Provision Of Wall Paneling And Miscellaneous Work At Anupgarh And Provn Of Certain Geysers In Certain Smqs Including Certain Minor And Major Revenue Work At Ge Af Station Suratgarh, GE AF SURATGARH-Rajasthan

Military Engineer Services-MES has published Provision Of Wall Paneling And Miscellaneous Work At Anupgarh And Provn Of Certain Geysers In Certain Smqs Including Certain Minor And Major Revenue Work At Ge Af Station Suratgarh. Submission Date for this Tender is 13-11-2020. Geyser Tenders in GE AF SURATGARH Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

25819244
Provision Of Wall Paneling And Miscellaneous Work At Anupgarh And Provn Of Certain Geysers In Certain Smqs Including Certain Minor And Major Revenue Work At Ge Af Station Suratgarh
Open Tender
Indian
Rajasthan
GE AF SURATGARH
13-11-2020

Tender Details

provision Of Wall Paneling And Miscellaneous Work At Anupgarh And Provn Of Certain Geysers In Certain Smqs Including Certain Minor And Major Revenue Work At Ge Af Station Suratgarh

Key Value

Document Fees
INR 500 /-
EMD
INR 44000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: PROVN OF WALL PANELLING & MISCELLANEOUS WORK AT ANUPGARH & PROVN OF CERTAIN GEYSERS IN CERTAIN SMQs INCLUDING CERTAIN MINOR & MAJOR REVENUE WORK AT GE AF STATION SURATGARH
Sl. No. Item Description Item Code / Make Quantity Units
1 0.01 BOQ (PROVN OF WALL PANELLING & MISCELLANEOUS WORK AT ANUPGARH & PROVN OF CERTAIN GEYSERS IN CERTAIN SMQs INCLUDING CERTAIN MINOR & MAJOR REVENUE WORK AT GE AF STATION SURATGARH)
2 1 Point wiring with 2.5 Sqmm (nominal area) in stove enamelled steel conduit insulated unsheathed multistranded copper conductor cable in and including stove enamelled steel conduit 20 mm dia medium grade ISI marked including fittings and accessories with continues stove enamelled steel conduit insulated copper cable with copper conductor of same size as in phase/neutral/earth cable connecting to common earth dolly including ( enamelled steel conduit / Wooden box of suitable size with laminated sheet cover of 3 mm thick for mounting swiches,socket,regulator) complete. (a) One Light point controlled by one switch. 8 Per Point
3 2 S & F Flame proof rotary type switch with termination box in LM-6 capacity 16 Amp single pole 240 v 50 Hz complete all as specified and directed . Make - Sudhir/ Bajaj / CG 8 Each
4 3 S & F Flame Proof wall mounted fans single phase 240 volts of size 18 inch sweep (metal body) and minimum 1440 RPM including flexible wire 3 core 0.5 Sqmm from wall mounted fan to ceiling rose complete all as specified and as directed. 8 Each
5 4 Material and labour for point wiring (Surface ) in and including rigid non metallic PVC heavy duty conduit, 19/20 mm dia as per site requirement for concealed conduit wiring with 2.5 sqmm FRLS PVC insulated unsheathed multi stranded copper conductor cable with flush type metal boxes modular type suitable for fixing modular switches, sockets, fan regulator etc with white or any colour cover plate with and including PVC insulated unsheathed multi stranded copper conductor cable of 2.5 Sqmm as an earth wire connected to common earth and earth dolly as per IS specification & as specified for one light /fan /buzzer/socket point controlled by one modular switch.\nNote: Metal flush box and other modular accessories except switches, sockets, and fan regulators shall be deemed included in the rate quoted. (a) One switch socket outlet 3 pin 15 amp on same board. Note for Item No. 4 :- The disturbed surfaces of wall for concealing the wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate for point wiring shall be deemed to include the cost of making good.\n 48 Per Point
6 5 S & F socket modular type 16 Amps, 3 pin combine, 2 module,240 volts all complete as specified and as directed. Make : Legrand/Anchor Roma/Crabtree 48 Each
7 6 S & F switch modular type 16 Amps, 1 module,240 volts complete all as specified and as directed. Make : Legrand/Anchor Roma/Crabtree. 48 Each
8 7 M&L for sub-main wiring with two single core 4 sq mm FR PVC insulated unsheathed stranded copper conductor cable drawn through including chasing cutting in any type of massinory including 25 mm dia non-metallic PVC conduit fixed in wall including 2.5 sq mm copper earth continuity wire, accessories and connecting to earth dolly complete, all as specified and as directed by Engr-in-charge. 205 RM
9 8 Supply and fix Earth continuity conductor or main earthing lead of 20 x 3 mm copper strip fixed to wall on insulators or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed . 35 RM
10 9 S & F sheet metal enclosures for DB's for incorporating MCBs, TPN, 4 way,Power coated sheet steel enclouser fitted with bus bar, DIN channel, neutral link and earth link, complete all as specified and directed. 1 Each
11 10 S & F MCB four poles, 63 Amps, breaking capacity 10 KA 'C' curve confirming to IS-8828, 415 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc. Make :- Legrand/L&T/Havells. 6 Each
12 11 S & F sheet metal enclosures for SPN DB's with double glazed door for incorporating MCBs,IP-43 , 8 way with 200 amps rated busbar, 240 volts, as per IS-8623, including taking down old unserviceable single phase DBs, complete all as specified and as directed. Make :- Legrand/L&T/Havells. 7 Each
13 12 S & F MCB SPN.32 amps 'C' series, breaking capacity 10 Ka, 'C' curve 240 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs complete all as specified and as directed. Make :- Legrand/L&T/Havells. 6 Each
14 13 S & F MCB SP, 6 to 32 Amps, C series, breaking capacity 10 KA, 'C' curve 240 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs complete all as specified and as directed. Make :- Legrand/L&T/Havells. 111 Each
15 14 Supply, laying and testing XLPE Insulated armoured ,screened, PVC bedded, heavy duty electric power cables with stranded aluminium conductor ,1100 Volts grade of size 16 sq mm 4 core complete all as specified and as directed. 360 RM
16 15 Excavation in trenches in hard/dense soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of cables and getting out of excavated material complete all as specified and directed. 82.8 CUM
17 16 Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed. 42.6 CUM
18 17 Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed. 40.3 CUM
19 18 Material and labour for sand cushioning below and around cable in trenches with river sand complete all as specified and directed. 25.7 CUM
20 19 Supply and fix window AC 2 Ton 3 star freq 50Hz,230V copper condenser complete all as specified and directed by engr-in-charge. Make:- Voltas /LG/ Blue Star/ Carrier/ / Samsung. 1 Each
21 20 Supply and fix window AC 1 Ton 5 star freq 50Hz,230V copper condenser complete all as specified and directed by engr-in-charge. Make:- Voltas /LG/ Blue Star/ Carrier/ / Samsung. 1 Each
22 21 M&L for commissioning, installation and testing of maintenance free UL approved copper bonded earth rod of 10 feet length, 17.2 mm dia. (as per drg) made of high tensile low carbon steel rod , molecularly bonded with 99.9% electrolytic grade copper on outer surface ( minimum copper bonding thickness - 250 microns) with exothermally jointed copper bus bar of 50 X 6 X 200 mm for connection. The rod and exothermic joint together successfully tested at 25 KA fault current by CPRI with 50 Kg eco friendly earth enhancing compound with each earth rod. The earth pit should be 125 mm dia. the compound should comply to IEC:62561-7 having passed leaching, corrossion, sulphur and resistivity test as per IEC: 62651-7 by NABL accredit Lab with FRP earth pit cover of top size lockable Lid. It includes GI Protection pipe light grade of size 40 mm dia. with GI strip of size 32X6 mm upto test point complete all as specified and directed by Engr-in-charge. Make JMV LPS Ltd/ OBO/ENNOV Infra solutions Pvt. Ltd/ erico /powerbolt \nNote:- Copper Strip connecting between two earthing will be measured and paid seperately in respective item. (a) The test result of each set of earthing is less than 1 Ohm. All earthing test will be carried out in presence of MES Rep, manufacturer Rep and test result will be recorded in a register with sign of manufacturer & Engr-in-charge. (b) 2 Year gurantee certificate from company for maintaining earth result less than 1 Ohm will be submitted by contractor (c) 1425 RTC SS universal clamp of size 175 x 50 x 3mm (d) Earth enhancing compound (PROCEM) ECS GB 25 tested as per IEC 62561-7-25Kg (e) Chemical earthing will be installed by manufacturer Rep and purchase voucher of earthing will be produced before payment. Payment shall be made only after getting satisfactory result. 2 Set of three
23 22 S & F test point terminal block made of gunmetal or phosphorus bronze size 75x75x25mm drilled and screwed incl 3 Nos 8mm dia 25mm long hexa head screw complete all as specified and directed. 2 Each
24 23 Supply and fix copper strip of size 20 x 3 mm on PVC/porcelain insulator at suitable distance with saddeles and fixing screw etc for roof/Wall conductors and down conductors above ground all joints of copper strip should be brazed properly.complete all as specified and directed. 55 Each set
25 24 Supply only ice lined refrigerator of capacity 260 ltrs or above, for maintainng temp 2 ºC to 8 ºC with temp display and transparent glass door.complete all as specified and directed. 1 Each
26 25 Supply and installed voltage stablizer for automatic operation sinle phase air cooled indoor type input variation between 170 V to 280 V with output voltage stablized at 230 V wall mounting of capacity 4/5 KVA as directed by Engineer-in-charge. Make: V Gaurd cat No. VG 500/Carrier/ Blue Star/ Volina. 5 Each
27 26 M & L for point wiring (concealed) complete with FR PVC insulated unsheathed 1100 Volts grade, conforming to IS-694, 1.5 sq mm (nominal area) multi stranded copper conductor cable drawn though in and including non metallic medium grade rigid PVC conduit accessories, ISI marked, 19/20 mm dia including all accessories, concealed in walls/floors/ceilings etc by cutting chases using machine and making good the disturbed surface, with and including sunken type pressed steel/welded MS terminal box 1.2 mm thick bakelite laminated sheet top cover 3 mm thick and 1.5 sq mm copper earth continuity wire connected to earth dolly complete for one 3 pin socket outlet, 5 amps on Independent board. 16 Per Point
28 27 M & L for modular Switch socket Combination 16A, 6 pin, 3 module complete all as specified and directed 1 Each
29 28 Supply only air circulator fans 230 volts single phase oscillating suitable for wall mounting complete all as specified and directed Make: Orient, Model:450 mm or 18” tornado Wall II 15 Each
30 29 Fixing Only air circulator fans 230 volts single phase oscillating 450 mm. Sweep suitable for wall mounting complete all as specified and directed 15 Each
31 30 S & F Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body complete all as specified and directed 15 Each
32 31 S & F Switch piano, flush type single pole, one way 5 Amp complete all as specified and directed 15 Each
33 32 M&L for sub main wiring (surface) with two single core 6 sqmm multi stranded copper conductor, FR, PVC insulated, unsheathed cable, ISI marked, 20 mm dia rigid PVC conduit for submain wiring including 4 sqmm FR PVC insulated and unsheathed stranded copper conductor as earth wire and making good the disturbed surface to match the existing surface complete all as specified and directed by EIC. Note: Two runs of 6 sqmm copper conductor cable one run of 4 sqmm copper conductor and one run of PVC conduit will be measured as one unit. 30 RM
34 33 Supply and install hi wall split air conditioner (1.5 ton) units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality of 1.5 TR capacity minimum 3 Star rating complete all as specified and directed. Make:- Voltas/LG/Whirpool. 1 Each
35 34 S & F single pole and neutral enclosure with two pin and earth plug and socket complete with one single pole MCB 240 V ,20 Amp capacity complete all as specified and directed 71 Each
36 35 M&L for point wiring (surface) in and including rigid non metallic PVC conduit, medium grade, ISI marked,19/20 mm dia, with 4 sqmm FR PVC insulated & unsheathed, stranded copper conductor cable, single core, 1100 volts grade, ISI marked with cast iron pressed steel terminal boxes of suitable depth and 1.6 mm thick for mounting switches, sockets with 3 mm thick Bakelite laminated sheet cover with brass screws, cup washer and including FR PVC insulated & unsheathed stranded copper conductor of 2.5 sqmm ISI marked as continuous earth wire complete for socket outlet 3 pin 15 Amps on independent board all as directed. 68 Per Point
37 36 S & F sheet metal enclosures for DB's for incorporating MCBs, TPN, 4 way, IP-43 double glazed door with 200 amps rated busbar, 415 volts, as per IS-8623, including taking down old unserviceable DBs, all as specified and as directed. Make :- Legrand/L&T/Havells. 4 Each
38 37 S & F MCB four poles, 63 Amps, breaking capacity 10 KA 'C' curve confirming to IS-8828, 415 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc complete all as specified and directed. Make :- Legrand/L&T/Havells. 4 Each
39 38 Supply and fixing 15 mm dia steel water tubing medium grade galvanised with all fittings and fixed complete to wall ,ceiling or laid in floors complete all as specifed and as directed 204 RM
40 39 Supply and fix 15 mm dia bore bib tap,Chromium plated,cast copper alloy with crutch or butter fly handle ,screwed for iron pipe or for brass ferrule complete all as specified and as directed 68 Each
41 40 Cutting Existing Steel tubing for alterations or additions (each cut measured) complete all as specified and directed 68 Each
42 41 Screwing Existing Steel tubing for alterations or additions (of lengthening screw on pipe to form connector) complete all as specified and directed 68 Each
43 42 Cutting holes in brick wall to passes the GI pipe 15/20 mm dia and making good distrubed portion with cement mortar 1:3 or cement concrete 1:2:4 type B-1 as required complete all as specified and directed 68 Each
44 43 S&F Electric Water Heater storage capacity 25 L including all fittings with 04 Nos fabricated anchor bolt T type of 8 mm dia 100 mm to 400 mm long with nut & washer including drilling ,making good the disturbed surfaces with PCC 1:2:4 type B1 using 20 mm graded stone aggregate and cement mortar etc matching with existing surfaces including electric and water connection complete all as specified and directed.. Make : Havells, Model No. Puro Plus, Product Code: GHWAPFTIV025, colour in white/Ivory or Equivalent OR V-Guard Crystal series/Bajaj Caldia 23 Each
45 44 Fixing only water heater of storage capacity 25 Ltr with 04 Nos fabricated anchor bolt T type of 8 mm dia 100 mm to 400 mm long with nut & washer including drilling ,making good the disturbed surfaces with PCC 1:2:4 type B1 using 20 mm graded stone aggregate and cement mortar etc matching with existing surfaces including electric and water connection complete all as specified and directed. NOTE : Geysers will be issued under Sch "B" for free for fixing . 45 Each
46 45 S&F PVC connection 15 mm size with PTMT nuts of length 600 mm as inlet for cold water.complete all as specefied and directed. 68 Each
47 46 Supply and fix PVC connection of 15 mm size,spirally reinforced with stainless steel wire inside the pipe for outlet hot water pipe connection,with brass nuts at both ends of length 600 mm complete all as specified and as directed 68 Each
48 47 S&F stop valves of size 15 mm dia. cast copper alloys screwed down high pressure with crutch or butterfly handle screwed both ends for iron pipes complete all as specified and as directed. 136 Each
49 48 Supply and laying/ fixing 40 mm dia galvanised iron tubing light grade conforming to IS 1239 part - 1979 in trenches, under floor / road crossing or on poles as protection to underground cable fixed with clamps all as specified and as directed. 50 RM
50 49 Supply and fixing burnt brick sub class B old size brick for cable protection laid adjacent to each other perpendicular to the direction of cable in trenches complete all as specified and directed. 2 Per 1000 nos
51 50 M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground ( earth pit not less than 2.25 mtrs deep below nominal ground level) with top edge of the plate not less than 1.5 mtrs below nominal ground level connected to GI wire 4mm dia. by means of bolts, nuts , check nuts and washers of GI all as shown in electrical plate No 5 connected to earthing test point and testing on completion. complete all as specified and as directed. Note:- the cast of excavation and earth work PCC pit and CI cover, funnel & watering pipe, wiremesh,charcoal dust and common salt and earth strip up to 7.5 mtrs long shall be deemed included in the unit rate for earthing all as specified and as directed. 4 Each
52 51 Demolition of un-reinforced cement concrete in any description and in any position ground floor and paving not exceeding 15 cm thick (below or above ground level),and rubbish off the premises , including disturb portion of working area shall be male good including removal of debris from site complete all as specified and directed. 0.2 CUM
53 52 M&L for PCC (1:2:4) type B-1( using 20.0 mm graded stone aggregate) as in roof kerbs ,bed block for hold fast ,coping, benching, etc including weathering ,slightly rounded or chamfered angles and throating , complete all as specified and directed. 0.5 CUM
54 53 S&F 1st class hard wood plain,solid, straight chowkats and frames, wrought ,framed but segmental fixed on wall or or ground with hold fast , including fixing of base brackets , anchorage plates, notch to suit the butt of rifle braacket, all necessary holes and locking arrangements and other requirements for fixing of racks with nuts , bolts, and washer complete all as specified and directed.( Rifle rack design & construction details shall be built and fixed all as directed by Engg-in-charge .). 1.1 CUM
55 54 S&F MS work as in hold fast embeding in concrete and screwing , locking arrangements , including flat iron fillets , and other similar work including all necessary drilling , bolting or rivetting etc conforming to Fe-290 Gde E-165 complete all as specified and directed. 90 Kg
56 55 S&F 5mm thick PVC sheet fillet of width 35mm for wall panelling inclusive of fixing on to wall to make PVC frame as per specification & drawings. 427 RM
57 56 S&F Solid PVC Wall Lining consisting of 5mm thick Plain colour PVC sheet inclusive of solvent cement and fixing at site on PVC frame as per specification & drawings. 131 SQM
58 57 M&L for 2nd class hard wood plain,solid, straight chowkats and frames, wrought ,framed rebated on the solid ,rounded or chamfered ,put together with glue pinned at joints complete all as specified and directed. 0.1 CUM
59 58 Taking down chowkats with shutter (without taking off shutter) from the frame, n exc 1.5 sqm each. 7 Each
60 59 Taking down chowkats with shutter (without taking off shutter) from the frame, exc 1.5 Sqm n exc 4 Sqm each. 2 Each
61 60 S & F of 30 mm thick Flush shutters, solid core construction, with block board core and plywood face panels, commercial type on one sides and one face is covered with decorative face veneer with lipping/frame to match complete all as specified and directed. 5 SQM
62 61 S&F aluminium anodized barrel tower bolts 200mm long, of extruded section complete all as specified and directed. 4 Each
63 62 S&F 250 mm long Aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast-aluminium alloy complete all as specified and directed. 2 Each
64 63 S&F Butt hinges, heavy weight, cold rolled mild steel, complete all as specified and directed. 9 Each
65 64 S&F aluminium ( extruded section body) Door closer hydraulically regulated,designation No. 3,universal type, suitable for door shutters of 851 to 1000 mm in width and of weight between61 to 80 kg complete all as specified and directed. 3 Each
66 65 S&F Extruded aluminium alloy handles, fabricated type,anodised complete all as specified and directed. 4 Each
67 66 S&F Mortice lock of brass,vertical type, size 100 mm 4 levers complete all as specified and directed. 2 Each
68 67 S & F Anodised aluminium door shutters, aluminium section weighing 0.55 kg/ m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws, handles and other fittings complete all as specified and directed. 10 SQM
69 68 S & F Anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed. 18 kg
70 69 S & F Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work con- forming to Fe.290.Gde-E-165 complete all as specified and directed. 1820 kg
71 70 Cutting openings, through brick walls for door, window and other openings or enlarging existing openings. converting window into door openings, etc. or cutting out defective brick work for under-pinning, including providing, fixing and removing shoring, cleaning and stacking bricks, removing surplus serviceable bricks, hard-core, etc.. to store and rubbish not exc. 50m brick wall built in mud mortar. 0.7 CUM
72 71 Forming jambs, etc. to openings (to foregoing item), including cutting, toothing and properly bonding into old work, also facing, jointing and pointing to match existing work in cement mortar 1:4 complete all as specified and directed. 1 SQM
73 72 Making good under cills or over arches, lintels and bressummers. including allpinning when necessary in cement mortar 1:4 complete all as specified and directed. 0.7 SQM
74 73 Cutting holes in brick walls in cement mortar for inserting holdfasts and making good dismantled portion in cement mortar 1:3 or cement concrete 1:2:4 Type B-1 as required exc half brick but n exc one brick complete all as specified and directed. 70 Each
75 74 Cutting out concrete blocks, slabs, brickwork or stone masonry (in alter nate course), forming tooth-ings for and bonding new work in cement mortar (1:4) into old work, including new materials entering old wall with type C1 1:3:6 ( 20 MM graded aggregate) complete all as specified and directed. 0.5 SQM
76 75 M & L for Rendering 10 mm thick on fair faces of brick work or concrete surfaces complete all as specifed and directed. 25 SQM
77 76 M&L for new steel surfaces, over 10cm in width or girth,and apply two coats of synthetic enamel paint over one coat of red oxide complete all as specifed and directed. 51 SQM
78 77 M&L for Preparing surfaces of wood and wood based materials, steel and iron work, new or old, of any description and girth, not otherwise described, and treated with tar or coal tar black paint complete all as specifed and directed. 2 SQM
79 78 M&L for Preparing old wall surface and applying one coat of oil emulsion distemper white or tinted complete as specified and directed. 150 SQM
80 79 M&L for new wood surfaces, over 10cm in width or girth,and apply two coats of synthetic enamel paint over one coat of pink primer complete all as specifed and directed. 21.9 SQM
81 80 M&L for preparing new plasterd surface of wall and applying two coats of oil bound distemper matching with existing surface over and including a coat of chalk whiting primer complete all as specified and directed. 10 SQM
82 81 M&L for preparing new plasterd surface of wall and applying two coats of cement base paint matching with existing surface over and including a coat of chalk whiting primer complete all as specified and directed. 15 SQM
83 82 Contract Amount shall be derived after affecting the amount of Schedule of Credit in General Summary on serial page No 15 of tender documents.