Military Engineer Services-MES has published Repair / Maintenance Of Unsv Lt Ug Cable Panels And Connected Wks In Tech Area At Mil Stn Dappar Under Ge ( P ) Dappar. Submission Date for this Tender is 07-11-2020. LT Cable Tenders in GE (P) Dappar Punjab. Bidders can get complete Tender details and download the document.
Name of Work: Repair / Maint of unsv LT UG cable panels and connected wks in Tech Area at Mil Stn Dappar under GE (P) Dappar | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Disconnecting & taking out old unserviceable LT cable of size 120 sq mm 3.5 core. | 350 | RM | |
2 | 2 | Disconnecting & Taking out old unserviceable LT cableof size 70 sq mm 3.5 core | 400 | RM | |
3 | 3 | Disconnecting & Taking out old unserviceable LT cable of size 50 sq mm 3.5 core | 600 | RM | |
4 | 4 | Disconnecting & Taking out old unserviceable LT cable of size 35 sq mm 3.5 core | 530 | RM | |
5 | 5 | Disconnecting & Taking out old unserviceable LT cable of size 25 sq mm 4 core | 650 | RM | |
6 | 6 | Disconnecting & Taking out old unserviceable LT cable of size 16 sq mm 4 core | 450 | RM | |
7 | 7 | Disconnecting & Taking out old unserviceable LT cable of size 10 sq mm 2 core | 300 | RM | |
8 | 8 | Supply, laying, jointing, connecting, testing & commissioning UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty 1100 volts grade with standard aluminium conductor of cross sectional area 120 sqmm x 3.5 core all as specified and directed by Engr-in-Charge.\nNOTE - (a). The quoted rate is deemed to be inclusive of arranging respective shutdown, disconnection of cables, commissioning of feeder after the completion of job and inclusive of any minor spares and jobs required for the completion of the job. (c). The cost of excavation, returning, filling, removal and PCC cable covers will be measured and paid under relevant items of this schedule. | 350 | RM | |
9 | 9 | Description all as per ser item No 8 here-in-before but size of LT under ground cable 70 sqmm 3.5 core. | 400 | RM | |
10 | 10 | Description all as per ser item No 8 here-in-before but size of LT under ground cable 50 sqmm 3.5 core. | 600 | RM | |
11 | 11 | Description all as per ser item No 8 here-in-before but size of LT under ground cable 35 sqmm 3.5 core. | 530 | RM | |
12 | 12 | Description all as per ser item No 8 here-in-before but size of LT under ground cable 25 sqmm 4 core. | 650 | RM | |
13 | 13 | Description all as per ser item No 8 here-in-before but size of LT under ground cable 16 sqmm 4 core. | 450 | RM | |
14 | 14 | Description all as per ser item No 8 here-in-before but size of LT under ground cable 10 sqmm 2 core. | 300 | RM | |
15 | 15 | Excavation in trenches in soft/loose/hard soil n exc 1.5 m wide and not exc 1.5 m in depth and getting out including forming bottom to required level or slope for laying pipes / laying of cable complete all as specified and as directed by Engineer-in-Charge. | 886 | Cum | |
16 | 16 | Returning filling in soft / loose soil in trenches including spreading, leveling and well ramming in 25 cm thick layers complete all as specified and as directed by Engineer-in-Charge. | 561 | Cum | |
17 | 17 | Removal of surplus soil to a distance n exc in 50 m and deposited where directed at a level n exc 1.5 m above the starting point complete all as specified and as directed by Engineer-in-Charge. | 325 | Cum | |
18 | 18 | Material and labour sand cushioning (dry sand) to underground cable for cable protection 23 cm thick in two layers (8 cm thick before laying of cables and 15 cm thick after laying the cable and punning down the sand to 18 cm thickness.). Complete all as specified and as directed by Engineer-in-Charge. (Note:- Only punned thickness 18 cm of sand shall be measured for payment purposes). | 236 | Cum | |
19 | 19 | M&L precast concrete cable cover, class LV, type 1 with peak, size 250mm x 150mm x 40mm. | 17493 | Each | |
20 | 20 | Material and labour for galvanized iron tubing size 40 mm bore (Light grade) with all necessary fittings laid in trenches under road crossing or fixed on poles / walls / under floors for cable protectioncomplete all as specfied and as directed. Make:- Jindal. Complete all as specified and as directed by Engineer-in-Charge. | 40 | RM | |
21 | 21 | M & L for earthing with galvanised iron earth plate of size 600x600x6mm thick buried directly in ground not less than 2.25m below normal ground level,earth plate packed on all sides with charcoal mixed with salt in alternate layers of 15 cm thickness connected by galvanised iron earth earth strip 32x6mm soldered & riveted toearth plate, galvanised iron earth strip will be provided by using 50mm bore galvanised iron pipe (light grade) earth plate to transformer body and neutral or test point of transformer, including flat iron clamp 25x3mm including bolts, nuts and washers complete including watering galvanised iron pipe 20 mm dia 'Light grade' 2.5mm long the earthing includes PCC pit including necessary earth works and disposal of surplus soil to a distance not less than 50m, chamber of PCC 1:4:8 type D-2 using 40mm graded stone aggregate, coping shall be of PCC 1:3:6 type C-I using 20mm graded stone aggregate, RCC pit cover 50mm thick in1:2:4 type B-I using 20mm graded stone aggregate, rein forced with 8mm dia @ 15cm c/c complete all as shown on sketch No 3 of SSR-I of 2009 and as specified and as directed by Engr-in-Charge. | 30 | Each | |
22 | 22 | M & L earth continuity conductor GI of 32x6 mm of GI strip by means of bolts, nuts, check nuts and GI washers complete all as specified. | 30 | RM | |
23 | 23 | M & L Synthetic insulating mat (rubber matting), ISI Marked suitable for 1100 Volts electrical grade 2mX1mX2mm thick chequered top, ISI marked to be laid in front of LT panel board complete all as specified and directed. | 4 | EACH | |
24 | 24 | M&L for Danger notice boards of 1.6mm thick mild steel sheet, vitreous enamelled white,with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT 25x20cm size. | 20 | EACH | |
25 | 25 | M&L for application of two coats of aluminium paint on steel tubular/rail pole of 9/11/13/15 M long externally after removal of old paint, rust, dust, oil, grease or any other foreign deposits by paint removers or burning off by blow lamps, cleaning with scrapers and chemicals for removal of rust for any number of coats of any width or girth incl. numbering of poles in blackbase & white letters paint and incld. painting five no. strips upto 30 cm on bottom of pole with black and yellow colour paint alternately all as specified and directed by Engr-in-Charge. | 200 | Each | |
26 | 26 | Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 25 to 50 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge. Make : Denson/M Seal/Birla | 12 | Each | |
27 | 27 | Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB FP, 36kA, 400 AMPS with Thermal - Magnetic Release Type Ics = 100% Icu, Adjustable Over Load setting: 0.4 -1.0 x In, Adjustable short circuit for each phase from 1.5 - 8 x In, Make - L&T, Cat No. - CM98401OOROOG including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel. | 1 | Each | |
28 | 28 | Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25kA, 250 AMPS with Thermal - Magnetic Release Type, Ics = 100% Icu, Adjustable Over Load setting: 0.4 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. -CM90642OOPO including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). | 1 | Each | |
29 | 29 | Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. - CM90642OONO including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). | 1 | Each | |
30 | 30 | Supply only fuse wire (Tin & Copper) 16/18/20 SWG complete all as specified and as directed by Engr-in-Charge. | 6 | Kgs | |
31 | 31 | Taking down unserviceable ACSR conductor and supply and fixing aluminium conductor steel reinforced any type complete all as specified and as directed by Engr-in-Charge. | 4 | Qtl | |
32 | 32 | Restringing and Fixing ACSR Conductor reinforced of any size to proper sag incl binding on insulator all as specified and as directed by Engr-in-Charge | 3200 | RM | |
33 | 33 | Cutting & trimming of tree branches any girth and size around overhead lines to a clear distance 1.5 mtr both sides of overhead line with in a 25 to 40 mtrs span gap of HT/LT lines including clearing the site all as specified and directed by the Engr-in-Charge. | 140 | Per Span | |
34 | 34 | M&L for cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide zinc chrome primer including removing old unserviceable rusted ones complete all as directed by Engineer-in-Charge | 4 | Qtls | |
35 | 35 | M&L for stay assembly complete with accessories as shown in electric plate No.I including loop type insulator, stay clamps etc complete all as specified & directed with diameter of stay 20 mm of stay rod complete all as specified & directed. \nNote: - Loop type insulator, PCC foundation, Exc & earth work & GI stay strand will be measured and paid seperately under relevent items of Sch 'A' | 25 | Per Set | |
36 | 36 | M&L for inspection of LT FPB all connected accessories/components like MCCB/MCB/ACB ON-OFF/Tripping operations, metering devices, cable lugs joints, bus bar connections, insulators, wiring, CTs, etc., cleaning of LT FPB using dry air pressure, vacuuming out all dust/foreign particles using vaccum cleaner complete, removing flash over/burnt carbon particles from cable lug joints, bus bars, etc. with CRC 226 or WD14 or equivalent cleaner, tightening of nuts/bolts and other electric connections, disconnecting all incoming and outgoing connected cables, cutting off burnt portions, crimping with suitable size aluminium/copper lugs and connecting up inclusive of replacement of cable glands (if any) all as directed at site by Engr-in-charge. Note:- (a). All spares like LED indicating lamps, ACB/MCCB/MCB, fuses with holders, voltmeter, ammeter, CTs, selector switches, copper/aluminium bus bar, control wiring, etc. required for replacement shall be measured and paid separately under relevant items of schedule here-in-after however the quoted rate is deemed to be inclusive of cost of cleaning agents, grease, cable lugs, cable glands, nut/bolt and washer combination all as approved by Engr-in-Charge. (b). The contractor has to arrange for electrical shutdown prior to carry own repairs. | 15 | EACH | |
37 | 37 | M&L for sheet metal work for replacement of unsv. panel doors, bus bar cover, metering devices/relay mounting doors in complete alignment with panel's existing doors with 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 or of shade as specified incld. necessary cutting of MS sheet so as to incorporate old serviceable panel accessories like LED indicating lamps, volt/ammeter, selector switches, MCCB/MCB handles, etc. welding and fixing jobs and dismantling of unsv./rusted doors to the complete satisfaction and as directed and specified by Engr-in-Charge. NOTE - (a). The contractor has to arrange for electrical shutdown prior to carry own repairs. (b). The quoted rate is deemed to be inclusive of cost of hinges, panel locks, accessories required for flush fitting of old serviecable LED indicating lamps, volt/ammeter, selector switches, MCCB/MCB handles, etc. on the new door or any other materials required for fixing and proper opereations of door. | 120 | Kg | |
38 | 38 | Supply and relplace existing u/s indicating lamp LED type suitable to operate on 230 volts AC Supply of R/Y/B colour as per site requirement all as specified and directed. | 35 | Each | |
39 | 39 | S&F in replacement Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) | 26 | Each | |
40 | 40 | S&F in replacement Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) | 25 | Each | |
41 | 41 | Supply and replace existing u/s selector switch for voltmeter. | 30 | Each | |
42 | 42 | Supply and replace existing u/s selector switch for Ammeter | 30 | Each | |
43 | 43 | supply and replace existing unserviceable CT as that of existing ratio and model suitable for 3 phase supply | 20 | Each | |
44 | 44 | S&F in replacement Street light control junction box 280x170x130mm upto 16 sq mm 4 core cables made out of FRP sheet moulded and arrangement of incoming 3 phase 4 wire system and out going 3 phase 4 wire system with R.Y.B.& N studs and control for incoming & outgoing cables with MCB SP 2.5 Amps 230 volts with neutral link including flat iron 25x3 mm “D” clamps (2 Nos) suitable to pole of any size including bolts nuts & washers.”NOTE: - The rates includes incoming & outgoing cables glands & lugs of size up to 16 sq mm 4 core. | 20 | Each | |
45 | 45 | M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of factory fabricated of size as per the existing IEC norms, floor mounted, IP 55 grade, outdoor type double door type LT cubical panel made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. Panel should be mounted/grouted PCC (1:4:8) type D2 of size on as per the panel dimensions such that there should be 100 mm offsets complete. The bottom of the panel (space between bottom of panel and top of PCC foundation) shall be covered with 3 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. The panel should have following accessories fitted in :- | 1 | Each Job | |
46 | 46 | (i) MCCB 400 Amps ,415 V 4 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM94106OOS1OG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - INCOMING | |||
47 | 47 | (ii) MCCB 320 Amps ,415 V 4 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM98403OOQOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - OUTGOING | |||
48 | 48 | (iii) MCCB 200 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OONO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. - OUTGOING | |||
49 | 49 | (iv) MCCB 100 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OOLO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - OUTGOING | |||
50 | 50 | (v) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM91712OOHOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. - OUTGOING | |||
51 | 51 | (vi) LED indicators - R/Y/B 240 V AC - 21 Nos. - 03 Nos per Incoming and outgoing feeders. | |||
52 | 52 | (vii) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) | |||
53 | 53 | (viii) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL132010OOOO and including suitable size CTs (set of 3) - 06 Nos. (Outgoing feeders) | |||
54 | 54 | (ix) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 06 Nos. (Outgoing feeders) | |||
55 | 55 | (x) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 20 Nos. | |||
56 | 56 | (xi) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | |||
57 | 57 | All as per SL Item No. 45 above but panel with following components - | 1 | Each Job | |
58 | 58 | INCOMER | |||
59 | 59 | ACB 630 Amps, manual draw out type, four pole, rapturing cap. 50kA, 415V AC, 50Hz incld. Suitable size, type and qty. of terminal adaptors all as per L&T Make, Model - 'C' Power, cat ref. no. - Make-L&T, SL95351 - 01 No. | |||
60 | 60 | OUTGOING | |||
61 | 61 | (i). MCCB 400 Amps ,415 V 4 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM94106OOS1OG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. | |||
62 | 62 | (ii) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL132010OOOO and including suitable size CTs (set of 3) - 03 Nos. (Incoming and Outgoing feeders) | |||
63 | 63 | (iii) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 03 Nos. (Incoming and Outgoing feeders) | |||
64 | 64 | (iv). LED INDICATORS - L&T make, CAT NO - HB07E - 09 Nos. | |||
65 | 65 | (V). 6 Amp MCB SP, Legrand Make, CAT No. - 6032 31 - 06 Nos. | |||
66 | 66 | (vi). Locking of ACB in Isolated position (LIP) - Make - L&T, SL93146OOOA - 01 No. | |||
67 | 67 | (vii). Lockable Trip Push Button (LTPB) - Make - L&T, SL93148OOOA - 01 No. | |||
68 | 68 | (viii). Suitable size Al BUS BAR for interconnections. | |||
69 | 69 | Supply and erection of factory made & assembled Double door type LT panel Board of suitable size, dust and vermin proof, fabricated out of 1.6 mm thick CRCA sheet steel, powder coated with 7 tank process, for better environment protection. MCCB Panel Board should be manufactured and supplied by ISO-9001 certified OEM of MCCB. The panel board should be suitable for floor or wall mounting and should be of robust construction. The panel board should have cable alleys on both sides for easy cable termination and should be complete with ammeter, voltmeter, selector switches, fuses, indicating lamps, etc. all as per Havells Cat No- IHLG04000400 or equivalent in L&T Make Model - Emergy-S SMDB, Schneider Make Cat No- Blokset LV Switchboard. | 2 | Each | |
70 | 70 | The panel board should comprises of the following items- | |||
71 | 71 | 1) Copper Bus Bar of rating equal or higher than the incomer MCCB current rating | |||
72 | 72 | 2) Incomer MCCB 400Amp, 4Pole, 36kA breaking capacity with adjustable thermal magnetic release- 1 No Havells Cat No- IHLG04000400 or equivalent in ABB, Schneider - INCOMING | |||
73 | 73 | 3) Outgoing MCCB 200Amp, 3Pole, 25kA breaking capacity with adjustable thermal magnetic release - 01 No Make Havells/ABB/Schneider | |||
74 | 74 | 4) Outgoing MCCB 160Amp, 3 Pole, 25kA breaking capacity with adjustable thermal magnetic release - 01 No Make Havells/ABB/Schneider | |||
75 | 75 | 5) Outgoing MCCB 63Amp, 3 Pole, 25kA breaking capacity with adjustable thermal magnetic release - 01 No Make Havells/ABB/Schneider | |||
76 | 76 | 6) Double door Cable Alley I/C 400 A,O/G 3P GF 2/4Way on both sides all as per Havells Cat No- ISSBOU0697 - 01 Set (Each set of Cable Alley consists of two numbers, one each on LHS and RHS) or equivalent in ABB, Schneider | |||
77 | 77 | 7) Double door Pre-Wired digital Meter Module with Voltmeter, Ammeter, Selector Switch, Ct’s Control Fuse & Indicating Lights all as per Havells Make Cat No- ISSBOU0707 or equivalent in ABB, Schneider - 01 No. | |||
78 | 78 | 8) Add on Incoming Changeover double door Switch Enclosure only suitable for 400 A/630 A Incoming change Over switch all as per Havells Make Cat No. ISSBOU0709 - 01 No. or equivalent in ABB, Schneider, L&T | |||
79 | 79 | 9) Automatic Transfer Switch with Controller 400 Amp without enclosure, Four pole with complete connections as per the satisfaction of engineer incharge all as per Havells make Cat No- IHYFCDO400 - 01 no. or equivalent in ABB, Schneider, L&T | |||
80 | 80 | All as per SL Item No. 45 above but panel with following components - | 1 | Each Job | |
81 | 81 | INCOMER | |||
82 | 82 | (i) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM91712OOHOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. | |||
83 | 83 | (ii) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) | |||
84 | 84 | (iii). LED INDICATORS - L&T make, CAT NO - HB07E - 13 Nos. | |||
85 | 85 | (iv). 6 Amp MCB SP for back supply for Multifunction meter and LED indicator lamps - 03 Nos. | |||
86 | 86 | (v). Ring Type CT 150/5A, 10 VA, CL1 Tape Wounded - 03 Nos. | |||
87 | 87 | APFC SECTION - | |||
88 | 88 | (vi). 10 Amp TP MCB for 25/10/5 KVAR capacitors - 06 Nos | |||
89 | 89 | (vii). Capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 5 kVAR 1 NO + 1 NC - 06 Nos. | |||
90 | 90 | (viii). APFC relay of 8 stage supply Voltage 415 V AC and current Input - 1A or 5 A with specs as - 3 Phase Current and Voltage measurement, PF display - 3 Digit after decimal, Individual harmonics measurement up to 31st order, Dual PF setting for Mains - DG application, Communication through Inbuilt MODBUS RS-485 Protocol all as per L&T Cat Part No. CS91050OOOO or eqivalent in Epcos/Schenider/Seimens - 01 No. | |||
91 | 91 | (iX). Rotary Type A/M Switch, 1 Pole, 2 Way with Off - 10 Nos. | |||
92 | 92 | (x). On Delay Timer, 3-120 Secs - 01 No. | |||
93 | 93 | (xi). 3 phase stud mounting cylindrical type, self standing units, self healing property with MPP film with safety device in the form of pressure sensitive (over pressure) mechanical interrupter, 415/440V, 3 phase, 50 Hz, Capacity 5 KVAR capacitor, AC conformance to Standards IEC 60831-1 2/96, IS 13340 - 06 Nos | |||
94 | 94 | (xii). Illuminated Flush Type Start Push Button with 1 NO - 6 Nos | |||
95 | 95 | (xiii). Illuminated Flush Type Start Push Button with 1 NO - 6 Nos | |||
96 | 96 | (xiv). Plastic body exhaust fan of suitable size fitted complete within the panel for heat dissipation purpose generated in the cubicle - 01 No. | |||
97 | 97 | (xv) Suitable size aluminium bus bar for R-Y-B phases. | |||
98 | 98 | M&L for dismantling, disconnecting connected cables of old unserviceable LT FPB, supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 55 grade, outdoor type LT cubical panel made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 of size not less than LBW-0.60mX0.60mX0.40m, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 with 100 mm offsets complete. The bottom of the panel (space between bottom of panel and top of PCC foundation) shall be covered with 3 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. The panel should have following accessories fitted in :- | 10 | Each Job | |
99 | 99 | (i) MCCB 63 Amps ,415 V TP pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM9200800L10G-01 including spreader terminals set of 04 direct rotary handle -01Nos or equivalent in legrand/ABB/Schenider | |||
100 | 100 | (ii) LED indicator - R/Y/B 240 V AC - 03 Nos. | |||
101 | 101 | (iii) Analogue Voltmeter having voltage of range : 0-500 V, MAKE - Legrand, CAT No. - 0046 60. | |||
102 | 102 | (iv) Voltmeter selector switch suitable with OFF, 16 Amps. MAKE - L&T, CAT No. - 61312 SCB03TDYR | |||
103 | 103 | (v) Analogue Ammeter having AC range : 0 - 30 A (4 modules) with suitable size resin cast ring type CT-03 Nos. MAKE - Legrand, CAT No. - 0046 02. | |||
104 | 104 | (vi) Ammeter selector switch suitable for line currents. MAKE - L&T, CAT No. - 61325 SCB03TDYR. | |||
105 | 105 | M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of factory fabricated of size as per the existing IEC norms, floor mounted, IP 55 grade, outdoor type double door type LT cubical panel made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. Panel should be mounted/grouted PCC (1:4:8) type D2 of size on as per the panel dimensions such that there should be 100 mm offsets complete. The bottom of the panel (space between bottom of panel and top of PCC foundation) shall be covered with 3 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. The panel should have following accessories fitted in :- | 1 | Each Job | |
106 | 106 | (i) MCCB 400 Amps ,415 V 4 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM94106OOS1OG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - INCOMING | |||
107 | 107 | (ii) MCCB 250 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OOPO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - OUTGOING | |||
108 | 108 | (iii) MCCB 200 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OONO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. - OUTGOING | |||
109 | 109 | (iv) LED indicators - R/Y/B 240 V AC - 12 Nos. - 03 Nos per Incoming and outgoing feeders. | |||
110 | 110 | (v) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) | |||
111 | 111 | (vi) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL132010OOOO and including suitable size CTs (set of 3) - 03 Nos. (Outgoing feeders) | |||
112 | 112 | (vii) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 03 Nos. (Outgoing feeders) | |||
113 | 113 | (viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 11 Nos. | |||
114 | 114 | (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | |||
115 | 115 | All as per SL Item No.50 above but panel with following components - | 1 | Each Job | |
116 | 116 | (i) MCCB 250 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OOPO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - INCOMING | |||
117 | 117 | (ii) MCCB 100 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OOLO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 03 Nos. - OUTGOING | |||
118 | 118 | (iii) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM91712OOHOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - OUTGOING | |||
119 | 119 | (iv) LED indicators - R/Y/B 240 V AC - 15 Nos. - 03 Nos per Incoming and outgoing feeders. | |||
120 | 120 | (v) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO and including suitable size CTs (set of 3) - 01 No. (for Incoming) | |||
121 | 121 | (vi) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL132010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) | |||
122 | 122 | (vii) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) | |||
123 | 123 | (viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 14 Nos. | |||
124 | 124 | (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | |||
125 | 125 | All as per SL Item No. 50. above but panel with following components - | 1 | Each Job | |
126 | 126 | (i) MCCB 200 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OONO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - INCOMING | |||
127 | 127 | (ii) MCCB 100 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OOLO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. - OUTGOING | |||
128 | 128 | (iii) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM91712OOHOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. - OUTGOING | |||
129 | 129 | (iv) LED indicators - R/Y/B 240 V AC - 15 Nos. - 03 Nos per Incoming and outgoing feeders. | |||
130 | 130 | (v) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO and including suitable size CTs (set of 3) - 01 No. (for Incoming) | |||
131 | 131 | (vi) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL132010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) | |||
132 | 132 | (vii) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) | |||
133 | 133 | (viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 14 Nos. | |||
134 | 134 | (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | |||
135 | 135 | All as per SL Item No. 50 above but panel with following components - | 1 | Each Job | |
136 | 136 | (i) MCCB 320 Amps ,415 V 4 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM98403OOQOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - INCOMING | |||
137 | 137 | (ii) MCCB 250 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM90642OOPO including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 01 No. - OUTGOING | |||
138 | 138 | (iii) MCCB 63 Amps ,415 V 4 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make ; Cat pat No : CM91712OOHOOG including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications and model or equivalent in legrand/ABB/Schenider - 02 Nos. - OUTGOING | |||
139 | 139 | (iv) LED indicators - R/Y/B 240 V AC - 12 Nos. - 03 Nos per Incoming and outgoing feeders. | |||
140 | 140 | (v) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as per L&T make, Cat No. - WL440010OOOO and including suitable size CTs (set of 3) - 01 No. (01 NO. for Incoming feeder) | |||
141 | 141 | (vi) Single function 3 phase LED voltmeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL132010OOOO and including suitable size CTs (set of 3) - 03 Nos. (Outgoing feeders) | |||
142 | 142 | (vii) Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 03 Nos. (Outgoing feeders) | |||
143 | 143 | (viii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 11 Nos. | |||
144 | 144 | (ix) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | |||
145 | 145 | Painting to electric control panel of E/M installations by cleaning the existing old paint with the help of mechanical tools such as wire brush, scraper and sand paper from the surface of panel and painting the prepared surface with two coat of synthatic enamel paint of approved shade over a coat of red oxide primer complete all as specified abd specified. | 20 | Sqm | |
146 | 146 | Repairing/servicing of APFC panel board by replacing the all defective components with new components, re-wiring, cleaning, testing, reconnecting, re-installing and commissioning the APFC panel board complete all as specified and directed by Engr-in-Charge. | 8 | Each Job | |
147 | 147 | S&F in replacement APFC relay of 8 stage supply Voltage 415 V AC and current Input - 1A or 5 A with specs as - 3 Phase Current and Voltage measurement, PF display - 3 Digit after decimal, Individual harmonics measurement up to 31st order, Dual PF setting for Mains - DG application, Communication through Inbuilt MODBUS RS-485 Protocol all as per L&T Cat Part No. CS91050OOOO or eqivalent in Epcos/Schenider/Seimens. | 3 | Each | |
148 | 148 | Dismantling, supply and install, connect, test and commission of capacitor, 3 phase, Super Heavy Duty cylindrical type, self standing units, self healing property with MPP film with safety device in the form of pressure sensitive (over pressure) mechanical interrupter, 415/440V, 3 phase, 50 Hz, Capacity 5 KVAR, AC conformance to Standards IEC 60831-1 2/96, IS 13340 including testing, commisioning as in repairs complete all as specified and directed. | 14 | Each | |
149 | 149 | All as per item no:52 above but 10 KVAR. | 16 | Each | |
150 | 150 | All as per item no:52 but 20 KVAR. | 16 | Each | |
151 | 151 | S&F in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 10 kVAR capacitor complete with connected switch gear/ components in various APFC panels of L&T make Type MO C10 Cat Part No. CS96156 or equivalent in Makes as per PS of this CA all as specified and directed by Engr-in-Charge. | 14 | Each | |
152 | 152 | S&F in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 15 kVAR capacitor complete with connected switch gear/ components in various APFC panels of L&T make Type MO C15 Cat Part No. CS90019 or equivalent in Makes as per PS of this CA all as specified and directed by Engr-in-Charge. | 15 | Each | |
153 | 153 | S&F in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts and Spreader Link Kit suitable for 25 kVAR capacitor complete with connected switch gear/ components in various APFC panels of L&T make Type MO C25 Cat Part No. CS96322 or equivalent in Makes as per PS of this CA all as specified and directed by Engr-in-Charge. | 14 | Each | |
154 | 154 | S&F in repairs NO element complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 14 | Each | |
155 | 155 | S&F in repairs NC element complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 14 | Each | |
156 | 156 | S&F in repairs Illuminated push button- RED complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 14 | Each | |
157 | 157 | S&F in repairs Illuminated push button- GREEN complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 14 | Each | |
158 | 158 | S&F in repairs 1.1 KV current transformer of ratio 150/5 complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 8 | Each | |
159 | 159 | S&F in repairs 1.5 Sqmm multistranded copper FRLSH wire for control circuit complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 120 | RM | |
160 | 160 | S&F in repairs 6 sqmm multistranded FRLSH copper flexible cable complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 120 | RM | |
161 | 161 | S&F in repairs 1.5 sqmm pin type lugs complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 60 | Each Job | |
162 | 162 | S&F in repairs 6 sqmm pin/fork/round type lugsr complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 60 | Each Job | |
163 | 163 | S&F in repairs 6-32 A SP MCB, 10 kA 'C' series, 240 V AC, 50 Hzcomplete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 25 | Each | |
164 | 164 | S&F in repairs 32 A TP MCB, 10 kA 'C' series, 415 V AC, 50 Hz complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 15 | Each | |
165 | 165 | S&F in repairs 63A TPN MCB, 10 kA 'C' series, 415 V AC, 50 Hz complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 12 | Each | |
166 | 166 | S&F in repairs 2 way slector adaptor 25 Amps complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge | 10 | Each | |
167 | 167 | Taking down old unsv fitting and supply and fix LED flood light fitting 90 watts, IP65 class with separate integral driver and with pressure dia-cast aluminium housing all as per Crompton Make, Cat Pat No LFLN-90-CDL or eq in Havells/Bajaj/HPL. NOTE - The quoted rate is deemed to be inclusive of cost of minor spares and misc jobs to be carried at site for fittment of luminarie. | 8 | Each | |
168 | 168 | S&F LED LUMINARIE, pressure die cast aluminum housing, 45 watts capacity, 240V, IP 65 class, with suitable in-built electronic driver complete all as directed and specified by Engr-in-charge. MAKE of make Crompton Greaves cat part no - LSTP-45-CDL or Equivalent in Makes as mentioned in PS of thsi tender. NOTE - Cost of all minor spares and jobs required for fixing of light fixture on wall and for electrical connections are deemed to be included in the quoted rate. | 29 | Each | |
169 | 169 | Supply only street/security light bracket made out of 40mm dia light grade 1.5mtr bent to shape for fixing on any type of pole/wall with clamps nuts and bolts complete all as directed by engr-in-Charge. Make of GI pipe shall be Jindal/TATA/Swastik. Note:Cost of necessary GI items such as reduce ,coupler ,etc required to be fitted with GI bracket so as toproper fitiment of luminaries with bracket is deemed to be included in the quoted rate. | 60 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy