| 1 | 1 | Supplying & delivery of following 1100 V grade XLPE insulated, PVC innersheathed armoured Aluminium cable-\n[Make: KEI/Havells/Finolex]. | 1 | | |
|---|
| 2 | 1.1 | 2 Core 10 Sq.mm (for street light connection)\n | 2 | 1349 | mtr |
|---|
| 3 | 1.2 | 4 Core 16 Sq.mm (Incoming cable from barrage motor panel to motor starter) | 3 | 100 | mtr |
|---|
| 4 | 1.3 | 2 Core 25 Sq.mm (for dauk barrage street light connection from over head to barrage panel box) | 4 | 300 | mtr |
|---|
| 5 | 1.4 | 4 Core 35 Sq.mm (Incoming cable from barrage panel to barrage motor panel) | 5 | 83 | mtr |
|---|
| 6 | 1.5 | 4 Core 70 Sq.mm (Incoming cable from Power house to barrage Panel board) | 6 | 385 | mtr |
|---|
| 7 | 2 | Laying of Cable for Dauk barrage sites | 7 | | |
|---|
| 8 | 2.1 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & FMS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and\npainting | 8 | 464 | RM |
|---|
| 9 | 2.2 | Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. | 9 | 100 | RM |
|---|
| 10 | 2.3 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting. | 10 | 58 | RM |
|---|
| 11 | 2.4 | Laying of one cable upto 150 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand | 11 | 150 | RM |
|---|
| 12 | 2.5 | Fixing of Cable along the lenth of O.H. pole incl. S & F MS pole clamps fabricated from 25 mm x 6 mm MS flat incl. Painting | 12 | 18 | RM |
|---|
| 13 | 2.6 | Laying of one No. cable upto 35 sqmm in underground trench 460mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. | 13 | 1116 | RM |
|---|
| 14 | 2.7 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed | 14 | 271 | RM |
|---|
| 15 | 2.8 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish, From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. \n | 15 | 10 | RM |
|---|
| 16 | 2.9 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish Above 35 sqmm to 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc. | 16 | 30 | RM |
|---|
| 17 | 3 | Supplying & delivery of 40mm GI pipe (ISI Medium) | 17 | 70 | mtr |
|---|
| 18 | 4 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/ PVC armoured cables as below : | 18 | | |
|---|
| 19 | 4.1 | For 2 core upto 10 sqmm | 19 | 75 | each |
|---|
| 20 | 4.2 | For 2 core upto 25 sqmm | 20 | 4 | each |
|---|
| 21 | 4.3 | For 4 core upto 16 sqmm | 21 | 26 | each |
|---|
| 22 | 4.4 | For 4 core upto 35 sqmm | 22 | 4 | each |
|---|
| 23 | 4.5 | For 4 core upto 70 sqmm | 23 | 4 | each |
|---|
| 24 | 5 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : | 24 | | |
|---|
| 25 | 5.1 | 2 core 10 sqmm | 25 | 75 | set |
|---|
| 26 | 5.2 | 2 core 25 sqmm | 26 | 4 | sets |
|---|
| 27 | 5.3 | 4 core 16 sqmm | 27 | 26 | set |
|---|
| 28 | 5.4 | 3½ core 35 sqmm | 28 | 4 | sets |
|---|
| 29 | 5.5 | 3½ core 70 sqmm | 29 | 5 | set |
|---|
| 30 | 6 | Supply & fixing of heat shrink kits for 1.1KV XLPE/PVC cables indoor/outdoor LT end termination. | 30 | | |
|---|
| 31 | 6.1 | For 2 Core upto 25 Sq.mm | 31 | 1 | Nos |
|---|
| 32 | 6.2 | For 4 core upto 70 sqmm | 32 | 1 | Nos |
|---|
| 33 | 7 | Supply, delivery, installation of octagonal pole with its arm backet and foundation bolt | 33 | | |
|---|
| 34 | 7.1 | Supply, delivery, of Octagonal pole Type: CPT-7030, Height 8 mtr, Top dia (A/F): 70mm, Bottom dia (A/F): 130 mm, Sheet thickness: 3 mm, Base plate dimensions(LxBxT) :200x200x16, Bolt size(noxdia): 4x20Dia, Pitch circle dia(PDC): 200mm, Bolt Length: 600mm, Projected Bolt length: 100 mm, Single arm bracket Height: 0.5 mtrs, Top dia (A/F): 70mm [ Make: Calcutta Poles& TubesCo/Bansal] | 34 | 9 | per job |
|---|
| 35 | 7.2 | Supply, delivery of Octagonal pole Type: CPT-7030, Height 8 mtr, Top dia (A/F): 70mm, Bottom dia (A/F): 130 mm, Sheet thickness: 3 mm, Base plate dimensions(LxBxT) :200x200x16, Bolt size(noxdia): 4x20Dia, Pitch circle dia(PDC): 200mm, Bolt Length: 600mm, Projected Bolt length: 100 mm, Double arm bracket Height: 0.5 mtrs, Top dia (A/F): 70mm[ Make: Calcutta Poles& Tubes Co/Uktarsha/Bansal] | 35 | 3 | per job |
|---|
| 36 | 8 | Erection of Octagonal pole on 400mm x 400mm x 750mm foundation made of Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) on Single Brick Flat Soling of picked jhama bricks and necessary electrical connection with it acessories for lighting connection. | 36 | 12 | per job |
|---|
| 37 | 9 | Supplying & Fixing GI waterproof type looping cable box size200x150x100 mm deep having 4 mm thick comprising of one 250V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint. | 37 | 26 | set |
|---|
| 38 | 10 | Fixing only outdoor / street light type fluorescent light fitting or MVlight fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. | 38 | 24 | each |
|---|
| 39 | 11 | Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt.long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56x35.56cmwith locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode. | 39 | 3 | set |
|---|
| 40 | 12 | Supply & fixing Copper Plate,Copper Strip\n | 40 | 20 | kg |
|---|
| 41 | 13 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts.\nlong and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip\n(4 Mts. long), 20 mm dia x 125 mm long galvanized bolt,\ndouble nuts, double washers including finishing both ends by\nmaking holes etc. and S & F 65 mm dia GI pipe (ISI-Medium)\nprotection (3 Mts. long) to be filled with bitumen partly under\nthe ground level and partly above ground level to an average\ndepth of 3.65 Mts. | 41 | 5 | set |
|---|
| 42 | 14 | Connecting the equipments body to earth busbar incl. S & F\n50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with\nGI saddle as required and connection to equipments with incl.\ndrilling holes, bolts, nuts,washers etc.\n | 42 | 44 | Mtr |
|---|
| 43 | 15 | S & F Lightning Conductor Air Terminal made of 20 mm dia 1000\nmm long GI pipe (ISI Medium) having five discharge prongs of 4\nSWG GI (Hot Dip) wire at top duly soldered with 7/16 stranded GI(Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapetetc. in CC mortar ( 4:2:1). | 43 | 1 | each |
|---|
| 44 | 16 | Supply and delivery of 72W LED street light. Make: Crompton, Model: NEXUS+, CAT REF: LSTP-72-CDL/ philips. | 44 | 17 | Nos |
|---|
| 45 | 17 | Supply and delivery of 45W LED street light. Make: Crompton, Model: NEXUS+, CAT REF: LSTP-45-CDL / philips. | 45 | 34 | Nos |
|---|
| 46 | 18 | Supply and delivery of 30W LED street light. Make: Crompton, Model: FREEDOM+, CAT REF: LSTS-30-CDL/ philips . | 46 | 20 | Nos |
|---|
| 47 | 19 | Supplying and delivery of 40W decorative posttop LED light. \nMake: Crompton Greaves Model:MAPEL Cat. Ref. no: LPTO-40-CDL/M/philips. | 47 | 2 | Nos |
|---|
| 48 | 20 | Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling by screws etc. | 48 | 71 | each |
|---|
| 49 | 21 | Supply, fabrication , erection, testing & commissioning of dust & vermin proof, properly painted with synthetic enamel paint (2 coats) on both surface L.T. distribution panel board with cable alleys and metering module made of 2 mm thick MS sheet on suitable size MS Angel frame [50 × 50 × 6 mm (For Panel Base frame & four nos 0.4mtr Leg) & 25 x 25 x 3 mm (For panel frame structure)] with 200 A rating 1 no. 4pole Aluminium Busbar, 100/125A rating 1 no. 2 pole Aluminium Busbar proper hinge & locking arrangement including all internal connection to be done by suitable size copper wire & socket comprising of the following electrical accessories:-\n | 49 | | |
|---|
| 50 | 21.1 | Dimension of the Panel Board:- 1.6m × 1.45m × 0.4m\ni) Aluminium Busbar, Rating-415Volt, 200A, Size:- 50mm × 5mm, Length- 0.6mtr each....04Nos & 100A, Size:- 25mm × 5mm, Length- 0.35mtr ….. 02 NOS.\nii) porcelin chair with GI Screw for Bus-Bar support-16nos\niii) 415 V Four Pole 63A MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. (Make-Havells,A-Frame/Schneider ) ………4 Nos | 50 | | |
|---|
| 51 | 21.2 | iv) 415 V Four Pole 125A MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. (Make-Havells,A-Frame/Schneider ) ……………1 Nos\nv) 415V, TPN, 125A on load front operated Changeover switch open execution type in SS enclosure/cubical with nuts bolts etc. Make: L&T, Havells, Standard ………………2 Nos.\nvi) 415V, TPN, 200A on load front operated Changeover switch open execution type in SS enclosure/cubical with nuts bolts etc. Make: L&T, Havells, Standard …………………1 Nos\n | 51 | | |
|---|
| 52 | 21.3 | vii) AC voltmeter, moving iron type, Range Min: 0-400V, Max. Range: 0-600V , ACC.CL: 1, (Make: Automatic Electric Model: PU4 / MECO) ………………… 2 Nos\nviii) AC ammeter ( Moving iron typee) Min. Range: 0-10A, Max. Range: 0-30A, ACC.CL: 1 (MaKes: Automatic Electric Model: PU4/MECO) ………………. 2 Nos.\nix) Voltmeter selector switch to read voltage between the phases with 90 degree OFF. Current rating 10A, pole=3, (Make: Kaycee, Model : N2S39VP/ L&T) ………………… 1 Nos. | 52 | | |
|---|
| 53 | 21.4 | x) Ammeter selector switch to read current in each phase with 90 degree OFF. Current rating 10A, pole=3, (Make: Kaycee, Model : N3S39AP/ L&T) …………………….. 1 Nos\nxi) Panel board LED indicator (red, yellow, green) of 22..5mm dia. 240 VAC (Make: L&T/ Havells)……………… 4 Nos\nxii) Indoor tape insulated ring type Low tension CT of rating 200/5 A, burden 15 VA, accuracy class 1 (Makes: automatic electric/midwest CT) ………………… 4 Nos\nxiii) Nut, bolt, washer & copper socket………. L.S | 53 | | |
|---|
| 54 | 21.5 | \nxiv) Copper wire for internal connection- \na) 1.5 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nb) 6 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nc) 10 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nd) 16 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nxv) 240/415 V, 40 A, SPN MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Make-Havells/Schneider/ABB ) ……… 3 Nos\nxvi) CC (6:3:1) muffing 0.3mtr. above the ground level around the frame base complete with 3 mm thick neatly finished cement plaster all-round. | 54 | 1 | job |
|---|
| 55 | 22 | Supply, fabrication , erection, testing & commissioning of dust & vermin proof, properly painted with synthetic enamel paint (2 coats) on both surface L.T. distribution panel board with cable alleys and metering module made of 2 mm thick MS sheet on suitable size MS Angel frame [50 × 50 × 6 mm (For Panel Base frame & four nos 0.4mtr Leg) & 25 x 25 x 3 mm (For panel frame structure)] with 200 A rating 2 no. 4pole Aluminium Busbar, proper hinge & locking arrangement including all internal connection to be done by suitable size copper wire & socket comprising of the following electrical accessories:-\n | 55 | | |
|---|
| 56 | 22.1 | Dimension of the Panel Board:- 1.8m × 1.8m × 0.4m\ni) Aluminium Busbar, Rating-415Volt, 200A, Size:- 50mm × 5mm, Length- 0.6mtr each……..08Nos.\nii) Busbar Support & Insulator, Size- 50 × 50 × M10 CONICAL……. 24 Nos.\niii) 415 V Four Pole 63A MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. (Make-Havells,A-Frame/Schneider ) ………3 Nos. | 56 | | |
|---|
| 57 | 22.2 | iv) 415 V Four Pole 100A MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. (Make-Havells,A-Frame/Schneider ) ……………1 Nos\nv) 415 V Four Pole 125A MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. (Make-Havells,A-Frame/Schneider ) …………4 Nos.\nvi) 415V, TPN, 125A on load front operated Changeover switch open execution type in SS enclosure/cubical with nuts bolts etc. (Make: L&T, Havells, Standard) ………………1 Nos.\n | 57 | | |
|---|
| 58 | 22.3 | vii) 415V, TPN, 200A on load front operated Changeover switch open execution type in SS enclosure/cubical with nuts bolts etc. Make: L&T, Havells, Standard …………………2 Nos\nviii) AC voltmeter, moving iron type, Range Min: 0-400V, Max. Range: 0-600V , ACC.CL: 1, (Make: Automatic Electric Model: PU4 / MECO) ………………… 2 Nos\nix) AC ammeter ( Moving iron typee) Min. Range: 0-10A, Max. Range: 0-30A, ACC.CL: 1 (MaKes: Automatic Electric Model: PU4/MECO) ………………. 2 Nos. | 58 | | |
|---|
| 59 | 22.4 | x) Voltmeter selector switch to read voltage between the phases with 90 degree OFF. Current rating 10A, pole=3, (Make: Kaycee, Model : N2S39VP/ L&T) ………………… 2 Nos\nxi) Ammeter selector switch to read current in each phase with 90 degree OFF. Current rating 10A, pole=3, (Make: Kaycee, Model : N3S39AP/ L&T) …………………….. 2 Nos\nxii) Panel board LED indicator (red, yellow, green) of 22.5mm dia. 240 VAC (Make: L&T/ Havells)……………… 6 Nos\nxiii) Indoor tape insulated ring type Low tension CT of rating 200/5 A, burden 15 VA, accuracy class 1 (Makes: automatic electric/midwest CT) ………………… 6 Nos\nxiv) Nut, bolt, washer & copper socket………. L.S\nxv) Copper wire for internal connection- \na) 1.5 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nb) 6 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nc) 10 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex).\nd) 16 Sqmm 'FR' stranded copper wire (Make-Polycab/Havells/Finolex). | 59 | | |
|---|
| 60 | 22.5 | \nxvi) FM1 / Quartz Daily 240 VAC Base/DIN Mounting timmer for street light. Make: L&T Cat. Ref .No: J648B1 / Havells/ standard. …. 2 Nos.\nxvii) Three pole power contractor-type ML for street light size: Fr-3 AC-3:70A, AC-1:100A, Aux contacts 2NO+2NC. Make: L&T, type: ML 4 Cat. No:SS90910 /Schneider. ……… 2 Nos.\nxviii) CC (6:3:1) muffing 0.3mtr. above the ground level around the frame base complete with 3 mm thick neatly finished cement plaster all-round. | 60 | 1 | job |
|---|
| 61 | 23 | Supply& delivery of 12.5 M high mast lighting system with its accessories. Mast shaft shall be in two sections thickness top 3mm & bottom 4mm with steel material conforming to BSEN 10025 and material shall be high tensile steel, grade S355, hot dip galvanised conforming to BSEN ISO 1461 and suitable for wind velocity as per IS 875. It shall also include accessories for high mast including head frame, 2 continus steel wire rope 6mm dia (7/19 construction), trailing cable, double drum winch, Galvanised Lantern carriege arrangement suitable for 6 luminaries symmetrically & its control gear boxes and lighting finial. The mast shall have an integral power tool installed inside the base compartment for its operation along with supply & fixing of Cu cable of power tool motor, wiring for Luminaries, Anchor plate, Foundation Bolt, Nut, Washer, Common Template all complete. Luminaire wiring materials not included in the mast supply prices.\nMake: Crompton/ Bajaj | 61 | 1 | Nos |
|---|
| 62 | 24 | Supply & delivery of 120W LED floodlight luminaire.\nMake: Crompton, Model: PLUTO, CAT REF: LFLN-120-CDL/60 / Philips/ Havells | 62 | 6 | Nos |
|---|
| 63 | 25 | Supply & delivery of twin dome aviation obstruction lights with GLS 2x100 BC. Make: Bajaj, Model: BJAOL 2 BC/Philips /Havells. | 63 | 1 | Nos |
|---|
| 64 | 26 | Supply & delivery of control panel housing 32 A TPN MCB incomer, double dial timer contactor circuit for the automatic switching control of luminaries, outgoing terminals and control circuit for the power tool motor, 2 nos 9A contactors and raise lower push button, incoming 35 sq. mm and outgoing 16 & 2.5 sq. mm terminals all complete. | 64 | 1 | Nos |
|---|
| 65 | 27 | Construction of shallow foundation with M20 graded concrete for the highmast considering the safe soil bearing capacity at site as 10T/sqmtr at 2 metre depth with all materialand labour.Foundation should be made as per drawing and reinforcement should be as per drawing. | 65 | 1 | job |
|---|
| 66 | 28 | Erection of highmast with help of suitable tools and plants, wiring of luminaries with all wiring materialslike PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sq.mm, lugs, MCB and all labour. | 66 | 1 | job |
|---|
| 67 | 29 | Supply & installation of ABC(Stored pressure) type Fire Extinguisher complete with all necessary fittings, conforming to IS: 15683 with ISI marked. Capacity - 6.0kg.\nMake: Ronak/Deflame/minimax | 67 | 1 | Nos |
|---|
| 68 | 30 | Supply & installation of Carbon- Di -Oxide type Fire Extinguisher complete with all necessary fittings, conforming to IS: 15683 with ISI marked. Capacity - 4.5kg.\nMake: Deflame/Ronak/minimax. | 68 | 1 | Nos |
|---|
| 69 | 31 | Supply & installation of Mechanical Foam(AFFF) (store pressured) type Fire Extinguisher complete with all necessary fittings, with ISI marked, Capacity 9L. \nMake: Ronak/Deflame/minimax | 69 | 1 | Nos |
|---|
| 70 | 32 | Supply & installation of G.I fire bucket along with fire bucket bracket and sand | 70 | 2 | Nos |
|---|
| 71 | 33 | Supply and delivery of Insulated G.I fire Axe. | 71 | 1 | Nos |
|---|
| 72 | 35 | supply and delivery of Insulated G.I fire hook Axe. | 72 | 1 | Nos |
|---|
| 73 | 37 | Supply and delivery of Insulated mat 11KV ( size- 2m x 1m x 2mm) with ISI . | 73 | 1 | Nos |
|---|
| 74 | 38 | Supply and delivery of Electrical hand gloves 11KV. With test certificate . | 74 | 4 | Nos |
|---|
| 75 | 39 | Supply and delivery of safety helmet with ISI Mark. Make: Karam/equivalent | 75 | 4 | Nos |
|---|
| 76 | 40 | Supply, installation, necessary connections, testing and commissioning of 62.5KVA Kirloskar generator set powered by Kirloskar make Model : 4R810TA G1, 83 BHP at 1500 RPM. Water cooled Diesel Engine Coupled with Krloskar Green 62.5KVA three phase, 0.8 power factor, 50 C/S Alternator along with suitabe Base frame, Fuel Tank, Control Panel & Battery (dry) with Leads, with Acoustic enclosure (Canopy). [Make: KIRLOSKAR] | 76 | 1 | job |
|---|
| 77 | 41 | Painting of Steel Tubular Pole of lengths and no. of coats of paint, as given below with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint. | 77 | | |
|---|
| 78 | 41.1 | Upto 9.0 mtr. long pole 1st coat of aluminium paint over 1 coat of RO priming | 78 | 29 | per pole |
|---|
| 79 | 41.2 | Upto 9.0 mtr. long pole 2nd coat of aluminium paint over 1st coat | 79 | 29 | per pole |
|---|