Repair /Maintenance Of Of Earthing System And Lightning Protection In The Area Of Age E/M-I Under Ge ( Af ) Palam , Delhi Cantt-10, GE (AF) PALAM-Delhi

Military Engineer Services-MES has published Repair /Maintenance Of Of Earthing System And Lightning Protection In The Area Of Age E/M-I Under Ge ( Af ) Palam , Delhi Cantt-10. Submission Date for this Tender is 22-12-2020. Electrification Work Tenders in GE (AF) PALAM Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

26083141
Corrigendum : Repair /Maintenance Of Of Earthing System And Lightning Protection In The Area Of Age E/M-I Under Ge ( Af ) Palam , Delhi Cantt-10
Open Tender
Indian
Delhi
GE (AF) PALAM
22-12-2020

Tender Details

Repair / Maintenance Of Of Earthing System And Lightning Protection In The Area Of Age E / M-I Under Ge ( Af ) Palam , Delhi Cantt-10

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 27-Nov-2020 CORRIGENDUM NO 02 Terms and Conditions 15-12-2020
2 15-Dec-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 22-12-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 60000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR /MAINTENANCE OF OF EARTHING SYSTEM AND LIGHTNING PROTECTION IN THE AREA OF AGE E/M-I UNDER GE (AF) PALAM, DELHI CANTT-10
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking out unserviceable/damaged Galvanised Iron /Copper strips of any description and in any position from hanger , roof, wall etc in any height all as specified and directed by Engr-in-Charge 750 RM
2 2 Taking out unserviceable/damaged aluminium strips of any description and in any position from hanger , roof, wall etc in any height all as specified and directed by Engr-in-Charge 300 RM
3 3 Taking out unserviceable/damaged air termination rod of copper/aluminium in any shape or size from hanger , roof, wall etc in any height all as specified and directed by Engr-in-Charge. 80 EACH
4 4 S&F for copper strip of size 20 x 3mm for earth continuity conductor including fixing on porcelain holder insulator for support on wall / roof etc with suitable size screw , nut bolts etc complete all as sprecified and directed by Engr-in-Charge. 450 RM
5 5 S&F for galvanised iron strip of size 32x6mm including fixing on porcelain holder insulator for support on wall / roof etc with suitable size screw , nut bolts etc complete all as specified and directed by Engr-in Charge. 300 RM
6 6 S&F for aluminium strip of size 25x6 mm including fixing on porcelain holder insulator for support on wall / roof etc with suitable size screw , nut bolts etc complete all as specified and directed by Engr-in-Charge. 300 RM
7 7 S&F for air termination, single pointed,copper rod 12mm dia and 300mm long complete all as specified and directed by Engr-in-Charge . 40 EACH
8 8 S&F for air termination, single pointed,aluminium rod 12mm dia and 300mm long complete all as specified and directed by Engr-in-Charge . 40 EACH
9 9 S&F in replacement of test point terminal block made of gun metal or phosphorus bronze of size 75mmx75mmx25mm drilled and screwed including 3 Nos. 8 mm dia 25mm longh head screw complete all as specified and directed by Engr-in-Charge. 25 EACH
10 10 S&F in replacement of PVC insulated multistranded single core copper conductor 1100 Volt grade FRLS of size 25 Sqmm with jointing with appropriate size of copper cable lugs and nut , bolt etc complete all as specified and directed by Engr-in-Charge . 400 RM
11 11 S&F in replacement of PVC insulated multistranded single core copper conductor 1100 Volt grade FRLS of size 10 Sqmm with jointing with appropriate size of copper cable lugs and nut , bolt etc complete all as specified and directed by Engr-in-Charge . 200 RM
12 12 Supply & fixing in replacement of GI pipe medium grade 15 mm dia with all fittings for laying in trenches, wall, floor etc all as specified and directed by Engr-in-Charge. 250 RM
13 13 M & L for earthing complete with copper earth plate electric 60 cm x 60 cm x 3.15mm buried directly and vertically in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to Copper strip 20mm x 3 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised steel and including necessary earth work in any type of earth/rock, PCC 1:3:6 type C-2 in chamber and 50mm thick precast chamber cover of RCC 1:2:4 type B-1 with 8 mm dia TMT reinforcement at 100mm both ways, 20mm dia GI watering pipe ,40mm dia GI light grade protection pipe for copper strip , salt, coal, magnesium sulphate and water funnel etc complete all as per Electrical plate No 4 of SSR Part I.( NOTE:-To obtained earth resistance value and prepare test sheet of newly constructed earth pit shall be the responsibility of contractor. If the desired earth resistance as per equipment requirement is not obtained, the earthing shall be re-done by contractor without any extra cost to the Govt . \n\n 20 EACH
14 14 Supply, installation, testing & commissioning of maintenance free earth (grounding) Elancrete electrode of size 85mm Dia x 3000 mm long with 17.2 mm Copper Bonded MS Conductor precast or in-situ cast in high purity electrically conductive granular material having ultra low resistive value of 0.001 Ohm-m. Electrode made of conductive earth enhancing material mixed with cement in the ration 3:1 to encase or backfill the voids surrounding the 17.2 mm Cu Bonded MS conductor or other metal components placed in augured bore hole of 85 mm dia x 3000 mm depth, resulting to increase in the effective surface area of the earth electrode or grids to lower the resistance. Earth enhancing material should not leach chemicals into the adjacent soil or underground water channels and should be in pH neutral range. Earth enhancing material should permanently protect the encased metal componets of the earthing systems. All hardware like nuts, bolts and washers should be of Stainless steel. Electrode should withstand fault current upto 35 KA for 1 second. Electrode's top terminal be sealed permanently packed with conductive concrete and Cu bonded MS / GI extension strip taken out be terminated on to earth bus bar. \n 42 EACH
15 15 Material, Labour and testing of electrically conductive material earthing for achieving Earth Resistance value below 1 Ohm by developing a bore in the ground of 30.5 meters depth and providing copper bonded MS rod of dia 17.2 mm, length 30.5 m electrode embedded with Marconite brand electrically conductive material of 100 Dia and length 30.5 m mixed with cement at the ratio of 3:1, complete with copper bonded MS flat test link of size 50 mm X 6 mm X 200 mm, RCC pit cover including brazing of all the joints upto test point complete all as specified and directed by Engr-in-Charge. Make: Marconite or its equivalent. 4 EACH
16 16 M & L in replacement of earthing with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI strip 32x6mm as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) of 1:3:6 type C-1 mix using 20mm graded stone aggregate with fair finish internal surface of concrete chamber with 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of mix 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe of 20mm bore medium grade and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed by Engr-in-Charge. 25 EACH
17 17 M & L for GI pipe medium grade 40 mm dia with all fittings and welding works complete including taking out old unserviceable GI pipe all as specified and directed by Engr-in-Charge. 60 RM
18 18 M&L for cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregate complete all as specified and directed by Engr-in-Charge. 6 CUM
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail