Provision Of Security Wall 04 X Elevated Sentry Posts With Guard Rest Room And Steel Gates Including External Services At Baddowal, Jalandhar Cantt-Punjab

Military Engineer Services-MES has published Provision Of Security Wall 04 X Elevated Sentry Posts With Guard Rest Room And Steel Gates Including External Services At Baddowal. Submission Date for this Tender is 21-09-2020. Wall construction Tenders in Jalandhar Cantt Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

25148212
Provision Of Security Wall 04 X Elevated Sentry Posts With Guard Rest Room And Steel Gates Including External Services At Baddowal
Open Tender
Indian
Punjab
Jalandhar Cantt
21-09-2020

Tender Details

Provision Of Security Wall 04 X Elevated Sentry Posts With Guard Rest Room And Steel Gates Including External Services At Baddowal

Key Value

Document Fees
INR 2000 /-
EMD
INR 545000.0 /-
Tender Value
INR 4.70 Crore /-

BOQ Items

Name of Work: PROVN OF SECURITY WALL 04 X ELEVATED SENTRY POSTS WITH GUARD REST ROOM AND STEEL GATES INCLUDING EXTERNAL SERVICES AT BADDOWAL (Tender ID : 2017_MES_117363_2)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Note: (i) Please refer Schedule 'A' Notes given on serial page No. 25 to 30 of tender documents.\n(ii) Item from Srl No. 3.00 to 6.02 of this document shall be Part-XII (Miscellaneous items) of BOQ.
2 2 LUMPSUM/ OTHER PRE-PRICED PROVISIONAL SCHEDULES OF WORKS
3 2.01 Lump sum price worked out by the contractor for BUILDING WORKS as listed in Schedule 'A' Part-I brought forward from serial page No. 31. 1 Each
4 2.02 Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS as listed in Schedule 'A' Part-II brought forward from serial page No. 32. 1 Each
5 2.03 Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS as listed in Schedule 'A' Part-III brought forward from serial page No. 33. 1 Each
6 2.04 Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS as listed in Schedule 'A' Part-IV brought forward from serial page No. 35. 1 Each
7 2.05 Lump sum price worked out by the contractor for ROAD, PATH & CULVERT WORKS as listed in Schedule 'A' Part-V brought forward from serial page No. 37. 1 Each
8 2.06 Lump sum price worked out by the contractor for AREA DRAINAGE WORKS as listed in Schedule 'A' Part-VI brought forward from serial page No. 38. 1 Each
9 2.07 Lump sum price worked out by the contractor for BOUNDARY WALL, FENCING & GATE WORKS as listed in Schedule 'A' Part-VII brought forward from serial page No. 42. 1 Each
10 2.08 Lump sum price worked out by the contractor for SITE CLEARANCE AND EARTH WORKS as listed in Schedule 'A' Part-IX brought forward from serial page No. 43. 1 Each
11 2.09 Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS as listed in Schedule 'A' Part-X brought forward from serial page No. 45. 1 Each
12 2.1 Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS as listed in Schedule 'A' Part-XI brought forward from serial page No. 46. 1 Each
13 2.11 Lump sum price worked out by the contractor for DEMOLITION WORKS as listed in Schedule 'A' Part-XIII brought forward from serial page No. 47. 1 Each
14 3 INTERNAL ELECTRIFICATION WORKS
15 3.01 Supply and fixing MCB, Single pole & neutral 240 volts, capacity 40 Amps, 50 Hz, breaking capacity 10 KA complete all as specified. 4 Each
16 3.02 Supply and fixing MCB, single pole 240 volts, capacity 6 Amps, 50 Hz, breaking capcity 10 KA complete all as specified. 16 Each
17 3.03 Supply and fixing MCB, single pole 240 volts, capacity 16 Amps to 32 Amps, 50 Hz, breaking capacity 10 KA complete all as specified. 8 Each
18 3.04 Supply and fix blanking plate complete all as specified 4 Each
19 3.05 Supply and fixing lamp holder insulated body with back plate for batten fittings including LED lamp 11 watt. 32 Each
20 3.06 Supply and fixing ceiling fan 1200 mm sweep 5 star rating with and including flexible copper conductor three core cable from connector to ceiling rose, fan hook and connecting complete all as specified 12 Each
21 3.07 Supply and fixing exhaust fan heavy duty with louvers complete 300mm with bolts,nuts and washers ,size of the bolt 15 cm long 12mm dia embedded in the wall including provision of PVC flexible copper cable of size 23/00.0076 three core from ceiling rose to exhaust fan and connecting complete all as specified. \nNote: Cost of opening in wall and grouting of mild steel work shall be deemed included in the lump sum cost of the building. 4 Each
22 3.08 Supply and fixing energy efficient LED, enviornment friendly single tube light fittings surface/ pendent mounted compete with slim box type batten of formed CRCA with snap on installer suitable for 1200 mm long 18/ 20W LED tube rod batten or LED tube light base complete with 1200m long LED rod 1x20 watt, 6500K for white illumination including all accessories and connection from ceiling rose to connector complete all as specified. 32 Each
23 3.09 Supply and fixing energy efficient LED enviornment friendly LED security lightB1 class for area/path illumination made up of pressure die cast aluminium housing with high power LED as lighting source and lense embedded for area/ path illumination as per National Lighting Code (SP 72:2010) by using security light of 25 watts (total input power), CCT - 5000- 5500K CRI > 67, PF > 0.95, rated output lumens 2100 Im, operating performance temp - 10 degree centigrade + 45 degree centigrade LED module life span 50000 burning hrs, with toughened glass, external surge and over voltage protection device up to 440V alongwith connection 3 core copper flexible cable of size 0.75 sqmm to be provided with weather proof connector, LED module & driver IP-66 rated duly ISI marked IS:16103 part (1&2) 2012 : efficency 85% constant current Vtd < 10%, lthd < 15% complete with 40mm dia GI pipe light grade 1.5 mtr long bracket and FI 40 x 6 mm clamp 2 Nos with nut blts etc including painting of clamps with two coats of aluminium paint over a coat of primer (for bldg security lights) complete all as specified. 20 Each
24 3.1 Supply and fixing energy efficient LED, enviornment friendly single tube light fittings surface/ pendent mounted compete with white powder coated slim box type batten of formed CRCA with snap on installer suitable for 20W LED tube rod batten or LED tube light base complete with 300m long LED rod 1x20 watt, 6500K for white illumination including all accessories and connection from ceiling rose to connector complete all as specified. 4 Each
25 3.11 Material and labour for concealed point wiring complete with 1.5 sqmm (nominal cross sectional area) FRLS PVC insulated multi-stranded copper conductor in and including heavy duty PVC conduit pipe (ISI marked) including fittings & accessories including MS concealed terminal boxes with 3mm thick plastic laminated bakelite (Hylum) sheet top cover for mounting switch socket etc including 1.5 sqmm FRLS PVC copper conductor multi-stranded as earth wire connected to the common earth dolly as specified for one light point/fan point/ exhaust point controlled by one switch complete all as specified and directed. 84 Per point
26 3.12 All as per item No. 3.11 above but one three pin socket outlet 5 Amp on same board. 12 Per point
27 3.13 All as per item No. 3.11 above but one three pin socket outlet 5 Amp on independent board. 16 Per point
28 3.14 All as per item No. 3.11 above but with 2.5 sqmm cable and 2.5 sqmm copper conductor cable in green colour code as earth wire for 15 Amps socket outlet complete. \nNote : Socket/ switch sahll be measured and paid for separately. 8 Per point
29 3.15 All as per item No. 3.11 above but with 2.5 sqmm cable and 2.5 sqmm copper conductor cable in green colour code as earth wire for 4 lights controlled by one switch complete for building security lights. 4 Per point
30 3.16 Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6.3 mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt, earth lead GI wire 4mm dia (8 SWG) connected to GI earth plate electrode by means of bolts, nuts, check nuts and washers of galvanized iron and thimbles and other end of earth wire connected to main switch board and protected by galvanized iron light grade 15mm bore and GI pipe 20mm bore medium grade with funnel and wire mesh for watering including necessary excavation and earth works. PCC Chamber in cement concrete (1:3:6) type C-2 & RCC cover in M-20 (Design mix) and all as shown in Electrical Plate No 3 of MES standard Schedule of Rates (Part-I) of 2009 complete all as specified and directed.\nNotes :\n(i) Outer edge of earth pit will be 1 m away from the outer edge of PCC chamber.\n(ii) GI earth wire and protection pipe upto main board is included in this item.\n(iii) Water pipe shall be provided in slanting position. 4 Each Set
31 4 SEWAGE DISPOSAL WORKS
32 4.01 Construction of RCC septic tank for 25 users in ordinary soil ,foundation in PCC (1:2:4) type B-1 using 20 mm stone aggregate ,brick work in cement mortar 1:4, RCC slab with M-25 design mix including plastering, vents, RCC manhole covers complete all as specified and as shown on drawings 4 Each
33 4.02 Construction of Soakage well in soft/loose soil, foundation in PCC 1:3:6, walls of honey combed massonery with top ring of M25 concrete incl intercepting chamber and screen chamber made of brick mansory in cement mortar, RCC cover slab in M25/SFRC cover, interconecting pipes of RCC/DWC complete filled with brick bats of size 1.8m x 3m effective depth complete all as specified and as shown on drawings 4 Each
34 5 EXTERNAL ELECTRIC SUPPLY WORKS
35 5.01 Material and labour for applying two coats of aluminium paint on 8.50 metre long old swaged steel poles and making 30 cm wide strips (total-05 Nos) with white and black paint alternatively on external surfaces above column/PCC benching including numbering with black paint and painting with bitumenuous paint externally for portion embedded in PCC all as specified and directed. 24 Each
36 5.02 Supply and fixing MCB, Single pole & neutral 240 volts, capacity 63 Amps, 50 Hz, 10 KA for fixing on existing panels complete all as specified. 4 Each
37 5.03 Supply and fixing energy efficient LED enviornment friendly LED flood lights for illumination of area as per National Lighting Code (SP 72:2010) by using flood lights of less than or equal to 120 watts with pressure die-cast aluminium housing complete with accessories (total input powerCRI > 67, PF > 0.95, , operating performance temp minus 10 degree centigrade plus 45 degree centigrade LED module life span 50000 burning hrs with external surge and over voltage protection device up to 440V) alongwith connection 3 core copper flexible sheathed weather proof connector duly ISI marked IS:16103 Part(1&2) 2012 driver IP-66 efficiency 85% constant current complete all as specified. 12 Each
38 5.04 Supply and fixing energy efficient LED enviornment friendly LED flood lights B1 class for illumination of road path/area as per National Lighting Code (SP 72:2010) by using security lights of less than or equal to 60 watts with heat resistant tempered glass for protection with 5KV surge protection (total input power) CCT-5000 to 5500 K CRI > 67, PF > 0.95,rated output lumens 3600 IM , operating performance temp minus 10 degree centigrade plus 45 degree centigrade LED module life span 50000 burning hrs with external surge and over voltage protection device up to 440V)alongwith connection 3 core copper flexible sheathed weather proof cable 0.75Sqmm connector. The security light to be modular in construction with on site replacement parts type-3 independent LED module IP 66 rate duly ISI marked IS:16103 Part(1&2) 2012 driver IP-67 efficiency 85% constant current Vthd<10% ltd 15% and with interconnection complete all as specified. 32 Each
39 5.05 Supply and fixing pole junction box made of thermoplastic with IP 65 degree of protection (EN60529),dust proof, water tight weight acid resistence, corrosion proof insulated and shock proof fire retardant self extingushing, halogen & silica free non-Toxic material,UV resistance (UI subject 94:V2) with internally embedded gasket size of test certificate and verification by glow wire test in accordance with IEC60695-2-11 cat no-K8250 (Make- Hensel) with 6 Amps MCB SP neutral link with three phase copper busbar/connector for connection of cable of suitable size complete all as specified. 32 Each
40 5.06 Material and labour for brackets using GI tubing light grade, 40mm dia, 1.2m long bent to shape as required incl two sets 40x6mm flat iron holding clamps,nut bolts and washer for fixing of street light fittings including two coats of aluminium paint on mild steel clamp surfaces complete all as specified. 32 Each
41 5.07 Material and labour earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6.3mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt, galvanized strip 32 x 6mm as eathing connected to GI earth plate electrode by means of bolts, nuts, check nuts and washers of galvanized iron and thimbles and other end of earth wire connected to main switch board and protected by galvanized iron light grade 40mm bore pipe and GI pipe 20mm bore medium grade with funnel and wire mesh for watering including necessary excavation and earth works. PCC chamber in cement concrete (1:3:6) type C-2 using graded stone aggregate and RCC cover in M-20 (Design mix) and all as shown in Electrical Plate No. 3 of MES Schedule (Part-I) of 2009 complete all as specified and directed. 5 Each
42 6 EXTERNAL WATER SUPPLY WORKS
43 6.01 Material and labour for construction of brick masonry valve pit of size 450 x 450 x 450 mm (internal size)depth of chamber to be reckoned from the top of PCC in addition with mild steel sheet cover 6 mm thick and frame of angle iron of size 50x50x 6mm with fixing hinges and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer including excavation and earth work in any type of soil returning filling in approved soil disposal of surplus soil to a distance not exceeding 50m,,150mm thick PCC (1:4:8) type D-2 as in foundation,brick work in cement mortar (1:4) and all internal sides of pit shall be plastered 15mm thick in cement mortar (1:4) and coping in PCC (1:2:4) type B-1 over brick wall complete all as specified. 4 Each
44 6.02 Cutting of existing pipe line and inserting GI tee of size 25x25x25mm jointing and making good of disturbed surfaces complete all as specified. 4 Each
Disclaimer :