Providing Electromechanical Infrastructure For Nfs Project At Iaf Station Bidar . 5Th Recall, NFS STATION IAF BIDAR-Karnataka

Bharat Sanchar Nigam Limited-BSNL has published Providing Electromechanical Infrastructure For Nfs Project At Iaf Station Bidar . 5Th Recall. Submission Date for this Tender is 15-12-2020. Electromechanical Work Tenders in NFS STATION IAF BIDAR Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

26100279
Corrigendum : Providing Electromechanical Infrastructure For Nfs Project At Iaf Station Bidar . 5Th Recall
Open Tender
Indian
Karnataka
NFS STATION IAF BIDAR
15-12-2020

Tender Details

Providing Electromechanical Infrastructure For Nfs Project At Iaf Station Bidar . 5Th Recall

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Dec-2020 CORRIGENDUM1 FOR ENIT47 Date 15-12-2020

Key Value

Document Fees
INR 590 /-
EMD
INR 21198.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Providing Electro-Mechanical Infrastructure for NFS Project (Package 1B) at IAF Station-1, BIDAR. (Sub Head:Providing Electrical Installation & Misc Works.) 5th Recall
Sl. No. Item Description Item Code / Make Quantity(3) Units
1 1 SUB HEAD - I: EI & Fans BI01010001010000000000000515BI0100001112
2 1.01 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. ( Legrand/Crabtree or SS Make )(Note: In areas where false ceiling are provided, termination of wires should be at the fittings. Flexible conduits from ceiling junction box to the fittings shall be provided duly coupled at both ends. This shall be included within the scope of point wiring.)(a)Group C BI01010001010000000000000515BI0100001113 50 point
3 1.02 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. (In Corridor) ( Legrand/Crabtree or SS Make ) BI01010001010000000000000515BI0100001114 2 point
4 1.03 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.(a)3x1.5Sqmm BI01010001010000000000000515BI0100001115 175 Mtr
5 1.04 (b)3x2.5Sqmm BI01010001010000000000000515BI0100001116 75 Mtr
6 1.05 (c)3x4Sqmm BI01010001010000000000000515BI0100001117 200 Mtr
7 1.06 (d)6x6Sqmm BI01010001010000000000000515BI0100001118 20 Mtr
8 1.07 (e)4 X 16 sq. mm + 2 X 16 sq. mm earth wire BI01010001010000000000000515BI0100001119 70 Mtr
9 2 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For Raw Power & UPS Power).(Legrand/Crabtree or SS Make )The word UPS 1 / UPS 2 shall be engraved/signwritten on all UPS sockets. The word RAW shall be engraved/signwritten on all RAW sockets BI01010001010000000000000515BI0100001120 19 Nos
10 2.01 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.(For Raw Power) ( Legrand/Crabtree or SS Make )The word RAW shall be engraved/signwritten on all RAW sockets BI01010001010000000000000515BI0100001121 16 Nos
11 2.02 Supplying and installing of following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. (a) 300 mm width X 50 mm depth X 1.6 mm thickness BI01010001010000000000000515BI0100001122 75 Mtr
12 2.03 Supplying and installing of following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. (a) 300 mm width X 50 mm depth X 1.6 mm thickness BI01010001010000000000000515BI0100001123 2 Nos
13 2.04 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee's with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. (a) 300 mm width X 50 mm depth X 1.6 mm thickness BI01010001010000000000000515BI0100001124 6 Nos
14 2.05 Supplying and installing following size of perforated painted with powder coating M.S. cable trays cross members with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. (a) 300 mm width X 50 mm depth X 1.6 mm thickness BI01010001010000000000000515BI0100001125 13 Nos
15 3 Supplying and Fixing of Polycarbonate cable management system of following sizes on the surface of wall/floor with necessary connected accessories like bends, Elbows, Tee, etc as required. [Make MK / LK or SS Make](a)50mm x 50mm BI01010001010000000000000515BI0100001126 20 Mtr
16 3.01 (b)100mm x 50mm BI01010001010000000000000515BI0100001127 20 Mtr
17 3.02 (c)50mm divider BI01010001010000000000000515BI0100001128 20 Mtr
18 4 Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.(a)20mm BI01010001010000000000000515BI0100001129 250 Mtr
19 4.01 (b)25mm BI01010001010000000000000515BI0100001130 200 Mtr
20 4.02 ( c )32mm BI01010001010000000000000515BI0100001131 125 Mtr
21 4.03 ( d )50mm BI01010001010000000000000515BI0100001132 50 Mtr
22 5 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing cable management/panel/surface/recessed steel/ PVC conduit as required.(a)1 Pair BI01010001010000000000000515BI0100001133 25 Mtr
23 6 PVC Insulated and sheathed tinned copper braided video core CCTV Cables of thickness 0.8mm , core 3+1 , Braid coverage 60% (Finolex or SS make) BI01010001010000000000000515BI0100001134 50 Mtr
24 7 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(a)Telephone socket outlet BI01010001010000000000000515BI0100001135 1 No
25 8 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.(a)1 or 2 Module (75mm X 75mm) BI01010001010000000000000515BI0100001136 1 No
26 8.01 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.(a)1 or 2 Module BI01010001010000000000000515BI0100001137 1 No
27 8.02 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(a) 50mm BI01010001010000000000000515BI0100001138 25 Mtrs
28 8.03 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps "C" curve, SP, MCB, in sheet steel enclosure,on surface or in recess, with chained metal cover for the socket out let and complete with connections,testing and commissioning etc.as required.(for Split AC)( Legrand/Hager or SS Make ) BI01010001010000000000000515BI0100001139 7 Nos
29 9 Supplying & Fixing wall mounting stabilizer unit, suitable for 1.5TR Air conditioner comprising of power relay of suitable range with input range 170V to 270V including time delay of 2 to 3minutes, low voltage and High Voltage cutoff etc complete as required(Make: M/s.V-Gaurd Model:VG400 or Similar superior make) BI01010001010000000000000515BI0100001140 7 Nos
30 10 Supplying and fixing following way single pole and neutral, sheet steel, MCB distribution board, 240V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/ Isolator) (Legrand or SS make) ( a ) 2 + 4 way/ 6 way , Double door (For Precision AC incomer) BI01010001010000000000000515BI0100001141 3 Nos
31 10.01 ( b ) 2 + 10 way/ 12 way , Double door (For UPS Emergency light) BI01010001010000000000000515BI0100001142 1 No
32 11 Supplying and fixing following way,horizontal type, three pole and neutal , sheet steel, MCB Distribution board, 415V,on surface/recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/ Isolator) (Legrand or SS make)(a)4 way (4 + 12), Double door (For Light & Power) BI01010001010000000000000515BI0100001143 2 Nos
33 12 S/F following electrical accessories in the existing Emergency light MCB DB i/c modification in the door, interconnection etc., as required.(a)RED & GREEN LED indicator lamps BI01010001010000000000000515BI0100001144 1 set
34 12.01 ( b )AC to AC MXO 40E (2 NO-2NC) contactor. Make. M/s L&T or SS Make BI01010001010000000000000515BI0100001145 1 No
35 12.02 ( c )Push Button BI01010001010000000000000515BI0100001146 1 No
36 13 Supplying and fixing rating, 240/415 volts miniature circuit breaker of following poles in the existing MCB DB complete with connections,testing and commissioning etc. as required. (Legrand or SS make)(a)6A Single pole [ B - curve ] for Lighting BI01010001010000000000000515BI0100001147 12 Nos
37 13.01 (b)6A Single pole [ D - curve ] for UPS Socket & Light plug BI01010001010000000000000515BI0100001148 8 Nos
38 13.02 ( c )16/25/32A Single pole [ C - curve ] for Power Plug BI01010001010000000000000515BI0100001149 12 Nos
39 13.03 (d)6A DP MCB [ D - curve ] for UPS Light BI01010001010000000000000515BI0100001150 1 Nos
40 13.04 (e)32A Four Pole MCB [ B - curve ] for Light TPDB BI01010001010000000000000515BI0100001151 1 Nos
41 13.05 (f)63A Four Pole MCB [ C - curve ] for Power TPDB & Precision AC unit incomer BI01010001010000000000000515BI0100001152 4 Nos
42 14 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. (For AFD Work) BI01010001010000000000000515BI0100001153 150 Mtrs
43 14.01 S/F End termination with brass termination gland for 2x1.5Sqmm Copper Conductor armoured UG cable etc as required. BI01010001010000000000000515BI0100001154 160 Nos
44 14.02 Supplying and fixing metal box of sizes 100 mm X 100 mm X 60 mm deep(nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.(For AFD Detectors) BI01010001010000000000000515BI0100001155 24 Nos
45 15 Supplying & fixing of following fittings / Fixtures i/c commissioning etc as required.(a)SITC of recess mounting LED light fitting 36watts, with all accessories in complete in the existing false ceiling i/c connections testing and commissioning etc as required. Make : ( Philips, Model RC365BLED33-5000 PSU OD WH ) or Ss make BI01010001010000000000000515BI0100001156 18 Nos
46 15.01 (b)SITC of surface mounting LED light 20W with all acceosies in complete on surface with LED bulb i/c connections testing and commissioning etc as required. Make : Philips,Model SM200C LED16S 6500 PSU OD WH ) or SS make BI01010001010000000000000515BI0100001157 23 Nos
47 15.02 ( c )Recessed Mounted LED downligter suitable for mounting in False Ceiling with all accessories in complete ( Make : Philips , Model DN190B LED3S-6500 PSU WH or similar superior make) for emergency light BI01010001010000000000000515BI0100001158 6 Nos
48 15.03 (d)Recessed Mounted LED Spot Light Luminire downligter with swivellig upto ± 25 degrees suitable for mounting in False Ceiling with 8 W(or 10W) LED type lamp (Bajaj BRDCLR8WWW or similar superior make) for Network Diagram / Safety poster BI01010001010000000000000515BI0100001159 7 Nos
49 15.04 (e)Surface mounted 4 feet 20 watt LED Batten fitting with LED tube (Philiphs Tarang /Wipro Garnet or similar superior make) BI01010001010000000000000515BI0100001160 6 Nos
50 15.05 (f)SITC LED Street light Luminare with all acessories in complete & suitable dia GI pipe bracket with fixing clamps for mounting on surface of wall , interconnection wire etc as required (Make: Phillips , Model : BRP022 LED 20 CW MR S1 PSU GR 4, IP 66 or similar superior make) BI01010001010000000000000515BI0100001161 7 Nos
51 16 SITC of 450 mm sweep, 1400 rpm heavy duty exhaust fan, metal body, 4 blades suitable for 230V AC supply i/c s/f Aluminium frame in the existing opening / window, S/F Louvers including making good the damages etc as required (Bajaj Supreme DLX HD 450mm or SS Make) BI01010001010000000000000515BI0100001162 2 Nos
52 17 SITC of 450mm sweep,1325rpm 3 blade wall mounting fan with thermal overload protection device with auto reset, oil reservoir lubrication, pull cord mechanism for on/off and speed control, aerodynamically designed aluminium blade, downward and upward tilit adjustment, 90 degree oscillation suitable for 230V AC supply etc as required. (Orient Tornado Wall II or SS Make) BI01010001010000000000000515BI0100001163 5 Nos
53 18 SITC of 450mm sweep wall mount industrial Air Circulator with impellar consisting of 3 blades, 1400 rpm with three speed control, heavy duty oscillation type propellar fan, Aluminium blade, close mesh gaurd suitable for 230V AC supply etc as required. (Crompton wall Air Circulator or SS Make) BI01010001010000000000000515BI0100001164 5 Nos
54 19 Supplying & fixing ISI mark ready to use Clean agent stored pressure type fire extinguisher of 2.0 kg capacity as per standard IS no. 15683:2006 with working pressure up to 15 kg/sqcm , fitted with pressure gauge, filled with listed environment friendly clean agent with hose of suitable length & horn duly charged along with suitable size of clamps to hold the fire extinguishers etc as required FIRE CLASS ABC (M/s Safex/Cease fire/Monark/Firex/ss make) \nNote- The firm shall submit mfgrs test cum guarantee certificate of each cylinder.(a)capacity 2 kg BI01010001010000000000000515BI0100001165 2 Nos
55 20 Supplying & fixing ISI mark ready to use CO2 type 4.5 Kg capacity fire extinguisher as per standard IS no. 15683:2006 with hose of suitable length, horn & duly charged along with suitable size of clamps to hold the fire extinguishers etc as required (M/s Safex/Cease fire/Monark/Firex/ss make) \nNote- The firm shall submit certificate of Department of Explosives (DOE)/CCE & mfgrs test cum guarantee certificate of each cylinder.) BI01010001010000000000000515BI0100001166 3 Nos
56 21 S/L Electrical insulating 2mm thick Rubber Mat in accordance with IS 15652/2006 (for 3.3KV) etc as required. BI01010001010000000000000515BI0100001167 4 Sqmtr
57 22 Supplying and fixing trunk box made of 16SWG MS sheet with openable covers including powder coated painting to match with existing panels/DB etc as required. BI01010001010000000000000515BI0100001168 2 Sqmtr
58 23 Providing and fixing 6 SWG dia G.I.wire on surface or in recess for loop earthing as required. BI01010001010000000000000515BI0100001169 150 Mtrs
59 24 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.(a)Above 35 sq. mm and upto 95 sq. mm BI01010001010000000000000515BI0100001170 10 Mtrs
60 25 Laying and Fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.(a)Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) BI01010001010000000000000515BI0100001171 20 Mtrs
61 26 Laying and Fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.(a)Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) BI01010001010000000000000515BI0100001172 20 Mtrs
62 27 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required.(a)Above 35 sq. mm and upto 95 sq. mm BI01010001010000000000000515BI0100001173 50 Mtrs
63 28 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(a)3 ½ x 95 Sqmm (45 mm) BI01010001010000000000000515BI0100001174 4 Nos
64 29 Providing, laying and fixing of 50mm dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75cm deep)and re-filling etc as required BI01010001010000000000000515BI0100001175 50 Mtrs
65 30 Supplying & Constructing masonary chamber 100x100x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for cable chamber, with water tight RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size), i/c necessary excavation, foundation concrete 1 :5:10( 1 Cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1 : 3(1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design: With common burnt clay F.P.S (non modular) bricks etc as reqd. BI01010001010000000000000515BI0100001176 2 Sets
66 31 Main M.V Panel (Power Room)SITC of MV Panel made up with CRCA steel sheet of 2mm thick for external panels & internal elements and 2.5mm thick for load bearing members , complying to latest IE rules suitable for Extensible type on both sides by addition of vertical sections after removal of the end cover, panel shall be powder coated with approved colour & shade panel shall have clear sign writing with fluorescent paint including supply & fixing the following switches & accessories, interconnection with suitable bus bar links for the incoming & outgoing & suitable size removable type gland plate at the bottom of sheet for outgoing cable, including earthing the switches with 2nos copper strip of size 20mmx5mm, providing tinned earth bus bar in the bottom, lifting hooks, providing C channel in bottom of size 100mmx50mmx5mm etc. as reqd. Details of switch gears & other accessories to be provided are listed below. (a)LCD Multifunction Meter (M/s. L & T make, series-4400 LCD meter CL 1 with RS 485, Cat No:WC440011OOOO) having parameters: V,A,F,PF,Kw, kWh, kVAh,Old Wh, On hours - 2 Nos(b)LED RYB Indication lamp (M/s.L & T, Vaishno or SS Make ) with toggle switch ,glass fuse with base - 2sets(c)C.T.150/5 AMP - 6 nos(d)250A, 4pole MCCB with thermal -Magnetic Release with 36KA Breaking Capacity, relay range of 100 to 125Amps. [L&T DN2-250D Cat No.CM92108OOL1OG or similar superior make] [For INCOMIMG] - 2Nos (e) Extended rotary handle (M/s. L&T Cat No. CM99830OOOO or similar superior make) -2Nos(f)ACC Spreader terminals DN2-250- 4Pole [ M/s. L&T Cat No. CM92007OOOO or similar superior make] - 2 Nos(g) DN2/DN3/DN4 Auxilary Contact 2C/O [M/s.L & T Cat No.CM99802OOOO or similar superior make ] - 2Nos (h) ACCDN2/DN3/DN4 Shunt release , 110/230/415V AC -Left [M/s.L & T Cat No.CM99805OOOO or similar superior make ] - 2Nos(i) Under Voltage release ACC DN2/DN3 UV 240V AC -Left [M/s.L & T or similar superior make] - 2Nos. (j) 100A, 4pole MCCB with 36KA Breaking Capacity, relay range of 63 to 80Amps. [M/s.L&T DN0-100D Cat No.CM97919OOJ2OG or similar superior make] [ Outgoing for 3 Nos Precision AC units, 2Nos UPS, 2Nos Eqpt Power Plant, 1No Spare] - Total- 8Nos(k) 63A , 415V , 4 Pole, 10kA, 'C ' Curve MCB ( L & T Cat No. BB40630C or SS make ) - 4 Nos (Light & power TPDB & Spare)(l) 32A , DPMCB,10kA , ' C ' Curve ( L & T Cat No.BB20320C or SS make ) - 7 Nos for Split AC(m)Electrical Mechanical interlocking between both incomers MCCB ( L & T or SS make )(n)4 Strip Aluminium bus bar of 300 Amps capacity- 1 set(o)Anti- condensation heaters & ventilating fan interlocked with thermostat, Wiring with Auto Manual Control.(p)Digital phase sequence indicator with MNX 25A contactor, Bell push switch , interconnectons etc., complete as required.Note:Panel Drawing is to be got approved from Engineer-in- Charge before fabrication). BI01010001010000000000000515BI0100001177 1 Job
67 32 UPS Distribution Panel (Power Room)Supply of wall mounting UPS Distribution Panel to server equipment, made up of 16G CRCA steel sheet, complying to latest IE rules suitable for extendable type , panel shall be powder coated with approved colour & shade panel shall have clear sign writing with fluorescent paint including supply & fixing the following switches & accessories, interconnection with suitable bus bar links for the incoming & outgoing & suitable size removable type gland plate at the bottom of sheet for outgoing cable, including earthing the switches with 2nos copper strip of size 20mmx5mm, providing tinned earth bus bar in the bottom, lifting hooks etc. as reqd. Details of switch gears & other accessories to be provided are listed below. (a)LCD Multifunction Meter (M/s. L & T make, series-4400 LCD meter CL 1 with RS 485, Cat No:WC440011OOOO) having parameters: V,A,F,PF,Kw, kWh, kVAh,Old Wh, On hours - 1 No(b)LED RYB Indication lamp ( M/s. L & T/Vaishno or SS make) with toggle switch with glass fuse with base-1set (c)C.T. 100/5 AMP -3 Nos(d)32 A, FP, 10kA, MCB D Curve MCB - 1 No [ Incoming] ( L & T Cat No.BB40320D or SS Make )(e)32A DP ELCB MCB - 3 Nos with 100mA rated sensitivity & Max permissible earth fault loop impedance of 1650 ohms. ( Havells or SS Make ).(f)6A SP MCB (10KA) C Curve - 18 Nos (Outgoing to server eqpt & Emergency Light) ( L & T Cat No.BB10060C or SS Make ) (g)4 Strip Copper bus bar of 100 Amps capacity- 1 set BI01010001010000000000000515BI0100001178 1 Job
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail