Defence Statutory Bodies & Commissions/Committees Closing in 0 days TDR #26051242

Special Repair To Under Ground Cable Connections An Feeder Panels At 1841 Pnr Unit At Karcham And Provn Of 100 Kva Stablizer Alongwith Lt Cable And Panel Board Installation Of Op Work Shelter At Central Mi Room Of 2136 Fd Hosp At Cholling Area At Kar

Issued by Statutory Bodies & Commissions/Committees · KARCHAM, Himachal Pradesh
Tender Value
28 Lakhs
Estimated cost
Bid Submission
23 Dec 2020
0 days left
EMD
56000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
KARCHAM → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Special Repair To Under Ground Cable Connections An Feeder Panels At 1841 Pnr Unit At Karcham And Provn Of 100 Kva Stablizer Alongwith Lt Cable And Panel Board Installation Of Op Work Shelter At Central Mi Room Of 2136 Fd Hosp At Cholling Area At Kar

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 27-Nov-2020 AMENDMENT IN CRITICAL DATES Date 07-Dec-2020
2 03-Dec-2020 AMENDMENTS TO CRITICAL DATES Date 16-Dec-2020
3 16-Dec-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 23-Dec-2020

BOQ

Name of Work : SPECIAL REPAIR TO UNDER GROUND CABLE CONNECTIONS & FEEDER PANELS AT 1841 PNR UNIT AT KARCHAM AND PROVN OF 100 KVA STABLIZER ALONGWITH LT CABLE AND PANEL BOARD INSTALLATION OF OP WORK SHELTER AT CENTRAL MI ROOM OF 2136 FD HOSP AT CHOLLING AREA AT KARCHAM IN THE AREA OF AGE E/M (WE) POOH UNDER GE 863 EWS
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 m in depth in a hard/dense soil for laying underground cables/ errection of steeltubular poles / stay pit etc.complete all as specified and directed.300Cum
22Excavation in trenches not exc 1.5 mtr wide and depth exc 1.5 m but not exc 3 mtr deep in hard/dense soil for laying underground cables/ errection of steeltubular poles / stay pit etc.complete all as specified and directed.184Cum
33M&L for sand cushioning the UG cable screened unwashed river sand and punning for cushioning to cable complete all as specified and directed.145CUM
44M&L for laying dry bricks old size with subclass 'B' made of burnt clay best quality locally available with permissible tolerance, laid straight in trenches for protection of cable complete all as specified and directed.13.8Per 1000 Nos
55Returning, filling in incl spreading,levelling watering and well ramming in layer n exc .25 cm in soil complete all as specified and directed.283Cum
66Removing excavated surplus material to a distance n.exc 50 m and depostimg where directed at alevel n exc. 1.5 m above the starting point in any type of soil complete all as specified and directed.201Cum
77Material & labour for earthing complete with galvanised steel earth plate electrode 60x60cmx6.30 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to galvanised earth wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or of steel all as shown in electrical plate No 3 of SSR part-I 2009 connected to main switch board all as specified and testing on completion including necessary excavation, earthwork, PCC works in 1:2:4 type B-I (using 20 mm graded stone aggregate) and CI earth pit cover with watering pipe 20mm dia GI pipe medium grade, funnel with wire mesh and lugs and GI pipe 15 mm dia of light grade for protection of earth lead including taking out /dismantling of old earthing complete all as specified and directed.4Each
88Supply and laying in replacement GI pipe, 50mm bore dia, light grade for cable protection complete with all fittings fixed to wall or laid in floor/road crossing or on pole, complete all as specified and directed.24RM
99All as per item No 8 here-in-before but for 80 mm bore dia12RM
1010Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminium conductor for working voltage upto and including 1100 volts, cross sectional area of cable 25 sq mm 3.5 core laid in trenches/fixed on pole/wall/passed through pipe including taking out old XLPE Cable complete all as specified and directed.300RM
1111All as per item no 10 above but size 16 sqmm 3.5 core140RM
1212All as per item no 10 above but size 35 sqmm 3.5 core150RM
1313All as per item no 10 above but size 50 sqmm 3.5 core250RM
1414All as per item no 10 above but size70 sqmm 3.5 core250RM
1515All as per item no 10 above but size 95 sqmm 3.5 core400RM
1616Supply, install, testing and commissioning LT panel cubical panel of double door outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangment both in front and rear side (Independent door for each item on front side) mounted 4 Nos angle iron 50 x 50 x 6mm, 30cm long, embedded in PCC 1:3:6 type C2 complete all as specified and directed incl provision of following accessories/equipment incl cable gland etc suitable for fixing under mentioned items including taking out/dismantling of old LT Panel :- \n(a) Aluminium bus bar chamber capacity 800 Amps 3 Phase 4 wire duly insulated with PVC sleeves (As per colour code) incl complete control wiring with suitable size of PVC copper conductor cable and provn of cable lugs etc. \n(b) Ammeter with CT and selector switch, 0 to 400 Amps - 01 Nos, Make : AE/Havells/EE\n(c) Volt meter with selector switch , 0 to 500 Volt - 01 Nos, Make : AE/Havells/EE\n(d) Phase indicator lamp, LED type - 03 Sets, Make : Havells/L&T/Crompton\n(e) MCCB 250 Amps, 4 Pole, 36 KA adjustable thermal and adjustable magnetic settings - 01 Nos (Incoming), Make : Havells/L&T/Legrand. \n(f) MCCB 100 Amps, 4 Pole, 25 KA adjustable thermal and adjustable magnetic settings - 02 Nos (Outgoing), Make : Havells/L&T/Legrand. \n(g) MCCB 63 Amps, 4 Pole, 25 KA adjustable thermal and adjustable magnetic settings - 02 Nos (Outgoing), Make : Havells/L&T/Legrand. \n1Each
1717Supply and fix in replacement of on/off load Change over 4 pole with side handle , 400 Volt AC , 100 Amp with suitable sheet metal enclouser complete all as specified and directed. \nMake :Havells CAT No IHCFFE0100 or equivalent model of make as per appx 'B' as approved.1Each
1818Supply, install, testing and commissioning Feeder panel cubical panel of double door outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangment both in front and rear side (Independent door for each item on front side) mounted at 1 No angle iron 45 x 45 x 6mm, 30 cm long, embedded in PCC 1:3:6 type C2 with complete incl provision of following accessories equipment suitable for fixing under mentioned items including taking out/dismantling of old Panel complete all as specified and directed:- \n(a) Aluminium bus bar chamber capacity 200 Amps 3 Phase 4 wire duly insulated with PVC sleeves (As per colour code) incl complete control wiring with suitable size PVC copper conductor cable and provn of cable lugs etc. \n(b) Ammeter with CT and selector switch, 0 to 200 Amps - 01 Nos, Make : AE/Havells/EE\n(c) Volt meter with selector switch , 0 to 500 Volt - 01 Nos, Make : AE/Havells/EE\n(d) Phase indicator lamp, LED type - 03 Sets, Make : Havells/L&T/Crompton\n(e) MCCB 125 Amps, 4 Pole, 25 KA with adjustable thermal and fixed magnetic setting - 01 Nos (Incoming), \n(f) MCCB 100 Amps, 4 Pole, 25 KA with adjustable thermal and fixed magnetic setting - 01 Nos (Outgoing), Make : Havells/L&T/Crompton\n(g) MCCB 63 Amps, 25 KA with adjustable thermal and fixed magnetic setting - 02 Nos (Outgoing), Make : Havells/L&T/Crompton\n(h) MCB DP 40 Amps, 16 KA - 02 Nos (Outgoing),\n(j) MCB SP 32 Amps, 16 KA-01 Nos (Outgoing),\n2Each
1919Supply installation, commissioning & testing Voltage stabilizer 100 KVA capacity for automatic operation servo controlled, three phase, naturally oil cooled, outdoor type IP-55 protection CPRI certified copper wound and designed for input variation between 300 V to 480 V suitable for unbalanced voltage in each phase with output voltage stabilized at 415 Volts with accuracy ± 1% on each phase and speed of correction 8 volts per second with initial filling of transformer oil having dielectric strength not less than 50 KV as per IS-335, complete with 0-500 volts voltmeter and arrangement to check input & output voltage, RYB indication lamp ampere meter high and low voltage cut off system, servo bypass switch overload and short circuit trip facility alongwith necessary PCC foundation casted in PCC 1:3:6 type C1 using 20mm graded stone aggregate, 150 mm above ground level with foundation bed and suitable form work complete all as specified and directed.1Each Job
2020Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminium conductor for working voltage upto and including 1100 volts, cross sectional area of cable 95 Sqmm 3.5 core laid in trenches/fixed on pole/wall/passed through pipe complete all as specified and directed.412RM
2121All as per item No. 20 above but size 70 sqmm 3.5 core90RM
2222All as per item No.20 above but size 50 sqmm 3.5 core60RM
2323All as per item No.20 above but size 35 sqmm 3.5 core80RM
2424All as per item No. 20 above but size 25 sqmm 4.0 core70RM
2525All as per item No. 20 above but size 16 sqmm 2.0 core140RM
2626M&L for street light fitting 45Watt LED type, energy saving & environmental friendly long life Versatile pressure die-cast aluminium, IP65 roadway luminaire with high power LEDs as light source and electronic driver incl provn of PVC insulated unsheathed maltistranded copper conductor two core cable for connection from MS termination box to fitting, including GI pipe bracket 1.2mtr long, a pair of clamp, bolts, nuts, washers complete all as specified and directed.3Each
2727Material & labour for Earthing complete with galvanised earth plate electrode 600x600x6.3mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to galvanised strip 32x6mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or of steel complete all as shown in electrical plate No 3 of SSR part-I 2009 connected to Voltage stabilizer/LT feeder pillar all as specified and testing on completion including necessary excavation, earthwork, PCC works in 1:2:4 type B-I (using 20mm graded stone aggregate) and CI earth pit cover with watering pipe 20mm dia GI pipe, medium grade, funnel with wire mesh and lugs and GI pipe 40 mm dia of light grade, for protection of earth strip including necessary excavation and earth work complete all as specified and directed. \nNote: Excavation/PCC/Earth work/Charcoal/ Salt shall be deemed to be include in this unit rate.8Each
2828Supply, installation, testing and commissioning LT Feeder pillar outdoor type factory made dust/vermin proof made out of CRCA sheet 3.15 mm thick CPRI approved duly powder coated having opening and locking arrangment both in front and rear side (Independent door for each item on front side) mounted on 4 Nos angle iron 50 x 50 x 6mm, 0.45 meter height, embedded in PCC 1:3:6 type C2 with and including provision of following accessories/eqpt incl cable gland etc suitable for fixing items (a) to (l):-\n(a) Aluminium bus bar chamber capacity 400 Amps 3 Phase 4 wire duly insulated with PVC sleeves (As per colour code) incl complete control wiring with suitable size PVC copper conductor cable.\n(b) Digital Ammeter with CT and selector switch, 0 to 200 Amps - 01 Nos.\n(c) Digital Volt meter with selector switch , 0 to 500 Volt - 01 Nos.\n(d) Phase indicator lamps, LED type - 03 Sets.\n(e) MCCB 250 Amps, 4 Pole 35 KA with adjustable thermal & fixed Magnetic settings - 01 Nos (Incoming).\n(f) MCCB 160 Amps, 4 Pole, 25 KA with adjustable thermal & fixed Magnetic settings- 01 Nos (Outgoing).\n(g) MCCB 125 Amps, 4 Pole, 25 KA with adjustable thermal & fixed Magnetic settings - 01 Nos (Outgoing).\n(h) MCCB 100 Amps, 4 Pole, 25 KA with adjustable thermal & fixed Magnetic settings - 01 Nos (Outgoing).\n(j) MCB SPN 63 Amps, 2 Pole, 10 KA - 02 Nos (Outgoing).\n(k) MCB SP 06 to 32 Amps, Single Pole, 10 KA - 03 Nos (Outgoing).\n(l) On load Change Over switch 200A, 4 pole - 01 Nos \n\n2Each Job
2929Net Contract Sum will be after deducting Sch Of Credit of Rs. 90158.00

AI Tender Summary

OUR REF NO 26051242
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 28 Lakhs
LAST DATE 23-12-2020
Authority
Authority Name Military Engineer Services
Work Description Special Repair To Under Ground Cable Connections An Feeder Panels At 1841 Pnr Unit At Karcham And Provn Of 100 Kva Stablizer Alongwith Lt Cable And Panel Board Installation Of Op Work Shelter At Central Mi Room Of 2136 Fd Hosp At Cholling Area At Kar
Basic Detail
Tender No GE863/EWS-T-41 OF 2020-21
Bidding Type Tender
Location
City KARCHAM
State Himachal Pradesh
Key Dates
Publish Date 16 Dec 2020
Submission Date 23 Dec 2020
Open Date 26 Dec 2020
Finance
Tender Value 28 Lakhs
Tender Fee 500
EMD 56000
Exemption Not Available
Document List
BOQ_442595.xls
T-41TD.pdf
701C2960-4A9D-4F82-B63C-902DED2571DF.html
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Dec 16, 2020
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 07, 2020
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Dec 16, 2020
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Completed
Dec 23, 2020
18:00 IST

Corrigendum-3 Issued

Clarifications on tender conditions and amendments issued.

Completed
Dec 23, 2020
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Dec 26, 2020

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
xls

BOQ_442595.xls

pdf

T-41TD.pdf

html

701C2960-4A9D-4F82-B63C-902DED2571DF.html

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders