication Fire Fighter's Telephone Jack with Monitor Module fitted on wall including the cost of breaking and making good the wall wherever required, complete in all respects as per specifications. | 45 | Nos | |
1534 | 154.3 | Fire Telephone Handset: Supply, Installation, Testing and commissioning of Fire Fighting Telephone Handset with required accessories. | 10 | Nos | |
1535 | 154.4 | Fault isolator Module: Supply, Installation, Testing, and Commissioning of Addressable Isolators. Should isolate the affected loop portion in case of fault or shortcircuit. Should be able to reste once the fault is removed. Should be capable of monitoring upto 30 or more devices. Should be UL or FM Certified. Should be supplied with base. | 64 | Nos | |
1536 | 154.5 | NOTIFICATION DEVICES | |||
1537 | 154.6 | Addressable Hooters: Supply, Installation, testing and commissioning of Addressable Hooters and strobe, mounting base and all other mounting accessories complete as required with necessary accessories. | 44 | Nos | |
1538 | 154.7 | Addressable Strobe/Flasher Light: Supply, Installation, testing and commissioning of Addressable strobe/Flasher Light, mounting base and all other mounting accessories complete as required with necessary accessories. | 44 | Nos | |
1539 | 154.8 | CABLES, CONDUITS & CABLE TRAYS | |||
1540 | 154.9 | Supply and laying of of ISI Certified 2Cx1.5 sq.mm, twisted shield, FRLS type, armored double insulated copper cable with Ferrules, Lugs, saddles, saddles base & other accessories complete as required. The cable specification shall meet FACP & detectors manufacturer requirement. - Red Color | 12750 | Rmt | |
1541 | 155 | Supply and laying of 16G GI conduit including bends, juction boxes, pull boxes, GI pull wire and necessary civil works such as chasing and making good of the wall for concealed conduiting or surface conduiting which shall include saddles and supports etc for surface conduiting and making good as required : 2" inch GI Conduit with 2mm thickness | 55 | Rmt | |
1542 | 155.1 | Fire Alarm System - Food Court\nFire Alarm Control Panel | |||
1543 | 155.2 | Supply, Installation, Testing & Commissioning of Microprocessor based Intelligent Analog Addressable Type 2 Loops Fire Alarm Control Panel with with auto dailer with 240 character LCD display, seven access level. 2500 event historic logging, flash EPROM sufficient numbers of programmable relay control, 240V DC standby & Battery backup/battery charger minimum of 24 hrs (please provide battery calculations), auto dialer, The FACP shall have provision of Minimun 2 loop expansion, FA panel should have a provision for Tenant FACP Panel integration.The FACP shall be networkable type over IP/OFC. The FACP loops is designed considering 250 devices per loop and each loop is loaded 80%. FA Panel should have Network Card for BMS integration over Modbus/BacnetIP. Panel should have minimum redundancy or 100% spare capacity so that multiple fails can be taken care with compromise on the functionality of the system. (Location: Food Court). | 1 | Nos | |
1544 | 155.3 | DETECTORS | |||
1545 | 155.4 | Photo Detectors: Supply, Installation, Testing and Commissioning of Intelligent Addressable Photo Electric Type Smoke Detectors Above False Ceiling with indicating lamp, mounting base and all other mounting accessories complete as required. | 44 | Nos | |
1546 | 155.5 | Multi Sensor Detector: Supply, Installation, Testing and Commissioning of Intelligent Addressable Multi Sensor Detectors with indicating lamp, mounting base and all other mounting accessories complete as required. | 50 | Nos | |
1547 | 155.6 | Heat Detector (Addressable): Supply, Installation, Testing and Commissioning of Intelligent Addressable Heat Detectors with indicating lamp, mounting base and all other mounting accessories complete as required. | 16 | Nos | |
1548 | 155.7 | Response Indicator: Supply, Installation, testing and commissioning of Response Indicator with all mounting accessories complete as required. | 44 | Nos | |
1549 | 155.8 | DEVICES | |||
1550 | 155.9 | Addressable Manual Call Points: Supply, Installation, testing and commissioning of Intelligent Addressable Manual Call Points with indicating lamp, mounting base and all other mounting accessories complete as required. | 8 | Nos | |
1551 | 156 | Control Relay Module For AHU's : Supply, Installation, testing and commissioning of Addressable Control Modules with indicating lamp, mounting base and all other mounting accessories complete as required.with all the mounting accessories complete as required. | 2 | Nos | |
1552 | 156.1 | Monitor Module: Supply, Installation, testing and commissioning of Addressable Monitor Modules (2Inputs/1 Output) with indicating lamp, mounting base and all other mounting accessories complete as required. | 11 | Nos | |
1553 | 156.2 | Remote Phone Jack: Supply, Installation, testing and commissioning of 2 way communication Fire Fighter's Telephone Jack with Monitor Module fitted on wall including the cost of breaking and making good the wall wherever required, complete in all respects as per specifications. | 3 | Nos | |
1554 | 156.3 | Fault isolator Module: Supply, Installation, Testing, and Commissioning of Addressable Isolators. Should isolate the affected loop portion in case of fault or shortcircuit. Should be able to reste once the fault is removed. Should be capable of monitoring upto 30 or more devices. Should be UL or FM Certified. Should be supplied with base. | 7 | Nos | |
1555 | 156.4 | NOTIFICATION DEVICES | |||
1556 | 156.5 | Addressable Hooters: Supply, Installation, testing and commissioning of Addressable Hooters and strobe, mounting base and all other mounting accessories complete as required with necessary accessories. | 2 | Nos | |
1557 | 156.6 | Addressable Strobe/Flasher Light: Supply, Installation, testing and commissioning of Addressable strobe/Flasher Light, mounting base and all other mounting accessories complete as required with necessary accessories. | 2 | Nos | |
1558 | 156.7 | CABLES, CONDUITS & CABLE TRAYS | |||
1559 | 156.8 | Supply and laying of of ISI Certified 2Cx1.5 sq.mm, twisted shield, FRLS type, armored double insulated copper cable with Ferrules, Lugs, saddles, saddles base & other accessories complete as required. The cable specification shall meet FACP & detectors manufacturer requirement. - Red Color | 700 | Rmt | |
1560 | 156.9 | Supply and laying of 16G GI conduit including bends, juction boxes, pull boxes, GI pull wire and necessary civil works such as chasing and making good of the wall for concealed conduiting or surface conduiting which shall include saddles and supports etc for surface conduiting and making good as required : 2" inch GI Conduit with 2mm thickness | 5 | Rmt | |
1561 | 157 | Public Address System- Main Building/FOOD Court\nSystem Controller | |||
1562 | 157.1 | Supply, Installation, Testing & Commissioning of IP based Voice alarm controller. Hardware system shall be 4IN/12OUT expandable upto 144 zones front panel knobs programable to map any function within the DSP library. Upto 53 min of audio storage inside the box, audio files can be activated via built in scheduler or any of 16 TTL resident inputs. Should have 8 control Outputs to inegrate with 3rd party devices. system should be EN/UL certified. neccessary software should be inculded. | 1 | Nos | |
1563 | 157.2 | IP Based audio Encoder/Decoder | |||
1564 | 157.3 | Supply, Installation, Testing & Commissioning of 2 channel audio over IP encoder/decoder which operates as an audio source for an IP network. Should equipped with G.711, G.722, G.726, G.727, G.729, MP3 audio codec and AAC+ decoder, paging with unicast, multicast, broadcast. The power is supplied via POE and/or an AC/DC power adapter as per the technical specification with all mounting accessories etc. (For Utility Building) | 2 | Nos | |
1565 | 157.4 | Zone Selector with Microphone | |||
1566 | 157.5 | Supply, Installation, Testing & Commissioning of IP based POE supported Touch screen call station with programamble keys and able to display the faults on screen. Maximum 168 programmable keys for any adoptable function as per the technical specification with all mounting accessories etc. | 2 | Nos | |
1567 | 157.6 | Booster Amplifiers | |||
1568 | 157.7 | Supply, Installation, Testing & Commissioning of Booster Amplifier for PA system with 480W / 500 W RMS as per the technical specification with all mounting accessories etc. | 12 | Nos | |
1569 | 157.8 | DVD Player | |||
1570 | 157.9 | Supply, Installation, testing and commissioning of DVD Player as per the technical specification with all mounting accessories etc | 2 | Nos | |
1571 | 158 | Speakers | |||
1572 | 158.1 | Ceiling speaker: Supply, Installation, Testing & Commissioning of Ceilng mount type Round Speakers of 6 Watts Rated Power with Dual Cone High Sensitivity Loudspeaker Drivers, Opening Angle of 180o and builtin 100 Volts Matching Transformer with the Tapping of 1.5, 3, 6 watts. The Speaker Cabinet shall be White Color and necessary accessories like backbox, etc.. as complete as required. | 527 | Nos | |
1573 | 158.2 | Wall Mount speaker: Supply, Installation, Testing & Commissioning of Ceilng mount type Round Speakers of 6Watts Rated Power with Dual Cone High Sensitivity Loudspeaker Drivers, Opening Angle of 180o and builtin 100 Volts Matching Transformer with the Tapping of 3,6, 12 watts. The Speaker Cabinet shall be White Color and necessary accessories like backbox, etc.. as complete as required. | 10 | Nos | |
1574 | 158.3 | BOX Speaker: Supply, Installation, Testing & Commissioning of Cabinet type Bi-directional Speakers of 12 Watts Rated Power with 2 nos of Dual Cone High Sensitivity Loudspeaker Drivers, Opening Angle of 195o Horizontal and builtin 100 Volts Matching Transformer with the Tapping of 3,6, 12 watts. The Speaker Cabinet shall be Black / White Color and necessary accessories like backbox, etc.. as complete as required. | 74 | Nos | |
1575 | 158.4 | Horn Speaker: Supply, installation, testing & commissioning of wall mounted Horn Speakers 30W with line Matching Transformer with the Tapping of 7.5, 15, 30 watts. The scope of work includes neccessary supports & fixings for the speakers in ceilings, Iron Beams, civil structures, iron tress etc. as per the site condition. The speaker should be suitable for outdoor use(IP65). | 10 | Nos | |
1576 | 158.5 | Cable & Conduit | |||
1577 | 158.6 | Supply and Laying of 2 core 1.5 Sq.mm ATC twin twisted, FRLS type Unarmored Cable. | 6820 | Nos | |
1578 | 158.7 | Supply & Laying of ISI Certified 1", 2mm thick,FRLS PVC Conduit with bends, collar, saddles, saddle base, and other accessories | 6700 | Nos | |
1579 | 158.8 | PA Rack | |||
1580 | 158.9 | Supply, Installation, Testing & Commissioning of rack with all accessories for mounting of System Controller, Amplifier. Size:42U Rack | 1 | Nos | |
1581 | 159 | Supply, Installation, Testing & Commissioning of rack with all accessories for mounting of System Controller, Amplifier. Size:12U Rack | 1 | Nos | |
1582 | 159.1 | CCTV - Main Building Cameras | |||
1583 | 159.2 | Supply, Installation, Testing and commissioning of IP 2MP Dome Cameras, IR Range 20m 30m Supply, Installation, Testing and commissioning of IP IR Dome Cameras, 1/2.7” Image Sensor, 3.8mm 2.8mm, 1080P(1920×1080) @25FPS, with Dual Stream H.264 Main Profile and MJPEG. Should support PoE Power (802.af Type 1). Should support Smart Detection, DWDR, Day/Night (ICR), 3DNR, AWB, AGC, BLC features. 0.01Lux/F2.0 (Color), 0Lux/F2.0(IR on). IR Range should be 30m or more. Camera should be IP65 rated or more. | 68 | Nos | |
1584 | 159.3 | Supply, Installation, Testing and commissioning of IP 2MP Bullet Cameras, IR Range Supply, Installation, Testing and commissioning of IP IR Dome Cameras, 1/2.7” Image Sensor, 3.6mm 2.8mm, 1080P(1920×1080) @25FPS, with Dual Stream H.264 Main Profile and MJPEG. Should support PoE Power (802.af Type 1). Should support Smart Detection, DWDR, Day/Night (ICR), 3DNR, AWB, AGC, BLC features. 0.01Lux/F2.0 (Color), 0Lux/F2.0(IR on). Camera should be IP65 rated or more. | 60 | Nos | |
1585 | 159.4 | Supply, Installation, Testing and commissioning of IP 2MP fixed Bullet Cameras, IR Range Supply, Installation, Testing and commissioning of IP IR Dome Cameras, 1/2.7” Image Sensor, 8mml 2.8mm lens 1080P(1920×1080) @25FPS, with Dual Stream H.264 Main Profile and MJPEG. Should support PoE Power (802.af Type 1). Should support Smart Detection, DWDR, Day/Night (ICR), 3DNR, AWB, AGC, BLC features. 0.01Lux/F2.0 (Color), 0Lux/F2.0(IR on). Camera should be IP65 rated or more. | 35 | Nos | |
1586 | 159.5 | Supply, Installation, Testing and commissioning of IP 2MP varifocal Bullet Cameras, IR Range Supply, Installation, Testing and commissioning of IP IR Dome Cameras, 1/2.7” Image Sensor, 3.6mm -12mm varifocal lens 1080P(1920×1080) @25FPS, with Dual Stream H.264 Main Profile and MJPEG. Should support PoE Power (802.af Type 1). Should support Smart Detection, DWDR, Day/Night (ICR), 3DNR, AWB, AGC, BLC features. 0.01Lux/F2.0 (Color), 0Lux/F2.0(IR on). Camera should be IP65 rated or more. | 2 | Nos | |
1587 | 159.6 | Supply, Installation testing and commissioning of PTZ camera 4MP and 30x zoom, Built-in IR LEDs with OptimizedIR, 1/2.8” Progressive scan CMOS, lens Varifocal, 4.3-135.6 mm, F1.4 - 4.0, Iris Autofocus, auto-iris, Shutter time 1/66000 to 2 s, Horizontal field of view: 63.5 °–2.3 °, Vertical field of view: 38.4 °–1.3 °, Autofocus, auto-iris,Color: 0.15lux , B/W: 0.01 lux at 30 IRE F1.4, F1.6, 0 lux with IR illumination on Color: 0.15 lux at 50 IRE, F1.6 B/W: 0.01 lux at 50 IRE, F1.6, 0 lux with IR illumination, Zoom: 32x optical, 12x digital, total 360x zoom, Video Compression H.264 (MPEG-4 Part 10/AVC) Baseline, Main and High Profiles H.265 (MPEG-H Part 2/HEVC) , Main and High Profiles, H.265 (MPEG-H Part 2), Motion JPEG, Resolutions and frame rates (H.264) Up to 50 fps in all resolutions , Pan/Tilt/Zoom Pan: 360° endless, Tilt: 180°, 32x Optical zoom and 12x Digital zoom, Total 360x zoom, 256 preset positions, flip, limited guard tour, control queue, on-screen directional indicator, set new pan 0°, focus window, focus recall, Audio Two-way, Password protection, IP address filtering, HTTPSa encryption, IEEE 802.1X (EAP-TLS)a network access control, digest authentication, user access log, centralized certificate management, brute force delay protection, signed firmware, secure boot, Internal Memory 1024 MB RAM, 512 MB Flash or better, Local storage ( S.D or Micro SD ) Support for SD/SDHC/SDXC card, ONVIF Version S& G Profile, Compression, saturation, brightness, sharpness, contrast, local contrast, white balance, exposure control, exposure zones, Forensic WDR: Up to 120 dB depending on scene, defogging, day/night shift level, tone mapping, fine tuning of low-light behavior, rotation: 0°, 180°, text and image overlay, image freeze on PTZ, electronic image stabilization, scene profiles, 20 individual polygon privacy masks , Casing IP66-, IK10- and NEMA 4X-rated Metal casing, clear dome. Certifications EN/UL/FCC. Bidders should provide 3 year Warranty | 4 | Nos | |
1588 | 159.7 | Supply, installation, testing and commissioning of PTZ Mounting Pole | 4 | Nos | |
1589 | 159.8 | Supply, installation, testing and commissioning of 2MP Thermal Camera, Temperature exception detection Linkage for audible alarm Uncooled sensor, resolution: 160 x 120 Supports dual-light fusion image Supports visible light and thermal imaging frame over lay Measurement Accuracy: No black body: ±0.5? With black body: ±0.3 Multi-area alarm: Indicates the metal position on the body. Max. 18 areas - Body temperature measurement application. | 1 | Set | |
1590 | 159.9 | Supply, installation, testing and commissioning of ANPR IP camera, 1280 × 960,Color, 1/3” Progressive scan CMOS ,5.2 – 58 mm with high precision motorized positioning, ANPR range 3 m – 12 m (10 feet – 40 feet), All pass/IR cut above 850 nm, Automatic motorized, programmable focus, Configurable day/night mode switching, ,IP65 with poles stand from the ground. Include for all foundation works and preparation c/w with conduits, junction boxes and necessary signal cables and power cabling with surge arrestors. Bidders should provide 3 year Warranty. | 2 | Set | |
1591 | 160 | Supply, Installation, Testing & Commissioning of Video management software to support upto 200 cameras on one site with expansion to unlimited cameras across multiple sites in future. Shall support off the shelf recording servers. The VMS shall support Video Analytics integration. The VMS shall be installed in a Server with minimum speciifcation of icore7, 8 GB RAM, 2 TB harddisk with all relevant licenses for MS and SQL. | 1 | Lot | |
1592 | 160.1 | Supply and Installation of 8TB external surveillance grade Storage with RAID-5 back up device to record images of all cameras at 25 FPS for 30days in 720p resolution. The bidder shall include data storage calculation along with offer. | 12 | Nos | |
1593 | 160.2 | Supply and installation of Intel i7 7th Gen Workstation with 16GB DDR4 Ram, 1 TB SATA HDD, Network card, Graphics card of minimum 2GB memory, DVD writer, HDMI ports, Giga Lan card, Keyboard, Wireless Mouse, & Microsoft Windows 10 Professional 64 bit, connected upto 3 monitors | 2 | Nos | |
1594 | 160.3 | Supply and installation 49" Full HD LED display, thin bezel for video wall application HDMI X 3, VGA X 1, Video IN X 1, USB X 2, RS232 X 1, Audio IN X1, 20W in built speaker, 100 Hz BLB, IPS LED display, USB media player | 6 | Nos | |
1595 | 160.4 | CCTV - Food court cameras | |||
1596 | 160.5 | Supply, Installation, Testing & Commissioning of 4MP Outdoor varifocal Bullet Camera , 1/2.8'' Progressive CMOS, Varifocal lens 3-10.5 mm, Shutter time 1/66500 s to 2 s, Varifocal P-Iris control, IR corrected, Megapixel resolution , Day & Night IR cut filter with auto switch, Minimum Illumination / Light Sensitivity Color: 0.12 lux ,B/W: 0 lux with IR illumination on.IP67 ingress protection level, Supports microSD cards with up to 64 GB, Multiple, individually configurable streams in H.264/H.265+ Main and Baseline profiles , Motion JPEG with high compression ratio, security Password protection, IP address filtering, HTTPSb encryption, IEEE 802.1Xb network access control, Intelligent video- Video Motion Detection 3, Active tampering alarm, casing -IP66-, NEMA 250 Type 4X-, and IK08-rated, polymer casing and all the required accessories. Certifications EN/UL/FCC. Bidders should provide 3 year Warranty. | 1 | Nos | |
1597 | 160.6 | Supply, Installation, Testing & Commissioning of 4MP Outdoor Bullet Camera , 1/2.8'',f2.0 Progressive CMOS, lens 2.8mm, F2.0 Shutter time 1/65000 s to 2 s, Color: 0.2 lux ,B/W: 0.04 lux at 50 IRE, F2.0 , 0 lux with IR illumination on Day & Night IR cut filter with auto switch, onvif version G,S & T, IP66 ingress protection level, Supports microSD cards with up to 64 GB, Multiple, individually configurable streams in H.264/H.265+ Main and Baseline profiles , Motion JPEG with high compression ratio, Remote zoom , Remote focus, security Password protection, IP address filtering, HTTPSb encryption, IEEE 802.1Xb network access control, Intelligent video- Video Motion Detection 3, Active tampering alarm, casing -IP66-, NEMA 250 Type 4X-, and IK08-rated, polymer casing and all the required accessories. Certifications EN/UL/FCC. Bidders should provide 3 year Warranty. | 7 | Nos | |
1598 | 160.7 | Supply, Installation, Testing and commissioning of IP 2MP varifocal Bullet Cameras, IR Range Supply, Installation, Testing and commissioning of IP IR Dome Cameras, 1/2.7” Image Sensor, 3.6mm-12mm 1080P(1920×1080) @25FPS, with Dual Stream H.264 Main Profile and MJPEG. Should support PoE Power (802.af Type 1). Should support Smart Detection, DWDR, Day/Night (ICR), 3DNR, AWB, AGC, BLC features. 0.01Lux/F2.0 (Color), 0Lux/F2.0(IR on). Camera should be IP65 rated or more. | 12 | Nos | |
1599 | 160.8 | DATA NETWORK - Main, Utility and Food Court | |||
1600 | 160.9 | Supply, Installation, Testing & Commissioning of WIFI Access point with router and Connected Accerssories-Wireless Access Point (Type Of Access Point: Controller Based, Allowed Values: Stand Alone, Controller Based, Deployment: Indoor, MU-MIMO (3x3:3) Supported Wi-fi Standards: 802.11a, 802.11b/g, 802 .11 B/g/n, 802.11ac, 802.11 A/b/g/n/ac, 802.11ac Wave 1, 802.11ac Wave 2, Wireless Speed Up To (Mbps): "5 GHz: 2304 2.4 GHz: 216.7") , Dual band, Integrated internal antennas, Data rates 300 Mbps, 100 mtrs Coverage minimum | 37 | Nos | |
1601 | 161 | Supply, Installation, Testing & Commissioning of FireWall-1 x 10/100/1000 Mbps Gigabit Ethernet WAN 4 x 10/100/1000 Mbps Gigabit Ethernet LAN Power, Appliance should be rack mountable, Unified Threat Management (UTM), Static URL blocking, keyword blocking, approved URL, MAC-based access control, IP/MAC binding, wireless profiles, Firewall Throughput 2.5 Gbps | 1 | Nos | |
1602 | 161.1 | Supply, Installation, Testing & Commissioning of 24 X 10/100/1000 BASE T RJ45 ports, 4 X 10 Gbps SFP ports Virtual Chassis Compatible Layer 3 Core Switch as per technical specifications in the tender document and accessories such as licenses, mounting kits, console cables, 3 years TAC, India power cord and others required for completion of work as per the scope. | 2 | Nos | |
1603 | 161.2 | Supply, Installation, Testing & Commissioning of manageable L2 PoE switch, 24Port, 10/100/1000, 2SFP Ports with support for Auto VLANS and support features like IP4/IP6, QoS, advanced security management, PoE management along with 4U Rack Should support 802.3af (802.3at Type 1) specification. (Considered Data, Wifi, CCTV, BMS and ACS) | 25 | Nos | |
1604 | 161.3 | Supply and installation of fully loaded 24 Ports CAT6 Patch Panel. | 25 | Nos | |
1605 | 161.4 | Supply and Installation of 12U Fully loaded Fiber LIU, Fiber Adaptor, Pigtail, Fiber disatribution Plate. | 25 | Nos | |
1606 | 161.5 | Supply and Installation of Fiber Patch Cord | 50 | Nos | |
1607 | 161.6 | Supply and Installtion of 1GBPS SFP Module | 25 | Nos | |
1608 | 161.7 | Network Rack | |||
1609 | 161.8 | Supply and Installation of Network Racks, 6U, wall mount with accessories, Fixtures, Power Managers, Cable Managers and Organizers and lockable Front side glass door. | 25 | Nos | |
1610 | 161.9 | Supply and Installation of Network Racks, 9U, wall mount with accessories, Fixtures, Power Managers, Cable Managers and Organizers and lockable Front side glass door. | 1 | Nos | |
1611 | 162 | Supply and Installation of Network Racks, 15U, wall mount with accessories, Fixtures, Power Managers, Cable Managers and Organizers and lockable Front side glass door. | 1 | Nos | |
1612 | 162.1 | Supply and Installation of Network Racks, 22U, Floor Mount with Network Rack Accessories, Fixtures, Power Managers, Ventilation Fans, Cable Managers and Organizers, Castor Wheels. Side and Back Doors should be removable with Front side glass door. Dim (wxdxh): 600x800x1170mm.1xSliding Shelf, 2xFixed shelfs. | 1 | Nos | |
1613 | 162.2 | Supply and Installation of one no of RJ-45 Data socket with Face plate mounted in manufacturers MS back box. | 200 | Nos | |
1614 | 162.3 | Supply and Installation of one no of RJ-11 Telephone socket with Face plate mounted in manufacturers MS back box. | 150 | Nos | |
1615 | 162.4 | Cables & Conduits | |||
1616 | 162.5 | Supply and laying of UTP CAT6 Network Cable from data point to Network Switch (Considered, Data, Wifi, CCTV, ACS and BMS System) | 12500 | Rmt | |
1617 | 162.6 | Supply and laying of 6 core Multi mode armoured OFC Network Cable from Network POE switch to Main Network Switch at below Ground level | 2000 | Rmt | |
1618 | 162.7 | Supply and laying of CAT6 Patch Cable, 1m | 400 | Nos | |
1619 | 162.8 | Supply and laying of CAT6 Patch Cable, 3m | 300 | Nos | |
1620 | 162.9 | Supply and laying of 25mm PVC ISI conduits with all accessories(1.6 mm thick) | 7000 | Rmt | |
1621 | 163 | Supply and laying of ISI Certified 63mm dia HDPE pipe with all accessories | 500 | Rmt | |
1622 | 163.1 | Supply and laying of perforated closed cable tray- 150 mm x 50mm with all required accessories | 950 | Rmt | |
1623 | 163.2 | EPABX | |||
1624 | 163.3 | Supply, Installation, Testing & Commissioning of fully automatic non blocking Hybrid EPABX with 04xCO Lines, 1xT1/E1/PRI, 2xDigital Ports, 150xSLT analogue extensions expandable upto 300 lines, 50 IP Users, VMS system. Should support features like Call forwarding, DND, Override do not disturb, Speed dialing, Barge in, Call back, Call parking, Class of service, calling line identification (CLIP) on digital as well as analog extension and external Lines (P&T). The system should have an in-built comport/LAN port from which call-billing data can be obtained. Should be supplied with call billing software.The EPABX shall be compatible with the public switched telephone network of BSNL/other ISPs operating in India, TEC/DOT or similar standards certified as in Technical Specification. | 1 | Nos | |
1625 | 163.4 | Telephones | |||
1626 | 163.5 | Supply and Installation of basic corded telephone with optical call alert, lcd display, CLIP feature, handsfree talking. | 90 | Nos | |
1627 | 163.6 | Supply and Installation of IP based Digital Key telephones for operator with 2 line lcd, soft touch keys, programable soft keys, supports hands free Telephone. | 10 | Nos | |
1628 | 163.7 | Accessories | |||
1629 | 163.8 | Supply and Installation of 200pair MDF Box, with 20nos krone type punch down 10pair modules, back frame, powder coated lockable door. -Main Building | 1 | Nos | |
1630 | 163.9 | Supply and Installation of 20pair IDF Box, with krone type punch down 10pair modules, back frame, powder coated lockable door.-Utility and Food Court | 2 | Nos | |
1631 | 164 | Supply and Installation of 10 pair MDF Box, with krone type punch down 10 pair modules, back frame, powder coated lockable door. | 20 | Nos | |
1632 | 164.1 | Cables & Conduits | |||
1633 | 164.2 | Supply and Laying of 0.5mm 10pair PVC Telephone cable | 500 | Rmt | |
1634 | 164.3 | Supply and laying of 0.5mm 50pair PVC Telephone cable | 200 | Rmt | |
1635 | 164.4 | Supply and Laying of 0.5mm 2pair PVC Telephone cable | 4200 | Rmt | |
1636 | 164.5 | Supply, Laying 0.5mm 20pair Jelly Filled PVC Armoured Telephone cable at below Ground level | 550 | Rmt | |
1637 | 164.6 | Supply and laying of 25mm PVC ISI conduits with all accessories (1.6 mm thick) | 1800 | Rmt | |
1638 | 164.7 | ACCESS CONTROL SYSTEM | |||
1639 | 164.8 | Supply, installation, testing and commissioning of 2 reader network controller with necessary enclosures for, transformers, power supply plugs and any other necessary accessories to complete installation. connect 2 wiegand reader. Each with 2 inputs and 1 output. power plug and supports Pull-Safe? cable locks, for secured wiring. option of DIN rail mounting.cable twist locks and zip-tie anchors for better cable management. tamper sensing, and power status LED. Controller 2-Reader controller, single/dual door modes, networked up to 1023 panels to one PC.Full online/offline operation. 30,000 Users, 20,000 event history. | 13 | Nos | |
1640 | 164.9 | Supply, installation, testing and commissioning of Access door readers RFID Bluetooth Reader-The Unit features three technologies: a built-in smart card (13.56 MHz) reader, an NFC-ID reader, and a Bluetooth reader, configuration card programming, programmable output formats and OSDP(open supervised device protocol) bus command support. Operating Environment UV-resistant, meets IP65, epoxy-potted, suitable for indoor and outdoor use. Comes with mounting template and installation kit for easy installation | 24 | Nos | |
1641 | 165 | Supply of Smart access cards ( Mifare DES Fire) for the access control system. | 100 | Nos | |
1642 | 165.1 | Biomteric Attendance System: Supply, Installation, Testing, and commissiong of Biometric Reader - should support Biometric, keypad, card (Any possible combination ) Mifare(13.56 MHz) RFID. Memory: Max Users 20,000 Fingerprints (Templates) 40,000 (1:1)30,000 (1:N),Logs 64,000, Images X communication Wireless LAN(Wi-Fi), Wiegand OUT, RS232, RS485, OSDP, Wiegand IN. Display LCD 2.8?Color, Backlight. Embedded Camera, Card 125khz-EM, HID Prox, HID iclass, 13.56MHz Smart Card Keypad, Function keys, Door Phone FP Sensor-Platen Area, Resolution. Dust/ Water Resistance IP65 / IK09. Operating Temperature -20 ~ 60? with required accessories | 1 | Nos | |
1643 | 165.2 | Access Software: Supply and installation of access software should have features like Attendance Report, Car Parking, Elevator Control, Visitor Management, Status Maps, Card + Card mode, Card Design (Photo ID), User Counters, Global Antipassback, Operators, CCTV integration and should work on client server architechure with Minimum 10 clients. | 1 | Nos | |
1644 | 165.3 | Supply, Installation, Testing and Commissioning of Exit Push Button (3x1") with required backboxes for Installation. | 10 | Nos | |
1645 | 165.4 | Supply, installation, testing and commissioning of Monitored 600 lbs Single Leaf EM Lock with Door contact and all other required Accessories | 10 | Nos | |
1646 | 165.5 | Supply, installation, testing and commissioning of Magnetic Door Contact to Monitor the Door status through FAS/BMS. Location: Refuge Doors. | 20 | Nos | |
1647 | 165.6 | Supply and Installation of Lane configuration: 3 Normal lane + 1 Wider lane: Sensor swing barrier:- (1) Wings open able in 0.3 second. (2) Wings made of 10 mm clear polycarbonate. (3) Wings lockable at each position with Tooth holding brake technology,with servo position drive. (4) Finishing stainless steel AISI 304. (5) MCBF (mean cycles between failures) for normal lanes 8 Million and wider lane 6 Million. (6) Throughput: 30 persons per minute. (7) Passage width 900 mm. (8) Concealed reader mounting and Way mode indicator. Guiding elements made of tubular AISI 304 stainless steel tubes Ø 60 mm with TSG 10 mm glass panel hand rail. Two door leaves are made of transparent polycarbonatedoor leaves, thickness 10 mm, upper edge 900mm with opening/ closing time of 0.3seconds minimum, which can be adjusted as per client requirement. The sensor system is integrated into the respective hand rail (L= 1660 mm / W= 130 mm / H= 45mm). The drive housing is made of AISI 304 stainless steel. In case of multiple installations, thehousing Unit acts as a guiding element – additional guiding bars are not required. The passagewidth can be widened to 900 mm when necessary for passage or for passage of people withreduced mobility.To improve personal safety, standards and guidelines relating to points where body parts could get pinched or squashed have been taken into account in the development of the sensor barrier (Machinery Directive 98/37/EC). The Unit can also be used in the emergency and escape route . | 1 | Set | |
1648 | 165.7 | Supply, Installation, Testing & Commissioning of 6 Mtr Boom barrier along with the barrier, pair of photo cells, safety loop, close loop, induction cables with Readers and required accessories for the installation. | 4 | Nos | |
1649 | 165.8 | Supply and installation of 1.5 Mtr Exit Boom barrier along with the barrier, pair of photo cells, safety loop, close loop, induction cables with Readers and required accessories for the installation. | 2 | Nos | |
1650 | 165.9 | Supply, Installation, testing and commissioning OF Door Frame metal Detector with USB recording: Metal Detector Multi Zone Door Frame Metal Detector 9 Zones with Micro Controller Based with camera and real time recording inbuilt control Unit and walk/ stop indicator with ABS coated infra red sensor and counter in/out with PC for 45 days recording facility.(one for main entrance near Tripod/one in Grant Reception)PC should be branded product like HP/Lenovo/Del Camera should be branded product. | 1 | Nos | |
1651 | 166 | Supply and installation of Control Push Button for Boom barriers along with the required accessories for the installation. | 6 | Nos | |
1652 | 166.1 | Supply and laying of 8 core 1 sq. mm. Unarmoured Shielded Cable along with the required accessories. | 1000 | Rmt | |
1653 | 166.2 | Supply and laying of 4 core 1 sq. mm. Unarmoured Shielded Cable along with the required accessories. | 1000 | Rmt | |
1654 | 166.3 | Supply and laying of 25 mm PVC conduits with the required accessories. | 1200 | Rmt | |
1655 | 166.4 | Supply and installation of Intel i7 7th Gen Workstation with 16GB DDR4 Ram, 1 TB SATA HDD, Netowork card, Graphics card of minimum 2GB memory, DVD writer, HDMI ports, Giga Lan card, Keyboard, Wireless Mouse, & Microsoft Windows 10 Professional 64 bit( Access control ) | 1 | Nos | |
1656 | 166.5 | Linear Sensor | |||
1657 | 166.6 | Supply, installation, testing & commissioning of 150mm ISI mark HDPE Pipes along with suitable accessories | 1300 | Rmt | |
1658 | 166.7 | Supply, installation, testing & commissioning of 200mm dia Hume Pipes along with suitable accessories | 500 | Rmt | |
1659 | 166.8 | Supply, installation, testing & commissioning of VDS Approved signal processor Unit. It should have LED & LC display both as well as a alarm, pre alarm and a fault relay. It shall be able to support 2 Zone with 250 mtrs (each) sensor cable length with 1 to 99 maximum sensor. The alarm triggering via differential and maximum temperature evaluation, High temperature resolution of 0.1 °C with a repeatability of ±0.1 °C along the entire sensor cable length. Panel shall be Free from false alarms, caused by natural ambient temperature fluctuations, due to intelligent evaluation algorithms. Highly durable via utilisation of maintenance-free components in a modular configuration, RoHS compliant. Individual password-protected access levels for operators, maintenance and service personnel, as well as for commissioning | 1 | Nos | |
1660 | 166.9 | Supply, installation, testing & commissioning of VDS approved, Heat Sensing Cable onto which the sensors are mounted in an encapsulation at every 4 mtr interval. Complete encapsulation to protect sensors from environmental influences, Pinpoint sensor location via individual addresses, Constant sensor monitoring via control and evaluation Unit Branching of cable routes via connection boxes. Cable should detect freely adjustable absolute alarm thershold & freely adjustable differential alarm thershold i.e. fixed temperature as well as rate of rise of temperature. | 500 | Rmt | |
1661 | 167 | Supply, installation, testing & commissioning of Communication Box along with accessories like end cap,clamps and power cable | 1 | Nos | |
1662 | 167.1 | BUILDING MANAGEMENT SYSTEM\nWORKSTATION & PRINTER | |||
1663 | 167.2 | Supply and installation of PC comprising i7 processor or higher, 16 GB RAM, 2GB Graphics Card, 2 TB HDD, 10/100 Mbps Ethernet card, Windows 10 pro or latest OS Professional Enterprise, 64-bit operating system, anti virus software, DVD-R/W drive, keyboard, mouse and with 21" colour monitor with all necessary accessories. | 1 | Lot | |
1664 | 167.3 | Supply and installation of A4 Size Laser Jet Monochrome Printer with all the neccessory accessories for the installation. | 1 | Lot | |
1665 | 167.4 | BMS SOFTWARE | |||
1666 | 167.5 | Supply and installation of BMS software meeting the requirements in the given I/O Summary. The system should be accessible from anywhere on LAN or WAN or Ethernet without additional licenses. The communication protocol shall be one of the industry standard open protocols such as BACNet, LON etc. The system should be scalable and non-proprietary.\nThe software must be provided with 15 clients for simultaneous access anywhere within the facility and must support role based access to each and every user.\nThe software must have a common programming and configuration environment. The software frameworks should include support programs, compilers, code libraries, tool sets, and Application Programming Interfaces (API) that bring together all the different components to enable development of a solution.\nThe software shall be BTL, UL and CE certified and shall meet the requirements in the technical specification. The Software should have valid BTL certification as Bacnet Advanced Operator Workstation. | 1 | Lot | |
1667 | 167.6 | Tenant Billing Software: Software required for Tenant Billing for generation of bills using Multi Data Electrical Meter, Ultrasonic BTUH Meters, Hot Water Measurement Meters, generate graphics and to generate management informations systems (MIS) reports as per specifications | 1 | No | |
1668 | 167.7 | THIRD PARTY INTEGRATOR | |||
1669 | 167.8 | Supply and installation of compact, embedded IoT (Internet of Things) controller and server platform for connecting multiple and diverse devices and sub-systems. The panel must consist of a Integrator where the 3rd party integrations and the DDC's must connect to the Integrator directly. 3rd party integrations should be done on the Integrator without use of any non-specified protocol converters/ terminal servers. The Integrator should have an internal RAM of minimum 1 GB and user memory of 2 GB. The Integrator shall be automatically configured to backup any Historical Trend, Logging, Alarm and System/user event databases according to user configurable periods to ensure databases are consistently and automatically maintained and databases regularly compacted to ensure maximum performance at all times. Critical stations and configurations must be backed up on the cloud which should be available for easy download and updation on Integrator. It should support Wi-Fi (Client or WAP) WPAPSK/WPA2PSK, BACnet, LON, Modbus drivers included by default. It shall support Analytics engine. It should have at least 25 analytic points inbuilt for intelligent analysis of key parameters. It should have USB type A connector back-up and restore support, 2 nos. of isolated RS-485 with selectable bias and termination expandable up to 6 ports, and 2 nos. of 10/100MB Ethernet ports. 24VAC/DC power supply to power the Integrator. Individual power rating to be calculated as per selection of controllers. It shall be BTL, UL and CE certified and shall meet the requirements in the technical specification. The Supervisory Controller/Integrator should have valid BTL certification as Bacnet Building Controller/Bacnet Router and should manufactured from India, US, Europe & UK only.\nList of third party devices are shown below: | 1 | Lot | |
1670 | 167.9 | Energy meters - 750 Points | |||
1671 | 168 | DG Integration - 75 points | |||
1672 | 168.1 | VFD Integration - 840 points | |||
1673 | 168.2 | UPS Integration - 750 points | |||
1674 | 168.3 | Fire Alarm Panel Integration - 2000 points | |||
1675 | 168.4 | BTU Integration - 300 points | |||
1676 | 168.5 | Diesel Generator-75 points | |||
1677 | 168.6 | Portable operator terminal kit for stand alone programming. | |||
1678 | 168.7 | STP,ETP-750 Points | |||
1679 | 168.8 | DDC CONTROLLERS | |||
1680 | 168.9 | Supply, Installation, Testing & Commissioning of Automation stations / DDC Controller with I/O module etc., The controllers shall be microprocessor based standalone and net workable type with real time clock and historical database of min 1 MB. The DDC's shall be capable of peer to peer communication without help of system interface controller or PC. with locable mounting cabinets duly powder coated connector strip, internal wiring and space to house controller & relays, connector strip current transformer, MCB, internal wiring. (Contractor shall confirm his I/O provision w.r.t requirement on basis of data point) on BACnet /IP. Ref IO Summary | |||
1681 | 169 | DDC-1 Controller with Rittal enclosures for Main Building as per IO Sumary | 1 | Lot | |
1682 | 169.1 | DDC-2 Controller with Rittal enclosures for AHU Stilt floor as per IO Sumary | 1 | Lot | |
1683 | 169.2 | DDC-3 Controller with Rittal enclosures for CSU corridor as per IO Sumary | 1 | Lot | |
1684 | 169.3 | DDC-4 Controller with Rittal enclosures for GF Electrical room as per IO Sumary | 1 | Lot | |
1685 | 169.4 | DDC-5 to DDC 25 Controller with Rittal enclosures for AHU Typical floor as per IO Sumary | 1 | Lot | |
1686 | 169.5 | DDC-26 to DDC 46 Controller with Rittal enclosures for AHU Typical floor per IO Sumary | 1 | Lot | |
1687 | 169.6 | DDC-47 Controller with Rittal enclosures for HRW as per IO Sumary | 1 | Lot | |
1688 | 169.7 | DDC-48 Controller with Rittal enclosures for CSU Terrace floor as per IO Sumary | 1 | Lot | |
1689 | 169.8 | DDC-49 Controller with Rittal enclosures for OH tank as per IO Sumary | 1 | Lot | |
1690 | 169.9 | DDC-50 Controller with Rittal enclosures for Staircase Pressurisation as per IO Sumary | 1 | Lot | |
1691 | 170 | DDC-51 Controller with Rittal enclosures for HRW Terrace as per IO Sumary | 1 | Lot | |
1692 | 170.1 | DDC-52 Controller with Rittal enclosures for AHU in food court as per IO Sumary | 1 | Lot | |
1693 | 170.2 | DDC-54 Controller with Rittal enclosures for Utility Terrace floor as per IO Sumary | 1 | Lot | |
1694 | 170.3 | DDC-55 Controller with Rittal enclosures for Utility as per IO Sumary | 1 | Lot | |
1695 | 170.4 | DDC-56 Controller with Rittal enclosures for Rain water pumps in utility as per IO Sumary | 1 | Lot | |
1696 | 170.5 | DDC-57 Controller with Rittal enclosures for Fire water sump as per IO Summary | 1 | Lot | |
1697 | 170.6 | DDC-58 Controller with Rittal enclosures for Raw water tank as per IO Summary | 1 | Lot | |
1698 | 170.7 | DDC-59 Controller with Rittal enclosures for STP exhasut in Utility as per IO Sumary | 1 | Lot | |
1699 | 170.8 | DDC-60 Controller with Rittal enclosures for Transformer as per IO Sumary | 1 | Lot | |
1700 | 170.9 | DDC-61 Controller with Rittal enclosures for Elec HT LT panel as per IO Sumary | 1 | Lot | |
1701 | 171 | DDC-62 Controller with Rittal enclosures for AHU food court as per IO Sumary | 1 | Lot | |
1702 | 171.1 | DDC-63 Controller with Rittal enclosures for CSU food court as per IO Sumary | 1 | Lot | |
1703 | 171.2 | DDC-64 Controller with Rittal enclosures for AHU pent floor as per IO Sumary | 1 | Lot | |
1704 | 171.3 | DDC-65 Controller with Rittal enclosures for CSU pent floor as per IO Sumary | 1 | Lot | |
1705 | 171.4 | FIELD DEVICES | |||
1706 | 171.5 | Supply and installation of differential pressure switch across the fans with all the necessary mounting accessories. It shall meet the requirements in the technical specification. It shall meet the requirements in the technical specification. It shall meet the requirements in the technical specification. | 134 | Nos | |
1707 | 171.6 | Supply and installation of differential pressure switch across the filters with all the necessary mounting accessories. It shall meet the requirements in the technical specification. | 130 | Nos | |
1708 | 171.7 | Supply and installation of duct type temperature sensor with all the necessary mounting accessories.\nThe sensor shall be Pt 1000 RTD type . It shall meet the requirements in the technical specification. | 172 | Nos | |
1709 | 171.8 | Supply and installation of duct type return air CO2 sensor with all the necessary mounting accessories. The sensor shall be 0 to 2000 ppm CO2 concentration.\nIt shall meet the requirements in the technical specification. | 46 | Nos | |
1710 | 171.9 | Supply and installation of duct type static pressure sensor with all the necessary mounting accessories. It shall meet the requirements in the technical specification. | 48 | Nos | |
1711 | 172 | Supply and installation of water level switch for tanks with all the necessary mounting accessories. It shall meet the requirements in the technical specification. | 11 | Nos | |
1712 | 172.1 | Supply and installation of outside air temperature+RH with all the necessary mounting accessories. It shall meet the requirements in the technical specification. | 1 | Nos | |
1713 | 172.2 | Supply and installation of outside air CO2 sensor with all the necessary mounting accessories. It shall meet the requirements in the technical specification. | 1 | Nos | |
1714 | 172.3 | Supply and installation of water meters with all the necessary mounting accessories. It shall meet the requirements in the technical specification. | 5 | Nos | |
1715 | 172.4 | CABLES | |||
1716 | 172.5 | Supply and laying of 2cx1.0 sq. mm unarmoured ATC conductor multistranded, PVC FRLS unscreened cable. ( For DI & DO) | 4000 | Rmt | |
1717 | 172.6 | Supply and laying of 4cx1.0 sq. mm unarmoured ATC conductor multistranded, PVC FRLS unscreened cable. ( For DI & DO) | 2500 | Rmt | |
1718 | 172.7 | Supply and laying of 2cx1.0 sq. mm unarmoured ATC conductor multistranded, PVC FRLS screened cable. ( For AI & AO) | 2000 | Rmt | |
1719 | 172.8 | Supply and laying of 4cx1.0 sq. mm unarmoured ATC conductor multistranded, PVC FRLS screened cable. ( For AI & AO) | 1500 | Rmt | |
1720 | 172.9 | Supply and laying of single pair - 2cx1.5 sq. mm. unarmoured, shielded twisted cable. | 4000 | Rmt | |
1721 | 173 | Supply and laying of CAT-6 UTP unarmoured cable. | 2500 | Rmt | |
1722 | 173.1 | CONDUITS | |||
1723 | 173.2 | Supplying and fixing of 25mm dia FRLS PVC conduit including all accessories (i.e clamps, nuts, bolts, bends, PVC junction boxes etc.) | 12000 | Rmt | |
1724 | 173.3 | CABLE TRAYS | |||
1725 | 173.4 | Supply and installation of 150 X 50 size of perforated powder coated cable tray with cover, support rods and brackets at regular intervals to fix the cables in position with necessary accessories like bends, couplers etc. | 650 | Rmt | |
1726 | 173.5 | Comprehensive Maintenance cum Operation Works | |||
1727 | 173.6 | Comprehensive Maintenance contract for 6years after defect liability period for Tidel Park,Pattbiram. Total 7 Years including DLP. \nMaintenance of the system supplied, installed, Commissioned by the successful tenderer for Tidel Park,Pattabiram for 7 years including the Defects Liability Period (DLP). This will include start up / commissioning, routine servicing, regular maintenance, preventive maintenance of equipments and components and break down repairs as and when occurred, ensuring that system does not remain out of service for a period more than 8 hours in case of major breakdowns and one hour in the case of minor breakdowns due to any unforeseen break down.The successful tenderer shall keep the essential spares for TIDEL Park,Pattabiram during the Defects Liability Period to avoid any delay in attending the faults/maintenace and also during the Comprehensive maintenace contract period. (First Year-Defect Liability Period) | |||
1728 | 173.7 | Man Power Requirement for IBMS Comprehensive Maintenace Services | |||
1729 | 173.8 | a. First Year - AMC- No Charges in DLP | |||
1730 | 173.9 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1731 | 174 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1732 | 174.1 | a. Second Year quote lumpsum fee for one year- AMC | 1 | Nos. | |
1733 | 174.2 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1734 | 174.3 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1735 | 174.4 | a. Third Year quote lumpsum fee for one year - AMC | 1 | Nos. | |
1736 | 174.5 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1737 | 174.6 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1738 | 174.7 | a. Operation Fourth Year quote lumpsum fee for one year - AMC | 1 | Nos. | |
1739 | 174.8 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1740 | 174.9 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1741 | 175 | a. Operation Fifth Year quote lumpsum fee for one year - AMC | 1 | Nos. | |
1742 | 175.1 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1743 | 175.2 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1744 | 175.3 | a. Sixth Year quote lumpsum fee for one year - AMC | 1 | Nos. | |
1745 | 175.4 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1746 | 175.5 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1747 | 175.6 | a. Operation Seventh Year quote lumpsum fee for one year - AMC | 1 | Nos. | |
1748 | 175.7 | b. Operation Incharge - 1 No. General Shift (Qualification - BE with 5 Years / Diploma with 7 Years) | 1 | Nos. | |
1749 | 175.8 | c. Operation Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1750 | 175.9 | Note:- | |||
1751 | 176 | 1.The Escalation in the maintenance cost for consecutive years should not exceed 5% of the Lumpsum fee quoted for previous year by the tenderer. | |||
1752 | 176.1 | 2.The Contractor has to do comprehensive maintenance for 6 years for IBMS at Tidel Park ,Pattabiram after DLP. | |||
1753 | 176.2 | 3.The above man power is minimum requirement for routine operation and maintenance of IBMS works. In case of annual maintenance, major Break downs, Emergency situations, etc. contractor has to provide required manpower, tools, tackles, etc to full fill the contractual requirement. If Contractor feels that the above minimum manpower is not adequate for routine maintenance of IBMS works, the contractor shall engage more manpower with in quoted price. | |||
1754 | 176.3 | 4. In case the services are not upto the mark (or) inadequate manpower are provided and corrective actions are not taken within Ten days a penalty equal to One month of Maintenance charges of that month will be levied as decided by TIDEL. In case of such defaults for more than 3 Occurrence during contract period, TIDEL reserves right to terminate. | |||
1755 | 176.4 | 5.The payment will be made on quarterly basis on submission of bills along with all relevant details/including particulars of attendance / EPF/ESI remittance and other statutory provisions. The attendance particulars are subject to verificationwith TIDEL IBMS reports/records. | |||
1756 | 176.5 | LIFT WORKS | |||
1757 | 176.6 | PASSENGER LIFT / MAIN BUIDLING | 10 | Nos | |
1758 | 176.7 | Design, Supply, Erection, Testing and commissioning of passenger lift with Rose Gold Mirror Polished Finish with Etched Pattern on all four side Car enclosure to carry 24 passengers of 1632 kgs. of machine room, DCS 10 Car Group with DOP of 4 Nos. of wall mounted keypad DOP and 2 Nos. of Touch pedestal DOP in main entrance lobby and 4 Nos. of Wall mounted keypad DOP in all other landings in the existing lift well / shaft having minimum speed of 2.5 m/sec with a total travel of 90.6 (Approx) mtrs. Ground plus 21 upper floors, servicing 22 stops and 22 landings on the same side with / without attendant operation. The car cabin wall shall be by the Rose Gold mirror Polished Finish thickness of (1.2mm + 0.8mm) for all four sides and Landing Doors and cabin door with Rose Gold Mirror Polished Finish with all necessary safety features and in accordance with Lift Service particulars, General / Technical Specification, special condition etc. The design pattern shall be of Rose Gold mirror Polished Finish and shall be as per EC / Client requirement and approval. | |||
1759 | 176.8 | The lift shall be of excellent quality and shall have Micro stroke push buttons, intelligent group controls , floor announcement system, Gearless and other features as per detailed specification. The door for car cabin shall be with two panel central opening. The lift car shall have two parallel car operating control panels in automatic mode (with or without attendant) and from one panel in attendant mode. | |||
1760 | 176.9 | The lift equipment being machine room the machine will be fixed on top of the car.All the lift equipments, i/c car, car doors self-levelling devices, control devices, indicators, landing doors, indicators, buffer ropes safety devices i/c all wiring connection, interconnection and all connected equipments shall be as per specifications. | |||
1761 | 177 | The rate shall include approval / obtaining completion certificate from the electrical / lift inspectorate of Local Competent Electrical Authority for installation and commissioning of lifts before handing over the entire installation of the lift. | |||
1762 | 177.1 | Note: Tenderer should be given options for car Interiors. The final Approval given by EC / Client. | |||
1763 | 177.2 | Note: Control of Operation ( DCS Controller ) should follow as per Technical Specification | |||
1764 | 177.3 | SERVICE LIFT / MAIN BUIDLING | 1 | Nos | |
1765 | 177.4 | Design, manufacture, supply erect at site, test, commission Service lift 1632 kg load capacity Machine room, synchronizing motor -Gearless VVVF controller in the existing lift well / shaft having minimum speed of 1.75 m/sec with a total travel of 90.6 (Approx) mtrs. Ground plus 21 upper floors servicing 22 stops and 22 landings on same side with simplex group with/without attendant operations and with all necessary safety features and in accordance with Lift service particulars, General/Technical specifications, Special conditions etc. | |||
1766 | 177.5 | The lift shall be of excellent quality and shall have Micro stroke push buttons, intelligent controls of Single lift (as required), floor announcement system, Gearless and other features as per detailed specifications. The lift car shall have Operating control panels in automatic mode (with or without attendant) and from one panel in attendant mode. | |||
1767 | 177.6 | The lift equipment being machine room the machine will be fixed on top of the car. All the lift equipments, i/c car, car doors self-levelling devices, control devices, indicators, landing doors, indicators, buffer ropes safety devices i/c all wiring connection, interconnection and all connected equipments shall be as per specifications. | |||
1768 | 177.7 | The rate shall include approval / obtaining completion certificate from the electrical / lift inspectorate of Competent Electrical Authority for installation and commissioning of lifts before handing over the entire installation of the lift. | |||
1769 | 177.8 | Note: Tenderer Shall give options for car Interiors. The final Approval given by EC/Client. | |||
1770 | 177.9 | Note: Control of Operation ( Simplex elevator controller ) should follow as per Technical Specification | |||
1771 | 178 | FOOD COURT BUILDING (15 Passenger) | 1 | Nos | |
1772 | 178.1 | Design, Supply, Erection, Testing and commissioning of passenger lift with SS –vandal Proof Hairline Finish on all four side Car enclosure to carry 15 passengers of 1020 kgs of machine roomless. General / Technical Specification, special condition etc. The design pattern shall be of combination of shall be as per EC / Client requirement and approval. | |||
1773 | 178.2 | The lift shall be of excellent quality and shall have Micro stroke push buttons, intelligent controls of Single lift (as required), floor announcement system, Gearless and other features as per detailed specifications. The lift car shall have Operating control panels in automatic mode (with or without attendant) and from one panel in attendant mode. | |||
1774 | 178.3 | The lift equipment being machine room less, the machine will be fixed on the guide rail. All the lift equipments, i/c car, car doors self-levelling devices, control devices, indicators, landing doors, indicators, buffer ropes safety devices i/c all wiring connection, interconnection and all connected equipments shall be as per specifications. | |||
1775 | 178.4 | The rate shall include approval / obtaining completion certificate from the electrical / lift inspectorate of Local Competent Electrical Authority for installation and commissioning of lifts before handing over the entire installation of the lift. | |||
1776 | 178.5 | Note: Control of Operation ( Simplex elevator controller ) should follow as per Technical Specification | |||
1777 | 178.6 | FOOD COURT BUILDING (8 Passenger) | 1 | Nos | |
1778 | 178.7 | Design, Supply, Erection, Testing and commissioning of passenger lift with SS –vandal Proof Hairline Finish on all four side Car enclosure to carry 8 passengers of 544 kgs of machine roomless. General / Technical Specification, special condition etc. The design pattern shall be of combination of shall be as per EC / Client requirement and approval. | |||
1779 | 178.8 | The lift shall be of excellent quality and shall have Micro stroke push buttons, intelligent controls of Single lift (as required), floor announcement system, Gearless and other features as per detailed specifications. The lift car shall have Operating control panels in automatic mode (with or without attendant) and from one panel in attendant mode. | |||
1780 | 178.9 | The lift equipment being machine room less, the machine will be fixed on the guide rail. All the lift equipments, i/c car, car doors self-levelling devices, control devices, indicators, landing doors, indicators, buffer ropes safety devices i/c all wiring connection, interconnection and all connected equipments shall be as per specifications. | |||
1781 | 179 | The rate shall include approval / obtaining completion certificate from the electrical / lift inspectorate of Local Competent Electrical Authority for installation and commissioning of lifts before handing over the entire installation of the lift. | |||
1782 | 179.1 | Note: Control of Operation ( Simplex elevator controller ) should follow as per Technical Specification | |||
1783 | 179.2 | GOODS LIFT / SUBSTATION BUIDLING | 1 | Nos | |
1784 | 179.3 | Design, manufacture, supply erect at site, test, commission Goods lift 2000kg load capacity Machine room, synchronizing motor - Gearless VVVF controller in the existing lift well / shaft having minimum speed of 1.00 m/sec with a total travel of (13.7m Approx). General / Technical Specification, special condition etc. The design pattern shall be of combination of shall be as per EC / Client requirement and approval. | |||
1785 | 179.4 | The lift shall be of excellent quality and shall have Micro stroke push buttons, intelligent controls of Single lift (as required), floor announcement system, Gearless and other features as per detailed specifications. The lift car shall have Operating control panels in automatic mode (with or without attendant) and from one panel in attendant mode. | |||
1786 | 179.5 | The lift equipment being machine room the machine will be fixed on top of the car. All the lift equipments, i/c car, car doors self-levelling devices, control devices, indicators, landing doors, indicators, buffer ropes safety devices i/c all wiring connection, interconnection and all connected equipments shall be as per specifications. | |||
1787 | 179.6 | The rate shall include approval / obtaining completion certificate from the electrical / lift inspectorate of Competent Electrical Authority for installation and commissioning of lifts before handing over the entire installation of the lift. | |||
1788 | 179.7 | Note: Tenderer Shall give options for car Interiors. The final Approval given by EC/Client. | |||
1789 | 179.8 | Comprehensive Maintenance Works | |||
1790 | 179.9 | Comprehensive Maintenance Contract for 6 years after defect liability period for Tidel Park,Pattbiram. Total 7 Years including DLP. \nMaintenance of the system supplied, installed, Commissioned by the successful tenderer for Tidel Park,,Pattbiram for 7 years including the Defects Liability Period (DLP). This will include start up / commissioning, routine servicing, regular maintenance, preventive maintenance of equipments and components and break down repairs as and when occurred, ensuring that system does not remain out of service for a period more than 8 hours in case of major breakdowns and one hour in the case of minor breakdowns due to any unforeseen break down.The successful tenderer shall keep the essential spares for TIDEL Park,Pattabiram during the Defects Liability Period to avoid any delay in attending the faults/maintenace and also during the Comprehensive maintenace contract period.(First Year-Defect Liability Period).\nNote:Incharge shall report the status of lifts and maintenance services twice in a week as per TIDEL requirement.InCharge shall be stationed in their Head Office/ Branch Office | |||
1791 | 180 | AMC with Requirement for Lift Comprehensive Maintenace Services - required man power details as below. | |||
1792 | 180.1 | a. First Year (Defects Liability Period) - AMC - No Charges in DLP | |||
1793 | 180.2 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1794 | 180.3 | a. Second Year quote lumpsum fee for one year - AMC | 1 | No. | |
1795 | 180.4 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1796 | 180.5 | a. Third Year quote lumpsum fee for one year - AMC | 1 | No. | |
1797 | 180.6 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1798 | 180.7 | a. Fourth Year quote lumpsum fee for one year - AMC | 1 | No. | |
1799 | 180.8 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1800 | 180.9 | a. Fifth Year quote lumpsum fee for one year - AMC | 1 | No. | |
1801 | 181 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1802 | 181.1 | a. Sixth Year quote lumpsum fee for one year - AMC | 1 | No. | |
1803 | 181.2 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1804 | 181.3 | a. Seventh Year quote lumpsum fee for one year - AMC | 1 | No. | |
1805 | 181.4 | b. Technician - 24/7 (Qualification - Diploma / ITI with Experience - 5 Years) | 3 | Nos. | |
1806 | 181.5 | Note:- | |||
1807 | 181.6 | 1.The Escalation in the maintenance cost for consecutive years should not exceed 5% of the Lumpsum fee quoted for previous year by the tenderer. | |||
1808 | 181.7 | 2.The Contractor has to do comprehensive maintenance for 6 years for lifts at Tidel Park,Pattabiram after DLP. | |||
1809 | 181.8 | 3.The above man power is minimum requirement for routine operation and maintenance of Lift and Allied works. In case of annual maintenance, major Break downs, Emergency situations, etc. contractor has to provide required manpower, tools, tackles, etc to full fill the contractual requirement. If Contractor feels that the above minimum manpower is not adequate for routine maintenance of Lift and Allied works, the contractor shall engage more manpower with in quoted price. | |||
1810 | 181.9 | 4. In case the services are not upto the mark (or) inadequate manpower are provided and corrective actions are not taken within Ten days a penalty equal to One month of Maintenance charges of that month will be levied as decided by TIDEL. In case of such defaults for more than 3 Occurrence during contract period, TIDEL reserves right to terminate. | |||
1811 | 182 | 5.The payment will be made on quarterly basis on submission of bills along with all relevant details/including particulars of attendance / EPF/ESI remittance and other statutory provisions. The attendance particulars are subject to verificationwith TIDEL IBMS reports/records. | |||
1812 | 182.1 | Note:(Common for all the Works)The necessary civil works involved shall be carried out by the vendor with no extra cost unless otherwise specified in the respective items. |