| 1 | 1 | Taking down existing unserviceable/old point wiring surface /batten excluding fitting fixtures ,ceiling roses, pendant/angle holders, regulators, sockets,switches but including PVC conduit complete all as specified and directed | | 380 | per point |
|---|
| 2 | 2 | Material and labour for point wiring ,using approved colour coding (Phase-red,Neutral-black,Earth-green) complete with FRLS PVC insulated and unshealthed stranded copper conductor cable 1.5 sqmm single core conforming to IS 694 including medium duty concealed unplasticised PVC conduit conforming to IS 9537(part-3) and ISI marked not less than 20 mm dia with concealed in wall pressed steel terminal box of not less than 2 mm thick of required size including painting terminal boxs inside and outside with two coat of synthetic enamle paint over one coat of red oxide primer with top cover 3 mm thick bakelite laminated sheet with brass screws and Cup washer with all assessories including FRLS PVC insulated and unshealthed stranded copper conductor cable 1.5 sqmm single core in green colour as earth wire connected to earth dolly complete all as specified and directed .(a)One light/fan/exhaust fan point/call bell point controlled by 1 No,one way 5/6 Amp switch complete all as specified and directed. | | 280 | Per point |
|---|
| 3 | 3 | (b)One 3 pin /5 pin socket outlet 5 Amp controlled by 1 No one way 5/6 Amp switch on same board along with other switches ,fan regulator etc. complete all as specified and directed. | | 50 | Per point |
|---|
| 4 | 4 | (c)One 3 pin /5 pin socket outlet 5 Amp controlled by 1 No one way 5/6 Amp switch on independent board. complete all as specified and directed. | | 50 | Per point |
|---|
| 5 | 5 | S&F switch piano flush button single pole one way 6 Amp, 240 Volts complete all as specified and directed. | | 330 | Each |
|---|
| 6 | 6 | S&F for socket outlet, 5 Pin, 6 Amp flush type complete all as specified and directed. | | 100 | Each |
|---|
| 7 | 7 | S&F call Bell switch ( bell push) flush type 5 Amp 240 volt complete all as specified and directed. | | 15 | Each |
|---|
| 8 | 8 | S&F call Bell AC 230 Volt, Single pole ding dong type complete all as specified and directed. | | 15 | Each |
|---|
| 9 | 9 | Material and labour for point wiring ,using approved colour coding (Phase-red,Neutral-black,Earth-green) complete for one socket outlet 15 Amp on independent board with FRLS PVC insulated and unshealthed stranded copper conductor cable 4 sqmm single core conforming to IS 694 including medium duty concealed unplasticised PVC conduit conforming to IS 9537(part-3) and ISI marked not less than 20 mm dia with concealed in wall pressed steel terminal box of not less than 2 mm thick of required size including painting terminal boxs inside and outside with two coat of synthetic enamle paint over one coat of red oxide primer with top cover 3 mm thick bakelite laminated sheet with brass screws and Cup washer with all assessories including FRLS PVC insulated and unshealthed stranded copper conductor cable 4 sqmm single core in green colour as earth wire connected to earth dolly complete all as specified and directed . | | 50 | Per point |
|---|
| 10 | 10 | S&F switch piano flush button single pole one way 15 Amp, 240 Volts Complete all as specified and directed | | 50 | Each |
|---|
| 11 | 11 | S&F for socket outlet, 3 Pin, 15 Amp flush type Complete all as specified and directed | | 50 | Each |
|---|
| 12 | 12 | S & F ceiling rose, surface Bakelite,isolated body three terminals Complete all as specified and directed | | 310 | Each |
|---|
| 13 | 13 | S&F MCB’s single pole, 10 KA ,6 Amp to 30 Amp 240 Volts,and of ''B'' series with required wiring connections and lugs etc and erecting in provided enclouser/destribution board.MCBs shall be of current limiting type ,ISI marked conforming to IS 8828-1996.the power loss per pole shall be low and shall be in accordance with IS 8828-1996,All cable entries shall be either from bottom or top .MCB shall be of C curve charactertics & shall have quick make and break non welding self wiping silver alloy contact for 10 KA short circuit both on manual & automatic operation .All the active ,live parts of MCBs should be out of human reach ,ensuring safty & conforming to IP 55 degree of protection .The MCBs must house transperent lebel holder to ensure circuit identification .The MCB must have fully insulated safty shutters.The MCB shall have lockable switching lever.The minimum electrical endureance shall be 20000 operations .The housing of MCB shall be mounted self-extinguishing DMC(Dough moulding compount).The short circuit current shall be brought zero within 4 t0 5 milliseconds from the time they are established including taking down old one complete all as specified and directed. Make:SHEINEDER/LEGRAND /L & T/ABB | | 48 | Each |
|---|
| 14 | 14 | S&F MCB’s single pole and neutal, 10 KA ,32 Amp to 40 Amp 240 Volts,and of ''B'' series with required wiring connections and lugs etc and erecting in provided enclouser/destribution board.MCBs shall be of current limiting type ,ISI marked conforming to IS 8828-1996.the power loss per pole shall be low and shall be in accordance with IS 8828-1996,All cable entries shall be either from bottom or top .MCB shall be of C curve charactertics & shall have quick make and break non welding self wiping silver alloy contact for 10 KA short circuit both on manual & automatic operation .All the active ,live parts of MCBs should be out of human reach ,ensuring safty & conforming to IP 55 degree of protection .The MCBs must house transperent lebel holder to ensure circuit identification .The MCB must have fully insulated safty shutters.The MCB shall have lockable switching lever.The minimum electrical endureance shall be 20000 operations .The housing of MCB shall be mounted self-extinguishing DMC(Dough moulding compount).The short circuit current shall be brought zero within 4 t0 5 milliseconds from the time they are established including taking down old one complete all as specified and directed. Make:SHEINEDER/LEGRAND /L & T/ABB | | 6 | Each |
|---|
| 15 | 15 | S&F Electronic fan regulator steped type (flush type) 240 volt ,50Hz ,single phase on existing phenotic laminated sheet including taking down old one and connecting complete all as specified and directed. | | 96 | Each |
|---|
| 16 | 16 | S&F sheet metal enclosures (MCB Distribution board) when MCB’s to be used single pole and neutral 8 ways 220 volt with 200 amps rated bus bar, double door with bus bar neutral link earth bar, Din rail, necessary blanking plated, including fixing DB flush in wall complete with making good disturbed surfaces as per existing including taking down old one Complete all as specified and directed. Make - Legrand/HAGER/L&T/ABB | | 6 | Each |
|---|
| 17 | 17 | S & F sub main wiring using approved colour coding (Phase-red,Neutral-black,Earth-green) complete with two single core FRLS PVC insulated and unshealthed stranded copper conductor cable 6 sqmm as current carrying conductor and one run of 6.0 sqmm as earth contunity conductor ,voltage rating 1100 volt ,ISI marked drawn in and including concealed PVC conduit ISI marked of dia not less than 25 mm and thickness 2 mm with stranded accessories along with one run of FRLS PVC green colour insulated,unshealthed,stranded copper conductor of size 6 sqmm all as specified and directed including taking down old one Complete all as specified and directedNote: Two run of single core FRLS PVC cable with one run of earth contunity conductor and conduit shall be measured as one unit. | | 80 | RM |
|---|
| 18 | 18 | S & F sub main wiring using approved colour coding (Phase-red,Neutral-black,Earth-green) complete with two single core FRLS PVC insulated and unshealthed stranded copper conductor cable 4 sqmm as current carrying conductor and one run of 4.0 sqmm as earth contunity conductor ,voltage rating 1100 volt ,ISI marked drawn in and including concealed PVC conduit ISI marked of dia not less than 25 mm and thickness 2 mm with stranded accessories along with one run of FRLS PVC green colour insulated,unshealthed,stranded copper conductor of size 4 sqmm all as specified and directed including taking down old one Complete all as specified and directed Note: Two run of single core FRLS PVC cable with one run of earth contunity conductor and conduit shall be measured as one unit. | | 60 | RM |
|---|
| 19 | 19 | S& F cast iron /pressed steel terminal rectangular box 60mm deep for mounting switches,sockets ,regulator etc. with 3mm thick plastic laminated sheet cover of size 150x75mm rectangular complete including taking down old one Complete all as specified and directed. | | 15 | Each |
|---|
| 20 | 20 | All as per item No. 19 here in before but of size 150x150mm | | 10 | Each |
|---|
| 21 | 21 | All as per item No. 19 here in before but of size 200x150mm | | 10 | Each |
|---|
| 22 | 22 | All as per item No. 19 here in before but of size 200x250mm | | 10 | Each |
|---|
| 23 | 23 | S&F in repair rigid medium PVC conduit of 25 mm dia exclusive of boxes out inclusive of all tees, bends, elbows, reducers, bell mouth tubes and fixing accessories such as coulers locknuts, saddles, pipe hooks of size including cutting of shape Complete all as specified and directed | | 250 | RM |
|---|
| 24 | 24 | M&L for earthing complete with galvanized steel earth plate 600x600x6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check-nuts, and washers of galvanised iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe light grade 15 mm bore for protection of GI strip from earth electrode to and including the earth test point of galvanised Iron/steel of size 75mm x75mm x 25mm, supplying and laying charcoal stone aggregate) chamber and mild steel angle iron frame 40x40x3mm and RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded crushed stone aggregate reinforced with 8 mm dia TMT bars @ 75mm C/C both ways with mild steel handle 12 mm dia, PGI funnel with wire mesh, 20 mm dia GI pipe light grade for watering all as shown in drawing in SSR Part I 2009 | | 2 | Each |
|---|
| 25 | 25 | Supplying and fixing earth continuity conductor or main earthing lead 32x6 mm Galavnised Iron strip/earth with saddle and fixing screw etc for roof conductor and down conductorsr any other position including jointing by tinned copper/ brass nuts bolts and washers in addition to brazing at every joint complete all as specified & directed. | | 28 | RM |
|---|