| 1 | 1 | Dismantling of old unserviceable/broken/jointed ACSR conductor or earth wire from poles and removing from site of work complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001132 | 3 | Qtl |
|---|
| 2 | 2 | Taking down existing old cross arms of MS channel or angle sections etc complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001133 | 2 | Qtl |
|---|
| 3 | 3 | Taking down burnt and broken out insulators of any size from LT Poles complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001134 | 200 | Each |
|---|
| 4 | 4 | Taking down old unserviceable cradle guard/earthing from LT Poles complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001135 | 1 | Qtl |
|---|
| 5 | 5 | Supply, laying, jointing & testing in replacement XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 2 core laid in trenches or passing through pipe or fixed on poles complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001136 | 300 | RM |
|---|
| 6 | 6 | Description all as per serial item No 5.00 here-in-before but of size 16 Sqmm 4 core. | BI01010001010000000000000515BI0100001137 | 275 | RM |
|---|
| 7 | 7 | Description all as per serial item No 5.00 here-in-before but of size 25 Sqmm 4 core. | BI01010001010000000000000515BI0100001138 | 250 | RM |
|---|
| 8 | 8 | Description all as per serial item No 5.00 here-in-before but of size 35 Sqmm 3.5 core. | BI01010001010000000000000515BI0100001139 | 250 | RM |
|---|
| 9 | 9 | Description all as per serial item No 5.00 here-in-before but of size 50 Sqmm 3.5 core. | BI01010001010000000000000515BI0100001140 | 250 | RM |
|---|
| 10 | 10 | Description all as per serial item No 5.00 here-in-before but of size 70 Sqmm 3.5 core. | BI01010001010000000000000515BI0100001141 | 100 | RM |
|---|
| 11 | 11 | Description all as per serial item No 5.00 here-in-before but of size 95 Sqmm 3.5 core. | BI01010001010000000000000515BI0100001142 | 285 | RM |
|---|
| 12 | 12 | Description all as per serial item No 5.00 here-in-before but of size 120 Sqmm 3.5 core. | BI01010001010000000000000515BI0100001143 | 100 | RM |
|---|
| 13 | 13 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes foundations of poles/stays/pipes etc .not exc 10 Sqm area on plan and getting out in soft/loose soil complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001144 | 370 | Cum |
|---|
| 14 | 14 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001145 | 240 | Cum |
|---|
| 15 | 15 | Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001146 | 130 | Cum |
|---|
| 16 | 16 | M&L for sand cushioning to UG cable laid in trenches with clean dry river sand 8 cm below & 15 cm above the cable & punned down to 18 cm thickness complete all as specified and directed by Engr-in-Charge. \nNote: - For payment purpose 18 cm thickness shall measured. | BI01010001010000000000000515BI0100001147 | 110 | Cum |
|---|
| 17 | 17 | S&f burnt brick of size 230x115x75 mm sub class B for cable protection laid adjacent to each other perpendicular to the direction of cable in trenches complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001148 | 11000 | Each |
|---|
| 18 | 18 | M&L for cement concreate 1:3:6 type C-1 (using 20 mm graded stone aggregate) as in coping etc including necessary form work and finishing the surface with cement mortar 1:4, 5mm thick finished to the portion of PCC muffs above ground level complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001149 | 1 | Cum |
|---|
| 19 | 19 | M&L for PCC 1:4:8 type D-2 (using 40 mm grade stone aggregrate in foundation, mass concrate) as in foundation of poles & stay etc complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001150 | 1 | Cum |
|---|
| 20 | 20 | Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 40 mm bore for cable protection along the poles under road under drains, laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etc including taking down of old unserviceble pipe complete all as specified and directed by Engr-in-charge.\n | BI01010001010000000000000515BI0100001151 | 12 | RM |
|---|
| 21 | 21 | Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 80 mm bore for cable protection along the poles under road under drains, laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etc including taking down of old unserviceble pipe complete all as specified and directed by Engr-in-charge.\n | BI01010001010000000000000515BI0100001152 | 12 | RM |
|---|
| 22 | 22 | M&L danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT 20x15cm size ccomplete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001153 | 5 | Each |
|---|
| 23 | 23 | M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 32 x 6mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common salt including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 20 mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge. \nNote: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. | BI01010001010000000000000515BI0100001154 | 16 | Each Set |
|---|
| 24 | 24 | Supply, Installation , testing and commissioing in replacement of outdoor type, weather proof, LT Panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 40x40x6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15x15x15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/openable by keys from both sides having chromium plated locks, louvers , IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments: - | BI01010001010000000000000515BI0100001155 | 2 | Each |
|---|
| 25 | 24.01 | (a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 Amps for phases and neutral - 01 set \n(b) Digital multifunction meter of size 96x96mm to measure current, voltage, freequency and power factor with built in selector switch and programmable CT of appropriate ratio - 01 Nos\n(c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos\n(d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 Sqmm copper wire single core - 01 Job \nINCOMING\n(a) MCCB 4 Pole, Ics = 100% Icu, 50 KA, 415 Volts, 500 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos \nOUT GOING\n(a) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 250 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos \n(b) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 200 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos \n(c) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos \n(d) Blank spare for MCCB/Change over switch of rating 200 Amps, 4 Pole -35/36KA-02 Nos | BI01010001010000000000000515BI0100001156 | | |
|---|
| 26 | 25 | Supply, Installation , testing and commissioing in replacement outdoor type, weather proof, LT Panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 40x40x6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15x15x15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/openable by keys from both sides having chromium plated locks, louvers, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments: - | BI01010001010000000000000515BI0100001157 | 1 | Each |
|---|
| 27 | 25.01 | (a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 500 Amps for phases and neutral - 01 set \n(b) Digital multifunction meter of size 96x96mm to measure current, voltage, freequency and power factor with built in selector switch and programmable CT of appropriate ratio - 01 Nos\n(c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos\n(d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 Sqmm copper wire single core - 01 Job \nINCOMING\n(a) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 400 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos \nOUT GOING\n(a) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 200 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos \n(b) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos \n(c) MCCB 4 Pole, Ics = 100% Icu,16KA, 415 Volts, 63 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos | BI01010001010000000000000515BI0100001158 | | |
|---|
| 28 | 26 | Supply, installation and commissioning in replacement LT Panel of size 75x75x45 cm outdoor type factory made manufactured by a CPRI approved manufacturer, made out of 3.15 mm thick CRCA sheet and self supporting, built upon Rigid frame work suitable fo 440 volt 3 phase 4 wire system having front and rear hinger doors with neorprene rubber gasket epoxy powder coated with danger plate, earthing strip point and bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc having colour code aluminium bus bar interconnections for easy identification including incoming/outgoing cable holes at bottom, provision of six nos connectors and embedded with mild steel anglr iron frame of size 50x50x6 mm and 450 mm above normal ground level complete with PCC foundation in cement concrete (1:2:4) type B1 graded stone aggregate and testing after installation including taking down unserviceable Feeder Pillar box with connected acessories after disconnecting all incoming and outgoing cable etc, complete all as specefied and comprising with the following: - | BI01010001010000000000000515BI0100001159 | 5 | Each |
|---|
| 29 | 26.01 | (a) Aluminium Bus-bar 400 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving. The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos \n(b) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 250 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos (AS INCOMING) | BI01010001010000000000000515BI0100001160 | | |
|---|
| 30 | 27 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable PVC insulated aluminium conductor served with an inner sheathing of PVC tape and overall PVC sheathed 4 Sqmm 2 core nominal cross section complete with all acessories complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001161 | 75 | RM |
|---|
| 31 | 28 | M&L Rigid steel conduit heavy of size 20 mm dia with all fittings and fixed to pole for protection to PVC cable connection from junction box to security light included MS clamp of size 25mmx3mm thick MS clamp, nuts, bolts and washers, duly painted complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001162 | 30 | RM |
|---|
| 32 | 29 | S&F modular box of size 280x170x130 mm made of FRP inpact resistance plastic & heat resistant materials including MCB SP 6 A, Connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specified and directed by Engr-in-charge. | BI01010001010000000000000515BI0100001163 | 31 | Each |
|---|
| 33 | 30 | M&L for road cuttig existing road for crossing of underground electric cable for laying of any size GI tubing including necessary excavation and earth work including repairing the same as per existing complete all as specified and directed by Engr-in-charge.\nNote: - Width of trench shall be 15 cm and depth shall be up to 30 cm. | BI01010001010000000000000515BI0100001164 | 16 | RM |
|---|