Repair/ Maint , Manning And Operation To External Electrification At Mh Under Ge ( East ) Jalandhar Cantt
Tender Value
Ref. Documents
Estimated cost
Bid Submission
07 Nov 2020
0 days left
EMD
83200
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jalandhar Cantt → Punjab
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Repair/ Maint , Manning And Operation To External Electrification At Mh Under Ge ( East ) Jalandhar Cantt
BOQ
| Name of Work: REPAIR/ MAINT, MANNING AND OPERATION TO EXTERNAL ELECTRIFICATION AT MH UNDER GE (EAST) JALANDHAR CANTT (TENDER ID NO 2020_MES_372996_1) | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Manning and operation for electrical installation (MH Power House) inclusive of 11 KV RMU-01 Nos, 11 KV VCBs 11 Nos, step down transformer 11 KV/ 0.433 KV 12 Nos, CSS 11 KV with RMU, VCB and transformer 03 Nos, LT electrical distribution panels and cabling network of complete Military Hospital JRC by deploying one electrician having minimum 05 years experience in electrical filed and ITI in electrical technology in one shift of 08 Hrs all as specified and directed.\nNotes : (a) Contractor will deploy ITI holder electrician 01 No each for 03 shifts per day with arrangement of reliever for their weekly rest permanent minimum for 11 months from the date of work order.\n(b) Electrical safety equipment like glovers, helmet, electrical tool kit, etc will be given to electricians on duty by the contractor and rate for these items will be deemed to be included in the quoted rates of this item\n(c) Rate deemed to be included for Basic Rate of Lift Operator, employer’s contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards bonus, overhead & profit & Labour Welfare Cess (LWC) as applicable further quoted rats shall also be inclusive or all taxes, cess, levies as applicable including GST.\n(d) The prevailing rate/ wage contribution shall be as applicable on the bid submission end date. | 1005 | Per Shieft | |
| 2 | 1.01 | (e) The quoted rats against contribution towards Bonus, towards EPF, contribution to ESIC are to be considered for payment only after submission of valid & authentic documents in support of having paid the requisite amount to the workmen i.e. proof of payment.\n(f) GST Liability : Such tender may fall under the category of works contract or services contract depending on nature of items included in the BOQ. In case tender contains both types of items viz items of outsourcing of services and also items for ordinary repairs and/ or comprehensive maintenance to be paid as ‘Material & Labour’ under separate parts of BOQ, GST may be at the higher of applicable rates corresponding to different types of items. However GST rate at which the contractor closes his GST liability afterwards on closure of his account will not be known to the department. Therefore, it is considered prudent to specify that the GST is included in the rates quoted against items of outsourcing as well as items of repairs/ comprehensive maintenance to be paid separately under material and labour parts. . Any variation in tax (including variation in GST rate) shall be adjusted and reimbursed to/ recovered from the contractor as mentioned here-in-after. | |||
| 3 | 1.02 | (g) At the time of bid evaluation, Accepting Officer shall ascertain the corresponding minimum wages, rates and contribution as mentioned above as per prevailing notifications and decide the reasonability of finance bid of all the bidders. Tender shall contain stipulation that any quoted rate against the items/ sub items mentioned above corresponds to/ work out to lower than the corresponding prevailing minimum rates of wages/ subscription/ contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/ wage/ contribution shall be as applicable on the bid submission end date.\n(h) In case the lowest bid is decided for acceptance after rejecting bid(s) declared non-bonafide in this manner, prior approval of PCDA/ CDA shall be obtained. In case only one eligible bid is found valid after rejection of non-bonafide bids, Accepting Officer will assess the bid for its reasonability. In case such single resultant valid bid is considered for acceptance, the same can be accepted only after obtaining prior approval of next higher Engineer Authority. | |||
| 4 | 1.03 | (j) The quoted rate against bonus is to be considered for payment on actual basis, Specific Note shall be included in the Notes to Schedule ‘A’ as well as Notes under respective item/ sub-item of BOQ for ‘Contribution towards Bonus’ that the amount is payable only after submission of valid and authentic documents in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment. Similarly items/ sub-items of ‘Contribution towards EPF’ and ‘Contribution towards ESIC’ shall also be payable after submission of valid & authentic document in support of proof of payment.\n(k) The contractor shall make payment to the workmen employed through online only. No cash payment will be made. No payment to the contractors/firms will be made unless proof of payment of wages through Aadhaar linked bank account is submitted by the contractors/firms. Proof of statutory deductions in favour of workers/labour shall be submitted by the contractor to the GE. The contractor will be required to submit copy of valid labour licence from the Labour Commissioner within 15 days of commencement of the work. If the contractor fails to submit the same within this stipulated period, the contract shall be liable to be cancelled and the Performance security of the firm shall be forfeited accordingly. | |||
| 5 | 2 | Manning and operation for electrical installation (MH Power House) inclusive of 11 KV RMU-01 Nos, 11 KV VCBs 11 Nos, step down transformer 11 KV/ 0.433 KV 12 Nos, CSS 11 KV with RMU, VCB and transformer 03 Nos, LT electrical distribution panels and cabling network of complete Military Hospital JRC by deploying electrician having matric certificate and 03 years experience in electrical filed in one shift of 08 Hrs as helper of electrician all as specified and directed.\nNotes : (a) Contractor will deploy electrician helper 01 No each for 03 shifts per day with arrangement of reliever for their weekly rest permanent minimum for 11 months from the date of work order.\n(b) Electrical safety equipment like glovers, helmet, electrical tool kit, etc will be given to electricians on duty by the contractor and rate for these items will be deemed to be included in the quoted rates of this item\n(c) Rate deemed to be included for Basic Rate of Lift Operator, employer’s contribution towards Employees Provident Fund (EPF) liability, contribution towards Employees State Insurance Corporation (ESIC), contribution towards bonus, overhead & profit & Labour Welfare Cess (LWC) as applicable further quoted rats shall also be inclusive or all taxes, cess, levies as applicable including GST.\n(d) The prevailing rate/ wage contribution shall be as applicable on the bid submission end date. | 1005 | Per Shieft | |
| 6 | 2.01 | (e) The quoted rats against contribution towards Bonus, towards EPF, contribution to ESIC are to be considered for payment only after submission of valid & authentic documents in support of having paid the requisite amount to the workmen i.e. proof of payment.\n(f) GST Liability : Such tender may fall under the category of works contract or services contract depending on nature of items included in the BOQ. In case tender contains both types of items viz items of outsourcing of services and also items for ordinary repairs and/ or comprehensive maintenance to be paid as ‘Material & Labour’ under separate parts of BOQ, GST may be at the higher of applicable rates corresponding to different types of items. However GST rate at which the contractor closes his GST liability afterwards on closure of his account will not be known to the department. Therefore, it is considered prudent to specify that the GST is included in the rates quoted against items of outsourcing as well as items of repairs/ comprehensive maintenance to be paid separately under material and labour parts. . Any variation in tax (including variation in GST rate) shall be adjusted and reimbursed to/ recovered from the contractor as mentioned here-in-after. | |||
| 7 | 2.02 | (g) At the time of bid evaluation, Accepting Officer shall ascertain the corresponding minimum wages, rates and contribution as mentioned above as per prevailing notifications and decide the reasonability of finance bid of all the bidders. Tender shall contain stipulation that any quoted rate against the items/ sub items mentioned above corresponds to/ work out to lower than the corresponding prevailing minimum rates of wages/ subscription/ contribution towards EPF, ESIC, Bonus and LWC shall be treated as non-bonafide and such bid shall not be considered for acceptance. The prevailing rate/ wage/ contribution shall be as applicable on the bid submission end date.\n(h) In case the lowest bid is decided for acceptance after rejecting bid(s) declared non-bonafide in this manner, prior approval of PCDA/ CDA shall be obtained. In case only one eligible bid is found valid after rejection of non-bonafide bids, Accepting Officer will assess the bid for its reasonability. In case such single resultant valid bid is considered for acceptance, the same can be accepted only after obtaining prior approval of next higher Engineer Authority. | |||
| 8 | 2.03 | (j) The quoted rate against bonus is to be considered for payment on actual basis, Specific Note shall be included in the Notes to Schedule ‘A’ as well as Notes under respective item/ sub-item of BOQ for ‘Contribution towards Bonus’ that the amount is payable only after submission of valid and authentic documents in support of having paid the requisite amount of bonus to the workmen, i.e. proof of payment. Similarly items/ sub-items of ‘Contribution towards EPF’ and ‘Contribution towards ESIC’ shall also be payable after submission of valid & authentic document in support of proof of payment.\n(k) The contractor shall make payment to the workmen employed through online only. No cash payment will be made. No payment to the contractors/firms will be made unless proof of payment of wages through Aadhaar linked bank account is submitted by the contractors/firms. Proof of statutory deductions in favour of workers/labour shall be submitted by the contractor to the GE. The contractor will be required to submit copy of valid labour licence from the Labour Commissioner within 15 days of commencement of the work. If the contractor fails to submit the same within this stipulated period, the contract shall be liable to be cancelled and the Performance security of the firm shall be forfeited accordingly. | |||
| 9 | 3 | Supply, installing, testing and commissioning in replacement LT panel, outdoor cubicle type weather and vermin proof totally enclosed made out of 3mm thick CRCA sheet machine pressed of suitable size, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz double door with front and rear openable with locking arrangement including inner independent enclosures for all switches/ MCCBs/ metering equipments with hinged shutters, bottom gland plate with sufficient numbers of circular cable entry holes with cable glands of suitable size of cable & cable glands as per number of outgoings, prewired complete duly powder coated with 7 tank process with base frame made of angle iron 50 x 50 x 6mm, legs 50cm long grouted in PCC (1:3:6) type C-1 including brick masonry platform duly plastered with cement mortar (1:4) 45cm above ground level and 30cm below ground level comprising with following complete :-\n(a) Bus bar strip, four pole and capacity 630 Amps, size be based on 1.5 Amps per Sqmm, copper, coloured with plastic coated insulated and sleeves in four colours (Red, Yellow, Blue and Black) fixed on porcelain insulators with necessary nuts and bolts and washers etc. | 1 | Each Job | |
| 10 | 3.01 | INCOMING : \n(i) MCCB 400 Amp, 415 V, 36 KA, 4 pole adjustable type with spreader links and phase barriers - 01 No.\n(ii) Indicator with LED lamps for RYB, 3 phase with MCBs set of three - 01 set. \n(iii) Digital ammeter (0-630 Amps. - 01 No\n(iv) Digital voltmeter (0-500) volts. - 01 No\nOUTGOING \n(i) MCCB 100 Amps, 415 V, 16 KA, 4 pole with adjustable type with spreader links and phase barriers - 03 Nos. \n(ii) MCCB 63 Amps, 415V, 16 KA, 4 pole with adjustable type with spreader links and phase barriers - 05 Nos.\n(iii) MCB TPN 40 Amp, 415 V, 10 KA-03 Nos | |||
| 11 | 4 | All as per item No. 3.00 here-in-before but LT feeder panel, outdoor cubical type, 3.0mm thick CRCA sheet with comprising following :-\n(a) Bus bar strip, four pole and capacity 250 Amps, size be based on 1.5 Amps per Sqmm, copper, coloured with plastic coated insulated and sleeves in four colours (Red, Yellow, Blue and Black) fixed on porcelain insulators with necessary nuts and bolts and washers etc.\nINCOMING \n(i) MCCB 160 Amp, 415 V, 16 KA, 4 pole adjustable type with spreader links and phase barriers - 01 No.\n(ii) Indicator with LED lamps for RYB, 3 phase with MCBs set of three - 01 set. \n(iii) Digital ammeter (0-250) Amps.-01 No \n(v) Digital voltmeter (0-500) volts.-01 No\nOUTGOING \n(i) MCCB 100 Amps, 415 V, 16 KA, 4 pole with adjustable type with spreader links and phase barriers - 02 Nos. \n(ii) MCCB 63 Amps, 415V, 16 KA, 4 pole with adjustable type with spreader links and phase barriers - 03 Nos.\n(iii) MCB TPN 40 Amp, 415V, 10 KA-03 Nos\n | 1 | Each Job | |
| 12 | 5 | Dismantling of cross arms of MS channel or angle section etc all as specified and directed. | 2 | Qtl | |
| 13 | 6 | Dismantling insulators any type and size all as specified and directed. | 80 | Each | |
| 14 | 7 | Dismantling stay assembly complete by demolition of concrete, etc and necessary excavation all as specified and directed. | 8 | Per set | |
| 15 | 8 | Dismantling ACSR or AAC conductors all as specified and directed. | 1.8 | Qtl | |
| 16 | 9 | M&L earthing in replacement complete for Transformers/ LT panels with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of the plate at a depth not less than 1.65 metre below normal ground level, connected with and including GI strip 32mm x 6mm in and including GI pipe 50mm bore medium grade as protection pipe (from top of earth plate up to the test point) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300x300x300mm(top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate of 25mm thick with 2 Nos MS handles of 12mm dia including necessary excavation/ earth work in any type of soil/rock and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified. (Cost of protection pipe upto 7.5 mtr from earth electrode will be included in the unit rate quoted by the contractor). | 15 | Each | |
| 17 | 10 | S&F in replacement in existing LT panel MCCB 4 pole, adjustable type, 630 Amps of breaking capacity 50 KA complete all as specified and directed | 1 | Each | |
| 18 | 11 | S&F in replacement in existing LT panel MCCB 3 pole, adjustable type, 100 Amps of breaking capacity 16 KA complete all as specified and directed | 2 | Each | |
| 19 | 12 | S&F in replacement in existing TPN DB MCCB 4 pole, adjustable type, 63 Amps of breaking capacity 16 KA complete all as specified and directed | 1 | Each | |
| 20 | 13 | S&F in replacement in existing LT panel MCCB 4 pole, adjustable type, 250 Amps of breaking capacity 25 KA complete all as specified and directed | 4 | Each | |
| 21 | 14 | S&F in replacement in existing LT panel MCCB 4 pole, adjustable type, 315 Amps of breaking capacity 25 KA complete all as specified and directed | 1 | Each | |
| 22 | 15 | S&F in replacement in existing LT panel MCCB 4 pole, adjustable type, 400 Amps of breaking capacity 36 KA complete all as specified and directed | 3 | Each | |
| 23 | 16 | Laying only in trenches/ clamped with wall/ on floor/ in ducts for replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables, 1100 volts grade with stranded aluminium conductor of size 6 sqmm to 35 Sqmm 2 core/ 3.5 core complete all as specified and directed | 750 | RM | |
| 24 | 17 | Laying only in trenches/ clamped with wall/ on floor/ in ducts for replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables, 1100 volts grade with stranded aluminium conductor of size 50 sqmm to 120 Sqmm 3.5 core complete all as specified and directed | 600 | RM | |
| 25 | 18 | Laying only in trenches/ clamped with wall/ on floor/ in ducts for replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables, 1100 volts grade with stranded aluminium conductor of size 150 sqmm to 300 Sqmm 3.5 core complete all as specified and directed | 250 | RM | |
| 26 | 19 | Supplying, laying, jointing and testing and commissioning of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sqmm 2 core complete all as specified and directed. | 450 | RM | |
| 27 | 20 | All as per srl item No 19.00 here-in-before but of size 16 sqmm 4 core.\n | 150 | RM | |
| 28 | 21 | All as per srl item No 19.00 here-in-before but of size 95 sqmm 3.5 core.\n | 250 | RM | |
| 29 | 22 | All as per srl item No 19.00 here-in-before but of size 185 sqmm 3.5 core.\n | 250 | RM | |
| 30 | 23 | All as per srl item No 19.00 here-in-before but of size 300 sqmm 3.5 core.\n | 350 | RM | |
| 31 | 24 | Supply, fixing and testing cable jointing kit for XLPE armoured aluminium cable of size 25 to 50 sqmm 3½ core 1.1 KV grade cable for outdoor type straight through heat shrinkable joint complete with jointing material and accessories complete all as specified and directed. | 1 | Each | |
| 32 | 25 | All as per srl item No 24.00 here-in-before but suitable for 70 to 120 sqmm 3½ core cable. | 1 | Each | |
| 33 | 26 | All as per srl item No 24.00 here-in-before but suitable for 150 to 185 sqmm 3½ core cable. | 1 | Each | |
| 34 | 27 | All as per srl item No 24.00 here-in-before but suitable for 240 to 300 sqmm 3½ core cable. | 1 | Each | |
| 35 | 28 | Supply, fixing and testing cable jointing kit for XLPE armoured aluminium cable of size 95 sqmm 3 core 11 KV grade cable for indoor type terminal joint heat shrinkable joint complete with jointing material and accessories complete all as specified and directed. | 2 | Each | |
| 36 | 29 | All as per srl item No 28.00 here-in-before but suitable for 120 to 185 sqmm 3 core cable. | 2 | Each | |
| 37 | 30 | Supply, fixing and testing cable jointing kit for XLPE armoured aluminium cable of size 95 sqmm 3 core 11 KV grade cable for outdoor type terminal joint heat shrinkable joint complete with jointing material and accessories complete all as specified and directed. | 2 | Each | |
| 38 | 31 | All as per srl item No 30.00 here-in-before but suitable for 120 to 185 sqmm 3 core cable. | 2 | Each | |
| 39 | 32 | Supply, fixing and testing cable jointing kit for XLPE armoured aluminium cable of size 95 sqmm 3 core 11 KV grade cable for outdoor type straight through joint heat shrinkable joint complete with jointing material and accessories complete all as specified and directed. | 2 | Each | |
| 40 | 33 | All as per srl item No 32.00 here-in-before but suitable for 120 to 185 sqmm 3 core cable.\n | 2 | Each | |
| 41 | 34 | Supply, laying, jointing and testing underground XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 11000 volt grade earthed system of size 95 sqmm 3 core conforming to IS laid in trenches, in floor, in duct, through pipes or along the pole complete all as specified and directed | 150 | RM | |
| 42 | 35 | All as per srl item No 34.00 here-in-before but of size 185 sqmm 3 core.\n | 220 | RM | |
| 43 | 36 | Excavation in trenches in soft/ loose soil n. exc. 1.50 mtr wide and n. exc. 1.50 mtr in depth for laying of cables and getting out complete all as specified and directed. | 450 | Cum | |
| 44 | 37 | All as per item No. 36.00 here-in-before but exc. 1.50 mtr and n. exc. 3.0 mtr in depth | 5 | Cum | |
| 45 | 38 | Returning filling in, including spreading, leveling, watering and well ramming in layers n.exc. 25 cm thick each layer complete all as specified and directed. | 230 | Cum | |
| 46 | 39 | Removal of surplus soil to a distance n. exc. 50 mtr and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed. | 225 | Cum | |
| 47 | 40 | M&L sand for cushioning with 8cm thick layer before laying of cable and 15cm thick layer after laying of cable in trenches complete all as specified and directed. | 250 | Cum | |
| 48 | 41 | Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/ abutting each other complete all as specified and directed. | 15 | Per 1000 Nos | |
| 49 | 42 | M&L PCC (1:3:6) type C-2 using 40mm graded crushed stone aggregate in foundation of stay/ coping of poles including necessary form work and fare finish to exposed surfaces without using extra cement etc complete all as specified and directed | 4 | Cum | |
| 50 | 43 | S&F in replacement LED flood lights IP 66 high power LED flood light with pressure die-cast aluminium housing complete with all accessories of 150W LED, efficiency 100 Lm/ watt, with secondary optics modular independent lenses provided with casing and capping to minimize glare and for better distribution of light complete all as specified and directed.\nNote :\n(i) All LED fittings shall have supporting LM-79 & LM-80 test certificate from Govt. approved NABL accredited lab showing all the parameters duly signed by the local office bearer of manufacturer.\n(ii) All LED fittings shall have 2 years written warranty from local office bearer of manufacturer. | 20 | Each | |
| 51 | 44 | S&F in replacement LED twin obstruction light luminaries in yellow painted die-case aluminium alloy housing with 5 parallel circuits with accessories of 100 Nos LEDs code LTAL 100 complete all as specified and directed | 1 | Each | |
| 52 | 45 | S&F in replacement LED street light fitting of 90 watt in epoxy powder coated pressure die-cast aluminium housing, heat resistant toughened clear glass fixed with SS screws controlled with potted CVCC type BIS marked electronic driver duly enclosed, of approved brand only in housing having protection against over voltage, short circuit and open circuit and surge protection against lightening of 5 KV minimum in circuit and 5 KV outside the driver but inside the fixture with IP-66, Class-1 protection for LED and control gear compartments with high power LED chips of rating 2.5 to 3 watt (maximum) with colour temperature 5700 K (max) with secondary optics modular independent lenses provided with casing and capping to minimize glare and for better distribution of light suitable for voltage band 100 volts to 300 volt, power factor 0.95 (minimum) having efficacy 100 lumens/ watt. \nNotes: \n(i) All LED fittings shall be made in India only.\n(ii) All LED fittings shall have supporting LM-79 & LM-80 test certificate from Govt. approved NABL accredited lab showing all the parameters duly signed by the local office bearer of manufacturer.\n(iii) All LED fittings shall have 2 years written warranty from local office bearer of manufacturer.\n(iv) Brand name should be embossed on fixture to ensure Indian brand only. | 20 | Each | |
| 53 | 46 | S&F in replacement for energy saving & environmental friendly long life versalite pressure di-cast aluminium luminaries with heat resistant glass and suitable optics for uniform distribution of light 25 watt LED for bldg security lights with high efficiently electronic driver, having IP-66 protection, surge protection min 2 KV power factor more than 0.9 complete operative on AC supply 140 volts to 270 volts pre-wired and product should be made in India qty including bracket made out of GI pipe 32mm dia bent to shape and clamps 40 x 6mm with nuts and bolts prewired products must be made in India only connection and testing complete all as specified. \nNote: (i) Contractor shall be provided 2 years written manufacture's guarantee for the LED fixture complete including driver from the certified date of completion.\n(ii) Contractor shall be produce LM-79 & LM-80 report of NABL accredited laboratory from manufacturer's. | 15 | Each | |
| 54 | 47 | S&F in replacement bracket for street light fitting made of 50mm dia light grade GI pipe, 1.5 mtr length bent to suitable shape for fixing of street light fitting with all necessary accessories bracket, nuts, bolts, washers, two clamps made out of flat iron two pieces of size 40mm x 6mm x 500mm fabricated in shape and drilled holes for nuts and bolts, and painting with one coat of red oxide paint and two coats of aluminium paint complete all as specified and directed. | 20 | Each | |
| 55 | 48 | S&F in replacement street light junction box with 4 pole copper terminals suitable for 25 sqmm cable and one MCB SP 6 Amp, box insulated and made out of polycarbonate with glass fiber reinforced. The polycarbonate junction box shall be not less than 205 x 255 x 112 suitable for 16/ 25 Sqmm cable size with 03 Nos cable polamide galnds and check nuts terminals, environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive. The junction box shall be rated for degree of ingress protection IP 66/ 67 in accordance with IEC 60529. the gasket material shall be polyurethane and the gasket shall be internally embedded . The JBs shall be complies with requirements of the standards IEC 60998-1, IEC 60998-2-1, IEC 60670-22 & IEC 60670-2.5. the junction box color according to RAL 9011. For better safety the polycarbonate encls shall be fire retardant & self-extinguishing in accordance with IEC 60695-2-11, DIN VDE 0304 Part 3, It should be tested at glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08 complete with bracket of powder coated MS strip, nuts, bolts and washers to fix junction box with pole/ wall all as specified and directed \nNote : Manufacturer should submit routine test certificate for CJB/ PJB | 20 | Each | |
| 56 | 49 | M&L prestressed concrete pole 9.0 metres long, 102 x 152mm at top and 102 x 289mm at bottom, class 10 complete all as specified and directed | 5 | Each | |
| 57 | 50 | S&F wiring to pole alongwith earth wire with size 2 x 1.5 sqmm + 1x 1.0 sqmm of FR PVC insulated copper conductor, single core cable in surface/ recessed/ concealed PVC conduit medium grade as required complete all as specified | 230 | RM | |
| 58 | 51 | Supply and installing in replacement LED post light 40 watt, energy saving, environment friendly pressure die cast housing with clear/ opal diffuser, suitable for landscape lighting 5700 K prismatic polycarbonate cover and IP 65 protection with operating upto RH 90%, TDH<10%, complete accessories all as specified and directed. | 20 | Each | |
| 59 | 52 | Supply and fixing LED post top light with polycarbonate diffuser and IP-65 protection, 25 watt, 230 volt, 50 Hz, alongwith GI pipe light grade 1.6 mtr 50mm dia with MS plate 8mm thick size 40cm x 40cm welded on base of the GI pipe, pipe and plate duly painted with two coats of super enameled paint over a coat of red oxide primer, embedded in PCC block (1:3:6), 40cm x 40cm x 40cm, complete all as specified and directed | 20 | Each | |
| 60 | 53 | M&L RCC (1:1½:3) type B-1 using 20mm graded stone aggregate as in slab support on walls, beams and columns in floors, roofs, landings balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed | 1 | Cum | |
| 61 | 54 | M&L 10mm thick rendering in cement mortar (1:3) on fair faces of brick wall or concrete surfaces finished even and smooth without using extra cement complete all as specified and directed. | 5 | Sqm | |
| 62 | 55 | M&L brick work with sub class 'B' old size bricks, straight or curved on plan exc. 6 mtr mean radius built in cement mortar (1:6) complete all as specified and directed. | 2 | Cum | |
| 63 | 56 | M&L MS work as in cross arms, bracing, supports, clamps and back plates etc. fabricated from structural steel section including nuts, bolts, washers etc. including welding, bending, drilling holes for bolt of any size including provision of two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.\nNote: Unexposed surface shall be given one coat of primer only. | 3 | Qtl | |
| 64 | 57 | S&F HDPE pipe of 150mm dia suitable for 0.4 mpa working pressure of ISI marked for passing cable fixed to poles/ walls/ laid under floor, roads etc complete with and including fittings as required complete all as specified and directed | 18 | RM | |
| 65 | 58 | S&F GI pipe light grade of size 50mm bore for cable protection under road/ floor along the pole including fittings complete all as specified. | 24 | RM | |
| 66 | 59 | All as per item No. 58.00 here-in-before but 100mm dia bore | 24 | RM | |
| 67 | 60 | M&L boring hole under the road/ pavement/ hard standing with the help of trenchless technology using ultra sound technique and necessary machine for inserting and including HDPE pipe of size 150mm dia suitable for 0.4 mpa working pressure not less than one metre below ground level complete all as specified & directed. | 24 | RM | |
| 68 | 61 | S&F in replacement switch air break gang operated switch outdoor type HT 11 KV triple poles of rating 200 Amps with fixed contacts of phosphorus bronze and moving contacts of copper with mechanically operating system from ground level vertical mounted complete with HT insulators on mild steel frame and operating rod made out of 25mm GI pipe medium grade worked from ground level with handle and locking arrangements with 12 insulators of 11 KV with drop out fuses including two coats of aluminium paint on steel structure complete including submission of test certificate from manufacturer all as specified and directed. Note: Clamps/ cross arms shall be measured and paid for separately. | 2 | Each | |
| 69 | 62 | Supply & filling transformer insulation oil for topping up the level of oil having di-electric strength 45-60 KV (minimum) at a electrode gap of 2.5mm upto the required level of transformer and testing of di-electric strength of oil in transformer before and after filling complete all as specified and directed. (Transformer oil shall be supplied in sealed containers). | 500 | Ltr | |
| 70 | 63 | Dehydration and filtration of existing transformer oil using transformer oil filtration-cum-dehydration plant to eliminate foreign particles and to improve di-electric strength upto 50 KV (min) in 2.5mm electrode gap and to bring the acidity within the permissible limit below 0.5 mg KOH/ cm complete all as specified and directed. (Record of di-electric strength of insulating oil achieved after dehydration shall be given in writing by the contractor to the deptt). | 3600 | Ltr | |
| 71 | 64 | S&F transformer oil temperature gauge 0-100° C graduated, analogue dial type, suitable for transformer of capacity 63 KVA to 500 KVA complete all as specified and directed. | 5 | Each | |
| 72 | 65 | S&F silica gel breather assembly suitable for transformer of capacity 63 KVA to 500 KVA all as specified and directed. | 5 | Each | |
| 73 | 66 | S&F in replacement aluminium tube terminal for XLPE aluminium cable of size 240 to 300 Sqmm complete all as specified and directed | 42 | Each | |
| 74 | 67 | S&F in replacement aluminium tube terminal for XLPE aluminium cable of size 95 to 185 Sqmm complete all as specified and directed | 60 | Each |
AI Tender Summary
Tender Timeline
Oct 17, 2020
11:30 IST
Tender Published
Tender notice published.
CompletedNov 07, 2020
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedNov 09, 2020
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender