| 1 | 1 | PART-I (M&O WORKS) | | | |
|---|
| 2 | 2 | Manning & Operation of CAT A & B substations (comprising of different equipment) with 11kV incoming supply and 11kV/415 Volts outgoing supply by providing one ITI holder skilled tradesman (with minimum 2years experience to attend 11kV sub-station) including maintaining proper log sheet and other relevant documents of the sub-station, attending complaints of cabling, LT panel, DG sets, VCBs, etc. in technical area in 03 (three) shifts (each shift of 08hours, one operator for each shift) on all days, round the clock, including Sundays and holidays all as specified hereafter and as directed by the Engineer-in-Charge | | | |
|---|
| 3 | 2.01 | ITI holder skilled tradesman (with minimum 2 years experience (minimum wages as notified) | | 1005 | Per shift per person |
|---|
| 4 | 2.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 1005 | Per shift per person |
|---|
| 5 | 2.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 1005 | Per shift per person |
|---|
| 6 | 2.04 | Contribution towards Bonus as per existing rules | | 1005 | Per shift per person |
|---|
| 7 | 2.05 | Contractor's Overheads & Profit on total of serial item Nos 2.01 to 2.04 | | 1005 | Per shift per person |
|---|
| 8 | 2.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 2.01 to 2.05 | | 1005 | Per shift per person |
|---|
| 9 | 3 | Manning & Operation of CAT A & B substations (comprising of different equipment) with 11kV incoming supply and 11kV/415 Volts outgoing supply by providing one male helper for assiting the operator / tradesman, including safely dusting / cleaning of machineries / equipments, cleaning off the premises and outside upto 5m periphery by cutting bushes, grass, etc. in 03 (three) shifts (each shift of 08hours, one helper for each shift) on all days, round the clock, including Sundays and holidays all as specified hereafter and as directed by the Engineer-in-Charge | | | |
|---|
| 10 | 3.01 | Unskilled labour (minimum wages as notified) | | 1005 | Per shift per person |
|---|
| 11 | 3.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 1005 | Per shift per person |
|---|
| 12 | 3.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 1005 | Per shift per person |
|---|
| 13 | 3.04 | Contribution towards Bonus as per existing rules | | 1005 | Per shift per person |
|---|
| 14 | 3.05 | Contractor's Over Head & Profit on total of serial item Nos. 3.01 to 3.04 | | 1005 | Per shift per person |
|---|
| 15 | 3.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 3.01 to 3.05 | | 1005 | Per shift per person |
|---|
| 16 | 4 | Manning & Operation of Hangar 1 & 2 substations (comprising of different equipment ) in substation having 11kV incoming supply and 11kV outgoing supply by providing one ITI holder skilled tradesman (with minimum 2years experience to attend 11kV sub-station) including maintaining proper log sheet and other relevant documents of the sub-station/DG set, attending complaints panel, DG sets, VCBs, etc. in technical area in 02 (two) shifts i.e. 0800hrs to 1600hrs and 1600hrs to 2400hrs (each shift of 08hours, one operator for each shift) on all days, including Sundays and holidays all as specified hereafter and as directed by the Engineer-in-Charge | | | |
|---|
| 17 | 4.01 | ITI holder skilled tradesman (with minimum 2 years experience) (minimum wages as notified) | | 670 | Per shift per person |
|---|
| 18 | 4.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 670 | Per shift per person |
|---|
| 19 | 4.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 670 | Per shift per person |
|---|
| 20 | 4.04 | Contribution towards Bonus as per existing rules | | 670 | Per shift per person |
|---|
| 21 | 4.05 | Contractor's Over Head & Profit on total of serial item Nos. 4.01 to 4.04 | | 670 | Per shift per person |
|---|
| 22 | 4.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 4.01 to 4.05 | | 670 | Per shift per person |
|---|
| 23 | 5 | Manning & Operation of GE office 11kV yard (comprising of different equipment) with 11kV incoming supply and 11kV/415 Volts outgoing supply by providing one ITI holder skilled tradesman (with minimum 2years experience to attend 11kV sub-station) including maintaining proper log sheet and other relevant documents of the sub-station, attending complaints of cabling, LT panel, DG sets, etc. in domestic areas in 03 (three) shifts (each shift of 08hours, one operator for each shift) on all days, round the clock, including Sundays and holidays all as specified hereafter and as directed by the Engineer-in-Charge. | | | |
|---|
| 24 | 5.01 | ITI holder skilled tradesman (with minimum 2 years experience) (minimum wages as notified) | | 1005 | Per shift per person |
|---|
| 25 | 5.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 1005 | Per shift per person |
|---|
| 26 | 5.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 1005 | Per shift per person |
|---|
| 27 | 5.04 | Contribution towards Bonus as per existing rules | | 1005 | Per shift per person |
|---|
| 28 | 5.05 | Contractor's Over Head & Profit on total of serial item Nos. 5.01 to 5.04 | | 1005 | Per shift per person |
|---|
| 29 | 5.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 5.01 to 5.05 | | 1005 | Per shift per person |
|---|
| 30 | 6 | Manning & Operation of GE office 11kV yard (comprising of different equipment) with 11kV incoming supply and 11kV/415 Volts outgoing supply by providing one male helper for assiting the operator / tradesman, including safely dusting / cleaning of machineries / equipments, cleaning off the premises and outside upto 5m periphery by cutting bushes, grass, etc. in 03 (three) shifts (each shift of 08hours, one helper for each shift) on all days, round the clock, including Sundays and holidays all as specified hereafter and as directed by the Engineer-in-Charge | | | |
|---|
| 31 | 6.01 | Unskilled labour (minimum wages as notified) | | 1005 | Per shift per person |
|---|
| 32 | 6.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 1005 | Per shift per person |
|---|
| 33 | 6.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 1005 | Per shift per person |
|---|
| 34 | 6.04 | Contribution towards Bonus as per existing rules | | 1005 | Per shift per person |
|---|
| 35 | 6.05 | Contractor's Over Head & Profit on total of serial item Nos. 6.01 to 6.04 | | 1005 | Per shift per person |
|---|
| 36 | 6.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 6.01 to 6.05 | | 1005 | Per shift per person |
|---|
| 37 | 7 | Manning & Operation of electrically operated passenger lift of capacity 8 passengers of make-Kone Elevators at New ATC building (G+4) by providing one skilled lift operator having proper training certificate in 03 (three) shifts (each shift of 08hours, one operator for each shift) on all days, round the clock, including Sundays and holidays including assisting in rescue operations in event of any faliure of lift in emergency, maintaining log sheet, relevent records, registers, cleaning and keeping tidy the lift and lift room all as specified hereafter and as directed by the Engineer-in-Charge\nNotes: \n(i) Contractor has to submit safety certificate from the OEM\n(ii) Contractor has to submit insurance of lift covering passenger and operator safety within 30 days of commencement of work | | | |
|---|
| 38 | 7.01 | One skilled lift operator having proper training certificate (minimum wages as notified) | | 1005 | Per shift per person |
|---|
| 39 | 7.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 1005 | Per shift per person |
|---|
| 40 | 7.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 1005 | Per shift per person |
|---|
| 41 | 7.04 | Contribution towards Bonus as per existing rules | | 1005 | Per shift per person |
|---|
| 42 | 7.05 | Contractor's Over Head & Profit on total of serial item Nos. 7.01 to 7.04 | | 1005 | Per shift per person |
|---|
| 43 | 7.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 7.01 to 7.05 | | 1005 | Per shift per person |
|---|
| 44 | 8 | Maintaining runway / taxi track lighting / cabling by providing labourers for assistance (number of labourers shall depend upon requirement of Users) including all necessary T&P required in re-routing / repairs / provisioning of XLPE cable by excavating, returning and filling, removing of spoil, cutting vegetative growths, making good the disturbed surfaces, etc. as required all as specified hereafter and as directed by the Engineer-in-Charge | | | |
|---|
| 45 | 8.01 | Unskilled labour (minimum wages as notified) | | 338 | Man Day |
|---|
| 46 | 8.02 | Contribution towards Employees Provident Fund (EPF) as per existing rules | | 338 | Man Day |
|---|
| 47 | 8.03 | Contribution towards Employees State Insurance Corporation (ESIC) as per existing rules | | 338 | Man Day |
|---|
| 48 | 8.04 | Contribution towards Bonus as per existing rules | | 338 | Man Day |
|---|
| 49 | 8.05 | Contractor's Over Head & Profit on total of serial item Nos. 8.01 to 8.04 | | 338 | Man Day |
|---|
| 50 | 8.06 | Labour Welfare Cess (LWC) as per existing rules on total of serial item Nos. 8.01 to 8.05 | | 338 | Man Day |
|---|
| 51 | 9 | Notes for serial item Nos. 1.00 to 8.06: \n(i) The timings for each shift shall be as decided by the Engineer-in-charge. No claim whatsoever on this aspect is admissible\n(ii) Bidder shall quote corresponding minimum wages, rates and contributions as per prevailing Govt. notifications as applicable. Any quoted rate against items / sub-items which corrosponds to / works out to lower than the corrosponding minimum rates of wages / subscription towards EPF, ESIC, bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate / wage / contribution shall be applicable on the bid submission end date | | | |
|---|
| 52 | 10 | (iii) Minimum fair wages as notified time to time by the Government of India / State Government / Local bodies / Labour Regulations whichever is higher including all statutory provisions such as EPF, ESI, Bonus, taxes, etc. as applicable shall be paid to the workers by the Contractor\n(iv) Increased wages including all other benefits in compliance of statutory provisions shall be paid to the workers by the Contractor. No other claim whatsoever shall be admissible on this account and the bidders shall note this aspect and quote their rates accordingly. It must be noted that in compliance of all statutory provisions, the increase shall be passed over to the workers\n(v) Conveyance/vehicle for moving around of the staff employed and or any T&P required and detailed specifics as per particular specifications shall be provided by the Contractor. | | | |
|---|
| 53 | 11 | PART-II (REPAIR & OTHER WORKS) | | | |
|---|
| 54 | 12 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundations, manholes, etc. or for laying pipes, etc. not exceeding 10sqm on plan and getting out in soft / loose soil complete all as specified and as directed | | 38 | Cum |
|---|
| 55 | 13 | Returning, filling in, including, spreading, leveling, watering and well ramming in layers not exceeding 25cm deep as in any type of soil complete all as specified and as directed | | 15 | Cum |
|---|
| 56 | 14 | Removing excavated materials (any type of soil) to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point including spreading in low lying area and leveling all as specified | | 23 | Cum |
|---|
| 57 | 15 | M&L for fine dry river sand cushioning by laying 8cm thick layer below the cable for making soft bed and 15cm above the cable and then punning down to its consolidated thickness of 18cm after the cable is laid all as specified in SSR Part-I complete all as specified and as directed\nNote: Only punned thickness of sand shall be considered for measurement purposes | | 7.5 | Cum |
|---|
| 58 | 16 | Supplying and laying unreinforced precast concrete cable covers, class HV, type I, flat, size 300x180x 40mm (length parallel to axis of cover), ISI marked, duly embossed with wordings 'HT CABLE' complete all as specified and as directed | | 390 | Each |
|---|
| 59 | 17 | Supplying, fixing / laying steel tubing, 80mm bore, light grade, galvanised with screwed and socketed joints, in any length, including supply and fixing all fittings, ISI marked conforming to IS -1239 and fixed to walls or laid in floors / trenches required for protection of electric clables duly fixed with FI 40x3mm clamps @1.5m c/c of suitable size / shape including all necessary nuts, bolts, washers, etc. complete all as specified and as directed | | 10 | Rm |
|---|
| 60 | 18 | M&L for rewinding of stabilisers with suitable size of copper winding wire including all insulation material, tightening of connections, crimping, soldering, etc. as required and taking out and disposing off burnt windings complete all as specified and as directed | | 22 | Kg |
|---|
| 61 | 19 | M&L for dehydrating and filtration of voltage stabiliser (of any type) oil by using proper filtration, heating, etc. machinery till di-electric strength reaches 40 to 60kV in one minute complete all as specified and as directed\nNotes: \n(i) Dehydration and filtration process shall have to be carried out in presence of rep of the AO\n(ii) Dehydration and filtration reports shall be submitted to claim any payment | | 2500 | Litres |
|---|
| 62 | 20 | M&L for draining out and filling in topping up transformer oil conforming to IS: 339-1989 having breaking down capacity more than 50kV complete all as specified and as directed | | 700 | Litres |
|---|
| 63 | 21 | M&L disconnecting 3 phase servo voltage stabilisers from main supply and carrying out maintenance and servicing including replacement of all defective / worn out parts / spares and testing on completion for proper functioning complete all as specified and as directed for the following capacities:\nNote: \n(i) Maintenance / servicing shall be got done through authorised service centres / rep of manufacturer as approved by the Engineer-in-charge\n(ii) Servicing certificate including guarantee thereof shall be submitted to claim payment\n(iii) Replacing defective spares shall be measured and paid separately under respective items herein after\n(iv) Quoted rate shall include carting out / in, loading / unloading, fixing in position of any item requiring repairs at workshop | | | |
|---|
| 64 | 22 | 20 to 50kVA | | 2 | Each Job |
|---|
| 65 | 23 | 60 to 100kVA | | 2 | Each Job |
|---|
| 66 | 24 | 125 to 250kVA | | 2 | Each Job |
|---|
| 67 | 25 | 250 to 500kVA | | 1 | Each Job |
|---|
| 68 | 26 | S&F in repairs DPDT switch of existing makes complete all as specified and as directed | | 15 | Each |
|---|
| 69 | 27 | S&F in repairs micro switch of existing makes complete all as specified and as directed | | 15 | Each |
|---|
| 70 | 28 | S&F in repairs panel lamp of existing makes / types complete all as specified and as directed | | 30 | Each |
|---|
| 71 | 29 | S&F in repairs potentiometer of existing makes complete all as specified and as directed | | 5 | Each |
|---|
| 72 | 30 | S&F in repairs suitable voltmeter of rating 0 to 500V complete all as specified and as directed | | 5 | Each |
|---|
| 73 | 31 | S&F in repairs ampere meter with CT of rating 0 to 200A complete all as specified and as directed | | 5 | Each |
|---|
| 74 | 32 | S&F in repairs electronic circuit card (PCB) of existing make and type complete all as specified and as directed | | 18 | Each |
|---|
| 75 | 33 | S&F in repairs PCB holder of existing make and type complete all as specified and as directed | | 15 | Each |
|---|
| 76 | 34 | S&F in repairs trigger transformer of existing make and type complete all as specified and as directed | | 10 | Each |
|---|
| 77 | 35 | S&F in repairs rotary selector switch 5A (RYB) of existing make and type complete all as specified and as directed | | 15 | Each |
|---|
| 78 | 36 | S&F in repairs RC network for 3KG motor, of existing make and type complete all as specified and as directed | | 10 | Each |
|---|
| 79 | 37 | S&F in repairs RC network for 10KG motor, of existing make and type complete all as specified and as directed | | 10 | Each |
|---|
| 80 | 38 | S&F in repairs carbon bush (set of three) of existing make and type complete all as specified and as directed | | 20 | Each Set |
|---|
| 81 | 39 | S&F electronic siren / hooter, horizontal type, single phase, single stage, continuous normal operationfor minimum 50mins with sound level 65 to 120dB measured at 1.5m above ground with sound output variation of +5dB at 500m dia range complete all as specified and as directed | | 1 | Each |
|---|
| 82 | 40 | S&F in repairs aluminium thimbles suitable for 16 to 50sqmm cable complete all as specified and directed | | 100 | Each |
|---|
| 83 | 41 | S&F in repairs aluminium thimbles suitable for 70 to 120sqmm complete all as specified and directed | | 100 | Each |
|---|
| 84 | 42 | S&F in repairs aluminium thimbles suitable for 150 to 240sqmm complete all as specified and directed | | 50 | Each |
|---|
| 85 | 43 | S&F in repairs aluminium thimbles suitable for 300 to 400sqmm complete all as specified and directed | | 50 | Each |
|---|
| 86 | 44 | M&L for shutting down of power supply and preparation of surfaces viz. scrapping old paints, smoothening, etc. of voltage stabilisers and painting with one coat of synthetic enamel paint of approved tint complete all as specified all as directed of the following capacities: | | | |
|---|
| 87 | 45 | 20 to 50kVA | | 10 | Each Job |
|---|
| 88 | 46 | 60 to 100kVA | | 5 | Each Job |
|---|
| 89 | 47 | 125 to 250kVA | | 4 | Each Job |
|---|
| 90 | 48 | 250 to 500kVA | | 2 | Each Job |
|---|
| 91 | 49 | S&F in repairs MCCB 4P 100A 415V 50Hz 16kA with adjustable thermal release fixed magnetic protection type complete all as specified and as directed | | 4 | Each |
|---|
| 92 | 50 | S&F in repairs MCCB 4P 200A 415V 50Hz 25kA with adjustable thermal release fixed magnetic protection type complete all as specified and as directed | | 4 | Each |
|---|
| 93 | 51 | S&F in repairs MCCB 4P 250A 415V 50Hz 25kA with adjustable thermal release fixed magnetic protection type complete all as specified and as directed | | 5 | Each |
|---|
| 94 | 52 | S&F in repairs MCCB 4P 315A 415V 50Hz 35kA with adjustable thermal release fixed magnetic protection type complete all as specified and as directed | | 3 | Each |
|---|
| 95 | 53 | S&F in repairs MCCB 4P 400A 415V 50Hz 35kA with adjustable thermal release fixed magnetic protection type complete all as specified and as directed | | 3 | Each |
|---|
| 96 | 54 | S&F in repairs MCCB 4P 630A 415V 50Hz 50kA with adjustable thermal release fixed magnetic protection type complete all as specified and as directed | | 2 | Each |
|---|
| 97 | 55 | Supplying, laying, jointing, testing & commissioning HT 11 KV (E) XLPE insulated cable, sound compacted aluminium conductor, screened with extruded semi conducting layer, insulation screening with copper tape cover laid up with PVC (ST-2) extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7096 part-II with amendment, laid in pipes/ducts/along poles/wall/equipment, etc. including taking down old unserviceable cable / OH conductor complete all as specified and as directed of the following sections: | | | |
|---|
| 98 | 56 | 3 core 95 sqmm | | 100 | Rm |
|---|
| 99 | 57 | 3 core 120 sqmm | | 100 | Rm |
|---|
| 100 | 58 | S&F bus bar chamber of size 600x600x450mm suitable of 3 phase 433V outdoor type fabricated out of 3.15mm thick MS sheet with 400A rated aluminium busbar 4Nos., PVC sleeves (coloured red, yellow, blue and black) with suitable locking arrangments and four legged angle iron stand made of angle iron of size 40x40x6mm duly grouted in and including foundation in PCC 1:2:4 type C1 using 20mm graded stone aggregates alongwith all necesary cable connections, lugs and cable glands including applying two coats of synthetic enamel paint (of approved tint) over a coat of red oxide zinc chrom primer including taking down and disposing old bus bar chamber / enclosure complete all as specified and as directed | | 2 | Each |
|---|
| 101 | 59 | S&F bus bar chamber of size 600x600x450mm suitable of 3 phase 433V outdoor type fabricated out of 3.15mm thick MS sheet with 200A rated aluminium busbar 4Nos., PVC sleeves (coloured red, yellow, blue and black) with suitable locking arrangments and four legged angle iron stand made of angle iron of size 40x40x6mm duly grouted in and including foundation in PCC 1:2:4 type C1 using 20mm graded stone aggregates alongwith all necesary cable connections, lugs and cable glands including applying two coats of synthetic enamel paint (of approved tint) over a coat of red oxide zinc chrom primer including taking down and disposing old bus bar chamber / enclosure complete all as specified and as directed | | 4 | Each |
|---|
| 102 | 60 | M&L for cable jointing kit for 1.1kV earthed grade cable for end termination indoor heat shrink type joint with jointing material and accessories suitable for 3.5 core, 50 to 150mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed | | 15 | Each |
|---|
| 103 | 61 | M&L for cable jointing kit for 1.1kV earthed grade cable for end termination oudoor heat shrink type joint with jointing material and accessories suitable for 3.5 core, 185 to 300mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed | | 10 | Each |
|---|
| 104 | 62 | M&L for cable jointing kit for 1.1kV earthed grade cable for indoor / outdoor straight through heat shrink type joint with jointing material and accessories suitable for 3.5 core, 185 to 300mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed | | 4 | Each |
|---|
| 105 | 63 | M&L for cable jointing kit for 1.1kV earthed grade cable for indoor / outdoor straight through heat shrink type joint with jointing material and accessories suitable for 3.5 core, 50 to 150mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed | | 4 | Each |
|---|
| 106 | 64 | M&L for cable jointing kit for 11kV earthed grade cable for indoor / outdoor straight through heat shrink type joint with jointing material and accessories suitable for 3 core, 95 to 120mm², XLPE insulated armoured aluminium conductor cable complete all as specified and as directed | | 6 | Each |
|---|
| 107 | 65 | M&L for cable jointing kit for 11kV earthed grade cable for indoor / outdoor straight through heat shrink type joint with jointing material and accessories suitable for 3 core, 185 to 300mm², XLPE insulated armoured aluminium conductor cable complete all as specified and as directed | | 4 | Each |
|---|
| 108 | 66 | M&L for cable jointing kit for 11kV earthed grade cable for indoor end termination heat shrink type joint with jointing material and accessories suitable for 3 core, 95 to 120mm², XLPE insulated armoured aluminium conductor cable complete all as specified and as directed | | 4 | Each |
|---|
| 109 | 67 | M&L for cable jointing kit for 11kV earthed grade cable for outdoor end termination heat shrink type joint with jointing material and accessories suitable for 3 core, 95 to 120mm², XLPE insulated armoured aluminium conductor cable complete all as specified and as directed | | 4 | Each |
|---|
| 110 | 68 | M&L for cable jointing kit for 11kV earthed grade cable for outdoor end termination heat shrink type joint with jointing material and accessories suitable for 3 core, 185 to 300mm², XLPE insulated armoured aluminium conductor cable complete all as specified and as directed | | 4 | Each |
|---|