| 1 | 1 | M&L for carrying out comprehensive maintenance and technical services for 03 Nos. IGBT based UPS of capacity 120 KVA each of MGE make at Transmitting Station at Dolphin hill, comprising of the following outlined services:- | | 11 | Job |
|---|
| 2 | 1.01 | (a) The Contractors technical team shall visit the installation site for periodic preventive maintenance check up of the UPS system and the batteries every month. During this the system shall be cleaned and general performance will be checked. | | | |
|---|
| 3 | 1.02 | (b) DC back up source will be maintained by applying white petrolium jelly, checking/ servicing of batteries etc as applicable. | | | |
|---|
| 4 | 1.03 | (c ) Apart from the periodic preventive maintenance visits, all break down calls on the systems covered under AMC and shall be attended. | | | |
|---|
| 5 | 1.04 | (d) Cost of all the spares except AQUI Card, AC/DC capacitors, replacement of Batteries to put the UPS in working condition shall be born by the contractor during theAMC period. | | | |
|---|
| 6 | 1.05 | (e) Response time during normal working hours shall be 4 Hrs from the time of receipt of complaint and the resolution time shall be maximum 48 Hrs, based on the nature of complaint and replacement of components and boards etc. | | | |
|---|
| 7 | 1.06 | (f) Major Spares such as AQUI Card, AC/DC capacitors, replacement of Batteries required will be measured & paid separately under relevant items of Schedule. All other spares required for rectifier & inverter section such as other connecting cards, IGBTs, Input fuses, SCR, Inverter cooling fan etc for keeping the UPS in operational state are deemed to be included in the quoted rate. | | | |
|---|
| 8 | 1.07 | (g) In addition to the above the contractor shall attend and rectify all types of defects arised during the contract period, to keep the UPS system in operational condition. | | | |
|---|
| 9 | 2 | All as per item No. 01 above but for 02 Nos online UPS of capacity 80KVA each Make: Uniline Energy Systems (P) Ltd, at Rukmani Hub, Transmitting Station at Dolphins hill. \nNote : The rectifier card/inverter card/ AC/DC capacitors, Batteries will be measured & separately under relevant schedule items. | | 11 | Job |
|---|
| 10 | 3 | Supply only the following spares for carrying out repairs to UPS of capacity 120 KVA each of MGE make under item No.1 above :- | | | |
|---|
| 11 | 3.01 | a) Aqui Card | | 1 | Each |
|---|
| 12 | 3.02 | b) AC capacitor | | 2 | Each |
|---|
| 13 | 3.03 | c) DC capacitor | | 2 | Each |
|---|
| 14 | 4 | Supply only the following spares for carrying out repairs to UPS of capacity 80 KVA of Make: Uniline Energy Systems (P) Ltd under item No.2 above :- | | | |
|---|
| 15 | 4.01 | a) Inverter card | | 1 | Each |
|---|
| 16 | 4.02 | b) Rectifier Card | | 1 | Each |
|---|
| 17 | 4.03 | c) AC capacitor | | 2 | Each |
|---|
| 18 | 4.04 | d) DC capacitor | | 2 | Each |
|---|
| 19 | 5 | S&F in repair AVR with functions to adjust generator output voltage, prevent voltage hunting, set under frequency roll off knee point, set generator droop to 5% at full load, match AVR input to accessory output, set the over excitation cut off level, set intial frequency related voltage dip, over-voltage protection cut off level, maximum short circuit current with sensing input voltage range 170 - 250 V AC max, 50 -60 HZ frequency with output max upto 120 V DC, continuous current 2.7A & transient 6A for 10 sec including necessary control wiring complete from alternator to AVR complete testing & commissioning for DG sets of capacity 62.5 KVA to 200 KVA | | 1 | Each |
|---|
| 20 | 6 | S&F in repair AVR with functions to adjust generator output voltage, prevent voltage hunting, set under frequency roll off knee point, set generator droop to 5% at full load, match AVR input to accessory output, set the over excitation cut off level, set intial frequency related voltage dip, over-voltage protection cut off level, maximum short circuit current with sensing input voltage range 170 - 250 V AC max, 50 -60 HZ frequency with output max upto 120 V DC, continuous current 2.7A & transient 6A for 10 sec including necessary control wiring complete from alternator to AVR complete testing & commissioning for DG sets of capacity 250 KVA to 500 KVA | | 1 | Each |
|---|
| 21 | 7 | S&F in repair engine controller suitable for 160 KVA Cummins make engine with indications of Volts, Winding temperatur, Oil pressure, RPM, Hours run etc complete including harnessing wiring complete all as directed by Engr-in-Charge | | 1 | Job |
|---|
| 22 | 8 | M&L for carrying out 'B' check for DG set 20/25 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, gasket, coolant etc complete. Make Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND | | 1 | Job |
|---|
| 23 | 9 | M&L for carrying out 'B' check for DG set 62.5 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, gasket, coolant etc complete. Make Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND | | 4 | Job |
|---|
| 24 | 10 | M&L for carrying out 'B' check for DG set 125 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, gasket, coolant etc complete. Make Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND | | 1 | Job |
|---|
| 25 | 11 | M&L for carrying out 'B' check for DG set 160 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, coolant etc complete. Make of Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND/Greaves | | 1 | Job |
|---|
| 26 | 12 | M&L for carrying out 'B' check for DG set 250 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, gasket, coolant etc complete. Make Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND | | 1 | Job |
|---|
| 27 | 13 | M&L for carrying out 'B' check for DG set 320 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, gasket, coolant etc complete. Make Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND | | 2 | Job |
|---|
| 28 | 14 | M&L for carrying out 'B' check for DG set 500 KVA, as per manufacturer's recommendation including replacement of filter, 'O' rings, engine oil, gasket, coolant etc complete. Make Engine: Kirloskar/ CUMMINS/ ASHOK LEYLAND | | 1 | Job |
|---|
| 29 | 15 | Disconnecting and removing existing unserviceable battery and S&F maintenance free battery 12 V 90 AH including terminal clamps, copper lead of suitable length including testing and commissioning all as directed by Engineer-in-Charge. [Make: Exide/ Amara Raja/ Tata Green] | | 4 | Each |
|---|
| 30 | 16 | Disconnecting and removing existing unserviceable battery and S&F maintenance free battery 12V 180 AH including terminal clamps, copper lead of suitable length including testing and commissioning all as directed by Engineer-in-Charge. [Make: Exide/ Amara Raja/ Tata Green] | | 4 | Each |
|---|
| 31 | 17 | Supply and fixing in repair generator starting system with packaged power supply for generator starting system consisting of pure lead-tin valve regulated lead acid (VRLA) monobloc sealed maintenance free batteries and a internal switched mode power supply (SMPS) to charge battery complete of capacity/ rating 24V 32 Ah suitable for 160 to 500 KVA generators. Make: Cummins Part No. AX1013235 | | 2 | Each |
|---|
| 32 | 18 | Cleaning of diesel tank of any capacity carefully by draining out fuel in the tank including disconnection from fuel system, descaling the diesel tank with water pressure and removing the complete sludge deposited, drying the tank, repair to any leakage, cleaning and testing of fuel line up to Fuel Pump inlet all as directed for the following capacities :- | | | |
|---|
| 33 | 18.01 | (a) 500 KVA DG set | | 1 | Job |
|---|
| 34 | 18.02 | (b) 320 KVA DG set | | 1 | Job |
|---|
| 35 | 18.03 | (c) 250 KVA DG set | | 1 | Job |
|---|
| 36 | 18.04 | (d) 125/160 KVA DG set | | 2 | Job |
|---|
| 37 | 18.05 | (e) 62.5 KVA DG set | | 4 | Job |
|---|
| 38 | 18.06 | (f) 20 KVA DG set | | 1 | Job |
|---|
| 39 | 19 | M & L for replacement of complete fuel and lub oil hose pipe set with clamp / clip etc of the following capacity of DG sets:- | | | |
|---|
| 40 | 19.01 | (a) 320 KVA DG set | | 1 | Job |
|---|
| 41 | 19.02 | (b) 250 KVA DG set | | 1 | Job |
|---|
| 42 | 19.03 | (c) 125/160 KVA DG set | | 2 | Job |
|---|
| 43 | 19.04 | (d) 62.5 KVA DG set | | 3 | Job |
|---|
| 44 | 19.05 | (e) 20 KVA DG set | | 1 | Job |
|---|
| 45 | 20 | M&L for De-scaling of radiator by dismantling the upper & lower tank and cleaning the core pipes with cleaning chemicals (radi wash), components and arrest the leaking core by brazing/ dummy with lead including cleaning of upper and lower tanks and replacing the upper and lower gaskets and required nuts, bolts, refixing the same including testing and painting complete all as specified and directed for the following capacities :-\n | | | |
|---|
| 46 | 20.01 | (a) 500 KVA DG set | | 1 | Job |
|---|
| 47 | 20.02 | (b) 320 KVA DG set | | 1 | Job |
|---|
| 48 | 20.03 | (c) 250 KVA DG set | | 1 | Job |
|---|
| 49 | 20.04 | (d) 125/160 KVA DG set | | 1 | Job |
|---|
| 50 | 20.05 | (f) 62.5 KVA DG set | | 2 | Job |
|---|
| 51 | 21 | Checking completely wiring for AMF panel and identifying fault in the safety and control system wiring from AMF panel to engine control gadgets like HWT,LLOP,and shut down valve,dynamo self-starter etc for following capacity DG set engine and rectiying fault in the AMF system including replacement of Relay,Burnt control wiring cable with thimbles and ferrules.blown out fuses for proper functioning and testing the DG set all as directed. | | | |
|---|
| 52 | 21.01 | (a) 320/500 KVA DG set | | 1 | Job |
|---|
| 53 | 21.02 | (b) 160/250 KVA DG set | | 1 | Job |
|---|
| 54 | 21.03 | (c) 20/62.5/125 KVA DG set | | 2 | Job |
|---|
| 55 | 22 | M&L for Servicing/Checking/inspection AHU of Make: Voltas of capacity 32000 CFM of (2x45 TR+1x30 TR) central AC plant at technical building of Rukamani Hub with and including dismantling units, sheet metal parts, blowing out the dust, chemical cleaning by spraying the organic based scale removing agent Vaniklin at the appropriate ratio till removal of complete dust & scale deposits in the fin area of evaporator coil, flushing through for proper air flow across the coil, cleaning of expansion valve; greasing of blower motor, checking of electrical connection, cleaning of air filters,greasing of blower motor,replacement of un serviceable bearings, water drain lines, renewal of rusted sheet metal screws, applying synthetic enamel paint over a coat of primer on the rusted portion and testing & commissioning the unit all as specified and as directed by Engineer-in-Charge. | | 1 | Job |
|---|
| 56 | 23 | Supply only engine oil 15W40 or as per manufacturers recommendations for topping up or replacemente all as diected by Engineer-in-Charge. | | 100 | Litre |
|---|
| 57 | 24 | Supply and fix as in repairs Deep sea (UK) controller with enclosure and Two nos of Auxiliary relays, Two nos of Power relays , Terminal blocks in AMF panel of 125 KVA DG set including testing complete all as specified and as directed by Engineer-in-Charge. | | 1 | Each Job |
|---|
| 58 | 25 | Supply and fix as in repairs Switch and emergency stop button of 125 KVA DG set including testing complete all as specified and as directed by Engineer-in-Charge. | | 1 | Each |
|---|
| 59 | 26 | Supply and fix as in repairs lube oil pressure sensor with necessary brass sockets of 125 KVA DG set including testing complete all as specified and as directed by Engineer-in-Charge. | | 1 | Each |
|---|
| 60 | 27 | Supply and fix as in repairs hot water temparature sensor with necessary brass sockets of 125 KVA DG set including testing complete all as specified and as directed by Engineer-in-Charge. | | 1 | Each |
|---|
| 61 | 28 | Supply and fix as in repairs engine controller ( Deep sea) (UK)-01 no, AVR-01no with necessary wiring modifications complete in AMF panel of 62.5 KVA DG set including testing complete all as specified and as directed by Engineer-in-Charge. | | 1 | Each Job |
|---|
| 62 | 29 | Supply and fix as in repairs engine controller ( Deep sea) (UK)-01 no, with necessary modifications complete in AMF panel of 500 KVA DG set including testing complete all as specified and as directed by Engineer-in-Charge. | | 1 | Each Job |
|---|
| 63 | 30 | Attending the day to day maintenance and electrical breakdowns to external electric supply network from 33/11 KV MRS to 11 KV/0.433 KV sub-stns and connected switch controls up to main distribution boards at buildings, RMUs, transformers, back up protection, 2 pole structures, street light feeders and all other connected items; routine maintenance includes minor replacments like fuses, jumpers, insulation taping, applying petroleum jelly, termination of burnt LT cables using lugs and tightening of busbars/terminations etc of entire sailors, Offrs Accn area & OTM area of entire Dolphin hills for smooth and trouble free operation round the clock all as specified and directed by Engineer- in- Charge. | | 11 | Job per Month |
|---|
| 64 | 30.01 | Note :- \n(a) Minimum one Electrician (SK) and one Mate (SSK) to be outsourced for each shift of 08 hrs round the clock in three shifts. Any additional manpower for early restoration of supply is deemed to be included in the quoted rate. \n(b) HT/LT Complaints should be attended with in 30 min and rectification sholud be recorded. Necessary transportation should be provided by the contractor and the rate quoted is deemed to be included in per shift rate. | | | |
|---|
| 65 | 30.02 | (c) The insulators, transformer oil, MCCBs, Changeoverswitches will be supplied under Supply only under relevant items for fixing under repairs. \n(d) The M/L for cable defect rectifications including earth work is not included in the scope and will be measured and paid separately under relevant Schedule items. \n(e) The rate quoted deemed to be inclusive of ACSR conductors along with pad clamps for jumpering, aluminium lugs, HT/LT insulation taping, petroleum jelly complete. | | | |
|---|
| 66 | 31 | Supply only MCCBs of following current carrying capacity for carrying out repairs under relevant Schedule . Make: C&S/Schneider/L&T/ Indoasian/GE/Havells | | | |
|---|
| 67 | 31.01 | (a) 320-400 Amps, 3P, Adjustable type,415V MCCB, 35KA rating | | 1 | Each |
|---|
| 68 | 31.02 | (b) 250 Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating | | 1 | Each |
|---|
| 69 | 31.03 | (c) 200Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating | | 1 | Each |
|---|
| 70 | 31.04 | (d) 160Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating | | 1 | Each |
|---|
| 71 | 31.05 | (e) 32 to 100 Amps, 3P, 415 V MCCB, 16KA rating | | 1 | Each |
|---|
| 72 | 31.06 | (f) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 250 A rated | | 1 | Each |
|---|
| 73 | 31.07 | (g) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 200 A rated | | 1 | Each |
|---|
| 74 | 31.08 | (h) 4 Pole MCCB, 415 V, Adjustable type with breaking capacity 50 KA, 630 A rated | | 1 | Each |
|---|
| 75 | 32 | Supply only 4 Pole on load changeover switch of following current carrying capacity for carrying out repairs under relevant Schedule including necessary additional/alteration to busbars of existing panel etc complete all as directed. Make: Havells/L&T/Indoasian /C&S/GE/STANDARD | | | |
|---|
| 76 | 32.01 | (a) 4 Pole on load changeover switch 250 A , suitable for operation on 415 V AC | | 1 | Each |
|---|
| 77 | 32.02 | (b) 4 Pole on load changeover switch 200 A , suitable for operation on 415 V AC supply | | 1 | Each |
|---|
| 78 | 32.03 | (c) 4 Pole on load changeover switch 125 A , suitable for operation on 415 V AC supply | | 1 | Each |
|---|
| 79 | 33 | M&L for detecting HT/ LT UG cable faults located in any stretch/ depth with sophisticated cable fault locator consisting of microprocessor based pre-locator system, HV surge generator, fault pin point surge wave reciever, cable indentification instrument , cable tracer for exact location of under ground cable routes. \nNote: The rate quoted deemed to be inclusive of transportation of equipment and charges for service engineer. The fault locator will be issued by department for operation. | | 4 | Each Job |
|---|
| 80 | 34 | M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for size 3 core 185 Sqmm including testing after jointing complete all as directed. Make: 3M / Denson / M-Seal / Raychem | | 2 | Each |
|---|
| 81 | 35 | M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for indoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for size 3 core 185 Sqmm including testing after jointing complete all as directed. Make: 3M / Denson / M-Seal / Raychem | | 2 | Each |
|---|
| 82 | 36 | M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminium conductor cable of size 185 Sqmm including testing after jointing complete all as directed. Make: 3M / Denson / M-Seal / Raychem | | 2 | Each |
|---|
| 83 | 37 | S&L XLPE insulated,screened, PVC bedded galvanised steel strip or wire armoured ,electric power cables heavy duty with aluminium conductor, 11000 Volts grade (earthed) of size 3 core 185 Sqmm complete in trenches/ ducts/ on pole etc complete all as directed.Make: Universal/ Nicco/ Polycab/Havells | | 40 | RM |
|---|
| 84 | 38 | M&L for heat shrinkable straight through joint for LT UG cable including jointing kits complete for making joints suitable for aluminium conductor cable of size 3.5/ 4 core 25 to 50 sq.mm. Make: 3M / Denson / M-Seal / Raychem | | 1 | Each |
|---|
| 85 | 39 | All as per Item No.33 herein before but for cable of size 3.5 core 70 to 150 sq.mm. | | 1 | Each |
|---|
| 86 | 40 | All as per Item No.33 herein before but for cable of size 3.5 core 185 to 300 sq.mm. | | 1 | Each |
|---|
| 87 | 41 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade 3.5 core XLPE , armoured, electric power cables (heavy duty) with aluminium conductor of the following size including dismantling old one. Note: The rate quoted inclusive of termination at ends with suitable aluminium lugs wherever required\nMAKE: Havells / Gloster / KEI Industries Ltd / Polycab / Asian Cables / Finolex | | | |
|---|
| 88 | 41.01 | 3.5 core 70 Sqmm | | 100 | RM |
|---|
| 89 | 41.02 | 3.5 core 120 Sqmm | | 150 | RM |
|---|
| 90 | 41.03 | 3.5 core 150 Sqmm | | 150 | RM |
|---|
| 91 | 41.04 | 3.5 core 185 Sqmm | | 120 | RM |
|---|
| 92 | 42 | Excavation in trenches n.exc 1.5mtr wide and not exc 1.5mtr depth and getting out in soft/loose soil all as directed. | | 230 | Cum |
|---|
| 93 | 43 | Returning and filling in of excavated soil including spreading,levelling,watering and well ramming in layers not exceeding 25 cm each. | | 161.5 | Cum |
|---|
| 94 | 44 | Removal of surplus soil not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point. | | 68.5 | Cum |
|---|
| 95 | 45 | M&L for Sand cushioning/ sand covering for underground cable protection complete all as specified.\nNote: Punned thickness only will be measured and paid. | | 58 | Cum |
|---|
| 96 | 46 | Supply and laying sub class 'B' bricks of old size (standard size as per local availability) laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge | | 5700 | Each |
|---|
| 97 | 47 | M&L for GI pipe light grade 50 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection.\n Make : Surya Roshni Ltd / Tata / Jindal steel / Prakash | | 6 | RM |
|---|
| 98 | 48 | M&L for GI pipe light grade 80 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection. \nMake : Surya Roshni Ltd / Tata / Jindal steel / Prakash | | 6 | RM |
|---|
| 99 | 49 | M&L for GI pipe light grade 100 mm dia for cable protection on road crossings /plinth protection/ lamps post etc with fixed to the pole wall etc. suitable fittings for cable protection.\n Make : Surya Roshni Ltd / Tata / Jindal steel / Prakash\n | | 6 | RM |
|---|
| 100 | 50 | Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings all as directed. | | 2 | Cum |
|---|
| 101 | 51 | M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminium conductor cable of size 240 Sqmm including testing after jointing complete all as directed . Make: Birla 3M / Denson / M-Seal / Raychem | | 1 | Each |
|---|
| 102 | 52 | S&L XLPE insulated,screened, PVC bedded galvanised steel strip or wire armoured ,electric power cables heavy duty with aluminium conductor, 11000 Volts grade (earthed) of size 3 core 240 Sqmm complete in trenches/ ducts/ on pole etc complete all as directed. \nMAKE: Havells / Gloster / KEI Industries Ltd / Polycab / Asian Cables / Finolex | | 35 | RM |
|---|
| 103 | 53 | M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for indoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for size 3 core 240 Sqmm including testing after jointing complete all as directed . Make: Birla 3M / Denson / M-Seal / Raychem | | 1 | Each |
|---|