Repair/ Replacement Of Unsv Ats Switches , Energy Meters , Ct/Pts , Control Wiring , Lt Cables And Joints , Flood Lights And High Mast Light And Connected Accessories At Various Mes Installations Under Ge ( E/M ) Base Hospital Delhi Cantt-10, GE E/M BASE HOSPITAL DELHI CANTT-Delhi

Military Engineer Services-MES has published Repair/ Replacement Of Unsv Ats Switches , Energy Meters , Ct/Pts , Control Wiring , Lt Cables And Joints , Flood Lights And High Mast Light And Connected Accessories At Various Mes Installations Under Ge ( E/M ) Base Hospital Delhi Cantt-10. Submission Date for this Tender is 14-12-2020. Electrification Work Tenders in GE E/M BASE HOSPITAL DELHI CANTT Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

26042875
Corrigendum : Repair/ Replacement Of Unsv Ats Switches , Energy Meters , Ct/Pts , Control Wiring , Lt Cables And Joints , Flood Lights And High Mast Light And Connected Accessories At Various Mes Installations Under Ge ( E/M ) Base Hospital Delhi Cantt-10
Open Tender
Indian
Delhi
GE E/M BASE HOSPITAL DELHI CANTT
14-12-2020

Tender Details

Repair/ Replacement Of Unsv Ats Switches , Energy Meters , Ct/Pts , Control Wiring , Lt Cables And Joints , Flood Lights And High Mast Light And Connected Accessories At Various Mes Installations Under Ge ( E/M ) Base Hospital Delhi Cantt-10

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Dec-2020 CORR01 Date 14-12-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 99960.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: REPAIR/ REPLACEMENT OF UNSV ATS SWITCHES, ENERGY METERS, CT/PTS, CONTROL WIRING, LT CABLES & JOINTS, FLOOD LIGHTS AND HIGH MAST LIGHT AND CONNECTED ACCESSORIES AT VARIOUS MES INSTALLATIONS UNDER GE (E/M) BASE HOSPITAL DELHI CANTT-10
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth for foundation/ fixing pole/ laying cable and pipe line etc or for man hole etc not exc 10 Sqm on plan and getting out in soft / loose soil complete all as specified and as directed. 108 Cum
2 2 Returning filling in including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick using excavated soil complete all as specified and as directed. 69 Cum
3 3 Removing excavated Soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. 39 Cum
4 4 M&L for providing dry river sand as in sand cushioning to under ground electric cable including punning down of sand in layer complete all as specified and as directed. \nNote: For measurement & payment purpose, punned thickness of sand only shall be considered. 33 Cum
5 5 Supply and Laying in replacement burn brick, sub class 'B', old size for cable covering complete all as specified and as directed. 3000 Each
6 6 Supply, laying, connecting, testing and commissioning in replacement, LT cable XLPE insulated, screened, PVC inner sheathed, armoured with galvanised steel strip or wire, electric power cable, heavy duty with stranded aluminium conductor 1100 Volt grade, laid in trenches / duct, passing through pipe / duct or fixed on pole, of size 10 Sqmm, 2 core including taking out old cable complete all as specified and as directed. 300 RM
7 7 All as per item No 6.00 here in before but cable of size 16 Sqmm, 2 core complete all as specified and as directed. 200 RM
8 8 All as per item No 6.00 here in before but cable of size 16 Sqmm, 4 core complete all as specified and as directed. 500 RM
9 9 All as per item No 6.00 here in before but cable of size 25 Sqmm, 4 core complete all as specified and as directed. 300 RM
10 10 All as per item No 6.00 here in before but cable of size 35 Sqmm, 3.5 core complete all as specified and as directed. 300 RM
11 11 All as per item No 6.00 here in before but cable of size 50 Sqmm, 3.5 core complete all as specified and as directed. 300 RM
12 12 All as per item No 6.00 here in before but cable of size 70 Sqmm, 3.5 core complete all as specified and as directed. 300 RM
13 13 Supply, fixing and connecting in repair 45W New generation energy saving and environment friendly long life LED street light fitting, made up of pressure die cast aluminium alloy housing for effective thermal management, sturdiness, excellent corrosion resistant with high power LED as lighting source and lens embedded PC/ toughened glass cover with IP66 protection and impact resistance of IK07, Minimum Lumen output of fixture 4950 lumens with minimum efficacy of 110lm/W, CRI>70, THD<10%, PF>0.95, CCT- 5700K, 4KV surge protection, Average life : 50000 hours complete all as specified and as directed. Make: Havells Cat Part No ENDURAPEARLNEOSL45 WLED757PASYTOPC / Phillips Cat Part No- BRP 409 LED 040 CW HO MR FG S1 PSU GR /Wipro Cat Part No - LR02-501-XXX-57-XX or equivalent Model of Make mentioned in PS.\n 3 Each
14 14 Supply, fixing and connecting in repair 60W New generation energy saving and environment friendly long life LED street light made up of pressure die cast aluminium housing alloy for effective thermal management, sturdiness, excellent corrosion resistant with high power LED as lighting source and lens embedded PC/ toughened glass cover having TOP Opening separate driver compartment for easy maintenance with IP66 protection and impact resistance of IK07, minimum Lumen output of fixture 6600lumens with minimum efficacy of 110lm/W, CRI>70, THD<10%, PF>0.95, CCT- 5700K complete all as specified and as directed. Make: Havells Cat Part No - ENDURAOMNI60 WSTREETLIGHT5700K / Phillips Cat part No- BRP409 LED 060 CW HE NR PC S1 PSU GR /Wipro Cat part No- LR02-671-XXX-57-G2) or equivalent Model of Make mentioned in PS. 3 Each
15 15 Supply, fixing and connecting in repair 70W New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing alloy for effective thermal management, sturdiness, excellent corrosion resistant with high power LED as lighting source and lens embedded PC/ toughened glass cover with IP66 protection and impact resistance of IK07, minimum Lumen output of fixture 7700 lumens with minimum efficacy of 110lm/W, CRI>70, THD<10%, PF>0.95, CCT- 5700K, 4KV surge protection complete all as specified and as directed. Make: Philips, Cat Part No : BRP410 LED CW 072 MR FG S1 PSU GR / Havells Cat Part No. : ENDURACITYLINEARNEOSL70WLED757PASYBOTG / Wipro, Cat Part No : LR02-781-XXX-57-G2 or equivalent Model of Make mentioned in PS. 3 Each
16 16 Supply, fixing and connecting in repair 90W New generation energy saving and environment friendly long life LED street light made up of pressure die cast aluminium housing alloy for effective thermal management, sturdiness, excellent corrosion resistant with high power LED as lighting source and lens embedded PC/ toughened glass cover with IP66 protection and impact resistance of IK07, minimum Lumen output of fixture 9900lumens with minimum efficacy of 110lm/W, CRI>70, THD<10%, PF>.95, CCT- 5700K, 4KV surge protection complete all as specified and as directed. \nMake: HAVELLS Cat part No :ENDURACITYLINERNEOSL90 WLED757SASYBOTG / PHILIPS Cat part No- BRP410 LED 091 CW HE MR PC S2 PSU GR / WIPRO Cat part No- LR02-102-XXX-57-G2) or equivalent Model of Make mentioned in PS. 3 Each
17 17 Supply, fixing and connecting in repair 120W New generation energy saving and environment friendly long life LED street light made up of pressure die cast aluminium housing alloy for effective thermal management, sturdiness, excellent corrosion resistant with high power LED as lighting source and lens embedded PC/ toughened glass cover with IP66 protection and impact resistance of IK07, minimum Lumen output of fixture 13200 lumens with minimum efficacy of 110lm/W, CRI>70, THD<10%, PF>0.95, CCT- 5700K, 4KV surge protection complete all as specified and as directed. \nMake: HAVELLS Cat part No : ENDURACITYLINERNEOSL120 WLED757 SASYBOTG / PHILIPS Cat part No : BRP410 LED 110 CW HE MR FG S2 PSU GR / WIPRO Cat part No: LR02-132-XXX-57-G2 or equivalent Model of Make mentioned in PS. 3 Each
18 18 Supply, fixing and connecting in repair LED Flood Light of system wattage 100W IP65 LED With Lens optics and Pressure die-cast aluminium housing for effective thermal management. Total system Lumen of 100W LED shall be 11500 or above in Cool day Light (5700K), Lumen Efficacy>115 Lm/W, Power factor>0.95, CRI>70, THD(%) < 10 with Average life of 50000 Burning hours, complete with Mounting Brackets & accessories as required with connections complete all as specified and as directed. Make: HAVELLS Cat part No : JETAIRISFLS 100WLED757SYMLTG/ Phillips Cat Part No- BVP122 LED 105 CW HE AK55° FG XTFCL S4/ Wipro Cat part No- LF20-122-060-57-G2 or equivalent Model of Make mentioned in PS. 3 Each
19 19 Supply, fixing and connecting in repair LED Flood Light of system wattage 120W IP65 LED With Lens optics and Pressure die-cast aluminium housing for effective thermal management. Total system Lumen shall be 13800 or above in Cool day Light (5700K), Lumen Efficacy>115 Lm/W, Power factor>0.95, CRI>70, THD(%) < 10 with Average life of 50000 Burning hours, complete with Mounting Brackets & accessories as required with connections complete all as specified and as directed. Make: Havells Cat Part No JETAIRISFLS 120WLED757SYMLTG/ Phillips Cat Part No- BVP122 LED 115 CW HE NB FG XTFCL S4/ Wipro Cat part No- LF07-122-060-50-V5 or equivalent Model of Make mentioned in PS. 5 Each
20 20 Supply, fixing and connecting in repair LED Flood Light of system wattage 150W IP65 LED With Lens optics and Pressure die-cast aluminium housing for effective thermal management, total system Lumen of 150W LED shall be 17250 or above in Cool day Light (5700K), Lumen Efficacy>115 Lm/W, Power factor>0.95, CRI>70, THD(%) < 10 with Average life of 50000 Burning hours. Complete with Mounting Brackets & accessories as required with connections complete all as specified and as directed. Make: Havells Cat Part No JETAIRISFLS 150WLED757SYMLTG/ Phillips Cat Part No- BVP122 LED 150 CW HE NB FG XTFCL S4/ Wipro Cat part No- LF07-152-060-50-V5 or equivalent Model of Make mentioned in PS. 4 Each
21 21 Supply, fixing and connecting in repair LED Flood Light of system wattage 200W IP65 LED With Lens optics and Pressure die-cast aluminium housing for effective thermal management, total system Lumen of 200W LED shall be 23000 or above in Cool day Light (5700K), Lumen Efficacy>115 Lm/W, power factor>0.95, CRI>70, THD(%) < 10 with Average life of 50000 Burning hours, complete with Mounting Brackets & accessories as required with connections complete all as specified and as directed. Make: Havells Cat Part No JETA VALOURFL200WLED757PINTWBLTG/ Phillips Cat Part No- BVP410 LED 215 CW HE NB FG S4 XTFCL/ Wipro Cat part No- LF07-282-090-50-V5 or equivalent Model of Make mentioned in PS. 4 Each
22 22 Supply, fixing and connecting in repair LED Flood Light of system wattage 240W IP65 LED With Lens optics and Pressure die-cast aluminium housing for effective thermal management, total system Lumen shall be 27600 or above in Cool day Light (5700K), Lumen Efficacy>115 Lm/W, Power factor>0.95, CRI>70, THD(%) < 10 with Average life of 50000 Burning hours, complete with Mounting Brackets & accessories as required with connections complete all as specified and as directed. Make: Havells Cat Part No JETA VALOURFL240WLED757 MODNBLTG + ASSEMBLEDCG BOXVALOUR240WAP / Phillips Cat Part No- BVP410 LED 250 CW HE NB FG S4 XTFCL/ Wipro Cat part No- LF07-272-090-50-V5 or equivalent Model of Make mentioned in PS. 4 Each
23 23 Supply, fixing and connecting in repair Automatic Transfer Switch 100 Amp Four Pole, AC-315A, 50 Hz, 415 Volts Automatic/manual With Complete Protection with Enclosure accessories complete all as specified and as directed. Make: Havells Cat Part No IHYFCDE100 or equivalent Model of Make mentioned in PS. 1 Each
24 24 Supply, fixing and connecting in repair Automatic Transfer Switch 200 Amp Four Pole, AC-315A, 50 Hz, 415 Volts Automatic/manual With Complete Protection with Enclosure accessories complete all as specified and as directed. Make: Havells Cat Part No IHYFCDE200 or equivalent Model of Make mentioned in PS. 2 Each
25 25 Supply, installation, testing and commissioning in repair factory made CPRI approved, outdoor type, wall mounted LT panel Board confirming to IS 8623 with IP-54 protection made out of 3.15mm thick CRCA sheet 415 V, 3P, 50 Hz with front openable double door with provision of locking arrangement, dust & vermin proof, gasket, TPN Bus bar duly insulated with colour coated heat shrinkable sleeves and mounted on proper insulator gland welding hinges of dust proof, overall powder coated, suitable for and consisting of the following equipments & Accessories, including dismantling of old panel complete all as specified and as directed: - \n(a) MCCB TP, 415V, 100 Amp, 35 KA - 01 No \n(b) Power Contractor, 3 Pole, 73 Amp - 01 No Make BCH Cat No CE15KN3 or equivalent model of Make Schneider/Siemens/L&T, \n(c) Auto/Manual switch - 01 No\n(d) R-Y-B indicator Lamp, \n(e) Timer Switch Clock Type 3 Each
26 26 Disconnecting LT supply and servicing of Air circuit breaker of capacity 630 to 1500 Amps and rating 1100 V by cleaning and de-carbonising the contacts point, cleaning with CRC, checking proper operations of moving parts, repair to charge spring mechanism, checking of AC supply, parts tightening all nuts and bolts of components, lubricating moving parts with petroleum jelly as directed and testing complete and keeping in on load complete all as specified and as directed. 10 Each Job
27 27 Supply, fixing and connecting in repair MCCB, 3 pole, 160 Amp, 35 KA breaking capacity, suitable for 415 volts, 50HZ, thermal magnetic release, fixed in existing panel including modification of existing frame and panel board door for proper installation of MCCB and connecting with existing cable including thimble, nut bolt and washers etc including disconnecting the existing unserviceable/burnt MCCB and taking out from panel board complete all as specified and as directed. 1 Each
28 28 All as per item No 27.00 here in before but MCCB of rating 250 Amp 35 KA breaking capacity, 3 pole complete all as specified and as directed. 1 Each
29 29 All as per item No 27.00 here in before but MCCB of rating 125 Amp, 25 KA breaking capacity, 3 pole complete all as specified and as directed. 1 Each
30 30 All as per item No 27.00 here in before but MCCB of rating 100 Amp, 25 KA breaking capacity, 3 pole complete all as specified and as directed. 1 Each
31 31 Supply, Installation, testing and commissioning PVC, weather proof KIOSK box, size 333 x 233 x 120 mm (outside) and minimum 1.5 mm wall thickness, made out of one piece mounted SMC base and door pole mounted hinged door, comprising of aluminium bus bar 4 strips for 3 phase and neutral 63 Amp including 06 Amp MCB, SP, for controlling the street light fitting including PVC sheathed copper stranded conductor cable, 1.5 Sqmm, two run, from street light fitting to KIOSK box and mild steel flat iron clamps 30x 4 mm with necessary MS nuts bolts and washers including embossing/ painting of Danger notice of size not less than 10 cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as specified and as directed. Make Sintex Cat part No GS JB 3020 or equivalent model of Make- FINOLEX/ UNIVERSAL Switchgear 40 Each
32 32 Supply, fixing and connecting in replacement, Two run of PVC insulated sheathed stranded copper conductor, single core cable 2.5 Sqmm size from existing kiosk box to street light fittings complete all as specified and as directed. Note: Two Run of Single core 2.5 Sqmm cable shall be measured as one length. 270 RM
33 33 Supply, jointing and testing straight through, heat shrinkable, jointing kit suitable for PVC/ XLPE insulated armoured heavy duty aluminium conductor 1100 volt grade of size 10/16 Sqmm, 4 core including taking out faulty portion of cable in any situation/ position complete all as specified and as directed. 5 Each
34 34 All as per srl item No 33.00 here in before but for cable of size 25/35 Sqmm, 3.5 core complete all as specified and as directed. 5 Each
35 35 All as per srl item No 33.00 but for cable of size 50/70 Sqmm, 3.5 core complete all as specified and as directed. 4 Each
36 36 All as per srl item No 33.00 but for cable of size 95/120 Sqmm, 3.5 core complete all as specified and as directed. 3 Each
37 37 M&L for locating the fault in underground electrical power cable of any length & any type of 1100 volt grade LT cables, by arranging fault locating Machine & pin point the fault, cutting the cable at fault to fixing the joint including testing of the cable after locating fault and jointing cable including excavation and earth work in any type of soil complete all as specified and as directed. \nNote:- (i) Jointing of cable shall be measured and paid separately under respective item of this Schedule. (ii) If fault is not rectified within 24 hours after receiving Message, the contractor shall be charged penalty for Rs 500/- per hour per complaint and shall be deducted from next payment due to contractor. 1 Each Job
38 38 M&L for painting on steel tubular Pole (of any height) for street light fittings including GI pipe/brackets fixed on poles, by applying two coats of synthetic enamel paint of aluminium colour including cleaning & preparing the surface properly with sand paper including making strip with yellow/black/ white colour synthetic enamel paint (road signal paint) of the required width as directed at site up to 1.5 metre height from ground level, writing numbers and letters of required size as directed at site above 1.5 metre height from ground level complete all as specified and as directed. \nNote: Quoted Rate shall deemed to be Inclusive of Painting numbering of Poles after Painting work. 100 Each Job
39 39 M&L for painting on PCC Pole (of any height) for street light fittings including GI pipe/brackets fixed on poles, by applying two coats of water Bonding cement based paint, Grey colour, including cleaning and preparation of surface properly with sand paper, making strip with yellow/black/ white colour synthetic enamel paint (road signal paint) of the required width as directed at site up to 1.5 metre height from ground level, writing numbers and letters of required size as directed at site above 1.5 metre height from ground level complete all as specified and as directed. \nNote: Quoted Rate shall deemed to be Inclusive of painting numbering of Poles after Painting work. 50 Each Job
40 40 M&L Horizontal boring of holes under road /pavement /hard standing or any other situation by manual mean and providing 50mm bore, medium grade GI pipe for passing cables etc and making good both the ends complete all as specified and as directed. 18 RM
41 41 All as per item No. 40.00 here in before but including 80mm bore, medium grade, GI pipe complete all as specified and as directed. 18 RM
42 42 S&F in replacement 3 pole power contactor ML-6 Male complete all as specified and as directed. Make Cat part No-SS90921/PC0636411 of Make L&T or equivalent model of Make Mentioned in PS 2 Each
43 43 S&F in replacement timer electronic type 415 Volt, 50HZ, one dial daily, complete all as specified and as directed. 10 Each
44 44 Cutting/trimming of tree branches around street light fitting up to 5 metre distance at all sides and disposal of debris out side MOD land complete all as specified and as directed. 100 Each Job
45 45 M&L excavation in trenches for tracing out the faults in any size of LT underground cable, in any type of soil i.e. Soft/loose/hard/dense soil, taking out the faulty portion of cable for jointing, jointing cables, refilling the excavated trenches with excavated material, disposal of surplus soils outside MOD land and making the disturbed surfaces to match with the surrounding area complete all as specified and as directed. 70 Each Job
46 46 Taking out street light pole any type/size and shifting to another place and other similar situation, re-connecting the electrical connection in the same/new position including PCC and coping work of pole Complete all as specified and as directed. \n\n 7 Each Job
47 47 Taking out feeder pillar box any type/size and shifting to another place and other similar situation, re-connecting the electrical connection in the same/new position including PCC and coping work of panel Complete all as specified and as directed. \n 7 Each Job
48 48 Supply, fixing and connecting in repair 40 Watt, decorative post top Lantern, for 360 degree indirect light, with IP 65 Protection, resistant to impact and corrosion, Glare free and better uniformity including taking out old unserviceable post Top lanterns Complete all as specified and as directed. Make CG Cat No LPTO-40-CDL/M or equivalent Model of Make mentioned in PS. 15 Each
49 49 Supply, installing, testing and commissioning in repair 12M high mast pole and shaft, in two section, suitable for 55 m/sec wind speed, along with head frame, luminaries carriage suitable for 12 luminaries in symmetrical arrangement and other accessories manufactured in factory including following components Complete all as specified and as directed: -\n(i) Supply of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightning finial. (Wiring material from JB to individual luminaries & MCB in base compartment are not included and are a part of installation). \n(ii) Supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template. \n(iii) Supply of control gear boxes for non-integral floodlight luminaries type BGENF22R \n(iv) Construction of shallow foundation with M20 grade concrete for the high mast considering the safe soil bearing capacity at site as 10 T/Sqm at 2 metre depth with all materials and labour. \n(v) Erection of the high mast with the help of suitable tools and plants, wiring of luminaries with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 Sqmm, lugs, MCB and all labour Complete all as specified and as directed. 3 Each Set
50 50 All as per item No 49.00 here in before but 16.00 Metre height High Mast pole Complete all as specified and as directed. 2 Each
51 50.01 Note Specification for ser Item No 49.00 & 50.00 : -\n(1) No. of sections- Two Material construction: S 355 grade as per BS-EN10 025\n(2) Base dia. and top diameter (A/F) :Top : 150 mm, Bottom : 410 mm\n(3) Plate thickness Top : 3 mm, Bottom : 3 mm, \n(4) Cross section of Mast : 20 side polygon\n(5) Standard for of galvanisation : : As per BS EN ISO 1461\n(6) Size of opening and door at base 1200 x 250 mm \n(7) Diameter of base plate : 570 mm\n(8) Thickness of base plate : 25 mm \n(9) Lightning protection finial : G.I single spike \n(10) Max. wind speed : 55m/s as per IS : 875 (Part - III)\n(11) Number of foundation bolts : 08 Nos. \n(12) PCD of foundation bolts : 490 mm\n(13) Type / diameter / length of foundation bolts : TS 600 / 30 mm dia / 850 mm long \n(14) LUMINAIRES CARRIAGE Material of construction : 50 NB ERW Class B - M. S. Pipe \n(15) Diameter of carriage ring (mm) : 535 mm (ID)\n(16) Construction : 6 Arm, Welded, 2 sections \n(17) Load carrying capacity : 12 Luminaries \nTRAILING CABLE \n(18) Conductor : Copper, 5 core, 4 sq mm 76\n(19) Insulation : EPR insulated, PCP sheathed \n(20) No. of circuits per mast : One no cable per mast\n(21) WINCH / POWER TOOL Type / SWL of winch : Double drum, SWL 750 Kg \n(22) Method of operation : Integral Motor\n(23) Motor capacity : 1 HP
52 50.02 (24) No of speeds : 6 Pole, Single speed \n(25) STAINLESS STEEL WIRE ROPE Grade / construction : AISI 316, 7/19 construction \n(26) Number of ropes : Two continuous \n(27) Breaking load capacity : 2350 kg x 2\n
53 53 Supply, fixing and connecting in repair LED type single dome aviation obstruction light complete all as specified and as directed. 5 Each
54 53.01 Supply, fixing and connecting in repair LED Flood Light of system wattage 300W, IP65, LED With Lens optics and Pressure die-cast aluminium housing for effective thermal management. Total system Lumen shall be 34500 or above in Cool day Light (5700K), Lumen Efficacy>115 Lm/W, Power factor>0.95, CRI>70, THD(%) < 10 with Average life of 50000 Burning hours, complete with Mounting Brackets & accessories as required with connections complete all as specified and as directed. \nMake: Havells Cat Part No JETA VALOURFL300WLED 757MODNBLTG + ASSEMBLEDCGBOX VALOUR300WAP/ Phillips Cat Part No- BVP383 LED360/CW 320W 220-240V NB IN/ Wipro Cat part No- LF07-472-060-50-V6 or equivalent Model of Make mentioned in PS. 48 Each
55 53.02 Supply, installation, testing and commissioning, in repair factory made, CPRI approved, outdoor type, Wall mounted LT Panel board, confirming to IS 8623 with IP-54 protection, made out of 3.15 mm thick CRCA sheet, 415 Volt, 3 phase, 50 HZ with front openable, double door with provision of locking arrangement, dust & vermin proof, gasket, including 100 Amp Aluminium TPN bus bar duly insulated with colour coated heat shrinkable sleeves and mounted on proper insulator, gland, welding hinges, dust proof, overall powder coated & Consisting of the following equipments including dismantling of old Panel complete all as specified and directed:- \nIncoming: Supply of outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminaries, power tool control with 2 No 9A contactors and raise lower push button, Incoming 35 Sqmm and out going 16 & 2.5 Sqmm terminals.\n 5 Each Set
56 54 M&L Earthing complete with galvanised Iron earth plate electrode 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25mtrdeep below GL) with top edge of the plate not less than 1.5 metre below normal ground level, surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all round the plate with using 32X6 mm GI earth strip electrode welded and revetted to earth plate up to a distance of 7.5 metre long, GI earth strip encased in and including 40mm bore GI light grade pipe, with 20mm bore GI pipe light grade as water pipe from earth chamber to upper edge of earth plate, MS funnel with wire mesh fixed on water pipe including excavation earth work, Provn of PCC pit in PCC 1:2:4 type B-1 chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type BI duly reinforced with MS bars 8mm dia @ 150 mm centre to centre, both ways complete with lifting handle all as shown in electrical plate No 3 of SSR of part-I complete all as specified and as directed. 10 Each
57 55 M & L GI strip 25mm x 6mm size as in earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit pipe or fixed to poles or any indicated situation for loop earthing etc as required complete all as specified and as directed. 30 RM
58 56 Supply, installation, testing and commissioning, in repair 10 KVA On line UPS System, 3 Phase Input & 1 phase output with SMF batteries for 30 minute backup (65 AH/12V SMF Battery 20 Nos) along with battery stand & battery interconnecting cable with the following Technical specifications complete all as specified and as directed:- 1 Each
59 56.01 Technical Specifications (10KVA UPS- 3Ø - 1Ø): -\n(i) Ratings 10 KVA \n(ii) Output Rating 8 KW \n(iii) Nominal DC 192 / 240 / 360 V DC \n(iv) Topology IGBT based DSP Control.\n(v) Input Voltage 335 to 475V AC.\n(vi) Input Frequency 48 to 52 Hz.\n(vii) PF >0.92.\n(viii) Output Voltage 230V AC ±1%.\n(ix) Output Frequency 50 Hz ±0.1% in Free running & ±4% in Sync.\n(x) Isolation Transformer shall be provided at Output.\n(xi) Power Factor 0.8 Lag to Unity.\n(xii) Crest Factor 3:1\n(xiii) Waveform Sinusoidal.\n(xiv) THD <3% on linear load.\n(xv) Overload 110% for 30 minutes, 125% for 10 minutes, 150% for 1 minute.\n(xvi) Transient Response For 0-50% & 50-100% load change voltage remains within ±5%.\n(xvii) DC Voltage Ripple <2%.\n(xviii) Inverter Efficiency >85%.\n(xix) Protections Input & Output Over / Under Voltage.\n(xx) DC - High / Under Voltage, Battery Charging Over Current.\n(xxi) Output Overload / Short Circuit / Over Temp.\n(xxii) Audio Alarm Mains Fail, Battery Low Pre-alarm, Inverter Trip.\n(xxiii) Metering LCD display to monitor Input & Output - Voltage, Current & Frequency;
60 56.02 (xiv) Battery - Voltage & Current: -\n (a) Messages Input - On / High / Low / Fail.\n (b) Boost Charging, Battery - Float / Discharging / Low Trip, DC High.\n (c) UPS - On / Off / Normal, Load on - UPS / Static, Overload % & time.\n (d) Output - Low / High / Overload / Fail / Short Circuit, Over Temp.\n(xv) Indications Mains On / Fail, Battery On / Low, Inverter On / Trip.\n(xvi) Switchgear MCB / MCCB for Input, Battery & Output; Manual Bypass Switch.\n (a) Termination Input, Battery & Output.\n (b) Enclosure IP 20.\n(xvii) Operating Temp. 0 to 40ºC.\n(xviii) Humidity Up to 95% Rh (non-condensing).\n(xix) Cooling Forced Air.\n (a) Noise <60 dB.\n (b) Charging Current 2 to 10 Amps.\n(xx) Communication RS 232\n(xxi) Monitoring Software UPS Monitoring Software on Windows XP Platform \n(xxii) Static Switch, Provided with changeover <5 msec in sync <20msec in non-sync.\n(xxiii) Castor Wheels shall be Provided.\n(xxiv) Dimensions (mm) (WxHxD) 500 x 1050 x 700\n(xxv) Weight (Approx Kgs) 110.\n(xxvi) Altitude <1500m.