| 1 | 1 | Supply, installation, testing and commissioning of electric traction lift as per following specifications. The lift should comply with ISI specifications with latest technology equipped with following details | | 2 | No |
|---|
| 2 | 2 | Installation of new lift includes all required civil works such as two coat of acrylic distemper (as per PWD detailed specifications after proper cleaning of existing surface) of lift well, hoist way and machine room, cleaning of pit and repairing of pit floors and other work related to machine room repairs to accommodate the new equipment, repairing of walls if required and making it suitable to accommodate Stainless steel doors at all floors, fixing of bracket, scaffolding, minor building works etc. With cost of materials, labour, T&P, taxes etc. for proper completion of work as per various regulations of Fire department and statutes and as per direction of authorized representative of Architect incharge. | | | |
|---|
| 3 | 3 | Note:- The work will have comprehensive defect liability period of one years from the date of handing over of lift. For the performance of the same, shall retain an amount equivalent 10% of quoted cost in the form of cash/bank guarantee in the format as security deposit towards performance during Defect Liability Period. | | | |
|---|
| 4 | 4 | Specifications:- | | | |
|---|
| 5 | 5 | (a) Load & Speed: About 1088 kg. (16 person) @ 1 m.p.s. | | | |
|---|
| 6 | 6 | (b) Travel : Ground, 1st Floor & 2nd Floor, about 8 meters | | | |
|---|
| 7 | 7 | (c) Stop & Opening : 3 stops /3 openings (all central opening on same side) | | | |
|---|
| 8 | 8 | (d) Power supply: 415 volts, 3 phase 50 hertz alternating current | | | |
|---|
| 9 | 9 | (e) Control: A.C. (VVVF) DriveVariable Voltage Variable Frequency | | | |
|---|
| 10 | 10 | (f) Operation: microprocessor based simplex collective selective control with provision of attendant control | | | |
|---|
| 11 | 11 | (g) Machine : GEARLESS (Located in shaft on top of guide rails | | | |
|---|
| 12 | 12 | (h) Car size: About 1600mm wide x 1500 mm deep & 2200 mm height inside dimensions. | | | |
|---|
| 13 | 13 | (i) Hoist Way available: About ( 2550 mm ) x (2000mm) deep inside dimensions | | | |
|---|
| 14 | 14 | (j) Car Enclosure finish : Stainless steel honey comb/Dama/Etching finish with cross flow fan for ventiliation and led | | | |
|---|
| 15 | 15 | (k) Floor finish –Vinyl tiles\nFalse ceiling finish- Stainless steel mirror finish\nHan rails-Stainless steel honey comb/Dama/Etching finish on rear car panels\nCar door finish- Stainless steel honey comb/Dama/Etching finish\nLanding door finish- tainless steel honey comb/Dama/Etching finish | | | |
|---|
| 16 | 16 | L)Door opening about 900 mm wide x 2000 mm H | | | |
|---|
| 17 | 17 | (m) Hoist way entrance: (Outer doors) Protected by Stainless steel finish door. | | | |
|---|
| 18 | 18 | (n) Door Operation & protection: Automatic. | | | |
|---|
| 19 | 19 | (o) Elevator pit depth:1350 mm | | | |
|---|
| 20 | 20 | (P) Over head-4000 mm | | | |
|---|
| 21 | 21 | (Q)Traction Media- Flat coated steel belt | | | |
|---|
| 22 | 22 | (R)Car Position indicated- Monochrome LCD- Blue background & white front dot matrix (LED) scrolling display | | | |
|---|
| 23 | 23 | (S) Hall Fixture face plate- Stainless steel hairline | | | |
|---|
| 24 | 24 | (T) Hall Button arrangement -LCD Monochrome type | | | |
|---|
| 25 | 25 | (U) Standard Fixtures:- Anti nuisance car call protection\nOverload device\nNudging\nEmergency fireman service\nEmergency Car light unit\nInfrared curtain door protection\nDoor time protection\nEmergency Alarm button\nExtra door time of lobby & parking\ndoor open & close button\nManual rescue operation\nBelt inspection drive\nAuto fan Cut off\n | | | |
|---|
| 26 | 26 | (V) Operation included automatic rescue operation, voice synthisizer, intercom | | | |
|---|