Automated Multilevel Tower Car Parking Facility At Aluva Metro Station , Kochi , Kerala, Kerala-Kerala

National Highways and Infrastructure Development Corporation Limited-NHIDCL has published Automated Multilevel Tower Car Parking Facility At Aluva Metro Station , Kochi , Kerala. Submission Date for this Tender is 03-12-2020. Parking Services Tenders in Kerala Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

25825183
Corrigendum : Automated Multilevel Tower Car Parking Facility At Aluva Metro Station , Kochi , Kerala
Open Tender
Indian
Kerala
Kerala
03-12-2020

Tender Details

Automated Multilevel Tower Car Parking Facility At Aluva Metro Station , Kochi , Kerala

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 12-Nov-2020 Amendment No. 1 Other 03-12-2020
2 26-Nov-2020 Amendment No. 2 Other 03-12-2020

Key Value

Document Fees
INR 5900 /-
EMD
INR 1390000.0 /-
Tender Value
INR 13.90 Crore /-

BOQ Items

Name of Work: Automated Multilevel Tower car parking facility at Aluva Metro station, Kochi, Kerala.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Civil Work- Carriage BI01010001010000000000000515BI0100001112
2 2 Carriage of lime morrum and malba , by mechanical transportation including loading, unloading and stacking BI01010001010000000000000515BI0100001113
3 3 Beyond 10 Km to 20Km BI01010001010000000000000515BI0100001114 135 cum
4 4 Beyond 20KM per additional Km BI01010001010000000000000515BI0100001115 135 cum
5 5 Carriage of excavated earth , by mechanical transportation including loading, unloading and stacking BI01010001010000000000000515BI0100001116
6 6 from 1 to 5KM BI01010001010000000000000515BI0100001117 301 cum
7 7 from 5km to 10 km BI01010001010000000000000515BI0100001118 180 cum
8 8 From 10 to 20km BI01010001010000000000000515BI0100001119 120 cum
9 9 EARTH WORK BI01010001010000000000000515BI0100001120
10 10 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge BI01010001010000000000000515BI0100001121
11 11 All kinds of soil BI01010001010000000000000515BI0100001122 1070 Cum
12 12 Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or stacked materials. BI01010001010000000000000515BI0100001123
13 13 All kinds of soil (1.5 to 3M) BI01010001010000000000000515BI0100001124 482 Cum
14 14 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50m and lift upto 1.5 m. BI01010001010000000000000515BI0100001125 749 Cum
15 15 Supplying and filling in plinth with jamuna sand under floors, including watering, ramming, consolidating and dressing complete. BI01010001010000000000000515BI0100001126 4 Cum
16 16 Surface dressing of the ground including removing vegetation and in- equalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. BI01010001010000000000000515BI0100001127
17 17 All kinds of soil BI01010001010000000000000515BI0100001128 800 sqm
18 18 Felling trees of the girth (measured at a height of 1 m above ground level), including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material. BI01010001010000000000000515BI0100001129
19 19 (a) Beyond 30 cm girth upto and including 60 cm girth BI01010001010000000000000515BI0100001130 1 Each
20 20 60 cm girth upto and including 120 cm girth BI01010001010000000000000515BI0100001131 1 Each
21 21 Beyond 120 cm girth upto and including 240 cm girth BI01010001010000000000000515BI0100001132 1 Each
22 22 Above 240 cm girth BI01010001010000000000000515BI0100001133 1 Each
23 23 Filling with available fly ash and earth (excluding rock) in trenches or embankment in layers (each layer should not exceed 15 cm), with intermediate layer of compacted earth (Soil density of 98%) after every four layers of compacted depth of fly ash, sides & top layer of filling shall be done with earth having total minimum compacted thickness 30 cm or as decided by Engineer -in-charge, including compacting each layer by rolling/ ramming and watering, all complete as per drawing and direction of Engineer -in - charge. BI01010001010000000000000515BI0100001134 5 cum
24 24 CONCRETE WORK BI01010001010000000000000515BI0100001135
25 25 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : BI01010001010000000000000515BI0100001136
26 26 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm size BI01010001010000000000000515BI0100001137 8.99 Cum
27 27 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 40 mm size BI01010001010000000000000515BI0100001138 5 Cum
28 28 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm size BI01010001010000000000000515BI0100001139 102.73 Cum
29 29 Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement:3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth. BI01010001010000000000000515BI0100001140
30 30 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 40 mm size BI01010001010000000000000515BI0100001141 37.23 sqm
31 31 Reinforcement cement concreate BI01010001010000000000000515BI0100001142
32 32 Centering and shuttering including strutting, propping etc. and removal of form for all heights : BI01010001010000000000000515BI0100001143
33 33 Foundations, footings, bases of columns, etc. for mass concrete BI01010001010000000000000515BI0100001144 200.72 Sqm
34 34 Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. BI01010001010000000000000515BI0100001145 562.51 Sqm
35 35 Suspended floors, roofs, landings, balconies and access platform BI01010001010000000000000515BI0100001146 911.67 Sqm
36 36 Lintels, beams, plinth beams, girders, bressumers and cantilevers BI01010001010000000000000515BI0100001147 140.54 Sqm
37 37 Columns, Pillars, Piers, Abutments, Posts and Struts BI01010001010000000000000515BI0100001148 400 Sqm
38 38 Stairs, (excluding landings) except spiral-staircases BI01010001010000000000000515BI0100001149 199.5 Sqm
39 39 Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). BI01010001010000000000000515BI0100001150
40 40 Suspended floors, roofs, landing, beams and balconies (Plan area to be measured) BI01010001010000000000000515BI0100001151 202.67 sqm
41 41 Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth level. BI01010001010000000000000515BI0100001152
42 42 Thermo-Mechanically Treated bars of grade Fe-500D or more. BI01010001010000000000000515BI0100001153 82893.9 KG
43 43 Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level. BI01010001010000000000000515BI0100001154
44 44 Thermo-Mechanically Treated bars of grade Fe-500D or more. BI01010001010000000000000515BI0100001155 24283.4 KG
45 45 Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using fly ash and cement content as per approved design mix, and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge.NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.“ (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC. Note :- The above item shall be used judiciously where specified quality of Fly Ash is available for mixing in concrete. Also, the guidelines issued by CDO, CPWD, vide circular no. CDO/ SE(RR)/ Fly Ash (Main)/102 dated 9th April 2009 shall be followed in such cases. BI01010001010000000000000515BI0100001156
46 46 All works upto plinth level BI01010001010000000000000515BI0100001157 367.38 Cum
47 47 All works above plinth level upto floor V level BI01010001010000000000000515BI0100001158 220.76 Cum
48 48 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof. BI01010001010000000000000515BI0100001159 220.76 Cum
49 49 Extra for providing richer mixes at all floor levels.\nNote:- Excess/less cement over the specified cement content used is\npayable /recoverable separately BI01010001010000000000000515BI0100001160
50 50 Providing M-30 grade concrete instead of M-25 grade BMC/\nRMC. (Note:- Cement content considered in M-30 is @ 340 kg/ cum) BI01010001010000000000000515BI0100001161 367.38 cum
51 51 Providing M-35 grade concrete instead of M-25 grade BMC/\nRMC. (Note : Cement content considered in M-35 is @ 350 kg/ cum BI01010001010000000000000515BI0100001162 367.38 cum
52 52 Providing M-40 grade concrete instead of M-25 grade BMC/\nRMC.(Note : Cement content considered in M-40 is @ 360 kg/cum BI01010001010000000000000515BI0100001163 220.76 cum
53 53 Add for using extra cement in the items of design mix over and above the specified cement content herein: BI01010001010000000000000515BI0100001164 1940.86 quintal
54 54 BRICK WORK BI01010001010000000000000515BI0100001165
55 55 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: BI01010001010000000000000515BI0100001166
56 56 Cement mortar 1:6 (1 cement : 6 coarse sand) BI01010001010000000000000515BI0100001167 31.11 Cum
57 57 Extra for brick work / AAC block masonry / Tile brick masonry in superstructure above floor V level, for each four floors or part thereof by mechanical means. BI01010001010000000000000515BI0100001168 318.09 Cum
58 58 Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means. BI01010001010000000000000515BI0100001169 5 Sqm
59 59 Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry. BI01010001010000000000000515BI0100001170 5 Sqm
60 60 Brick work with clay flyash F.P.S. (non modular) brick of class designation 7.5 in superstructure above plinth level up to floor five level in : BI01010001010000000000000515BI0100001171
61 61 Cement mortar 1:6 (1 cement : 6 coarse sand BI01010001010000000000000515BI0100001172 318.09 Cum
62 62 Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work. BI01010001010000000000000515BI0100001173 5.28 Cum
63 63 Half brick masonry with non modular fly ash bricks of class designation 10, conformingio IS :12894, in super structure above plinth and upto floor V level. BI01010001010000000000000515BI0100001174
64 64 cement mortar 1:4 (1 cement : 4 coarse sand)\n BI01010001010000000000000515BI0100001175 5 Sqm
65 65 Stone work / Marble and Granite work BI01010001010000000000000515BI0100001176
66 66 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building, all complete as per the architectural drawings, with18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand), laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. BI01010001010000000000000515BI0100001177
67 67 Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent BI01010001010000000000000515BI0100001178 5 Sqm
68 68 Wood and PVC work BI01010001010000000000000515BI0100001179
69 69 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. BI01010001010000000000000515BI0100001180 157551 KG
70 70 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete BI01010001010000000000000515BI0100001181
71 71 Hot finished welded type tubes BI01010001010000000000000515BI0100001182 9056.26 KG
72 72 Providing and fixing mild steel round holding down bolts with nuts and washer plates complete. BI01010001010000000000000515BI0100001183 6912 kg
73 73 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. BI01010001010000000000000515BI0100001184
74 74 In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete BI01010001010000000000000515BI0100001185 500 kg
75 75 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works BI01010001010000000000000515BI0100001186 18037.6 kg
76 76 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. BI01010001010000000000000515BI0100001187
77 77 M.S. tube BI01010001010000000000000515BI0100001188 6680.5 kg
78 78 Providing and Fixing Carbon Steel galvanised (min 5 micron) dash fastener (min 5 micron) of 10 mm dia double threaded 6.8 grade counter sunk head screw comprising of 10 mm dia polyamide PA 6 grade sleeve. BI01010001010000000000000515BI0100001189
79 79 Size 10 mm x 80 mm BI01010001010000000000000515BI0100001190 10 Nos.
80 80 Flooring BI01010001010000000000000515BI0100001191
81 81 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. BI01010001010000000000000515BI0100001192
82 82 40 mm thick with 20 mm nominal size stone aggregate BI01010001010000000000000515BI0100001193 440.85 sqm
83 83 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. BI01010001010000000000000515BI0100001194 333.78 sqm
84 84 Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement :4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including pointing the joints with white cement and matching pigment etc., complete. BI01010001010000000000000515BI0100001195 175.57 Sqm
85 85 Providing and laying vitrified floor tiles in different sizes 9 to 10 mm thickness with water absorption less than 0.08%\nand conforming to IS : 15622, of approved make, in all colors and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc.\n BI01010001010000000000000515BI0100001196
86 86 Size of Tile 600x600 mm). BI01010001010000000000000515BI0100001197 5 Sqm
87 87 Providing and laying Vitrified tiles in different sizes 9-10mm (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colors & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joint with white cement & matching pigments etc. complete.\n BI01010001010000000000000515BI0100001198
88 88 Size of Tile 600x600 mm BI01010001010000000000000515BI0100001199 0.5 sqm
89 89 Roofing BI01010001010000000000000515BI0100001200
90 90 Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. BI01010001010000000000000515BI0100001201
91 91 GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending. BI01010001010000000000000515BI0100001202 1 Sqm
92 92 Finishing BI01010001010000000000000515BI0100001203
93 93 12 mm cement plaster of mix : BI01010001010000000000000515BI0100001204
94 94 1:4 (1 cement: 4 fine sand) BI01010001010000000000000515BI0100001205 878.32 Sqm
95 95 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand BI01010001010000000000000515BI0100001206 1040.42 Sqm
96 96 6 mm cement plaster of mix : BI01010001010000000000000515BI0100001207
97 97 1:3 (1 cement : 3 fine sand) BI01010001010000000000000515BI0100001208 885.79 Sqm
98 98 Neat cement punning BI01010001010000000000000515BI0100001209 18 Sqm
99 99 Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers BI01010001010000000000000515BI0100001210 137.8 Per bag of 50 kg cement used in the mix
100 100 Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof. BI01010001010000000000000515BI0100001211 914.41 sqm
101 101 White washing with lime to give an even shade : BI01010001010000000000000515BI0100001212
102 102 a) New work (three or more coats) BI01010001010000000000000515BI0100001213 1764.11 Sqm
103 103 Distempering with 1st quality acrylic distemper (ready mixed) of approved manufacturer, of required shade and colour complete, as per manufacturer's specification. BI01010001010000000000000515BI0100001214
104 104 Two or more coats on new work BI01010001010000000000000515BI0100001215 1764.11 Sqm
105 105 Finishing walls with water proofing cement paint of required shade : BI01010001010000000000000515BI0100001216
106 106 a) New work (Two or more coats applied @ 3.84 kg/10 sqm) BI01010001010000000000000515BI0100001217 60 Sqm
107 107 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade BI01010001010000000000000515BI0100001218
108 108 New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) BI01010001010000000000000515BI0100001219 316.8 Sqm
109 109 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. BI01010001010000000000000515BI0100001220
110 110 On steel work BI01010001010000000000000515BI0100001221 10 sqm
111 111 Providing and applying two coats of fire retardant paint on cleaned wood / ply surface/steel @ 3.5 sqm per litre per coat including preparation of base surface as per recommendations of manufacturer to make the surface fire retardant. BI01010001010000000000000515BI0100001222 5 sqm
112 112 Painting with synthetic enamel paint of approved brand and manufactured to give an even shade BI01010001010000000000000515BI0100001223
113 113 Two or more coats on new work Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and\nmanufacture\n BI01010001010000000000000515BI0100001224 5 sqm
114 114 Providing and applying white cement based putty of average thickness1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete BI01010001010000000000000515BI0100001225 5 Sqm
115 115 Dismentlling and Demolishing BI01010001010000000000000515BI0100001226
116 116 Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 meters lead as per direction of Engineer - in - charge. BI01010001010000000000000515BI0100001227
117 117 Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) BI01010001010000000000000515BI0100001228 5.4 cum
118 118 Demolishing R.C.C. work by mechanical means and stockpiling at designated locations and disposal of dismantled materials up to a lead of 1 kilometer, stacking serviceable and unserviceable material separately including cutting reinforcement bars. BI01010001010000000000000515BI0100001229 130.8 cum
119 119 Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 meters lead as per direction of Engineer-in-charge BI01010001010000000000000515BI0100001230
120 120 In cement mortar BI01010001010000000000000515BI0100001231 13.8 Cum
121 121 Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. BI01010001010000000000000515BI0100001232 120 cum
122 122 Road Work BI01010001010000000000000515BI0100001233
123 123 Supplying and stacking at site. BI01010001010000000000000515BI0100001234
124 124 Good earth BI01010001010000000000000515BI0100001235 3 Cum
125 125 Manufacturing, supplying and fixing retro reflective sign boards made up of 2 mm thick aluminum sheet, face to be fully covered with high intensity encapsulated type heat activated retro reflective sheeting conforming to type - IV of ASTM-D 4956-01 in blue and silver white or other colour combination including subject matter, message (bi-lingual), symbols and borders etc. as per IRC ; 67:2001, pasted on substrate by an adhesive backing which shall be activated by applying heat and pressure conforming to class -2 of ASTM-D-4956-01 and fixing the same with suitable sized aluminum alloy rivets @ 20 cm c/c to back support frame of M.S. angle iron of size 25x25x3 mm along with theft resistant measures, mounted and fixed with 2 Nos. M.S. angles of size 35x35x5 mm to a vertical post made up to M.S. Tee section ISMT 50x50x6 mm welded with base plate of size 100x100x5 mm at the bottom end and including making holes in pipes, angles flats, providing & fixing M.S. message plate of required size, steel work to be painted with two or more coats of synthetic enamel paint of required shade and of approved brand & manufacture over priming coat of zinc chromate yellow primer (vertical MS-Tee support to be painted in black and white colours).Backside of aluminum sheet to be painted with two or more coats of epoxy paint over and including appropriate priming coat including all leads and lifts etc. complete as per drawing , specification and direction of Engineer--in-charge. BI01010001010000000000000515BI0100001236
126 126 a) Mandatory/ Regulatory sign boards of 900 mm diameter with support length of 3750 mm BI01010001010000000000000515BI0100001237 5 each
127 127 b)Cautionary /warning sign boards of equilateral triangular shape having each side of 900 mm with support length of 3650 mm BI01010001010000000000000515BI0100001238 5 each
128 128 Manufacturing, supplying and fixing retro reflective overhead signage boards made up of 2 mm thick aluminum sheet, face to be fully covered with high intensity and encapsulated lens type heat activated retro reflective sheeting conforming to type - III of ASTM-D-4956-01 as approved by Engineer-in-charge, letters, borders etc. as per IRC : 67-2001 in silver white with blue colour back ground and with high intensity grade, pasted on substrate by pressure sensitive adhesive backing which shall be activated by applying pressure conforming to class II of ASTM-D-4956-01 and fixing the same to the plate of structural frame work by means of suitable sized aluminum alloys, rivets or bolts & nuts @ 300 mm centre to centre all along the periphery as well as in two vertical rows along with theft resistant measures, including the cost of painting with two or more coats of epoxy paint in grey colour on the back side of aluminum sheet including appropriate priming coat. The rate includes the cost of rounding off the corners, lowering down the structural frame work from the gantry, fixing and erecting the same in position all complete as per drawings, specification and direction of the engineer-in- charge.(Structural frame work including M.S. plate to be provided separately. Rectangular area of the sheet only shall be measured for payment). BI01010001010000000000000515BI0100001239
129 129 Overhead informatory road signage BI01010001010000000000000515BI0100001240 5 each
130 130 Providing and applying 2.5 mm thick road marking strips (retro- reflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicable specifications. BI01010001010000000000000515BI0100001241 41.85 sqm
131 131 Providing, laying and making kerb channel 30 cm wide and 50 mm thick with cement concrete 1:3:6 (1 cement: 3 coarse sand:6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth etc. complete and as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001242 6 sqm
132 132 Providing and laying 75 mm thick compacted bed of dry brick aggregate of 40 mm thick nominal size including spreading, well ramming, consolidating and grouting with jamuna sand, including finishing smooth etc. complete as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001243 30 sqm
133 133 Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape , laid in required colour pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc all complete as per the direction of engineer-in-charge BI01010001010000000000000515BI0100001244 10 sqm
134 134 Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). BI01010001010000000000000515BI0100001245 15.01 cum
135 135 Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-in- charge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately). BI01010001010000000000000515BI0100001246 49.83 Cum
136 136 Providing and laying matt finished vitrified tile of size 100x100x16mm having water absorption less than 0.5% and conforming to IS: 15622 of approved make in all colours and shades in out door floors such as footpath, court yard multi models etc., laid on 20mm thick base of cement mortar 1:4 (1cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as direction of Engineer-in-Charge BI01010001010000000000000515BI0100001247 635.07 sqm
137 137 Drainage BI01010001010000000000000515BI0100001248
138 138 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in water tank with required M-25 concrete, manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design or approved by the Engineer in charge/consultant. BI01010001010000000000000515BI0100001249 50 each
139 139 PILE WORK BI01010001010000000000000515BI0100001250
140 140 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). \nNote: Truck Mounted rotary/TMR/Tubewell boring machine shall not be used. BI01010001010000000000000515BI0100001251
141 141 450 mm dia piles BI01010001010000000000000515BI0100001252 1545 metre
142 142 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. \nNote: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. \nNote: 2. Testing agency shall submitt the design of loading platform for the approval of Engineer-in-charge. BI01010001010000000000000515BI0100001253
143 143 Single pile upto 50 tonne Safe capacity BI01010001010000000000000515BI0100001254
144 144 Initial test (Test Load 2.5 times the Safe capacity) BI01010001010000000000000515BI0100001255 3 per test
145 145 Routine test (Test Load 1.5 times the Safe capacity) BI01010001010000000000000515BI0100001256 3 per test
146 146 Lateral load testing of single pile in accordance with IS Code of practice IS : 2911 (Part IV) for determining safe allowable lateral load on pile : BI01010001010000000000000515BI0100001257
147 147 Upto 50 tonne capacity pile BI01010001010000000000000515BI0100001258 3 per test
148 148 Integrity testing of Pile using Low Strain/ Sonic Integrity Test/ Sonic Echo Test method in accordance with IS 14893 including surface preparation of pile top by removing soil, mud, dust & chipping lean concrete lumps etc. and use of computerised equipment and high skill trained personal for conducting the test & submission of results, all complete as per direction of Engineer-in-charge. \nNote :- The inclusion of the above item in the schedule of work shall be judiciously decided by the technical sanctioning authority, keeping in view the quality control, type of soil strata & importance of the BI01010001010000000000000515BI0100001259 100 per test
149 149 Aluminium Work BI01010001010000000000000515BI0100001260
150 150 Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminum sections(2mm thick) shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminum snap beading for glazing / panelling, C.P. brass / stainless steel screws, Hinges , all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and panelling to be paid for separately): BI01010001010000000000000515BI0100001261
151 151 For fixed portion BI01010001010000000000000515BI0100001262
152 152 Powder coated aluminium (minimum thickness of powder coating 50micron ) BI01010001010000000000000515BI0100001263 49.32 KG
153 153 For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). BI01010001010000000000000515BI0100001264
154 154 Powder coated aluminium (minimum thickness of powder coating 50micron ) BI01010001010000000000000515BI0100001265 19.52 KG
155 155 Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS:12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer-in-charge. BI01010001010000000000000515BI0100001266
156 156 Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side BI01010001010000000000000515BI0100001267 10 sqm
157 157 Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. with PVC/neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminum snap beading shall be paid in basic item): BI01010001010000000000000515BI0100001268
158 158 With float glass panes of 5.50mm mm thickness BI01010001010000000000000515BI0100001269 10 sqm
159 159 Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete. BI01010001010000000000000515BI0100001270
160 160 Upto 5mm depth and 5 mm width BI01010001010000000000000515BI0100001271 115.2 meter
161 161 Providing and fixing aluminum tubular handle bar 32 mm outer dia,3.0 mm thick & 400 mm long with SS screws etc .complete as per direction of Engineer-in-Charge. BI01010001010000000000000515BI0100001272
162 162 Powder coated aluminium (minimum thickness of powder coating 50micron )aluminum tubular handle bar BI01010001010000000000000515BI0100001273 2 each
163 163 Water Proofing BI01010001010000000000000515BI0100001274
164 164 Providing and laying water proofing treatment in lift pit, water tanks etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. BI01010001010000000000000515BI0100001275 940 Sqm
165 165 Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer- in-charge. (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer- in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : BI01010001010000000000000515BI0100001276
166 166 With average thickness of 120mm and minimum thickness at khurra as 65 mm. BI01010001010000000000000515BI0100001277 190 Sqm
167 167 Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guaranteed for 10 years against any leakage. BI01010001010000000000000515BI0100001278
168 168 For vertical surface two coats @0.70 kg per sqm per coat BI01010001010000000000000515BI0100001279 501 sqm.
169 169 For horizontal surface one coat @1.10 kg per sqm. BI01010001010000000000000515BI0100001280 439 sqm.
170 170 Structural Glazing Aluminium Composite panel BI01010001010000000000000515BI0100001281
171 171 Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: \n(a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)- cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:\n(b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers.\n(c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. \n(d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. \n(e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. \nNote:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places. \nNote:- 2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories \n(1) Performance Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr \n(2) Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-09 testing method for a range up to 2000 ml. \n(3) Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml \n(4) Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm \n(5) Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test. Tests to be conducted on site. \n(6) Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml BI01010001010000000000000515BI0100001282 749.06 sqm
172 172 Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminum Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc. including BI01010001010000000000000515BI0100001283
173 173 Structural analysis & design and preparation of shop drawings for pressure equalization or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design. BI01010001010000000000000515BI0100001284
174 174 Providing, fabricating and supplying and fixing panels of aluminum composite panel cladding in pan shape in metallic colour of approved shades made out of 4mm thick aluminum composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminum sheets (each 0.5mm thick). The aluminum composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. BI01010001010000000000000515BI0100001285
175 175 The fastening brackets of Aluminum alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item's The Contractor shall provide curtain wall with aluminum composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places." BI01010001010000000000000515BI0100001286 1123.58 Sqm
176 176 Providing & Fixing of 8mm thick Heat Reflective toughened Glass of Saint Gobain / Glaverbel of approved colour & make complete with wastages, installation, loading, un-loading, stacking and carrying to all heights & levels as required. BI01010001010000000000000515BI0100001287 749.06 Sqm
177 177 Providing and laying Non shrinkage compound fosroc make Conbextra GP2, compressive strength BS 1881-Part116:1983,Flexural strength ( BS 4551,1998), Tensile strength 3.5N/sqmm,Pullout bond strength 17N/Sqmm in 7 days, 20N/Sqmm in 28 days, Young Modulus(ASTM469-94)-28KN/sqmm with required amount of water as per chemical specification including cleaning the surface, shuttering work, etc complete or as per directed by the Engineer in charge. BI01010001010000000000000515BI0100001288 1.82 cum
178 178 Sand blastng in structue steel as per direction of Engineer in charge BI01010001010000000000000515BI0100001289 166607 kg
179 179 Extra over on used sulphate resistance cement over OPC cement as per the direction of Engineer in charge BI01010001010000000000000515BI0100001290 5831.5 bag
180 180 Extra Over TMT Bar for corrsion restance steel as per the direction of Engineer in charge BI01010001010000000000000515BI0100001291 107177 Kg
181 181 Providing and fixing roofing consist of 0.8 mm thick galvanized steel deck sheet confirming to IS 277:1992 used as permanent shuttering over which MS wire mesh 3mm laid at 100x100 mm grid including edge trim covered with concrete. This metal deck will be supported on structural steel beam with shear studs. (Structural steel like Beam, column, joists etc. & concrete of different grade as per design will be paid separately). BI01010001010000000000000515BI0100001292 28.95 sqm
182 182 SOIL, WASTE, VENT, RAIN WATER PIPES AND FITTINGS BI01010001010000000000000515BI0100001293
183 183 Excavating trenches of required width for pipes, cables, etc including,excavation for sockets, and dressing of sides, ramming of bottoms,depth upto 1.5 m, including getting out the excavated soil, and then,returning the soil as required, in layers not exceeding 20 cm in depth,including consolidating each deposited layer by ramming, watering,etc. and disposing of surplus excavated soil as directed, within a lead of 50 Mtr,All kinds of soil BI01010001010000000000000515BI0100001294
184 184 Pipes, cables etc, not exceeding 80 mm dia. BI01010001010000000000000515BI0100001295 20 metre
185 185 Pipes, cables etc. exceeding 80 mm dia. but notexceeding 300 mm dia . BI01010001010000000000000515BI0100001296 70 metre
186 186 Structural steel work riveted,bolted or welded in built up section trusses and framed work , including cutting ,hoisting,fixing in position and applying a priming coat of of approved steel primer all complet. BI01010001010000000000000515BI0100001297 30 Kg
187 187 Providing and fixing M.S. holder bat clamps of approved design to C.I. or S.C.I. rain water pipes embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and cost of cutting holes and making good the walls etc. : BI01010001010000000000000515BI0100001298
188 188 100 mm diameter BI01010001010000000000000515BI0100001299 160 each
189 189 150 mm diameter BI01010001010000000000000515BI0100001300 160 each
190 190 Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. BI01010001010000000000000515BI0100001301
191 191 110 mm diameter BI01010001010000000000000515BI0100001302 250 metre
192 192 Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams. BI01010001010000000000000515BI0100001303 5 each
193 193 Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required. BI01010001010000000000000515BI0100001304
194 194 bituminous portion BI01010001010000000000000515BI0100001305 5 cum
195 195 Water bound macadam BI01010001010000000000000515BI0100001306 5 cum
196 196 Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass,including painting of fittings and cutting and making good the walls and floors wherever required : BI01010001010000000000000515BI0100001307
197 197 Single half stall urinal with 5 litre P.V.C. automatic flushing cistern BI01010001010000000000000515BI0100001308 1 Each
198 198 Providing and fixing wash basin with C.I. brackets, 15 mm PTMT pillar cock, 32 mm PTMT waste coupling of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required. White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm PTMT pillar cock. BI01010001010000000000000515BI0100001309 2 Each
199 199 Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in charge. BI01010001010000000000000515BI0100001310 2 Each
200 200 Providing and fixing CP Brass 32mm size Bottle Trap of\napproved quality & make and as per the direction of Engineer in-charge.\n BI01010001010000000000000515BI0100001311 4 Each
201 201 Providing and installation of 600x450 and 6 mm thick mirror fixed with stain less steel studs on wall for wash basin. BI01010001010000000000000515BI0100001312 2 Each
202 202 Providing and fixing toilet paper holder BI01010001010000000000000515BI0100001313
203 203 CP Brass BI01010001010000000000000515BI0100001314 2 Each
204 204 Providing and fixing soil, waste and vent pipes : BI01010001010000000000000515BI0100001315
205 205 100 mm dia BI01010001010000000000000515BI0100001316
206 206 Sand cast iron S&S pipe as per IS: 1729 BI01010001010000000000000515BI0100001317 74 metre
207 207 Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. BI01010001010000000000000515BI0100001318
208 208 100 mm dia BI01010001010000000000000515BI0100001319
209 209 Sand cast iron S&S as per IS - 1729 BI01010001010000000000000515BI0100001320 20 each
210 210 Providing and fixing plain bend of required degree. BI01010001010000000000000515BI0100001321
211 211 100 mm dia BI01010001010000000000000515BI0100001322
212 212 Sand cast iron S&S as per IS - 1729 BI01010001010000000000000515BI0100001323 20 each
213 213 Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 ( 1 cement : 2 fine sand) in S.C.I./ C.I. Pipes : BI01010001010000000000000515BI0100001324
214 214 100 mm dia pipe BI01010001010000000000000515BI0100001325 115 Each
215 215 Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : BI01010001010000000000000515BI0100001326
216 216 100 mm inlet and 100 mm outlet BI01010001010000000000000515BI0100001327
217 217 Sand cast iron S&S as per IS: 3989 BI01010001010000000000000515BI0100001328 1 Each
218 218 Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms. BI01010001010000000000000515BI0100001329 2 Each
219 219 Providing and fixing floor mounted, white vitreous china single piece, double traps syphonic water closet of approved brand/make, shape, size and pattern including integrated white vitreous china cistern of capacity 10 litres with dual flushing system, including all fittings and fixtures with seat cover, cistern fittings, nuts, bolts and gasket etc including making connection with the existing P/S trap, complete in all respect as perdirections of Engineer-in-Charge. BI01010001010000000000000515BI0100001330 2 Each
220 220 Providing and fixing G.I. pipes medium complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall/ceiling BI01010001010000000000000515BI0100001331
221 221 25mm dia nominal bore BI01010001010000000000000515BI0100001332 110 metre
222 222 50mm dia nominal bore BI01010001010000000000000515BI0100001333 48 metre
223 223 Providing and fixing G.I. Pipes medium complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall : 18.11.1 BI01010001010000000000000515BI0100001334
224 224 15 mm dia nominal bore BI01010001010000000000000515BI0100001335 22 metre
225 225 Providing and fixing G.I. pipes of medium complete with G.I. fittings including trenching and refilling etc. for toilet waste line.(internal/external.( C class heavy duty) BI01010001010000000000000515BI0100001336
226 226 50 mm dia BI01010001010000000000000515BI0100001337 10 metre
227 227 Fixing water meter and stop cock in G.I. pipe line including cutting and threading the pipe and making long screws etc. complete (costof water meter and stop cock to be paid separately). BI01010001010000000000000515BI0100001338 1 Each
228 228 Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete BI01010001010000000000000515BI0100001339
229 229 15 mm nominal bore BI01010001010000000000000515BI0100001340 1 Each
230 230 20 mm nominal bore BI01010001010000000000000515BI0100001341 1 Each
231 231 25 mm nominal bore BI01010001010000000000000515BI0100001342 1 Each
232 232 Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : BI01010001010000000000000515BI0100001343
233 233 With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 BI01010001010000000000000515BI0100001344 6 Each
234 234 Painting G.I. pipes and fittings with synthetic enamel white/Green paint with two coats over a ready mixed priming coat, both of approved quality for new work : BI01010001010000000000000515BI0100001345
235 235 15 mm diameter pipe metre 9.95 BI01010001010000000000000515BI0100001346 22 metre
236 236 25 mm diameter pipe metre 15.50 BI01010001010000000000000515BI0100001347 110 metre
237 237 50 mm diameter pipe BI01010001010000000000000515BI0100001348 48 metre
238 238 Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : BI01010001010000000000000515BI0100001349
239 239 15 mm nominal bore BI01010001010000000000000515BI0100001350 4 Each
240 240 Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 BI01010001010000000000000515BI0100001351
241 241 15mm nominal bore BI01010001010000000000000515BI0100001352 8 Each
242 242 Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) BI01010001010000000000000515BI0100001353
243 243 of approved make and quality as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001354 5 Each
244 244 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design etc. complete. BI01010001010000000000000515BI0100001355
245 245 150 mm diameter RCC/S.W.Pipe/PVC pipe BI01010001010000000000000515BI0100001356 90 Metre
246 246 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: BI01010001010000000000000515BI0100001357
247 247 100 x 100 mm. size P type BI01010001010000000000000515BI0100001358
248 248 With common bunt clay FPS (non modular) bricks of class disignation 7.5 BI01010001010000000000000515BI0100001359 2 Each
249 249 Providing and laying non-pressure NP2 class (light duty) R.C.C.pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. BI01010001010000000000000515BI0100001360
250 250 150 mm diameter RCC BI01010001010000000000000515BI0100001361 90 metre
251 251 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : BI01010001010000000000000515BI0100001362
252 252 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions,total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :19.7.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 BI01010001010000000000000515BI0100001363 3 Each
253 253 Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete : BI01010001010000000000000515BI0100001364
254 254 For pipes 100 to 250 mm diameter- sewer connection BI01010001010000000000000515BI0100001365 1 Each
255 255 Providing sand cast iron drop connection externally for 60 cm drop from branch sewer line to main sewer manhole including inspection and cleaning eye with chain and lid, sand cast iron drop pipe and bend encased all-round with cement concrete 1:5:10 (1 cement :5 fine sand : 10 graded stone aggregate 40 mm nominal size) with all centering and shuttering required, cutting holes in walls and making good with brick work in cement mortar 1:4 (1 cement : 4 coarse sand) plastered with cement mortar 1:3 (1 cement : 3coarse sand) on inside of the manhole wall, lead caulked joints between sand cast iron pipes and fittings, stiff cement mortar 1:1(1 cement : 1 fine sand) joints between sand cast iron tee and S.W. pipe, making required channels complete as per standard design and specifications : BI01010001010000000000000515BI0100001366
256 256 100 mm dia sand cast iron drop connection BI01010001010000000000000515BI0100001367 2 Each
257 257 Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design BI01010001010000000000000515BI0100001368
258 258 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 : BI01010001010000000000000515BI0100001369 5 Each
259 259 Supply fixing and installation of 12 mm thick frosted toughned glass partition for urinal as per architects design. ( size approx 2.5'X1.5') BI01010001010000000000000515BI0100001370 2 Each
260 260 Providing and installation of hand shower (Health Faucet) with 8 mm dia 1Meter longflexible tube and wall hook with N.R.V (Back Flow Preventer) as per approved make : BI01010001010000000000000515BI0100001371 2 Each
261 261 Providing and installation Stainless Steel round jali 125 mm as per approved make : BI01010001010000000000000515BI0100001372 8 Each
262 262 RWH Works BI01010001010000000000000515BI0100001373
263 263 Carriage of excavated earth , by mechanical transportation including loading, unloading and stacking BI01010001010000000000000515BI0100001374
264 264 For 5KM BI01010001010000000000000515BI0100001375 38.38 Cum
265 265 For 10 km ; Rate = 149.17+(5*10.85)=203.42 BI01010001010000000000000515BI0100001376 23.03 Cum
266 266 For 20km; rate=203.42+(10*8.91)=292.52 BI01010001010000000000000515BI0100001377 15.35 Cum
267 267 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge BI01010001010000000000000515BI0100001378
268 268 All kinds of soil BI01010001010000000000000515BI0100001379 184.61 Cum
269 269 Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : BI01010001010000000000000515BI0100001380
270 270 All kinds of soil BI01010001010000000000000515BI0100001381
271 271 Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia BI01010001010000000000000515BI0100001382 80 metre
272 272 pipes cables etc exceeding 300mm dia but not exceeding 600mm BI01010001010000000000000515BI0100001383 20 metre
273 273 Extra for excavating trenches for pipes, cables etc. in all kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over corresponding basic item for depth upto 1.5 metre). BI01010001010000000000000515BI0100001384 20 metre
274 274 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50m and lift upto 1.5 m. BI01010001010000000000000515BI0100001385 107.84 Cum
275 275 Extra for every additional lift of 1.5 m or part thereof in excavation /banking excavated or stacked materials. BI01010001010000000000000515BI0100001386
276 276 All kinds of soil 1.5m or part of it BI01010001010000000000000515BI0100001387 81.55 Cum
277 277 Surface dressing of the ground including removing vegetation and in- equalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. BI01010001010000000000000515BI0100001388
278 278 All kinds of soil BI01010001010000000000000515BI0100001389 19.01 Sqm
279 279 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : BI01010001010000000000000515BI0100001390
280 280 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm size) BI01010001010000000000000515BI0100001391 0.56 Cum
281 281 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm size BI01010001010000000000000515BI0100001392 9.36 Cum
282 282 Centering and shuttering including strutting, propping etc. and removal of form for all heights : BI01010001010000000000000515BI0100001393
283 283 Suspended floors, roofs, landings, balconies and access platform BI01010001010000000000000515BI0100001394 13.62 Sqm
284 284 Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth level. BI01010001010000000000000515BI0100001395
285 285 Thermo-Mechanically Treated bars of grade Fe-500D or more. BI01010001010000000000000515BI0100001396 408.48 Kg
286 286 Providing and laying in position ready mixed M-25 grade concrete for reinforced cement concrete work, using fly ash and cement content as per approved design mix, and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work, including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering, shuttering, finishing and reinforcement, including cost of admixtures in recommended proportions as per IS : 9103 to accelerate / retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge.NOTE- (1) Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.“ (2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS : 456. Uniform blending with cement to be ensured in accordance with clauses 5.2 and 5.2.1 of IS:456 -2000 in the items of BMC and RMC. Note :- The above item shall be used judiciously where specified quality of Fly Ash is available for mixing in concrete. Also, the guidelines issued by CDO, CPWD, vide circular no. CDO/ SE(RR)/ Fly Ash (Main)/102 dated 9th April 2009 shall be followed in such cases. BI01010001010000000000000515BI0100001397
287 287 All works upto plinth level BI01010001010000000000000515BI0100001398 2.72 Cum
288 288 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: BI01010001010000000000000515BI0100001399
289 289 Cement mortar 1:6 (1 cement : 6 coarse sand) BI01010001010000000000000515BI0100001400 32.5 Cum
290 290 Providing Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and including a priming and painting coat of approved epoxy paint on surface as per specifications. \n BI01010001010000000000000515BI0100001401 10 Kg
291 291 12 mm cement plaster of mix : BI01010001010000000000000515BI0100001402
292 292 1:4 (1 cement: 4 fine sand) BI01010001010000000000000515BI0100001403 80.54 Sqm
293 293 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand BI01010001010000000000000515BI0100001404 40.14 Sqm
294 294 6 mm cement plaster of mix : BI01010001010000000000000515BI0100001405
295 295 1:3 (1 cement : 3 fine sand) BI01010001010000000000000515BI0100001406 9 Sqm
296 296 Neat cement punning BI01010001010000000000000515BI0100001407 127.82 Sqm
297 297 Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers BI01010001010000000000000515BI0100001408 59.98 Per bag of 50 kg cement used
298 298 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : BI01010001010000000000000515BI0100001409
299 299 250 mm dia. R.C.C. pipe BI01010001010000000000000515BI0100001410 80 metre
300 300 450mm dia R.C.C pipe BI01010001010000000000000515BI0100001411 20 Metre
301 301 Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in water tank with required M-25 concrete, manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design or approved by the Engineer in charge/consultant. BI01010001010000000000000515BI0100001412 20 Each
302 302 Supplying and fixing C.I. cover without frame for manholes : BI01010001010000000000000515BI0100001413
303 303 455x610 mm rectangular C.I. cover (light duty) the weight of the cover to be not less than 23 kg BI01010001010000000000000515BI0100001414 2 Each
304 304 560 mm diameter C.I. cover (heavy duty) the weight of the cover to be not less than 108 kg BI01010001010000000000000515BI0100001415 1 each
305 305 Providing and fixing in position pre-cast R.C.C. manhole cover and frame of required shape and approved quality BI01010001010000000000000515BI0100001416
306 306 M D - 10 BI01010001010000000000000515BI0100001417
307 307 Square shape 450 mm internal dimension BI01010001010000000000000515BI0100001418 1 each
308 308 Circular shape 500 mm internal diameter BI01010001010000000000000515BI0100001419 1 each
309 309 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. BI01010001010000000000000515BI0100001420
310 310 All types of soil BI01010001010000000000000515BI0100001421
311 311 400 mm dia BI01010001010000000000000515BI0100001422 30 Metre
312 312 Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge. BI01010001010000000000000515BI0100001423
313 313 200 mm nominal size dia BI01010001010000000000000515BI0100001424 20 Metre
314 314 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001425
315 315 200 mm nominal size dia BI01010001010000000000000515BI0100001426 10 Metre
316 316 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001427 2.5 Cum
317 317 Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001428 3.6 Cum
318 318 Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -incharge. BI01010001010000000000000515BI0100001429 3.6 Cum
319 319 Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. BI01010001010000000000000515BI0100001430 2.45 Cum
320 320 Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: BI01010001010000000000000515BI0100001431
321 321 200 mm dia BI01010001010000000000000515BI0100001432 1 Each
322 322 Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. BI01010001010000000000000515BI0100001433
323 323 200 mm clamp BI01010001010000000000000515BI0100001434 2 Each
324 324 FIRE PUMPs AND ELECTRICAL PANEL BI01010001010000000000000515BI0100001435
325 325 Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :\n(a) Horizontal type, multistage, centrifugal, split casing\npump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.\n(b) Suitable HP Squirrel cage induction motor, TEFC,\nsynchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.\n(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.\n(d) Suitable cement concrete foundation duly plastered with anti vibration pads. BI01010001010000000000000515BI0100001436
326 326 2280 LPM AT 70 M HEAD BI01010001010000000000000515BI0100001437 2 Nos
327 327 Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for\nautomatic operation and consisting of following,\ncomplete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft,mechanical seal conforming to IS 1520.Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer,instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered\nand with anti vibration pads.\n BI01010001010000000000000515BI0100001438
328 328 2280 LPM AT 70 M HEAD BI01010001010000000000000515BI0100001439 1 Nos
329 329 Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for\nautomatic operation and consisting of following,\ncomplete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft,mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. BI01010001010000000000000515BI0100001440
330 330 180 LPM AT 70 M HEAD BI01010001010000000000000515BI0100001441 2 Nos
331 331 Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body& bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads. BI01010001010000000000000515BI0100001442
332 332 900 lpm at 35 m Head BI01010001010000000000000515BI0100001443 1 Nos
333 333 Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes\ncomplete as required. BI01010001010000000000000515BI0100001444
334 334 150 mm dia BI01010001010000000000000515BI0100001445 55 Metre
335 335 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : BI01010001010000000000000515BI0100001446
336 336 25 mm dia BI01010001010000000000000515BI0100001447 110 Metre
337 337 32 mm dia BI01010001010000000000000515BI0100001448 5 Metre
338 338 40 mm dia BI01010001010000000000000515BI0100001449 15 Metre
339 339 50 mm dia BI01010001010000000000000515BI0100001450 85 Metre
340 340 65 mm dia BI01010001010000000000000515BI0100001451 85 Metre
341 341 80 mm dia BI01010001010000000000000515BI0100001452 18 Metre
342 342 100 mm dia BI01010001010000000000000515BI0100001453 40 Metre
343 343 150 mm dia BI01010001010000000000000515BI0100001454 95 Metre
344 344 200 mm dia BI01010001010000000000000515BI0100001455 10 Metre
345 345 250 mm dia BI01010001010000000000000515BI0100001456 10 Metre
346 346 Supplying and fixing single headed internal hydrant\nvalve with instantaneous Gunmetal/Stainless Steel\ncoupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank\nGunmetal/Stainless Steel cap and chain as required. BI01010001010000000000000515BI0100001457
347 347 Single headed Stainless steel BI01010001010000000000000515BI0100001458 12 Set
348 348 Supplying and fixing Single headed external yard\nhydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : BI01010001010000000000000515BI0100001459
349 349 Single headed Stainless steel BI01010001010000000000000515BI0100001460 2 Set
350 350 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : BI01010001010000000000000515BI0100001461
351 351 50 mm dia BI01010001010000000000000515BI0100001462 2 Set
352 352 65 mm dia BI01010001010000000000000515BI0100001463 4 Set
353 353 80 mm dia BI01010001010000000000000515BI0100001464 5 Set
354 354 100 mm dia BI01010001010000000000000515BI0100001465 4 Set
355 355 150 mm dia BI01010001010000000000000515BI0100001466 12 Set
356 356 200 mm dia BI01010001010000000000000515BI0100001467 1 Set
357 357 250 mm dia BI01010001010000000000000515BI0100001468 1 Set
358 358 Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : BI01010001010000000000000515BI0100001469
359 359 150 mm dia Set BI01010001010000000000000515BI0100001470 2 Set
360 360 Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 14.1 40mm dia Set 5646.00 14.2 Set 14.3 14.4 14.5 14.6 125mm dia Set 15700.00 14.7 14.8 .00 14.9 250mm dia Set 45081.00 14.10 300mm dia Set 60243.00 BI01010001010000000000000515BI0100001471
361 361 65mm dia BI01010001010000000000000515BI0100001472 1 Set
362 362 80 mm dia BI01010001010000000000000515BI0100001473 4 Set
363 363 100 mm dia BI01010001010000000000000515BI0100001474 1 Set
364 364 150 mm dia BI01010001010000000000000515BI0100001475 4 Set
365 365 200 mm dia BI01010001010000000000000515BI0100001476 1 Set
366 366 Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. BI01010001010000000000000515BI0100001477
367 367 250 mm dia BI01010001010000000000000515BI0100001478 1 Each
368 368 Supplying and fixing 63 mm dia, 15 m long RRL hose\npipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required BI01010001010000000000000515BI0100001479
369 369 Stainless steel (Grade-304) BI01010001010000000000000515BI0100001480 24 Set
370 370 Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red,conforming to IS 884 complete with the following as required20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle.Drum and brackets for fixing the equipmets on wall.Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. BI01010001010000000000000515BI0100001481
371 371 30 m BI01010001010000000000000515BI0100001482 12 Set
372 372 Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :- Gun metal BI01010001010000000000000515BI0100001483
373 373 Gun Metal BI01010001010000000000000515BI0100001484 12 Nos
374 374 Providing and fixing fire brigade inlet connection of cast iron body with ss-304 grade 63mm dia instantaneous type male coupling with built in check valves and 150mm dia flanged outlet complete with bolts, nuts and rubber insertions as per IS:904. (to be connected to static tank). : BI01010001010000000000000515BI0100001485
375 375 Four Way inlet connection BI01010001010000000000000515BI0100001486 3 Set
376 376 Supplying and fixing air vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. BI01010001010000000000000515BI0100001487 2 Set
377 377 Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories. BI01010001010000000000000515BI0100001488
378 378 Pendent type BI01010001010000000000000515BI0100001489 60 Each
379 379 Horizontal Side wall sprinkler BI01010001010000000000000515BI0100001490 72 Each
380 380 Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. BI01010001010000000000000515BI0100001491 7 Each
381 381 Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 23.1 100mm dia Each 7362.00 23.2 150mm dia Each 8869.00 BI01010001010000000000000515BI0100001492
382 382 100/80 mm dia BI01010001010000000000000515BI0100001493 6 Each
383 383 Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : BI01010001010000000000000515BI0100001494
384 384 150mm dia BI01010001010000000000000515BI0100001495 1 Set
385 385 Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. BI01010001010000000000000515BI0100001496
386 386 1000mm Set 1540.00 BI01010001010000000000000515BI0100001497 8 Set
387 387 Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. BI01010001010000000000000515BI0100001498 8 Set
388 388 Providing and fixing gunmetal single acting air release valve with screwed inlet 25 mm dia and with necessary G.I. coupling, valve to be fitted on top of Air vessel or on wet riser as per specification. BI01010001010000000000000515BI0100001499 3 Each
389 389 Providing and fixing of pressure vessals tank 450mm dia. x 2.0 M high with dished top, made of minimum 6 mm thick M.S. pipe/plate complete with 25 mm dia. Brass Air Valve (Ball valve, pressure guage type), 25 mm dia. Stop with brass stop cock,nipple, tees, elbow and all accessories as required incl. fixing bracketsof base etc. BI01010001010000000000000515BI0100001500 1 Each
390 390 Supply and fixing 150 mm dia CI foot valve in suction line from water tank complete. BI01010001010000000000000515BI0100001501 1 Each
391 391 FIRE FIGHTING PUMP PANELS & EQUIPMENTS BI01010001010000000000000515BI0100001502
392 392 Fabrication, supply, Insallation testing & commissioning of Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : Incomings 320A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800Amps. Outgoings (Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 200 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets BI01010001010000000000000515BI0100001503 1 Nos
393 393 Jockey Pump BI01010001010000000000000515BI0100001504
394 394 100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets, BI01010001010000000000000515BI0100001505
395 395 Terrace Pump BI01010001010000000000000515BI0100001506
396 396 100 Amp, 50kA TPN MCCB, Ics=100% Icu, with 20 HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with suitable volt meter , Ampear meter & selector switch along with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 1 sets BI01010001010000000000000515BI0100001507
397 397 Diesel Engine Control BI01010001010000000000000515BI0100001508
398 398 Control for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons,start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication BI01010001010000000000000515BI0100001509
399 399 125 A 4 POLE MCCB 1 NO. (Spare) BI01010001010000000000000515BI0100001510
400 400 Providing & fixing Fire Brigade connection for drawout 150/100 mm dia of cast iron body / Gunmetal instantaneous inlet couplings complete as required. BI01010001010000000000000515BI0100001511 1 Each
401 401 Providing and fixing M.S. fire hose shaft door with frame fabricated from angle iron frame 40 x 40 x 5 mm thick, angle iron, shutter 16 g M.S. sheet of fully welded construction with hinged double front door with locking arrangement and butt hinges, 15 x 3 mm lugs 10 cm long (6 Nos) embedded in cement conc. blocks ( 1: 3: 6 mix) or with rawl plug and screws/bolts and nuts as required, partly glass door 4 mm thick , painted with one coat of primer, stove enamelled fire red finished, "Fire Hose" written on front, suitable to accommodate 1 Nos single headed Hydrant landing valve, 1 fire hose reel, 2 nos.15m long 63mmdia hose,1-branch pipe, 1 fire-man's axe as required. (Approx.size 0.9m x 2.1m) BI01010001010000000000000515BI0100001512 12 Each
402 402 Providing and fixing Weather proof hose cabinets fabricated from 16 g M.S. Sheet with full glass door and locking arrangement, suitable to accommodate 2 Nos. single headed Hydrant landing valve, 2 nos. 15 M long hose and 1 No branch pipe/ fire brigade connectors, 2 Nos. fire extinguishers. The cabinet shall be painted with one coat of primer and finished stove enamelled "Fire Red", "Fire Hose" written on front including suitably mounted on a raised masonry platform as required.(Approx 0.75m x 0.6 m x 0.3 m). BI01010001010000000000000515BI0100001513 2 Each
403 403 Construction of brick masonry valve chamber 60x60x100 cms. (inside) with 75 class designation brick work in cement mortar 1:5 (I cement : 5 coarse sand) for valves with C.I.surface box 60 x 45 cms.(inside) with locking arrangement and RCC roof slab 1:2:4 mix (I cement :2 coarse sand :4 graded stone aggregate 20 mm nominal size) and inside plastering with cement mortar l:3(1cement :3 coarse sand) finished with a floating coat of neat cement as per standard design. BI01010001010000000000000515BI0100001514 1 Each
404 404 Supply Installation and testing forged brass Ball valve with hard chrome plated ball inside PTFE (Teflon) seat & ring with chrome plated centre handle with female BSP threads suitable for 15 kg/sq cm. complete in all respects. BI01010001010000000000000515BI0100001515
405 405 20 mm dia nominal bore BI01010001010000000000000515BI0100001516 8 Each
406 406 25 mm dia nominal bore BI01010001010000000000000515BI0100001517 8 Each
407 407 Providing and fixing dial type pressure gauge at hydrant station, complete in all respects. Dial dia 100 mm, calibration 0-15 kg/sq cm. Valve shall be paid separately. BI01010001010000000000000515BI0100001518
408 408 20 mm dia nominal bore BI01010001010000000000000515BI0100001519 7 Each
409 409 Providing and fixing 25 mm dia inspecting & testing assembly with gunmetal valve, gunmetal sight glass, bypass valve & connected to drain line. BI01010001010000000000000515BI0100001520 6 Each
410 410 Providing and fixing for domestic water tank and fire water tank of puddle flange in G.I Material, with Hot Dip Galvanized puddle flange, 600 mm lenght ,C Class Pipe puddle plate 6 mm of thickness (150 + dia of pipe + 150 ) one end threaded. and as per the stite requirement , BI01010001010000000000000515BI0100001521
411 411 250 mm BI01010001010000000000000515BI0100001522 1 Nos
412 412 150 mm BI01010001010000000000000515BI0100001523 1 Nos
413 413 100 mm BI01010001010000000000000515BI0100001524 1 Nos
414 414 80 mm BI01010001010000000000000515BI0100001525 1 Nos
415 415 50 mm BI01010001010000000000000515BI0100001526 6 Nos
416 416 Providing and fixing of suitable flexible neoprene rubber expansion joint, single arch with integral rubber flanges tested at 20 Kg/cm2 with SRR drilled as per BS-10, Table-D, complete. BI01010001010000000000000515BI0100001527
417 417 200mm dia BI01010001010000000000000515BI0100001528 1 Each
418 418 150mm dia BI01010001010000000000000515BI0100001529 6 Each
419 419 100 mm dia BI01010001010000000000000515BI0100001530 1 Each
420 420 80 mm dia BI01010001010000000000000515BI0100001531 3 Each
421 421 65mm dia BI01010001010000000000000515BI0100001532 3 Each
422 422 Supply and fixing of perforated 1.6 mm thick CRCA sheet steel painted cable tray of following sizes complete with bend/ tee joints, coupling plate & nuts, bolts etc. including providing and fixing GI hanger etc. as required. BI01010001010000000000000515BI0100001533
423 423 150 mm wide 50 mm depth BI01010001010000000000000515BI0100001534 35 Metre
424 424 300 mm wide 50 mm depth and 2,mm thikness BI01010001010000000000000515BI0100001535 20 Metre
425 425 Supplying, laying, connecting, testing & commisioning of under noted size of PVC insulated, PVC sheathed armoured and overall PVC sleaved control cables\n2C x 1.5 sq.mm copper solid cunductor BI01010001010000000000000515BI0100001536 50 Metre
426 426 Supply and fixing of on-line UPS of rating 3.2/3.5 KVA (Single Phase i/c & single phase o/g) with 30 mins power back-up, 1 Nos ups DB double door with 40 amp D.P MCB,incomer and 6 , Nos 16 Amp S.P MCB for out going supply along with all accessories and as per requirement.( for Staircase emergency light) BI01010001010000000000000515BI0100001537 1 set
427 427 Supplying, laying, connecting, testing & commissioning of under noted sizes of aluminium / copper conductor XLPE insulated, PVC sheathed armoured and overall PVC sleeved 1.1 KV grade power distribution cables in pipe, wall, racks, cable trays, including, dressing, clamping with M.S Zinc passivated clamps etc as required conforming to relevant IS code and technical specifications. BI01010001010000000000000515BI0100001538
428 428 3½ X 150 sq. mm (Aluminium Armoured) BI01010001010000000000000515BI0100001539 60 Metre
429 429 3.5C x 95 sq.mm (Aluminium Ar) BI01010001010000000000000515BI0100001540 40 Metre
430 430 3.5C x 25 sq.mm (Aluminium Ar) BI01010001010000000000000515BI0100001541 40 Metre
431 431 3C x 16 sq.mm (Aluminium Ar) BI01010001010000000000000515BI0100001542 40 Metre
432 432 2C x1.5 sq.mm (copper Ar) BI01010001010000000000000515BI0100001543 30 Metre
433 433 D.G Control cable,6 core 2.5 sqmm multistandard BI01010001010000000000000515BI0100001544 10 Metre
434 434 Supply and making end termination with brass single compression gland including providing and crimping of aluminium/copper solder less lugs/ferrules for XLPE/ PVC armoured/ Unarmoured aluminium/ copper conductor cable 1.1 KV grade of following sizes: BI01010001010000000000000515BI0100001545
435 435 3½ X150 sq. mm (50mm) BI01010001010000000000000515BI0100001546 4 Nos
436 436 3.5C x 95 sq.mm (Aluminium Ar) BI01010001010000000000000515BI0100001547 8 Nos
437 437 3.5C x 25 sq.mm (Aluminium Ar) BI01010001010000000000000515BI0100001548 8 Nos
438 438 3C x 16 sq.mm (Aluminium Ar) BI01010001010000000000000515BI0100001549 8 Nos
439 439 2C x1.5 sq.mm (copper Ar) BI01010001010000000000000515BI0100001550 2 Nos
440 440 D.G Control cable,6 core 2.5 sqmm multistandard BI01010001010000000000000515BI0100001551 2 Nos
441 441 FIRE ALARM AND DETECTION SYSTEM. BI01010001010000000000000515BI0100001552
442 442 Supply, Installation, testing and commissioning of 12 Zone Microprocesser base Main Fire Detection & Alarm Control Panel with PA system including Amplifier and Mic complete with 12 hrs SMF batteries, battery charger and in accordance with the specification and as per requirement of local fire Authorities. Note:- Parking system supplier to make his on arranged to give constant power supply to his parking equipments BI01010001010000000000000515BI0100001553 1 Set
443 443 Supplying and fixing of following fire alarm Meter and detection accessories complete with connection etc. as required. BI01010001010000000000000515BI0100001554
444 444 Manual Break Glass Units. BI01010001010000000000000515BI0100001555 11 Each
445 445 Fire Alarm Bell / Hooter. BI01010001010000000000000515BI0100001556 11 Each
446 446 Smoke Detectors. BI01010001010000000000000515BI0100001557 30 Each
447 447 Control relay module BI01010001010000000000000515BI0100001558 1 Each
448 448 10, zones (16 working + 4 spare for future) annunciater Panel for flow control switches, providing Audio/Visual Indication of actuation of Automatic Sprinkler system / fault hooter,along with module for singnal etc., for each zone complete as per specifications. The panel should have interface for connection to complete controlled building management system. BI01010001010000000000000515BI0100001559 1 Each
449 449 Supplying and fixing of following sizes of MS conduit along with the accessories in surface / surface including painting in case of surface conduit in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. BI01010001010000000000000515BI0100001560
450 450 25 mm dia. BI01010001010000000000000515BI0100001561 375 Metre
451 451 Supplying and drawing following sizes of PVC insulated FRLS copper conductor single core cable in the existing surface / recessed steel conduit as required. BI01010001010000000000000515BI0100001562
452 452 2 x 1.5 sq.mm . BI01010001010000000000000515BI0100001563 376 Metre
453 453 Portable Chemical Fire Extinguishers. BI01010001010000000000000515BI0100001564
454 454 SUPPLY & FIXING OF ISI (IS:15683) marked Water type stored pressure (stored pressure) type capacity 9 ltrs. with gun-metal cap and nozzle and complete in all respects including initial fill and wall suspension bracket. Capacity 9 ltrs. BI01010001010000000000000515BI0100001565 5 Each
455 455 SUPPLY & FIXING OF ISI marked (IS:15683) Portable fire Extinguisher, Carbon-dioxide type flat base including valve, discnarge hose of not less than 10 mm dia. 1m long & complete in all respects including initial fill with C02 gas confirming to IS:307-1966 filled to a filling ratio of not more than 0.667of not more than 0.667and wall suspension bracket. BI01010001010000000000000515BI0100001566
456 456 Capacity 4.5 Kg BI01010001010000000000000515BI0100001567 2 Each
457 457 SUPPLY & FIXING OF ABC dry powder conforming to IS:15683, stored pressure type fire extinguishers (Mono ammonium phosphate confirming to IS 14609) minimum 85% effective discharge, finished externally with red enamel paint and fixed to wall with brackets, complete, with internal charge. BI01010001010000000000000515BI0100001568
458 458 Capacity : 4 kg (Min Jet length 4.0 m) BI01010001010000000000000515BI0100001569 5 Each
459 459 Fire Rated DOOR BI01010001010000000000000515BI0100001570
460 460 Providing and fixing of 50mm thick and 120 minutes fire rating, conforming to BS:476 part 22 IS: 3614 part-II, specifications similar to that of prototype tested & certified at CBRI Roorkee, suitable for mounting on door frame made out of hardwood redmarrandi of section 120x70mm. The Shutter shall be comprising of 2 non- metallic, asbestos free, fire/smoke check doors Calcium Silicate boards each 12mm thick sandwiching 20mm thick fire resistant insulation filler faced with 3mm thick commercial ply on both faces with hard wood lipping all around the shutter with heat activated Intumescent fire seal strip of size 20 mm x 4 mm on all sides except bottom shutter and the Frame is fitted with 2no. Intumuscent fire seals strip of size 10x4mmin Main Frame (for smoke sealing). The shutter will be fixed with the frame with the help of SS ball bearing hinges of size 100x75x3mm. Provisions/reinforcement for fixing all fixtures shall be built in on the doors prior to the supply. BI01010001010000000000000515BI0100001571
461 461 The board shall be Resistant to vermin, mould growth, minor impact, abrasion and short term water attack and shall be Off –white in colour with a smooth surface suitable to receive most forms of decoration. The Construction design shall be similar to the design tested as per BS 476 part 22 and IS 3614 Part II, at CBRI, India. The rate also include SS Ball Bearing Hinges of size 100mm x 75mm x 3 mm of Becker Fire Solutions the shutter is provided with appropriate openings for view panel glass, if required. Prototype Test certificate for fire rating of doors from CBRI, Roorkee for earlier tested design shall be attached along with manufacturers test certificate.Intumescent hinge Liner & intumescent lock jackets of Lorient Make should be provided. Provisions/reinforcement for fixing all fixtures shall be built in on the doors prior to the supply. All wood work will be primed with FR-880 primer and putty . BI01010001010000000000000515BI0100001572
462 462 Door size sheet (AS PER THE ENGINEER IN CHARGE ) BI01010001010000000000000515BI0100001573
463 463 Frame Hardwood Red Marrandi with fire reted primer & fire reted paint finish . BI01010001010000000000000515BI0100001574 40 Metre
464 464 Shutter with primer finish BI01010001010000000000000515BI0100001575 32 Sqm
465 465 1mm thick Laminate finish BI01010001010000000000000515BI0100001576 32 Sqm
466 466 OPTIONAL HARDWARE BI01010001010000000000000515BI0100001577
467 467 vision Panel - Supply of 6mm thick Clear, 120 minute Rated Non Wired, Toughened Glass tested in accordance to EN 1363 / EN 1364 and Compliant to BS 476 Part 22. The Glass should be compliant to Class A Category of Impact Resistance to BS 6206:1981 Safety Glazing Material. The Glass should have a Light Transmission ration of approx 87% according to EN 410 standards. Supply should be complete with Matrix Mineral Boards and VIPER Intumescent Putty SP - 711 complete in all respects OF SIZE 300X300MM BI01010001010000000000000515BI0100001578 1.53 Sqm
468 468 HINGES - Providing of SS Ball Bearing Hinges of 100 x 75 x 3mm complete with SS Screws ( 4 Nos per panel ) BI01010001010000000000000515BI0100001579 54 Nos
469 469 DOORCLOSER- Providing fixing of UL Listed fire rated Becker Fire Solutions make BLC Heavy Duty door closers warranty offered by manufacturer BI01010001010000000000000515BI0100001580 18 Nos
470 470 Panic Bar- Providing of U L Listed Becker Fire Solutions fire rated Panic Bar of SBL 990 series single / double leaf panic exit devices offered by manufacturer BI01010001010000000000000515BI0100001581
471 471 Single Leaf Panic Bar Set BI01010001010000000000000515BI0100001582 1 Nos
472 472 Double Leaf Panic Bar Set BI01010001010000000000000515BI0100001583 1 Nos
473 473 PANIC TRIM- Providing of Openable locks / trims for Panic Bars (Becker Fire Solutions) to operate panic bar from outside with necessary screws as required.The lock and handle should be an amalgamanted single motion piece from the same manufacturer as that of Panic Bar BI01010001010000000000000515BI0100001584 1 Nos
474 474 Mortise Dead Lock- Providing of Mortise IR make Schlage EL 2010 with 80mm cilenderwith both side key of warranty offered by manufacturer with One side key & one side no. BI01010001010000000000000515BI0100001585 18 Nos
475 475 Fashner- Providing of fashner M10X150mm Length with hole plug BI01010001010000000000000515BI0100001586 72 Nos
476 476 ELECTRICAL ITEMS BI01010001010000000000000515BI0100001587
477 477 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) BI01010001010000000000000515BI0100001588
478 478 12 way, Double door BI01010001010000000000000515BI0100001589 4 Each
479 479 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. BI01010001010000000000000515BI0100001590
480 480 Single Pole BI01010001010000000000000515BI0100001591 48 Each
481 481 Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. BI01010001010000000000000515BI0100001592
482 482 40 A BI01010001010000000000000515BI0100001593 2 Each
483 483 Supplying and fixing following rating, four pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. BI01010001010000000000000515BI0100001594
484 484 63 A BI01010001010000000000000515BI0100001595 2 Each
485 485 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. BI01010001010000000000000515BI0100001596
486 486 Group C BI01010001010000000000000515BI0100001597 90 Point
487 487 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS, PVC insulated copper conductor single core cable in surface/ recessed conduit with modular switch modular plate suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required. BI01010001010000000000000515BI0100001598
488 488 Group C BI01010001010000000000000515BI0100001599 6 Point
489 489 Wiring for Light/ power plug points with 2 x 4 sq.mm. FRLS, PVC insulated, Cu. Conductor, single core cable in surface/ recessed conduit along with 1 No. 4sq.mm. FRLS PVC insulated copper conductor single core cable for loop earthing as required. BI01010001010000000000000515BI0100001600 335 Metre
490 490 Wiring for circuit/ submain wiring alongwith earth wire with the follwing size of FRLS PVC Insulated copper conductor single core cable in surface/ recess steel conduit as required. BI01010001010000000000000515BI0100001601
491 491 2x 2.5 sqmm+ 1x 2.5 sqmm earth wire BI01010001010000000000000515BI0100001602 50 Metre
492 492 2x 6 sqmm+ 1x 6 sqmm earth wire BI01010001010000000000000515BI0100001603 205 Metre
493 493 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6 A modular type switch, connections painting etc. as reqd, for Light plug point.(For light plugs to be used in non residential buildings.) BI01010001010000000000000515BI0100001604 5 Each
494 494 Supplying and fixing suitable size Gl box with modular plate and cover in Front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connection etc. as required. BI01010001010000000000000515BI0100001605 30 Each
495 495 Supplying and fixing of Stepped type electronic fan regulator on the existing modular plate & switch box including connections but excluding modular plate etc. as reqd. BI01010001010000000000000515BI0100001606 2 Each
496 496 Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. BI01010001010000000000000515BI0100001607 90 Each
497 497 Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc., including supplying and fixing ball and socket arrangement, 2 Nos. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiringthe down rods and connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.as required. BI01010001010000000000000515BI0100001608 5 Each
498 498 Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 em) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. BI01010001010000000000000515BI0100001609 2 Each
499 499 Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry 'enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. BI01010001010000000000000515BI0100001610 13 Set
500 500 Earthing with Cu. earth Plate 600mm x 600mm x 3mm thick including accesssories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe 2.7 mtr lenght etc. with charcoal or coke and salt as required. BI01010001010000000000000515BI0100001611 2 Set
501 501 Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. BI01010001010000000000000515BI0100001612 20 Metre
502 502 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. BI01010001010000000000000515BI0100001613 20 Metre
503 503 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. BI01010001010000000000000515BI0100001614 6 Metre
504 504 Providing and fixing 25mm x 5mm GI Strip on surface or in recess for connections etc. as required. BI01010001010000000000000515BI0100001615 600 Metre
505 505 Providing and fixing 6SWG dia GI Wire on surface or in recess for loop earthing as required. BI01010001010000000000000515BI0100001616 25 Metre
506 506 Supplying and installing following size of perforated Hot Dipped Glvanised Iron cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts etc. as required. BI01010001010000000000000515BI0100001617
507 507 150 mm width X 50 mm depth X 1.6 mm thickness BI01010001010000000000000515BI0100001618 154 Metre
508 508 300 mm width X 50 mm depth X 1.6 mm thickness BI01010001010000000000000515BI0100001619 65 Metre
509 509 Constructing brick masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand), inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard desgin: 0.91 m deep with SFRC cover and frame (heavy duty, HD20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete.(Excavation,foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) :19.9.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 BI01010001010000000000000515BI0100001620 2 Set
510 510 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed I XLPE aluminium conductor cable of 1.1 kV grade as required. BI01010001010000000000000515BI0100001621
511 511 3½ X150 sq. mm (50mm) BI01010001010000000000000515BI0100001622 8 Each
512 512 3½ X 95 sq. mm (45mm) BI01010001010000000000000515BI0100001623 4 Each
513 513 3½ X 25 sq. mm BI01010001010000000000000515BI0100001624 2 Each
514 514 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required. BI01010001010000000000000515BI0100001625
515 515 Upto 35 sq. mm (clamped with 1mm thick saddle) BI01010001010000000000000515BI0100001626 225 Metre
516 516 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) BI01010001010000000000000515BI0100001627 225 Metre
517 517 Supplying and laying PVC pipe (heavy duty-6Kg Pr. class) under the road crossings, including making of joints complete with excavation of suitable size of trenches, refilling & removal of surplus soil. BI01010001010000000000000515BI0100001628
518 518 250 mm BI01010001010000000000000515BI0100001629 50 Metre
519 519 Supply of 1 x 18/20/22 watt surface/wall mounting type LED tube light with fitting and complete with all accessories as per Engineer in Charge ; BI01010001010000000000000515BI0100001630 90 Each
520 520 Supply of New generation recess mounting luminaire with high brightness SMD LEDs as light source, suitable for\nArmstrong/Grid ceiling compatible for Analog / DALI Dimming Dust proof 40/42 watt LED Light Fixture size in mm (LxWxH) 600x600x70. suitable for mounting directly on the ceiling/ recessed and as per the Engineer In charge. BI01010001010000000000000515BI0100001631 5 Each
521 521 supply Installation of Ventil Air Dsp 300 mm Grey Exhaust Fans inculuding Hardware & Electricals - Pepperfry BI01010001010000000000000515BI0100001632 1 Each
522 522 Supply of following sizes of ceiling fan complete with double ball bearing. motor, Aluminum blades, downrod, canopy, capacitor, regulator etc. suitable for operation on 230 volts 50 Hz A.C. supply complete as required. BI01010001010000000000000515BI0100001633
523 523 Size 1200mm. BI01010001010000000000000515BI0100001634 2 Each
524 524 Supply ,Installation,Testing and Commisioning of Split Type AC Unit: Air cooled Hi-Wall Split AC Units complete with indoor & outdoor units, 134 A refrigerant or equivalent, integral refrigerant cupper piping duly insulated with closed cell insulation, vibration isolating pads and wiring between indoor and outdoor unit, complete uPVC drain piping including fitting and inverter based compressur with 3 star reting etc., including other accessories as required and as per specifications. The units shall be suitable for operation on 230 Volts, 50 cycles, 1 phase AC supply. Units shall be complete with first charge of oil & refrigerant. The work shall include Power cabling from Outdoor Units upto the voltage stabilizers, with necessary PVC conduiting & cable trunking etc. as per requirement of electrical specifications. \n2 TR Note : - A.C Drain Pipe is Included in This rate BI01010001010000000000000515BI0100001635 1 Each
525 525 Supplying and fixing of non-skid rubber mat of 1.1 KV dielectric strength 900mm width ISI approved as required including cutting to required lengths. BI01010001010000000000000515BI0100001636 5 Metre
526 526 Supplying of 1.1 KV hand gloves as required. BI01010001010000000000000515BI0100001637 1 Pair
527 527 Supplying of first aid box as approved complete with standard kit as prescribed by Indian Red Cross. BI01010001010000000000000515BI0100001638 1 Each
528 528 Supplying and fixing of shock treatment chart written in English and Local language duly framed in glass as required. BI01010001010000000000000515BI0100001639 1 Each
529 529 Supplying and fixing of shock treatment chart written in English and Hindi duly framed in as required. BI01010001010000000000000515BI0100001640 1 Each
530 530 Supplying, Erection, Installation, Testing & commissioning of ESE type Lightning Protection complete with the Lightning Air TeMeterinal - Configured as a. Insulation material used to electrically isolate the panels shall be comprised of a base polymer which provides high Ozone & UV resistance with a di-electric strength of 24-38 kv/mm & ESE teMeterinal shall with-stand a minimum Switching Impulse Voltage of 500 KV tested as per NFC 17-102 & UNE 21-186 to be installed at the roof of and the centre of the building with the protection. BI01010001010000000000000515BI0100001641 1 Each
531 531 Supplying, Erection, Installation, Testing & commissioning of Test Link Joint Kit in a IP 55 weather proof enclosure of suitable dimension and approved make & design. BI01010001010000000000000515BI0100001642 1 Each
532 532 Supplying, Erection, Installation, Testing & commissioning of FRP Mast with GI Mast \nNote : FRP Mast at Top Minimum 1.25 Mtr with GI Mast 4 Mtr along with G.I. mast (Total 5 Mtr std mast reqd. for mounting the teMeterinal & adaptor to mount the Air TeMeterinal with Coupler/reducer, Multi strand stray wires, Joints, Clamps & Accessories. BI01010001010000000000000515BI0100001643 1 Each
533 533 Supplying, Erection, Installation, Testing & commissioning of Lightning Strike Recorder / counter (6 digits display) of not resistible type in an IP 67 enclosure with the minimum sensitivity of 1500A & \nmaximum capacity of 220KA (8/20 micro second wave foMeter) tested . BI01010001010000000000000515BI0100001644 1 Each
534 534 Supplying, Erection, Installation, Testing & commissioning of Down conductor Recommended : 70 Sqr mm insulated copper Flaxible cable for lightning current dissipation to earth with necessary Fixing Clamp, Connector accessories etc. BI01010001010000000000000515BI0100001645 80 Metre
535 535 Supplying, Erection, Installation, Testing & commissioning (UL Listed) copper bondesd 3 mtr long 17.2 mm dia as per RDSO spec.with terrafill (TF-50) Mouster booster compound 2 Bag. BI01010001010000000000000515BI0100001646 1 Each
536 536 Supplying, Erection, Installation, Testing & commissioning of Polyplastic Earth pit cover BI01010001010000000000000515BI0100001647 2 Each
537 537 Design, Supply, installation, testing & commissioning of Plumbing motor starter pump panel cubical type CRCA sheet steel free standing indoor type motor control centre with Aluminium bus bars, LED type indicating lamps, dust & vermin proof doors, interlock, interconnection with under noted mountings as per specifications. INCOMER:- 1 No. - 125Amps. TPN MCCB ( 35 KA ) 1 Set -(0-125 A) Ammeter with selector switch & CT's. 1 Set -(0-500V) Voltmeter with selector switch & control fuses 1 Set -Phase indication lights ( R, Y, B ) BUS BARS:- 150,Amps. TP&N aluminium bus bars (35 KA) OUT GOINGS:- 2Nos.-63/32A, TP, MCCB (35 KA). 2Nos.63A Dp MCB(10KA) 2Nos.63A TPN MCB (10 KA) 2 Set - (2 Nos Starter for Pump) Fully Automatic DOL/stardelta STARTER up to 5/10 HP complete with Contactors with 2NO + 2NC for remote operations, Start/ Stop Push Buttons, Single Phase Preventor Relay (Current Base), ON/ OFF Indication lamps & Ammeter with CT's of suitable ratings. BI01010001010000000000000515BI0100001648 1 Set
538 538 Providing and fixing Sump pump for pump room of sump pit @12 meter head voltage 240 /415,Including associated valve and non return valve, etc including all electrical cables. BI01010001010000000000000515BI0100001649 1 Set
539 539 Providing and fixing domestic water transfer pumps flooded suction for over head tank centrifugal type CI casing Head 50 Meter DISCHARGE Minimum 2 LPS. voltage 415 etc including all electrical cables. BI01010001010000000000000515BI0100001650 2 Nos
540 540 Supplying of under noted sizes of aluminium / copper conductor XLPE insulated, PVC sheathed armoured and overall PVC sleeved 1.1 KV grade power distribution cables in pipe, wall, racks, cable trays, including, dressing, clamping with M.S Zinc passivated clamps etc as required conforming to relevant IS code and technical specifications. BI01010001010000000000000515BI0100001651
541 541 3½ X 150 sq. mm (Aluminium Armoured) BI01010001010000000000000515BI0100001652 165 Metre
542 542 3.5C x 95 sq.mm (Aluminium) BI01010001010000000000000515BI0100001653 105 Metre
543 543 3.5C x 25 sq.mm (Aluminium) BI01010001010000000000000515BI0100001654 25 Metre
544 544 2,C x1.5 sq.mm (copper) BI01010001010000000000000515BI0100001655 55 Metre
545 545 D.G Control cable,8 core 2.5 sqmm multistandard BI01010001010000000000000515BI0100001656 35 Metre
546 546 Supply and making end termination with brass single compression gland including providing and crimping of copper solder less lugs/ferrules for XLPE/ PVC armoured/ Unarmoured aluminium/ copper conductor cable 1.1 KV grade of following sizes: BI01010001010000000000000515BI0100001657
547 547 2,C x1.5 sq.mm (copper) BI01010001010000000000000515BI0100001658 6 Nos
548 548 D.G Control cable,8 core 2.5 sqmm multistandard BI01010001010000000000000515BI0100001659 6 Nos
549 549 Design, Fabrication, Supply, Erection,Testing and commissioning of Powder coated Main Distribution Panel fabricated out of 14 guage CRCA sheet steel in cubical, compartmentallised, free standing floor /wall mounted, dust and veMeterin proof, with reinforcement of suitable size angle iron, channel, T -iron or flats as required. Cable gland plates shall be provided on top as well as bottom of the panels. Panels shall be treated with all anti-corrosive process before painting as per specification. Panels shall be suitable for 415V, 3-Phase, Four wire, 50 Hz supply complete with earth bus and lifting hooks as required in case of large panels. Approval shall be taken for each panel before fabrication. (All hardware like nuts and bolts used shall be Galvanized and Zinc passivated) Note;- The Panel Inside shall be provision available 2nos NO & 2nos NC point for the incase of fire and building remote cotrolling . MAIN DISTRIBUTION BOARDS INCOMER 1 nos. 320A 415V, TPN 4P MCCB of 35kA with O/C, S/C & E/F release. 1 no. Digital multifunction meter (V+A+Hz) with a set of cast resin CTs 320/5A. 1 Set of phase indicating lamp with MCB. BUS BARS: 400 A TPN bus bars of aluminium alloy. OUT GOING: 1 nos. 320A 415V, TPN MCCB of 35kA. 3 nos. 125A 415V, TPN MCCB of 25kA. 1 nos. 63 A 415V, TPN MCCB of 25kA. 3,nos. 63 A 240V, DP MCB of 25kA. 2 nos.40 A 240V, DP MCB of 25kA. BI01010001010000000000000515BI0100001660 1 Set
550 550 Supply fixing testing and commissioning of Auto Main Failure including auto by-pass panel for the 125 KVA DG set as per specification and requirement. Note;- The Panel Inside shall be provision available 2nos NO & 2nos NC point for the incase of fire and building remote cotrolling . i.)1 No 250 Amp, 4 pole MCCB with electromagnetic release for O/C & E/F and shunt trip. ii). 1 No 320 Amp, 4 pole MCCB with electromagnetic release for O/C & E/F and shunt trip. iii.) Auto/Manual/Test/Off selector switch vi.) 2 Nos over voltage relay, 2 Nos reverse power relay and 2 Nos under voltage relay. v.) 3 Sets of current transfoMeterers 15 P 10 accuracy for protection and 15 VA class-1 for metering. vi.) Energy analyzer unit to indicate current voltage frequency power factor and KWH.vii.) Indicating lamps for load on mains and load on set. viii.) Fuse for instruments. ix.) Battery charger complete with transfoMeterer/rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off. and boost and current adjustment. x. ) Mains supply failure monitor. xi) Supply failure timer. Restoration timer Control unit with three impulse automatic engine start/stop and failure to start lockout. Impulse counter with locking and reset facility. ON/OFF/Control circuit switch with indicator Audio/Video annunciation for High water temperature Low lubricating oil pressures Engine over speed Engine fails to start Full load/maximum load warning BI01010001010000000000000515BI0100001661 1 Set
551 551 Automatic Digital Servo Voltage Stabilizer BI01010001010000000000000515BI0100001662
552 552 Supply Installation Testing and Commissioning of Three Phase, Unbalanced Type Input Voltage & Balanced Type Output Voltage, Oil Cooled Type , 65 KVA Servo Voltage stabilizer. INPUT VOLTAGE: 170V – 270V; 50 c/s A.C. between any Phase & Neutral Correspond to 300V - 470V Phase to Phase. OUTPUT VOLTAGE : 230V +/- 1% ; 60 c/s A.C. between any Phase to Neutral Correspond to 400V +/- 1 % Phase to Phase and as per the specification & drawing. BI01010001010000000000000515BI0100001663 2 Nos
553 553 DG Sets with Auto Mains Failure system BI01010001010000000000000515BI0100001664
554 554 Supplying, installation, erection, testing and commissioning of Air cooled Diesel Engine with rated capacity of 125 KVA at 0.8 P.F., 1500 RPM. 4 stroke , multicylinder coupled to brush less type 415 volts 50 cycle/second self exited alternator completed with cushy pads, domestic silencer, exhaust pipe with in 3 M. height complete with Alternator, auxiliaries, radiator, 24 volts chargeable battery including initial charging of batteries, control panel in sound proof canopy complete as per specification.of the following capacity DG Sets at 0.8 P.F. (lagging), air cooled diesel engine alternator set in acoustical enclosure on common base frame, day oil tank capacity should be as per standard , fuel piping, return fuel cooler, battery & battery charger, Anti Vibration mounting pads, including residential silencer Engine alternator safeties with accessories and Auto Mains Failure complete as per specification as required. BI01010001010000000000000515BI0100001665
555 555 125 KVA BI01010001010000000000000515BI0100001666 1 Set
556 556 Operation and complimentary Maintenance ( for First year). Payable in a single post completion package annually. BI01010001010000000000000515BI0100001667 1 LS
557 557 Comprehensive Operation and Maintenance (for Year 2-5) for annual installment of the quoted amount. BI01010001010000000000000515BI0100001668 1 LS
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail