Public Health Engineering Department-PHED has published Pipe Line Crossing At Nhai And Railways For Universal Coverage Of Water Supply To Jharsuguda Municipality Pipe Line Crossing At Nhai And Railways For Universal Coverage Of Water Supply To Jharsuguda Municipality 608 Mtrs Of Crossing. Submission Date for this Tender is 09-12-2020. Pipe Laying Tenders in Jharsuguda Odisha. Bidders can get complete Tender details and download the document.
Name of Work: Pipe line crossing at NHAI / Railways for Universal coverage of water supply to Jharsuguda Municipality. (608 mtrs of crossing) | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Crossing National Highway / R&B Major Roads at different location of Jharsuguda Municipality | BI01010001010000000000000515BI0100001113 | ||
2 | 2 | Pahadi Mandir Chowk | BI01010001010000000000000515BI0100001114 | ||
3 | 3 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 600 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | BI01010001010000000000000515BI0100001115 | ||
4 | 4 | For 300 mm dia Carrier Pipe | BI01010001010000000000000515BI0100001116 | 30 | Mtr |
5 | 5 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | BI01010001010000000000000515BI0100001117 | ||
6 | 6 | 610 mm OD & 10mm thick for Casing Pipe | BI01010001010000000000000515BI0100001118 | 30 | Mtr |
7 | 7 | 323.93 mm OD & 7.10mm thick for Carrier Pipe | BI01010001010000000000000515BI0100001119 | 30 | Mtr |
8 | 8 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | BI01010001010000000000000515BI0100001120 | 20 | each |
9 | 9 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | BI01010001010000000000000515BI0100001121 | 6 | Mtr |
10 | 10 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.0 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | BI01010001010000000000000515BI0100001122 | ||
11 | 11 | 300 mm Diameter | BI01010001010000000000000515BI0100001123 | 1 | each |
12 | 12 | Badheimunda Chowk - I | BI01010001010000000000000515BI0100001125 | ||
13 | 13 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 400 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | BI01010001010000000000000515BI0100001126 | ||
14 | 14 | For 250 mm dia Carrier Pipe | BI01010001010000000000000515BI0100001127 | 33 | Mtr |
15 | 15 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
16 | 16 | 406.4mm OD & 8.8mm thick for Casing Pipe | 33 | Mtr | |
17 | 17 | 255.6mm OD & 6.3mm thick for Carrier Pipe | 33 | Mtr | |
18 | 18 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 28 | each | |
19 | 19 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
20 | 20 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.0 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
21 | 21 | 250 mm Diameter | 1 | each | |
22 | 22 | Badheimunda Chowk - II | |||
23 | 23 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 400 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | |||
24 | 24 | For 200 mm dia Carrier Pipe | 40 | Mtr | |
25 | 25 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
26 | 26 | 406.4mm OD & 8.8mm thick for Casing Pipe | 40 | Mtr | |
27 | 27 | 219.1mm OD & 6.3mm thick for Carrier Pipe | 40 | Mtr | |
28 | 28 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 21 | each | |
29 | 29 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
30 | 30 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.0 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
31 | 31 | 200 mm Diameter | 1 | each | |
32 | 32 | L.N College Square | |||
33 | 33 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 300 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | |||
34 | 34 | For 150 mm dia Carrier Pipe | 37 | Mtr | |
35 | 35 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
36 | 36 | 323.93mm OD & 7.10mm thick for Casing Pipe | 37 | Mtr | |
37 | 37 | 168.3mm OD &5.4mm thick for Carrier Pipe | 37 | Mtr | |
38 | 38 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 25 | each | |
39 | 39 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
40 | 40 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.0 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
41 | 41 | 150 mm Diameter | 1 | each | |
42 | 42 | Beheramal Chowk -I | |||
43 | 43 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 600 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | |||
44 | 44 | For 400 mm dia Carrier Pipe | 40 | Mtr | |
45 | 45 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
46 | 46 | 610 mm OD & 10mm thick for Casing Pipe | 40 | Mtr | |
47 | 47 | 406.4mm OD & 8.8mm thick for Carrier Pipe | 40 | Mtr | |
48 | 48 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 21 | each | |
49 | 49 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
50 | 50 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
51 | 51 | 400 mm Diameter | 1 | each | |
52 | 52 | Beheramal Chowk -II | |||
53 | 53 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 400 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | |||
54 | 54 | For 200 mm dia Carrier Pipe | 40 | Mtr | |
55 | 55 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
56 | 56 | 406.4mm OD & 8.8mm thick for Casing Pipe | 40 | Mtr | |
57 | 57 | 219.1mm OD & 6.3mm thick for Carrier Pipe | 40 | Mtr | |
58 | 58 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 25 | each | |
59 | 59 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
60 | 60 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
61 | 61 | 200 mm Diameter | 1 | each | |
62 | 62 | SP Office Square | |||
63 | 63 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 600 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | |||
64 | 64 | For 400 mm dia Carrier Pipe | 40 | Mtr | |
65 | 65 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
66 | 66 | 610 mm OD & 10mm thick for Casing Pipe | 40 | Mtr | |
67 | 67 | 406.4mm OD & 8.8mm thick for Carrier Pipe | 40 | Mtr | |
68 | 68 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 21 | each | |
69 | 69 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
70 | 70 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
71 | 71 | 400 mm Diameter | 1 | each | |
72 | 72 | Prasanna Panda Chowk | |||
73 | 73 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 600 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | |||
74 | 74 | For 400 mm dia Carrier Pipe | 54 | Mtr | |
75 | 75 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
76 | 76 | 610 mm OD & 12.5mm thick for Casing Pipe | 54 | Mtr | |
77 | 77 | 406.4mm OD & 8.8mm thick for Carrier Pipe | 54 | Mtr | |
78 | 78 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 27 | each | |
79 | 79 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | 6 | Mtr | |
80 | 80 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
81 | 81 | 400 mm Diameter | 1 | each | |
82 | 82 | Jharianair | |||
83 | 83 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across National Highway by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 300 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of National Highway & direction of Engineer-In-Charge & approved by National Highway Department etc all complete. | 56 | Mtr | |
84 | 84 | For 150 mm dia Carrier Pipe | |||
85 | 85 | Providing and laying M.S pipes of all classes confirming to IS:3601 of the following outer diameter with internal cement mortar lining and outside painting etc. all complete as per specification and direction of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | 56 | Mtr | |
86 | 86 | 323.93 mm OD & 5.6mm thick for Casing Pipe | 56 | Mtr | |
87 | 87 | 168.3mm OD & 4.5mm thick for Carrier Pipe | 27 | each | |
88 | 88 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per direction of Engineer-In-Charge. | 6 | Mtr | |
89 | 89 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification and direction of Engineer-In-Charge. | |||
90 | 90 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.0(IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
91 | 91 | 150 mm Diameter | 1 | each | |
92 | 92 | Crossing Railway Track at different location of Jharsuguda Municipality | |||
93 | 93 | Panchpada Road (ROB) | |||
94 | 94 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across Railway line by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 400 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of Railway Track (BS 105: Guidelines on Pipeline Crossings Under Railway Track) & direction of Engineer-In-Charge & approved by Railway department etc all complete. | |||
95 | 95 | For 200 mm dia Carrier Pipe | 46 | Mtr | |
96 | 96 | Supplying all materials, labour and T&P for Providing M.S Pipes of all classes confirming to IS:3589 & IS:3601 of the following outer diameter with internal grit blasted to Sa 2.5 to ISO : 8501-1 followed by 500-700 micron two component 100% soild solvent free liquid epoxy coating all complete as per AWWA-210-07 and diretion of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
97 | 97 | 406.4mm OD & 8.8mm thick for Casing Pipe | 46 | Mtr | |
98 | 98 | 219.1mm OD & 6.3mm thick for Carrier Pipe | 46 | Mtr | |
99 | 99 | Supplying all materials, labour and T&P for Providing Cathodic Protection system on Casing Pipe all complete as per specification and diretion of Engineer-In-Charge inclduing soil restivity test, supplying of all labour, material, tools & plants required to perferm the work. (the choice of sacrificial anodes for cathodic protection depends upon the soil resistivity valves. If this valve is within 1000 Ohms-cm, Zinc anodes will be used and if the valve in between 1000-7500 Ohms-cm , Mg anodes will be used) | 46 | Mtr | |
100 | 100 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per specification ((BS 105;Guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 25 | each | |
101 | 101 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification (BS 105:guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 5 | Mtr | |
102 | 102 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
103 | 103 | 200 mm Diameter | 1 | each | |
104 | 104 | OSAP (ROB) | |||
105 | 105 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across Railway line by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 400 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of Railway Track (BS 105: Guidelines on Pipeline Crossings Under Railway Track) & direction of Engineer-In-Charge & approved by Railway department etc all complete. | |||
106 | 106 | For 200 mm dia Carrier Pipe | 46 | Mtr | |
107 | 107 | Supplying all materials, labour and T&P for Providing M.S Pipes of all classes confirming to IS:3589 & IS:3601 of the following outer diameter with internal grit blasted to Sa 2.5 to ISO : 8501-1 followed by 500-700 micron two component 100% soild solvent free liquid epoxy coating all complete as per AWWA-210-07 and diretion of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
108 | 108 | 406.4mm OD & 8.8mm thick for Casing Pipe | 46 | Mtr | |
109 | 109 | 219.1mm OD & 6.3mm thick for Carrier Pipe | 46 | Mtr | |
110 | 110 | Supplying all materials, labour and T&P for Providing Cathodic Protection system on Casing Pipe all complete as per specification and diretion of Engineer-In-Charge inclduing soil restivity test, supplying of all labour, material, tools & plants required to perferm the work. (the choice of sacrificial anodes for cathodic protection depends upon the soil resistivity valves. If this valve is within 1000 Ohms-cm, Zinc anodes will be used and if the valve in between 1000-7500 Ohms-cm , Mg anodes will be used) | 46 | Mtr | |
111 | 111 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per specification ((BS 105;Guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 23 | each | |
112 | 112 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification (BS 105:guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 6 | Mtr | |
113 | 113 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
114 | 114 | 200 mm Diameter | 1 | each | |
115 | 115 | Balijori (ROB) | |||
116 | 116 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across Railway line by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 600 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of Railway Track (BS 105: Guidelines on Pipeline Crossings Under Railway Track) & direction of Engineer-In-Charge & approved by Railway department etc all complete. | |||
117 | 117 | For 400 mm dia Carrier Pipe | 45 | Mtr | |
118 | 118 | Supplying all materials, labour and T&P for Providing M.S Pipes of all classes confirming to IS:3589 & IS:3601 of the following outer diameter with internal grit blasted to Sa 2.5 to ISO : 8501-1 followed by 500-700 micron two component 100% soild solvent free liquid epoxy coating all complete as per AWWA-210-07 and diretion of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
119 | 119 | 610mm OD & 10mm thick for Casing Pipe | 45 | Mtr | |
120 | 120 | 406.4mm OD & 8.8mm thick for Carrier Pipe | 45 | Mtr | |
121 | 121 | Supplying all materials, labour and T&P for Providing Cathodic Protection system on Casing Pipe all complete as per specification and diretion of Engineer-In-Charge inclduing soil restivity test, supplying of all labour, material, tools & plants required to perferm the work. (the choice of sacrificial anodes for cathodic protection depends upon the soil resistivity valves. If this valve is within 1000 Ohms-cm, Zinc anodes will be used and if the valve in between 1000-7500 Ohms-cm , Mg anodes will be used) | 45 | Mtr | |
122 | 122 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per specification ((BS 105;Guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 25 | each | |
123 | 123 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification (BS 105:guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 6 | Mtr | |
124 | 124 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
125 | 125 | 400 mm Diameter | 1 | each | |
126 | 126 | Balijori | |||
127 | 127 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across Railway line by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 300 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of Railway Track (BS 105: Guidelines on Pipeline Crossings Under Railway Track) & direction of Engineer-In-Charge & approved by Railway department etc all complete. | |||
128 | 128 | For 150 mm dia Carrier Pipe | 30 | Mtr | |
129 | 129 | Supplying all materials, labour and T&P for Providing M.S Pipes of all classes confirming to IS:3589 & IS:3601 of the following outer diameter with internal grit blasted to Sa 2.5 to ISO : 8501-1 followed by 500-700 micron two component 100% soild solvent free liquid epoxy coating all complete as per AWWA-210-07 and diretion of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
130 | 130 | 323.9mm OD & 5.6mm thick for Casing Pipe | 30 | Mtr | |
131 | 131 | 168.3mm OD & 5.4mm thick for Carrier Pipe | 30 | Mtr | |
132 | 132 | Supplying all materials, labour and T&P for Providing Cathodic Protection system on Casing Pipe all complete as per specification and diretion of Engineer-In-Charge inclduing soil restivity test, supplying of all labour, material, tools & plants required to perferm the work. (the choice of sacrificial anodes for cathodic protection depends upon the soil resistivity valves. If this valve is within 1000 Ohms-cm, Zinc anodes will be used and if the valve in between 1000-7500 Ohms-cm , Mg anodes will be used) | 30 | Mtr | |
133 | 133 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per specification ((BS 105;Guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 20 | each | |
134 | 134 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification (BS 105:guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 6 | Mtr | |
135 | 135 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.0 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
136 | 136 | 150 mm Diameter | 1 | each | |
137 | 137 | Cox Colony | |||
138 | 138 | Supply all material, labour, T&P for crossing of M.S/D.I pipe line across Railway line by Horizontal thrust boring method (In slope of 1 in 40 towards downsteam) including encasing the pipe line 600 mm dia inclduing excavation of push pit, dewatering if any, laying & joining of casing & carrier pipe, capping & sealing casing pipe etc for carrier pipe & installation of sign boards on either side of Railway Track (BS 105: Guidelines on Pipeline Crossings Under Railway Track) & direction of Engineer-In-Charge & approved by Railway department etc all complete. | |||
139 | 139 | For 350 mm dia Carrier Pipe | 71 | Mtr | |
140 | 140 | Supplying all materials, labour and T&P for Providing M.S Pipes of all classes confirming to IS:3589 & IS:3601 of the following outer diameter with internal grit blasted to Sa 2.5 to ISO : 8501-1 followed by 500-700 micron two component 100% soild solvent free liquid epoxy coating all complete as per AWWA-210-07 and diretion of Engineer-In-Charge inclduing supplying of all labour, material, tools & plants required to perform the work. | |||
141 | 141 | 610mm OD & 10mm thick for Casing Pipe | 71 | Mtr | |
142 | 142 | 355.6mm OD & 8mm thick for Carrier Pipe | 71 | Mtr | |
143 | 143 | Supplying all materials, labour and T&P for Providing Cathodic Protection system on Casing Pipe all complete as per specification and diretion of Engineer-In-Charge inclduing soil restivity test, supplying of all labour, material, tools & plants required to perferm the work. (the choice of sacrificial anodes for cathodic protection depends upon the soil resistivity valves. If this valve is within 1000 Ohms-cm, Zinc anodes will be used and if the valve in between 1000-7500 Ohms-cm , Mg anodes will be used) | 71 | Mtr | |
144 | 144 | Supply all materials, labour and T&P for providing and fixing High Denisity Polyethylene spacers between casing & Carrier Pipe to avoid contact 2.5m c/c all complete as per specification ((BS 105;Guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 37 | each | |
145 | 145 | Supply all materials, labour and T&P for providing and fixing 50 mm Dia Vent / Drain Pipe at both ends of Casing Pipe including cutting, fixing, joing, etc all complete as per specification (BS 105:guidelines on Pipeline Crossing under Railway Track) and direction of Engineer-In-Charge. | 5 | Mtr | |
146 | 146 | Supply, Installation & Testing of Cast Iron Sluice Valve of RATING PN - 1.6 (IS:14846) with double flanged ends for water works purpose conforming to IS:2685 for the following rating and nominal diameters as per specification complete including supplying of all labour, material, tools & plants required to perform the work (inclduing cost of Nut bolt & Washer, Rubber Insertion sheet, etc.) | |||
147 | 147 | 350 mm Diameter | 1 | each |