Construction Of Block Development Office Bangana Distt Una Hp Sh Providing Electrical Installation And Main Panel Therein Block Part I
Tender Value
10.74 Lakhs
Estimated cost
Bid Submission
15 Oct 2020
0 days left
EMD
21500
Bank guarantee accepted
Document Fee
350
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bangana → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Construction Of Block Development Office Bangana Distt Una Hp Sh Providing Electrical Installation And Main Panel Therein Block Part I
BOQ
| Name of Work: C/O Block Development Office Bangana Distt. Una (H.P.) [ SH : - Providing Electrical Installation & Main Panel therein] Block/ Part-I | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit with modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. | BI01010001010000000000000515BI0100001113 | ||
| 2 | 1.01 | Group C. | BI01010001010000000000000515BI0100001114 | 307 | point |
| 3 | 2 | Wiring for twin control light point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit, with 2-way modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. | BI01010001010000000000000515BI0100001115 | ||
| 4 | 2.01 | Group C. | 12 | point | |
| 5 | 3 | Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required. | 22 | each | |
| 6 | 4 | Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required. | 44 | each | |
| 7 | 5 | Supplying and fixing of Single Pole 25 Amp. 240V MCB and socket outlet complete with sheet steel encloser, mounting box and cover including plug top, ready to use with existing Air Condicitioner on surface or in recess, complete with connections, testing and commissioning etc. as required. Make : Havells, L&T or any other approved by Enginner-in-charge. | 21 | each | |
| 8 | 6 | Supplying and fixing electrical switch board, having 4 No. of 5/6 amp. Modular Switches and Modular Socket on suitable size of G.I. modular boxes of 12 modules (205mmx135mmx60mm) deep ( nominal size) on surface or in recess with suitable size along with modular base and cover plate for modular switches in the front including providing and fixing 4 No. 5 pin 5/6 amp modular socket outlet and 5/6 amp modular switch, connection, painting etc.as required. (For Light Plug/Computer Points) | 37 | each | |
| 9 | 7 | Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:- | |||
| 10 | 7.01 | Single pole 6 Amp. Cat-A. | 81 | each | |
| 11 | 7.02 | Single pole 16 Amp. Cat-A. | 44 | each | |
| 12 | 7.03 | Single pole 25 Amp. Cat-A. | 21 | each | |
| 13 | 8 | Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:- | |||
| 14 | 8.01 | Double pole. 40 Amp.Cat-A. | 12 | each | |
| 15 | 8.02 | Double pole. 63 Amp. Cat-A. | 12 | each | |
| 16 | 9 | Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required. | |||
| 17 | 9.01 | 40 Amps. Cat-A. | 12 | each | |
| 18 | 9.02 | 63 Amps. Cat-A. | 12 | each | |
| 19 | 10 | Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:- | |||
| 20 | 10.01 | Double door-8 way | 1 | each | |
| 21 | 10.02 | Double door-12 way | 23 | each | |
| 22 | 11 | Providing, fixing and installation of following rating and breaking capacity MCCB with Thermal Release Having inbuilt Overload and Short Circuit Protection in the existing cubical panel board suitable for input voltage: 415/500 Volt AC, 50 Hz, complete with all accesories, including making connections, testing and commissioning etc. as required. Make: L&T, Havells, Schneider, Standard or any other approved by Engineer-in-Charge. | |||
| 23 | 11.01 | MCCB DU100H 3-Pole 63 Amp Breaking Capacity 30-KA | 2 | each | |
| 24 | 11.02 | MCCB DU100H 3-Pole 100 Amp Breaking Capacity 30-KA | 4 | each | |
| 25 | 12 | Supplying and fixing of MCCB Enclosure,suitable for 3-pole or 4-pole MCCB, on surface / recess, complete with tinned neutral link, earth bar, din-bar, detachable gland plate, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:- Make: L&T, Havells or any other approved by Engineer-in-Charge. | |||
| 26 | 12.01 | MCCB Enclosure Siza-I for DU100H/DU125H/DU100D/DU125D/DN0 | 6 | each | |
| 27 | 13 | Supplying and fixing sheet metal bus-bar chamber suitable for 63 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 450mm & cross-sectional area (16mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (530mmx350mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:- | 2 | each | |
| 28 | 14 | Supplying and fixing sheet metal bus-bar chamber suitable for 100 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 450mm & cross-sectional area (25.4mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (530mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:- | 4 | each | |
| 29 | 15 | Supplying and erection of wall mounted metal boards for switch gear mounting of suitable size, with permissible variation in size of plus minus 5mm, welded frame work made of M.S. angle iron (25 mm x 25 mm x 6 mm thick) with sufficient numbers of horizontal and vertical intermediate members (25mm x 6mm thick) flat iron including painting and bonding to the existing earth as required:- | 6 | Sq. mtr. | |
| 30 | 16 | Supplying and erection of floor mounted fixed type metal frame work / boards of welded construction for switch gear mounting fabricated with M.S. angle iron (50 mm x 50 mm x 6 mm thick) of suitable dimensions with supporting members grouted 23 cm underground and frame work covered with 3mm thick M.S. sheet from top to a given height, with M.S. angle iron / 50mmx50mmx 6mm thick welded on the back and grouted into the back wall complete with painting and bonding to the existing earth as required:- | 2 | Sq. mtr. | |
| 31 | 17 | Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No. HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required. | |||
| 32 | 17.01 | 2x1.5 Sq. mm. | 490 | Meter | |
| 33 | 17.02 | 2x2.5 Sq. mm. | 270 | Meter | |
| 34 | 17.03 | 2x6.0 Sq. mm. | 190 | Meter | |
| 35 | 17.04 | 2x10 Sq. mm. | 215 | Meter | |
| 36 | 18 | Wiring for circuit/sub-main with 4x1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.1.5 Sq.mm.(4X1.5+2X1.5) HRFRLS/PVC insulated single core copper conductor cable for earthing as required. | 155 | Meter | |
| 37 | 19 | Wiring for circuit/sub-main with 4x2.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.2.5 Sq.mm.(4X2.5+2X2.5) HRFRLS/PVC insulated single core copper conductor cable for earthing as required. | 200 | Meter | |
| 38 | 20 | Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required. | 540 | Meter | |
| 39 | 21 | Wiring for power plug with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 2 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required. | 373 | Meter | |
| 40 | 22 | Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, unarmoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:- | |||
| 41 | 22.01 | Unarmoured cable 16 sq. mm (four core) | 20 | R.Mtr. | |
| 42 | 22.02 | Unarmoured cable 25 sq. mm (3.5 core) | 70 | R.Mtr. | |
| 43 | 23 | Sub-Main Distribution Panel:- Providing and fixing floor/wall mounted L&T make SMDB Panel TN400D, O/G 100A 8-Ways Panel, having Main MCCB Incomer 400 Amp. & Outgoing 8-Way Sub-Incomer 100 Amp. of suitable dimensions made from 1.6 mm thick CRCA sheet, wire-set, neutral link, earth bar, din-bar, detachable gland plate, cable, identification labels, interconnections, phosphatized and powder painted and LED phase indicating set, Digitial Metering complete with following accessories including earthing etc. as required : - SMDB Panel Highlights: -?Compliance with latest standard - IEC 61439-3,?DEKRA and ASTA certified, ? Ingress protection - IP 44,Provision for :-Main MCCB Incomer 400 Amp.Outgoing 8-way Sub-Incomer MCCB 250 Amp.Size: - 1087mm(H) x 870mm(W) x 208.5mm(D)Cat.No.- DA40D1084CZZ0 = 1 No. Incoming Device: - ?DN3-400D 3 Pole MCCB - 400A breaking capacity-50KA = 1 No.Cat.No.- CM94005OOR1OG, Outgoing Device: -?DN0-100D 3 Pole MCCB - 100 A breaking capacity-36KA = 8 No. Cat.No.- CM97893OOK2OG,Metering, Bottom Cabling & Corner Box: - ?Provision of 3 nos of 1-phase ammeter (96x96), 1 nos of 1-phase voltmeter (96x96) with voltage selector switch & indicating lamps Metering Extension Box [Cat.No.CM90439OOPO] = 1 No.Bottom Cabling Box [Cat.No.CM91062OOOO] = 1 No.Corner Box [Cat.No.CM91089OOOO] = 4 No.Left Side Cabling Box [Cat.No.CM91087OFOO] = 1 No.Right Side Cabling Box [Cat.No.CM91088OFOO] = 1 No.1Ph LED Ammeter Cl 1 [Cat.No.WL111010OOOO] = 3 No.1Ph LED Voltmeter Cl 1 [Cat.No.WL111010OOOO] = 1 No.Voltmeter Selector Switche [Cat.No.61312 SAB13TDYR] = 1 No.LED RED Indicator 22.5 mm [Cat.No.EILR240A] = 1 No.LED Yellow Indicator 22.5 mm [Cat.No.EILY240A] = 1 No.LED Blue Indicator 22.5 mm [Cat.No.EILB240A] = 1 No. | 1 | each |
AI Tender Summary
Tender Timeline
Oct 01, 2020
11:30 IST
Tender Published
Tender notice published.
CompletedOct 15, 2020
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedOct 17, 2020
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer